Salwico Consilium GD GS5000 Installation and Service Manual
Salwico Consilium GD GS5000 Installation and Service Manual
1 Introduction ...................................................................................... 1
1.1 About this manual ............................................................................ 1
1.2 Symbols Used in the Manual ........................................................... 2
3 Installation ....................................................................................... 7
3.1 Prerequisites for Installation ........................................................... 7
3.2 Mechanical Installation ................................................................... 7
3.2.1 Installation order ............................................................................ 7
3.2.2 Control Panels ................................................................................ 7
3.2.3 Gas Detectors ................................................................................. 7
3.2.4 Mounting of modules ..................................................................... 7
4 Configuration ................................................................................... 23
4.1 Uploading a configuration file to the gas detection system ............ 23
4.1.1 Uploading a configuration file from the USB memory stick ......... 23
5 Verification ....................................................................................... 27
5.1 Prerequisites for Verification ........................................................... 27
5.2 Verification of Power Boost loops ................................................... 27
5.3 Testing of System Parts .................................................................... 28
5.3.1 Prerequisites for Testing ................................................................ 28
5.3.2 About testing .................................................................................. 28
5.3.3 Test the control panel display ........................................................ 28
14 Appendix ........................................................................................... 69
14.1 Central Unit Terminal & Cabling Layout ....................................... 69
14.2 RS485/PB485 Termination .............................................................. 71
14.2.1 General Recommendations for Installation of RS485 ................... 71
Table of contents
Index ................................................................................................. 79
Installation Manual 1 Introduction
1 Introduction
NOTE!
This guide is valid for Control panel software versions beginning with version
1.0.0.
Chapter Verification, page 27 describes how to test the installed system. After
the installation is completed, the system is verified, which must be performed by a
person with good knowledge of the various functions. This chapter also includes
verification and troubleshooting.
5103018-00A01 1
1 Introduction Installation Manual
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint!
Tip symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
2 5103018-00A01
Installation Manual 2 Gas Detection System
Figure 3. An example with several Power Boost Loops in one Salwico Gas detection system
5103018-00A01 3
2 Gas Detection System Installation Manual
4 5103018-00A01
Installation Manual 2 Gas Detection System
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
Hint!
For detailed requirements, refer to the data sheets.
5103018-00A01 5
2 Gas Detection System Installation Manual
6 5103018-00A01
Installation Manual 3 Installation
3 Installation
The different parts of the system, the control and system modules, should first be
mechanically installed. The different gas detectors are thereafter electrically
installed and set up according to the definition of the detectors and drawings.
The cables must be tested separately before the detectors are connected to the
system module. This eliminates any problem with the cables and the electrical
installation of the detectors.
The installation is completed with the electrical installation of the the control and
system modules.
The mechanical installation of different types of gas detectors are described in their
respective data sheets. Some guidelines on where to place detectors are given in
Location of sensors, page 35.
5103018-00A01 7
3 Installation Installation Manual
The cables connecting from the backbone bus to the control panels or stretched
central part must meet the following requirements:
NOTE!
Channel 1 and Channel 2 should be routed separately for improved safety if both
channels are used.
8 5103018-00A01
Installation Manual 3 Installation
Power Boost Loop cables must meet the following minimum requirements. We
refer to current regulations for the rest of the specification.
5103018-00A01 9
3 Installation Installation Manual
NOTE!
Wires for communication (PB-485) must be twisted over its entire length.
Figure 8. Connection examples of cables between Analogue M 4-20 and gas detectors
Cables between Analogue M 4-20 and gas detectors must meet the following
minimum requirements. We refer to current regulations for the rest of the
specification.
• cable type
• shielded or unshielded cable
• power consumption
A cable is considered shielded if the shielded part is more than 10% of the cable's
total length.
10 5103018-00A01
Installation Manual 3 Installation
Cable resistance
5103018-00A01 11
3 Installation Installation Manual
Hint!
Please contact Consilium for advice concerning cable lengths.
12 5103018-00A01
Installation Manual 3 Installation
5103018-00A01 13
3 Installation Installation Manual
CAUTION!
Do not remove protection cap from the gas detectors until all polluting activities
(such as construction work and painting) are finished and the area has been
cleaned.
