ABP 22 Ab Eelectrification and Control Systems

The document is an electrical plan for a residential house. It includes floor plans showing lighting and outlet layouts, lists of appliances, lighting computations, branch circuit sizing tables, one-line diagrams, and detailed computations. The lighting computations determine that the house will require a total of 553 lamps across various areas like the living room, kitchen, bedrooms, and bathrooms. Branch circuit sizing tables outline the circuit breaker sizes needed for the main panelboard and four sub-panelboards to safely supply the house's electrical needs.

Uploaded by

Esau Madeaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
532 views

ABP 22 Ab Eelectrification and Control Systems

The document is an electrical plan for a residential house. It includes floor plans showing lighting and outlet layouts, lists of appliances, lighting computations, branch circuit sizing tables, one-line diagrams, and detailed computations. The lighting computations determine that the house will require a total of 553 lamps across various areas like the living room, kitchen, bedrooms, and bathrooms. Branch circuit sizing tables outline the circuit breaker sizes needed for the main panelboard and four sub-panelboards to safely supply the house's electrical needs.

Uploaded by

Esau Madeaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 36

ABP 22

AB EELECTRIFICATION AND CONTROL SYSTEMS

RESIDENTIAL ELECTRICAL PLANNING PROJECT

Submitted by:
De Austria, Manny M.

Submitted to:
Engr. Mark Keylord S. Onal

June 26, 2023


Table of Contents
Project Overview
Floor Plan with Dimension and Names
Floor Plan with Furniture and Appliances
Floor Plan with Lighting Layout
Floor Plan with Convenience Outlet Layout
Floor Plan with Lighting Branch Circuit Layout
Floor Plan with Outer Branch Circuit Layout
List of Appliances
Light Computation
Table 2. Summary of Lighting Computation
Detailed Computation for Lighting
Branch Circuit Sizing
Table 3. Summary of Branch Circuit Sizes for Power Panelboard A (PPA)
Table 4. Summary of Branch Circuit Sizes for Power Panelboard B (PPB)
Table 5. Summary of Branch Circuit Sizes for Power Panelboard C (PPC)
Table 6. Summary of Branch Circuit Sizes for Power Panelboard D (PPD)
Table 7. Summary of Branch Circuit Sizes for the Main Power Panelboard
One Line Riser Diagram
Figure 1. One Line Riser Diagram for Power Panelboard A (PPA)
Figure 2. One Line Riser Diagram for Power Panelboard B (PPB)
Figure 3. One Line Riser Diagram for Power Panelboard C (PPC)
Figure 4. One Line Riser Diagram for Power Panelboard D (PPD)
Figure 5. One Line Riser Diagram for the Main Power Panelboard
Detailed Computations for Branch Circuit
Power Panelboard A (PPA)
Power Panelboard B (PPB)
Power Panelboard C (PPC)
Power Panelboard D (PPD)
Detailed Computations for Main Power Panelboard
Service Entrance Sizing for Power Panelboard A (PPA)
Service Entrance Sizing for Power Panelboard B (PPB)
Service Entrance Sizing for Power Panelboard C (PPC)
Service Entrance Sizing for Power Panelboard D (PPD)
Service Entrance Sizing for Main Power Panelboard
Appendices
Project Overview

The project involved designing an electrical plan for a 1-storey residential house in
Alcate, Victoria, Oriental Mindoro. The house has a floor area of approximately 391 square
meters and consists of a living room, dining area, kitchen, bathroom, garage, scullery, two
bedrooms, and a master bedroom.
The following assumptions were made for the computations:

 The voltage supplied will be 220 V.


 THHW Copper Conductors at 90°C and rigid PVC tubes will be used as insulators for
conductors and conduits, respectively.
 Energetic Light Bulbs 75-W 1200lm light bulbs will be used for the lighting of the whole
house. Two lamps per fixture will be used.
 The capacity of the panel board is 10 circuit breakers.
 For air-conditioning unit sizing, 30 BTU/ft2 will be used as heating coefficient.
Appliance
Table Brand with brand,
1. List of appliances Model Wattage
model, wattage, Sample Image
and sample image.