For further information refer to Gas Detectors Installation, page 35.
Connection Examples
14 5103018-00A01
Installation Manual 3 Installation
• Transmitter interface 1, 0 ± 10 ms
• Transmitter interface 2, 125 ± 10 ms
• Transmitter interface 3, 250 ± 10 ms
• Transmitter interface 4, 375 ± 10 ms
NOTE!
DIP switch addresses below 31 will NOT be delayed.
See the following example Figure 18. how the cable screen should be connected to
avoid an earth loop.
= Wires marked with this symbol in the drawing must be twisted over its
entire length
5103018-00A01 15
3 Installation Installation Manual
CAUTION!
The screens/shields of field cabling should not be connected in a manner that
creates earth loops or that will result in the screens/shields carrying large currents
from the equipment.
The illustration in Figure 19. shows an example on how the cable screens should
not be connected.
16 5103018-00A01
Installation Manual 3 Installation
Figure 19. This example shows some incorrect connections of the cable screens
The use of a single, screened/shielded cable for each field device (detector) ensures
good screening/shielding and reduces crosstalk. Cabling arrangements that use a
single cable to connect a number of field devices compromise screening and
increase the potential for crosstalk. Such arrangements should only be employed if
the electrical installation design authority is confident that this will not adversely
affect the reliability or performance of the system.
5103018-00A01 17
3 Installation Installation Manual
Figure 20. Test for cable break between the PBx terminals
18 5103018-00A01
Installation Manual 3 Installation
When gas detectors are connected, it is not allowed to use an insulation tester with
a voltage exceeding 30 V.
Figure 22. Test for short circuit between the + terminal and the - terminal
Measure the resistance between the PBx terminal and the - terminal
Connect an ohm-meter between the two terminals, as shown in the following
figure.
Figure 23. Test for short circuit between the PBx terminal and the - terminal
Measure the resistance between the PBx terminal and the + terminal
Connect an ohm-meter between the two terminals, as shown in the following
figure.
5103018-00A01 19
3 Installation Installation Manual
Figure 24. Test for short circuit between the PBx terminal and the + terminal
NOTE!
Measure and repeat the procedure for the - terminal.
20 5103018-00A01
Installation Manual 3 Installation
All Salwico Gas Detection System addressable modules must be given an unique
address in order to make it possible for the software to identify the modules. The
address is set with an 8-pole DIP switch with the exception of module Control M
Gas (there the address is set on the panel via Menu » Settings » Set CM address).
For instructions on how to set the address on DIP switch, refer to the data sheet for
each module.
On some modules (for example Power Boost M and BusCon M Gas) different
functions are set by DIP-switches.
For Relay M 8 and Analogue M 4-20 the DIP switch 8 on these modules must be
set to ON when they are used in a Gas detection system.
For instructions on how to set the DIP-switches, refer to the data sheet for each
module.
5103018-00A01 21
3 Installation Installation Manual
For other electrical installations, such as printers, refer to the specific project
drawings.
22 5103018-00A01
Installation Manual 4 Configuration
4 Configuration
NOTE!
The old configuration file will be overwritten. Please save the old file before
proceeding.
Note that old versions of the definition program may effect the upload or system
operations. Use a program version of the CCP Configuration program compatible
with the system version used in your gas detection system.
The configuration file can be uploaded using an approved USB memory stick
(available from an authorized dealer).
CAUTION!
Do not remove the USB memory stick until the upload is finished.
5103018-00A01 23
4 Configuration Installation Manual
Hint!
When requesting assistance on technical issues please send the configuration file
and the system log file to your local retailer.
The configuration file can be downloaded using an approved USB memory stick
(available from an authorized dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
24 5103018-00A01
Installation Manual 4 Configuration
5103018-00A01 25
4 Configuration Installation Manual
26 5103018-00A01
Installation Manual 5 Verification
5 Verification
5103018-00A01 27
5 Verification Installation Manual
• The display
28 5103018-00A01
Installation Manual 5 Verification
1 To test the control panel display, use: Menu » Service » Settings » Display
& LED test.
1 Look for the last system modules Refer to Test 1: Test for cable
answering on each side of the loop. The break, page 17, for more
cable break is situated after or between the information.
answering modules.
5103018-00A01 29
5 Verification Installation Manual
1 Examine the faulty cable to locate the earth Refer to Test 3: Test for earth
fault. failure, page 20 for more
details.
1 Search for the short circuits between the Refer to Test 2: Test for short
central unit and the first Power Boost circuits, page 18 for more
module. details.
1 The control panel displays which system Refer to Test 2: Test for short
modules are missing. Search for the short circuits, page 18 for more
circuit between the fault reported modules details.
to find the exact location of the fault.
The faults are reset from the Fault list under Menu » 2 Fault and warnings » 1
Faults.
From the Repeater panel it is only possible to mute faults and alarms, not reset
them.
NOTE!
The cause of the problem must disappear before a fault can be reset.
30 5103018-00A01
Installation Manual 5 Verification
NOTE!
Access Level 4 is required to upgrade firmware in the system. You may be required
to login with correct credentials during the firmware upgrade process.
NOTE!
The system will only update the modules that have software that differs from what
is in the service package stored locally in the control module.
Hint!
When requesting assistance on technical issues please send the system log file and
the systems configuration file to your local retailer.
5103018-00A01 31
5 Verification Installation Manual
The system log file can be downloaded using an approved USB memory stick
(available from an authorized dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
32 5103018-00A01
Installation Manual 6 Commissioning Requirements
6 Commissioning Requirements
6.1 Prerequisite
The procedure described below in Loop requirements is to be followed by the
installation team.
If nothing else is agreed, no commissioning engineer will be sent before the steps
below are confirmed and the appropriate papers are signed and sent to your local
Consilium office or authorized representative.
The list in Part A: Power Boost loop configuration includes all data you need when
configuring the loops.
Part B: Loop status is more like a checklist - follow it point by point. When you
have completed this part you should have filled in, signed and faxed a test report
containing each Power Boost loop unit/detector in the system.
Part C: Central status is also a checklist, but it deals with the status of the central
unit.
5103018-00A01 33
6 Commissioning Requirements Installation Manual
4 A test report must be filled in for each Power Boost loop unit/detector.
The test report must contain at least the following information for each
unit/detector:
• Type of unit/detector
• Location
• Address
• Installation date
5 Send one copy of the signed test protocol to your local Consilium office or
authorized representative.
6 When all protocols are signed, your local Consilium office or authorized
representative will make the final control and adjustment of the system.
NOTE!
Deviations from the above criteria may cause time delays. These time delays will
be invoiced.
6.6 Summary
For each gas detector, a test report as described in Part B: Loop status, page 33
must be filled in and sent to your local Consilium office or authorized
representative before commissioning of the system starts.
34 5103018-00A01
Installation Manual 7 Gas Detection Installation Guidelines
CAUTION!
Always refer to and act according to current local rules and regulations.
• We strongly recommend protecting the gas detector sensor cell when doing
painting work to avoid the high amount of silicones that exists in paint. In order
to protect the sensor cell Consilium has installed a protection cover that is
mounted on the detector cell from delivery. Keep the covers mounted as long as
possible, recommendable is to keep them on until first sea-trial. It’s also a
benefit to keep the gas detectors without power. When the gas detector is
currentless it’s less affected by paint.
• To help maintain the correct IP class, plug any unused cable glands.
• Keep the detectors protection caps on as long as possible. The protection caps
should be removed after commissioning is completed and the system is handed
over.
NOTE!
For detailed connection and installation information, refer to the data sheet for each
unit.
There are a number of simple and quite often obvious considerations that help to
determine detector location:
• To detect gases that are lighter than air (e.g. Methane and Ammonia), detectors
should be mounted at high level and preferably use a collecting cone.
• To detect heavier than air gases (e.g. Butane, Sulphur Dioxide and Propane),
detectors should be mounted at a low level.
5103018-00A01 35
7 Gas Detection Installation Guidelines Installation Manual
• Consider how escaping gas may behave due to natural or forced air currents.
Mount detectors in ventilation ducts if appropriate.