Air
CS-PU12VKH-8
Conditioner Panasonic 1070

Electric Samsung NE59J7630SS 3300


Range

Microwave
Samsung MC35R8088LC 2850
Oven

Rice
Panasonic SRY18G 600
Cooker

Blender Nutribullet NBF35520-23 1500

Refrigerator Samsung RF85A920CSG 160


Water
Panasonic DH 3JP2P 3500
Heater

Exhaust
Asahi EF-24 600
Fan

Stand Fan Panasonic F-405LB


60

Flat Screen UHD KD


Sony 388
TV 85x80L

Washer
LG FV1208D4W 1200
and Dryer

SON-CMT-
Audio
Sony MAINSB40BT-
System 50
KSP
Water
Ingco VPM3708 370
Pump

Desktop ACER
TC1750-I78G 300
Computer ASPIRE

Water
Asahi WD-107 500
Dispenser

Coffee Bambino Plus


Breville 1600
Maker BES500
Light Computations

Recommended
Area Area Lumens No. of No. of
CU LLF Illumination
Description (m2) Produced Lamps Fixtures
(lux)
Living
43.45 0.45 0.80 100 12069.44 10.06 5.03
Room
Dining
51.1 0.45 0.80 150 21291.67 17.74 8.87
Room
Kitchen 73.54 0.45 0.80 1500 3064146.67 255.34 127.67
Master’s
42.35 0.45 0.80 500 58819.44 49.02 24.51
Bedroom
Room A 33 0.45 0.80 500 45833.34 38.2 19.1
Room B 33 0.45 0.80 500 45833.34 38.2 19.1
Wardrobe 8 0.35 0.70 500 16326.53 13.60 6.8
Master’s
11.25 0.35 0.70 500 22959.18 19.13 9.565
Bathroom
Bathroom A 6.6 0.35 0.70 500 13469.38 11.22 5.61
Bathroom B 6.6 0.35 0.70 500 13469.38 11.22 5.61
Main
9.88 0.35 0.70 500 20163.26 16.80 8.4
Bathroom
Scullery 16.72 0.35 0.70 500 33510.20 27.92 13.96
Garage 39 0.25 0.60 100 26000 21.67 10.835
Table 2. Summary of lighting computations.

Detailed Computation for Lighting


No. of Lamps Recommended

( Recommended Illumination)( Area per Luminaire)


¿
( Lamp Lumens per Luminaire)(CU )(LLF )(2 Lamps per Fixture )
Lumens produced by a single lamp = 1200 lm

Kitchen
Living Room

100 lux× 43.45 m2


=5.03 fixtures 1500 lux× 73.54 m2
lamps =127.67 fixtures
1200lm × 0.45× 0.80 ×2 lamps
fixture 1200lm × 0.45× 0.80 ×2
fixture
Adjusted = 3 fixtures
Master’s Bedroom
Dining Room
2
500 lux× 42.35 m
=24.51 fixtures
lamps
1200lm × 0.45× 0.80 ×2
fixture
Bathroom A
150 lux ×51.1 m2
=8.87 fixtures
lamps
1200lm × 0.45× 0.80 ×2
fixture 500 lux× 6.6 m2
=5.61 fixtures
lamps
Adjusted = 4 fixtures 1200lm × 0.35× 0.70 ×2
fixture
Room A
Adjusted = 1 fixture
2
500 lux ×33 m Bathroom B
=19.1 fixtures
lamps
1200lm × 0.45× 0.80 ×2
fixture
2
500 lux× 6.6 m
Adjusted = 1 fixture =5.61 fixtures
lamps
1200lm × 0.35× 0.70 ×2
Room B fixture