• Detectors should be positioned a little way back form high pressure parts to
allow gas clouds to form. Otherwise any leak of gas is likely to pass by in a
high speed jet and not be detected.
• Consider ease of access for functional testing and servicing.
• Detectors should be installed at the designated location with the detector
pointing downwards. This ensures that dust or water will not collect on the front
of the sensor and stop the gas entering the detector.
7.1.3 IR detectors
There are two main types of IR Detectors, open-path or single point. Open-path
detectors are mainly used in outdoor situations and Single point detectors in indoor
situations.
Many combustible gases have absorption bands in the infrared region of the
electromagnetic spectrum of light and the principle of infrared absorption is used to
detect the gas concentration.
IR Detectors has a very fast response (typically less than 10 seconds). They can
also be designed to be unaffected by any known ‘poisons’, they are failsafe and
they will operate successfully in inert atmospheres, and under a wide range of
ambient temperature, pressure and humidity conditions. The technique operates on
the principle of dual wavelength IR absorption, whereby light passes through the
sample mixture at two wavelengths, one of which is set at the absorption peak of
the gas to be detected, whilst the other is not. A detector compares the signal
strengths of sample and reference beams and, by subtraction, can give a measure of
the gas concentration.
The response time for catalytic sensors are typically between 20 and 30 seconds.
36 5103018-00A01
Installation Manual 7 Gas Detection Installation Guidelines
Three active gas diffusion electrodes are immersed in a common electrolyte for
efficient conduction of ions between the working and counter electrodes.
Depending on the specific cell the target gas is either oxidised or reduced at the
surface of the working electrode. This reaction alters the potential of the working
electrode relative to the reference electrode. The primary function of the associated
electronic driver circuit connected to the cell is to minimise this potential
difference by passing current between the working and counter electrodes, the
measured current being proportional to the target gas concentration. Gas enters the
cell through an external diffusion barrier that is porous to gas but impermeable to
liquid.
Gas specific electrochemical sensors can be used to detect the majority of common
toxic gases, including CO, H2S, Cl2, O2, SO2 etc. Electrochemical sensors are
compact, require very little power, have excellent linearity and repeatability and
generally have a long life span, typically one to three years. Response times are
typically 30-60 seconds.
5103018-00A01 37
7 Gas Detection Installation Guidelines Installation Manual
When installing metal cable tubes – following must be taken into account:
• If there is more than one cable in the same tube, the cross section (counted of
mutual external diameters) may be max 40% of the inner cross section of the
tube.
• If the tube is more than 10 m long, drafting holes has to be done.
• Tubes must be installed on support so that the background may be painted.
• Tube installation must be done by welding or by tube joints. Fastening distances
are located 100 mm from the tube end and afterwards every 1.5 m.
• Bending radius must be at least 6 times the external diameter of the tube.
• The upper tube end in open decks must be sealed up, this to prevent water from
coming in.
When installing plastic cable tubes – following must be taken into account:
• Bending radius must be at least six times external diameter of the tube.
• Installation must be done onto the warm side of a thermal insulation and at least
100 mm from a hot surface, preferably below it. Piping is not allowed inside a
thermal insulation.
• The tubes are tied with galvanized wire clips. The first clip is located
approximately 100 mm from the tube end and afterwards every 1 m.
7.2.4 Cabling
When installing the cables – take into account the minimum internal bending
radius, that has nominal value of six times the external diameter of the cable.
• If two separate routes for the cables are required – all supplies and involved
control cables must be passed by separate routes according to the drawings and
cable passing list.
• Do not bundle low voltage cables together with power cables, they have to be
separated from each other.
• When cable bundles are mounted on trays this can be done as follows:
• On the trays along the ship – the power cables on the left side (Port-side)
and the low voltage cables on the right side (Starboard-side) of the tray.
• On the trays across the ship – the power cables to the fore side and the low
voltage cables in the stern side of the tray.
• On the fore or stem bulkhead trays in vertical shaft – the power cables to the
Port-side or the Starboard-side bulkhead trays, the power cables to the fore
side and the low voltage cables to the stern side of the tray.
38 5103018-00A01
Installation Manual 7 Gas Detection Installation Guidelines
• In cable junctions and when exiting the cable trays bridges with fastening bolts
have to be used – low voltage cables for alarm, communication, navigational
and measuring equipment have to be installed in their own bundles.
• Each gas detector installed in engine room areas shall have two (2) meters extra
cables, this to make it possible to relocate the detector position when
performing “real” gas tests with fans etc. running.
• Wet spaces:
• Cables are penetrated from the bellow or from the side with diaphragm
seals.
• Let the cables enter the sealing at a right angle (or as near a right angle as
possible).
• Dry spaces:
• Free entering
No cables are to be installed below 50 mm distance from bottom or fuel oil tank,
except cables ending in these spaces.
7.2.7 Markings
• Cables entering terminal boxes and equals shall be marked with identification
markings.
5103018-00A01 39
7 Gas Detection Installation Guidelines Installation Manual
• The cable is passed in switchboards, decks and terminals unpeeled as near the
connection place as possible.
• Mark extra wires (not used) and do not cut them.
• Earthing wire is marked with yellow/green sleeve.
• Cable wire ends of 0.5–2.5 mm2 shall be equipped with compression-type
collar, if the contact screw presses direct wires.
• A cable eye shall be installed at the end of a conductor, connected by means of
a screw or a bolt.
• No more than two conductors shall be connected onto one side of the same
terminal.
40 5103018-00A01
Installation Manual 8 Calibration Instruction for Salwico GD True IR
8.1 Preliminaries
This instructions applies to the following products: 5200138-00A, 5200138-01A,
5200204-00A, 5200204-01A and 5200204-02A.
CAUTION!
Before initial calibration allow the detector to stabilize for 30 minutes after
applying power. When in zero and span calibration mode the current output from
the detector is inhibited (default 2mA) to avoid false alarms. For Flammable gas
calibration use a calibration gas concentration of between 25%LEL and 75%LEL
to ensure that the required accuracy can be attained.
Considerations:
• To calibrate the detector, use an appropriate span gas cylinder, constant flow
regulator.
• A compressed air cylinder (20.9%Vol oxygen) should be used to perform the
zero calibration, if the area where the detector is located contains any residual
amount of the target gas. If no residual gas is present then the background air
can be used to perform the zero calibration.
5103018-00A01 41
8 Calibration Instruction for Salwico GD True IR Installation Manual
42 5103018-00A01
Installation Manual 8 Calibration Instruction for Salwico GD True IR
5103018-00A01 43
8 Calibration Instruction for Salwico GD True IR Installation Manual
44 5103018-00A01
Installation Manual 9 Calibration Instruction for Salwico GD
9.1 Preliminaries
This instructions applies to the following products: 5200260-01A, 5200260-02A,
5200260-03A, 5200260-04A, 5200261-01A, 5200262-01A, 5200262-02A and
5200262-03A.
CAUTION!
Before initial calibration allow the detector to stabilize for 30 minutes after
applying power. When in zero and span calibration mode the current output from
the detector is inhibited (default 2mA) to avoid false alarms. For Flammable gas
calibration use a calibration gas concentration of between 25%LEL and 75%LEL
to ensure that the required accuracy can be attained.
Considerations:
• To calibrate the detector, use an appropriate span gas cylinder, constant flow
regulator.
• A compressed air cylinder (20.9%Vol oxygen) should be used to perform the
zero calibration, if the area where the detector is located contains any residual
amount of the target gas. If no residual gas is present then the background air
can be used to perform the zero calibration.
NOTE!
The Oxygen sensor does not require a zeroing procedure. Background air
(20.9%Vol oxygen) can be used to span the oxygen sensor in place of a compressed
air cylinder (20.9%Vol oxygen).
5103018-00A01 45
9 Calibration Instruction for Salwico GD Installation Manual
46 5103018-00A01
Installation Manual 9 Calibration Instruction for Salwico GD
If successful the display shows ‘ZEro (If not successful, the display
PASS’. shows ‘Zero FAIL’ and
(If not successful, the display shows ‘Zero returns to configuration
FAIL’ and returns to configuration mode). mode.)
15 The display shows ‘SPAn’ with ‘YES’
flashing.