500 lux ×33 m


2 Adjusted = 1 fixture
=19.1 fixtures
lamps Main Bathroom
1200lm × 0.45× 0.80 ×2
fixture
Adjusted = 1 fixture 500 lux× 9.88 m
2
=8.4 fixtures
Wardrobe lamps
1200lm × 0.35× 0.70 ×2
fixture
500 lux× 8 m2
=6.8 fixtures
lamps
1200lm × 0.35× 0.70 ×2
fixture
Adjusted = 1 fixtures
Master’s Bathroom
2
500 lux ×11.25 m
=9.565 fixtures
lamps
1200lm × 0.35× 0.70 ×2
fixture
Adjusted = 1 fixtures
Note: Additional 8 fixtures were added on the outside of the house.

Branch Circuit Sizing

Table 3: Summary of branch circuit sizes for power panelboard A (PPA).


PANEL: Power Panelboard A
FEEDER CONDUCTOR: 22 mm2 Copper Conductor in a 25 mm Rigid PVC Conduit
Current Conductor Circuit Breaker
Conduit
No Qty Description Size Size Ampacity No. of Frame Trip
Insulator (mm)
(A) mm2 (A) Poles (A) (A)
General THHW
1 8 12 2 25 2 50 15 15
Lighting 90° Cu
General THHW
2 6 9 2 25 2 50 20 15
Purpose 90° Cu
Air Conditioning THHW
3 1 4.86 2 25 2 50 20 15
Unit 90° Cu
Garage
Air Conditioning THHW
4 1 4.86 2 25 2 50 20 15
Unit 90° Cu
General THHW
5 5 8.73 2 2 25 2 50 20 15
Purpose 100 lux ×39 m 90° Cu
THHW =10.835 fixtures
6 1 Water Heater 15.91 2 lamps 25 2 50 20 15
1200lm × 0.25× 0.60 ×2 90° Cu
7 3
General
5.73 2
fixture
THHW
25 2 50 20 15
Purpose 90° Cu
THHW
8 1 Water Heater 15.91 2 25 2 50 20 15
90° Cu
9 Spare
FEEDER BREAKER: 100 A Frame, 90 A Trip

Table 4: Summary of branch circuit sizes for power panelboard B (PPB).


PANEL: Power Panelboard B
FEEDER CONDUCTOR: 30 mm2 Copper Conductor in a 32 mm Rigid PVC Conduit
No Qty Description Current Conductor Circuit Breaker Conduit
Size Size Ampacity No. of Frame Trip
Insulator (mm)
(A) mm2 (A) Poles (A) (A)
General THHW
1 8 12 2 25 2 50 15 15
Lighting 90° Cu
General THHW
2 6 9 2 25 2 50 20 15
Purpose 90° Cu
Air Conditioning THHW
3 1 4.86 2 25 2 50 20 15
Unit 90° Cu
Microwave THHW
4 1 12.95 2 25 2 50 20 15
Oven 90° Cu
THHW
5 1 Electric Range 12 2 25 2 50 20 15
90° Cu
Water THHW
6 1 2.27 2 25 2 50 20 15
Dispenser 90° Cu
THHW
7 1 Refrigerator 0.73 2 25 2 50 20 15
90° Cu
8 Spare
9 Spare
FEEDER BREAKER: 100 A Frame, 100 A Trip

Table 5: Summary of branch circuit sizes for power panelboard C (PPC).


PANEL: Power Panelboard C
FEEDER CONDUCTOR: 14 mm2 Copper Conductor in a 25 mm Rigid PVC Conduit
FEEDER BREAKER: 100 A Frame, 60 A Trip
Current Conductor Circuit Breaker
Conduit
No Qty Description Size Size Ampacity No. of Frame Trip
Insulator (mm)
(A) mm2 (A) Poles (A) (A)
THHW
1 1 Coffee Maker 7.27 2 25 2 50 20 15
90° Cu
THHW
2 1 Rice Cooker 2.73 2 25 2 50 20 15
90° Cu
THHW
3 1 Blender 6.82 2 25 2 50 20 15
90° Cu
Washing THHW
4 1 5.45 2 25 2 50 20 15
Machine 90° Cu
THHW
5 1 Water Pump 1.68 2 25 2 50 20 15
90° Cu
General THHW
6 2 3 2 25 2 50 20 15
Purpose 90° Cu
THHW
7 5 Garage 7.5 2 25 2 50 20 15
90° Cu
8 Spare
9 Spare

Table 6: Summary of branch circuit sizes for power panelboard D (PPD).


PANEL: Power Panelboard D
FEEDER CONDUCTOR: 22 mm2 Copper Conductor in a 25 mm Rigid PVC Conduit
FEEDER BREAKER: 100 A Frame, 90 A Trip

No Qty Description Current Conductor Circuit Breaker Conduit


Size Size Ampacity No. of Frame Trip
Insulator (mm)
(A) mm2 (A) Poles (A) (A)
General THHW
1 6 9 2 25 2 50 15 15
Lighting 90° Cu
General THHW
2 6 9 2 25 2 50 20 15
Purpose 90° Cu
General THHW
3 3 5.73 2 25 2 50 20 15
purpose 90° Cu
Water Heater THHW
4 1 15.91 2 25 2 50 20 15
90° Cu
Air Conditioning THHW
5 1 4.86 2 25 2 50 20 15
Unit 90° Cu
Air Conditioning THHW
6 1 4.86 2 25 2 50 20 15
Unit 90° Cu
General THHW
7 3 5.73 2 25 2 50 20 15
purpose 90° Cu
Water Heater THHW
8 1 15.91 2 25 2 50 20 15
90° Cu
9 Spare

Table 7: Summary of branch circuit sizes for the main panelboard.


PANEL: Main Power Panelboard
FEEDER CONDUCTOR: 200 mm2 Copper Conductor in a 65 mm Rigid PVC Conduit
FEEDER BREAKER: 400 A Frame, 350 A Trip
Current Conductor Circuit Breaker
Conduit
No Qty Description Size Size Ampacity No. of Frame Trip
Insulator (mm)
(A) mm2 (A) Poles (A) (A)
THHW
1 1 PPA 79.86 22 90 2 50 90 25
90° Cu
THHW
2 1 PPB 90.72 30 115 2 100 100 32
90° Cu
THHW
3 1 PPC 57.49 14 70 2 50 60 25
90° Cu
THHW
4 1 PPD 79.86 22 90 2 50 90 25
90° Cu
5 Spare 2 50 15 15
6 Spare 2 50 15 15
7 Spare 2 50 15 15
8 Spare 2 50 15 15
9 Spare
One Line Riser Diagrams

A 90 A Trip 22mm2 THHW Cu

(spare) 9 20 A 20 A
AAc AAc
2mm2 THHW Cu 7 8 2mm2 THHW Cu

20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu

20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu 1 2 2mm2 THHW Cu

Figure 1. One Line Riser Diagram for Power Panelboard A (PPA)


B 100 A Trip 30 mm2 THHW Cu

(spare) 9 20 A
AAc
2mm2 THHW Cu 7 8 (spare)
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu

20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu
1 2 2mm2 THHW Cu

Figure 2. One Line Riser Diagram for Power Panelboard B (PPB)


C 60 A Trip 14mm2 THHW Cu

(spare) 9 20 A
AAc
2mm2 THHW Cu 7 8 (spare)
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu

20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 1 2 2mm2 THHW Cu

Figure 3. One Line Riser Diagram for Power Panelboard C (PPC)


D 90 A Trip 22mm2 THHW Cu

(spare) 9 20 A 20 A
AAc AAc
2mm2 THHW Cu 7 8 2mm2 THHW Cu

20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu

20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu
1 2 2mm2 THHW Cu

Figure 4. One Line Riser Diagram for Power Panelboard D (PPD)