5103018-00A01 47
9 Calibration Instruction for Salwico GD Installation Manual
48 5103018-00A01
Installation Manual 9 Calibration Instruction for Salwico GD
If the span calibration is successful the (If the span calibration fails
instrument will briefly display ‘SPAn the instrument will briefly
PASS’. display ‘SPAN FAIL’ and
return to configuration mode.)
8 The display alternates between “Purg gAS”
and the gas reading to indicate that the unit
is expecting the span gas to be removed
from the sensor.
5103018-00A01 49
9 Calibration Instruction for Salwico GD Installation Manual
50 5103018-00A01
10 Calibration Instruction for Salwico ST200 and
Installation Manual Salwico ST600EX
10.1 Preliminaries
This instructions applies to the following products:
NOTE!
It is recommended to periodically carry out a gas response check on the gas
detector to ensure correct operation.
The ST200 and ST600EX detectors for 0-100% LEL Hydrocarbon can be
calibrated and the out-signal adjusted.
Hint!
Reading at 0% is 4.0 mA, and full range 100% LEL is 20 mA.
Tools
Tools required for this operation are:
5103018-00A01 51
10 Calibration Instruction for Salwico ST200 and
Salwico ST600EX Installation Manual
10.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.
52 5103018-00A01
10 Calibration Instruction for Salwico ST200 and
Installation Manual Salwico ST600EX
5103018-00A01 53
10 Calibration Instruction for Salwico ST200 and
Salwico ST600EX Installation Manual
54 5103018-00A01
10 Calibration Instruction for Salwico ST200 and
Installation Manual Salwico ST600EX
5103018-00A01 55
10 Calibration Instruction for Salwico ST200 and
Salwico ST600EX Installation Manual
56 5103018-00A01
11 Calibration Instruction for Salwico ST600EX-IR
Installation Manual and Salwico ST700IR
11.1 Preliminaries
This instructions applies to the following products:
11.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.
5103018-00A01 57
11 Calibration Instruction for Salwico ST600EX-IR
and Salwico ST700IR Installation Manual
58 5103018-00A01
11 Calibration Instruction for Salwico ST600EX-IR
Installation Manual and Salwico ST700IR
5103018-00A01 59
11 Calibration Instruction for Salwico ST600EX-IR
and Salwico ST700IR Installation Manual
60 5103018-00A01
Installation Manual 12 Calibration Instruction for Salwico ST400 H2S
12.1 Preliminaries
This instructions applies to the following products:
Figure 35. Salwico ST400 H2S, 0-30 ppm 4-20 mA. Part no. 4462
DANGER!
H2S – Hydrogen Sulphide – is toxic and dangerous also in rather low
concentrations.
H2S is a sticky gas and smells very distinctly from rotten eggs.
Consilium Replacement article number for ST400 H2S detectors is no. 004462-S.
A new sensor is supplied without the metal housing and must be fitted in the
housing. This applies to both H2S and O2 sensors of ST400 type.
Calibration equipment
Normal measuring range is 0-30 ppm, our standard calibration bottle no.
5201005-00A contains 20 ppm of gas in air.
For SW2020 a mix-bottle is often used, with H2S 20 ppm as well as N2 99% and
C3H8 50% LEL, article no. 5201010-01A.
Test points (A) for the multi-meter as well as “SPAN” (B) and “ZERO” (C)
potentiometers are indicated below.
CAUTION!
Do not adjust the other potentiometers.
5103018-00A01 61
12 Calibration Instruction for Salwico ST400 H2S Installation Manual
A Test points
B SPAN potentiometer
C ZERO potentiometer
12.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.
62 5103018-00A01
Installation Manual 12 Calibration Instruction for Salwico ST400 H2S
7 NOTE!
For the following steps in the zero
calibration instruction proceed to
the Salwico ST400 detector.
To verify which type is in use, make a span calibration as below and verify the
display reading in the central cabinet.
5103018-00A01 63
12 Calibration Instruction for Salwico ST400 H2S Installation Manual
Span calibration
64 5103018-00A01
Installation Manual 13 Calibration Instruction for Salwico ST400 O2
13.1 Preliminaries
This instructions applies to the following products:
NOTE!
The lifespan of the sensor is about one year, and it has a short shelf life – stocking
it on board is not advised and this will reduce the operational lifetime.
Consilium Replacement article for sensor only of ST400 O2 detector is no. 004472.
A new sensor is supplied without the metal housing and must be fitted in the
housing. This applies to both H2S and O2 sensors of ST400 type.
Calibration equipment
The O2 is calibrated with fresh breathing air, and is normally 20.8%.
Test points (A) for the multi-meter as well as “SPAN” (B) and “ZERO” (C)
potentiometers are indicated below.
CAUTION!
Do not adjust the other potentiometers.
5103018-00A01 65
13 Calibration Instruction for Salwico ST400 O2 Installation Manual
A Test points
B SPAN potentiometer
C ZERO potentiometer
13.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.
66 5103018-00A01
Installation Manual 13 Calibration Instruction for Salwico ST400 O2
7 NOTE!
For the following steps in the zero
calibration instruction proceed to
the Salwico ST400 detector.
A gas bottle with Hydrocarbons in N2 can also be used, as long as the O2 content is
zero per cent.
5103018-00A01 67
13 Calibration Instruction for Salwico ST400 O2 Installation Manual
68 5103018-00A01
Installation Manual 14 Appendix
14 Appendix
For complete information, see the data sheet for each module.
5103018-00A01 69
14 Appendix Installation Manual
70 5103018-00A01
Installation Manual 14 Appendix
5103018-00A01 71
14 Appendix Installation Manual
72 5103018-00A01
Installation Manual 14 Appendix
5103018-00A01 73
14 Appendix Installation Manual
74 5103018-00A01
Installation Manual 14 Appendix
5103018-00A01 75
14 Appendix Installation Manual
A module that is a part of the Platform, that is can be used to build Centrals. Modules
Module within the platform generally supply a Backbone Bus interface. Controller Modules
also have an Interface.
Module Address Module Addresses are set via DIP switches on the Modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
PA Public Addressing.
Power Boost Loop The Power Boost Loop is a subsystem in the CCP Gas system.
The Power Boost M is designed to distribute power and supervise connections in a gas
Power Boost M
alarm system.
System function for transfer of xGas status between the Power Boost modules on a
Power Boost xGas (Pbx) Power Boost Loop (Signal name PbxGas) and the modules connected to the Power
Boost module on the internal Backbone Bus (BBI).
Power Output Output providing power supply, normally used to power external devices.
A condition preceding the Alarm Condition to give early warning for potentially
Pre-Alarm Condition
dangerous situations.
Programmable Output Output which signal behaviour is configurable via the Configuration Program.
PSU Power Supply Unit.
Refers to the quality or state of being redundant, that is exceeding what is necessary or
Redundancy normal. In the System the term is used to describe backup functionality like in
Controller Modules.
Electrically operated switch output, normally providing C/NO/NC contacts for
Relay
connection of signal receiver.
Modules enter 'safe state' when they detect system faults. Modules in Safe State put
Safe State their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
SCS Single Central System.
76 5103018-00A01
Installation Manual 14 Appendix
A central that is physically distributed to two or more physical locations. One location
Stretched central (DCS) may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Universal Serial Bus, a communications bus that may be used to connect flash
USB
memories, keyboards, mice or other devices.
The state of the system when a warning is detected. Warnings are not as serious as
Warning Condition faults and only of informative nature, for example that a Gas Detector is in need of
calibration.
The Backbone Bus contains a signal, xGas, which will be activated by any module that
xGas
detects a gas alarm.
Zone A group of detectors located in a geographical area.