M 350 A Trip 200mm2 THHW Cu

(spare) 9
(spare) 7 8 (spare)

(spare)
5 6 (spare)
60 A 90 A
AAc AAc
14mm2 THHW Cu 3 4 22mm2 THHW Cu
90 A 100
AAc A
22mm2 THHW Cu 1 AAc 2 30mm2 THHW Cu

Figure 5. One Line Riser Diagram for Main Power Panelboard


Detailed Computations for Branch Circuit

Power Panelboard A (PPA)


Branch Circuit No. 1
8 receptacles x 1.5 estimated load = 12 A
Branch Circuit No. 2
6 outlets x 1.5 estimated load = 9 A
Branch Circuit No. 3
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 4
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 5
Components: 2 receptacle, 2 outlet, and 1 exhaust fan
Exhaust fan wattage: 600 W
600W
=2.73 A
220 V
(2 outlets x 1.5 estimated load) + 2.73 A = 5.73 A
2 receptacles x 1.5 estimated load = 3 A
5.73 A + 3 A = 8.73 A
Branch Circuit No. 6
Water heater wattage: 3500 W
3500W
=15.91 A
220 V
Branch Circuit No. 7
Components: 1 receptacle, 1 outlet, and 1 exhaust fan
Exhaust fan wattage: 600 W
600W
=2.73 A
220 V
(1 outlet x 1.5 estimated load) + 2.73 A = 4.23 A
1 receptacle x 1.5 estimated load = 1.5 A
4.23 A + 1.5 A = 5.73 A
Branch Circuit No. 8
Water heater wattage: 3500 W
3500W
=15.91 A
220 V

Conductor, Circuit Breaker & Conduit Selection for PPA


50 A Frame 15 A Trip
Branch Circuit:
Branch Circuit No. 1
Conductor Size: 2 mm2
Conduit Size: 15 mm

50 A Frame 20 A Trip
Branch Circuit:
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Branch Circuit No. 8
Conductor Size: 2 mm2
Conduit Size: 15 mm
Power Panelboard B (PPB)
Branch Circuit No. 1
8 receptacles x 1.5 estimated load = 12 A
Branch Circuit No. 2
6 outlets x 1.5 estimated load = 9 A
Branch Circuit No. 3
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 4
Microwave oven wattage: 2850 W
2850W
=12.95 A
220 V
Branch Circuit No. 5
Electric range wattage: 3300 W
Applying demand system, Nameplate rating up to 3.3kW, demand factor = 80%
3300 W x 0.80 = 2640 W
2640W
=12 A
220 V

Branch Circuit No. 6


Water dispenser wattage: 500 W

                                   
Branch Circuit No. 7
Refrigerator wattage: 160 W

                                   

Conductor, Circuit Breaker & Conduit Selection for PPB


50 A Frame 15 A Trip
Branch Circuit:
Branch Circuit No. 1
Conductor Size: 2 mm2
Conduit Size: 15 mm

50 A Frame 20 A Trip
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Conductor Size: 2 mm2
Conduit Size: 15 mm

Power Panelboard C (PPC)


Branch Circuit No. 1
Coffee maker wattage: 1600 W
1600W
=7.27 A
220 V
Branch Circuit No. 2
Rice cooker wattage: 600 W
600W
=2.73 A
220 V
Branch Circuit No. 3
Blender wattage: 1500 W
1500W
=6.82 A
220 V
Branch Circuit No. 4
Washing machine wattage: 1200 W
1200W
=5.45 A
220 V
Branch Circuit No. 5
Water pump wattage: 370 W
370W
=1.68 A
220 V
Branch Circuit No. 6
Components: 1 receptacle, and 1 outlet
1 receptacle x 1.5 estimated load = 1.5 A
1 outlet x 1.5 estimated load = 1.5 A
1.5 A + 1.5 A = 3 A
Branch Circuit No. 7
Components: 3 receptacles, and 2 outlets
3 receptacles x 1.5 estimated load = 4.5 A
2 outlets x 1.5 estimated load = 3 A
4.5 A + 3 A = 7.5 A