5103018-00A01 77
14 Appendix Installation Manual
78 5103018-00A01
Index
Index
A I
About testing.......................................................... 28 Installation guidelines, Cabling and electrical
Analogue M 4-20 ................................................... 69 installation.............................................................. 37
Analogue M 4-20, Cable requirements.................. 10 Installation order, Mechanical installation............. 7
Analogue M 4-20, Connection example ................ 14 IR detectors ............................................................ 36
B L
Backbone Bus External (BBE), Cable LED test ................................................................. 28
requirements........................................................... 8 Location of sensors ................................................ 35
Backbone Bus External (BBE), Electrical
installation.............................................................. 8
Bus Isolator M........................................................ 69
M
Muting faults, Trouble shooting............................. 30
BusCon M Gas....................................................... 69
C P
Power Boost loop, Connection example................ 12
Cable break, Trouble shooting ............................... 29
Power Boost Loops, Cable requirements............... 9
Cable lengths, Electrical installation...................... 10
Power Boost loops, Verification of ........................ 27
Cable markings ...................................................... 39
Power Boost M ...................................................... 69
Cable requirements, Electrical installation ............ 8
Procedure for installation commissioning ............. 33
Cabling, Installation guidelines ............................. 37
Protective earthings................................................ 40
Catalytic detectors.................................................. 36
PSU M AC/DC 5A ................................................ 69
Central unit terminal layout with cabling .............. 69
Channel 1 & 2, Cable requirements....................... 8
Commissioning requirements ................................ 33 R
Control M Gas External ......................................... 69 Reconnecting disabled detectors............................ 44
Control M Gas Internal .......................................... 69 Reconnecting disabled detectors............................ 49
Control M X........................................................... 69 Reconnecting disabled detectors............................ 54
Control panel display, Testing................................ 28 Reconnecting disabled detectors............................ 60
Control panels, Mechanical installation................. 7 Reconnecting disabled detectors............................ 64
Control M Gas, Installation order .......................... 7 Reconnecting disabled detectors............................ 68
Control panels, Electrical installation .................... 22 Relay M 8 Gas ....................................................... 69
Reset faults, Trouble shooting ............................... 30
RS485 Termination ................................................ 71
D RS485, Application examples for installation ....... 71
Download configuration file .................................. 24
Download configuration file .................................. 31
S
Short circuit, Trouble shooting .............................. 30
E Span calibration, GD.............................................. 48
Earth connections................................................... 15
Span calibration, GD True IR ................................ 43
Earth fault, Trouble shooting ................................. 30
Span calibration, ST200......................................... 53
Electrical siren, Installation guidelines .................. 37
Span calibration, ST400 H2S................................. 59
Electrochemical detectors ...................................... 37
Span calibration, ST400 H2S................................. 63
Span calibration, ST400 O2................................... 67
F Span calibration, ST600EX ................................... 53
Fault list ................................................................. 30 Span calibration, ST700IR..................................... 59
Fault list ................................................................. 30 ST200, Calibration instructions ............................. 51
ST400 H2S, Calibration instructions ..................... 61
ST400 O2, Calibration instructions ....................... 65
G ST600EX, Calibration instructions........................ 51
Gas detection system, System data ........................ 5
ST600EX-IR, Calibration instructions................... 57
Gas detection system, System description ............. 3
ST700IR, Calibration instructions ......................... 57
GD True IR, Calibration instructions..................... 41
Surge Prot M H ...................................................... 69
GD, Calibration instructions .................................. 45
System modules, Description................................. 69
Guidelines, Gas detectors installation.................... 35
5103018-00A01 79
Index
T
Terminal layout, Electrical installation .................. 21
Test for cable break ................................................ 17
Test for earth failure............................................... 20
Test for short circuits ............................................. 18
Test the control panel display ................................ 28
U
Upload configuration file....................................... 23
W
Wrong number of gas detectors, Trouble shooting 29
Wrong number of system modules, Trouble
shooting.................................................................. 29
Z
Zero calibration, GD .............................................. 46
Zero calibration, GD True IR................................. 42
Zero calibration, ST200 ......................................... 53
Zero calibration, ST400 H2S ................................. 63
Zero calibration, ST400 O2 ................................... 67
Zero calibration, ST600EX.................................... 53
Zero calibration, ST600EX-IR............................... 58
Zero calibration, ST700IR ..................................... 58
80 5103018-00A01
Global Service and Support
Own companies
Sales- and service representatives
Consilium is constantly increasing and improving its global sales and service
organisation in order to provide our customers with the most competent
service and support. Today Consilium has established own companies in
16 countries plus sales and service representatives in more than 50 countries.
You will find updated contact information on our web-site www.consilium.se.
www.consilium.se