Conductor, Circuit Breaker & Conduit Selection for PPC


50 A Frame 20 A Trip
Branch Circuit:
Branch Circuit No. 1
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Conductor Size: 2 mm2
Conduit Size: 15 mm

Power Panelboard D (PPD)


Branch Circuit No. 1
6 receptacles x 1.5 estimated load = 9 A
Branch Circuit No. 2
6 outlets x 1.5 estimated load = 9 A
Branch Circuit No. 3
Components: 1 receptacle, 1 outlet, and 1 exhaust fan
Exhaust fan wattage: 600 W
600W
=2.73 A
220 V
(1 outlet x 1.5 estimated load) + 2.73 A = 4.23 A
1 receptacle x 1.5 estimated load = 1.5 A
4.23 A + 1.5 A = 5.73 A
Branch Circuit No. 4
Water heater wattage: 3500 W
3500W
=15.91 A
220 V
Branch Circuit No. 5
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 6
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 7
Components: 1 receptacle, 1 outlet, and 1 exhaust fan
Exhaust fan wattage: 600 W
600W
=2.73 A
220 V
(1 outlet x 1.5 estimated load) + 2.73 A = 4.23 A
1 receptacle x 1.5 estimated load = 1.5 A
4.23 A + 1.5 A = 5.73 A
Branch Circuit No. 8
Water heater wattage: 3500 W
3500W
=15.91 A
220 V

Conductor, Circuit Breaker & Conduit Selection for PPD


50 A Frame 15 A Trip
Branch Circuit:
Branch Circuit No. 1
Conductor Size: 2 mm2
Conduit Size: 15 mm
50 A Frame 20 A Trip
Branch Circuit:
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Branch Circuit No. 8
Conductor Size: 2 mm2
Conduit Size: 15 mm

Main Panelboard
Service Entrance Sizing for PPA
A. General Lighting & Required Circuits
Floor Area: 391 m2
VA
391 m2 x 32 2 = 12512 VA
m
No. of General-Purpose Circuits: 4 Branch Circuits
1500 VA x 4 branch Circuits = 6000 VA
Total Load: 12512 VA + 6000 VA = 18512 VA
Applying Demand System:
3000 VA x 100% = 3000 VA
(18512 VA – 3000 VA) x 0.35 = 5429.2 VA
Total: 3000 VA + 5429.2 VA = 8429.2 W
B. Heating and Air Conditioning
Air Conditioner Size Estimation for master’s bedroom:
1. Floor Area (master’s bedroom): 42.35 m2
2
1 ft
42.35 m2 x ( ) =455.85 ft 2
0.3048 m
2 Btu
455.85 ft x 30 2
=13675.5 BTU
ft
2. Windows
North Facing: N/A
South Facing:
(0.9 m x 1.2 m) x 2 x 871 = 1881.36 BTU
3. Person Load:
2 persons x 400 = 800 BTU
4. Lighting Load:
lamps Btu
2 fixtures x 2 x 75 W x 4.25 = 1275 BTU
fixtures W
5. Appliance Load:
Desktop: 300 W x 3.15 = 945 BTU
Stand Fan: 60 W x 3.15 = 189 BTU
Total:
(13675.5 BTU + 1881.36 BTU + 800 BTU + 1275 BTU + 945 BTU + 189
BTU)
= 18765.86 BTU
Air conditioning capacity: 18765.86 BTU
Air conditioning wattage: 1070 W

Air Conditioner Size Estimation for living room:


1. Floor Area (living room): 43.45 m2
2
1 ft 2
43.45 m2 x ( ) =467.69 ft
0.3048 m
2 Btu
467.29 ft x 30 2
=14030.7 BTU
ft
2. Windows
North Facing: N/A
South Facing:
(0.9 m x 1.2 m) x 2 x 871 = 1881.36 BTU
3. Person Load:
4 persons x 400 = 1600 BTU
4. Lighting Load:
lamps Btu
3 fixtures x 2 x 75 W x 4.25 = 1912.5 BTU
fixtures W
5. Appliance Load:
Television: 388 W x 3.15 = 1222.2 BTU
Audio System: 50 W x 3.15 = 157.5 BTU
Stand Fan: 60 W x 3.15 = 189 BTU
Total: 1222.2 BTU + 157.5 BTU + 189 BTU = 1568.7 BTU
Total:
(14030.7 BTU + 1881.36 BTU + 1912.5 BTU + 1275 BTU +
1568.7 BTU) = 20993.26 BTU
Air conditioning capacity: 20993.26BTU
Air conditioning wattage: 1070 W

B. Other Appliances
Fixed:
Water Heater = 3500 W
2 x 3500 W = 7000 W
Total Demand Load:
8429.2 W + 1070 + 1070 + 7000 W = 17569.2 W
17569.2W
=79.86 A
220 V

Use 100 A Frame, 90 A Trip circuit breaker with 22 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.

Service Entrance Sizing for PPB


A. General Lighting & Required Circuits
Floor Area: 391 m2
VA
391 m2 x 32 2 = 12512 VA
m
No. of General-Purpose Circuits: 2 Branch Circuits
1500 VA x 2 branch Circuits = 3000 VA
Total Load: 12512 VA + 3000 VA = 15512 VA
Applying Demand System:
3000 VA x 100% = 3000 VA
(15512 VA – 3000 VA) x 0.35 = 4379.2 VA
Total: 3000 VA + 4379.2 VA = 7379.2 W
B. Heating and Air Conditioning
Air Conditioner Size Estimation for dining room:
1. Floor Area (dining room): 51.1 m2
2
1 ft
51.1 m2 x ( ) =550.04 ft 2
0.3048 m
Btu
550.04 ft 2 x 30 2
=16501.2 BTU
ft
2. Windows
North Facing: N/A
South Facing: N/A
3. Person Load:
4 persons x 400 = 1600 BTU
4. Lighting Load:
lamps Btu
4 fixtures x 2 x 75 W x 4.25 = 2550 BTU
fixtures W
5. Appliance Load: N/A
Total:
(13562.53 BTU + 1600 BTU + 2550 BTU) = 17712.53 BTU
Air conditioning capacity: 17712.53 BTU
Air conditioning wattage: 1070 W
C. Electric Range
Electric range wattage: 3300 W
Applying Demand System for one range: R<12000W
Demand Load = 8000 VA
D. Other appliances
Fixed: N/A
Non-fixed:
Microwave Oven: 2850 W
Refrigerator: 160 W
Water Dispenser: 500 W
Total: 3510 W

Total Demand Load:


7379.2 W + 1070 W + 8000 W + 3510 W = 19959.2 W
19959.2W
=90.72
220 V
Use 100 A Frame, 100 A Trip circuit breaker with 30 mm2 Copper Conductor with
THHW @ 90°C insulation in 32 mm diameter conduit.

Service Entrance Sizing for PPC


A. General Lighting & Required Circuits
Floor Area: 391 m2
VA
391 m2 x 32 2 = 12512 VA
m
No. of General-Purpose Circuits: 2 Branch Circuits
1500 VA x 1 branch Circuits = 3000 VA
Total Load: 12512 VA + 3000 VA = 15512 VA
Applying Demand System:
3000 VA x 100% = 3000 VA
(15512 VA – 3000 VA) x 0.35 = 4379.2 VA
Total: 3000 VA + 4379.2 VA = 7379.2 W
B. Other Appliances
Fixed:
Washing Machine: 1200 W
Water Pump: 370 W
Non-fixed:
Coffee Maker: 1600
Blender: 1500 W
Rice Cooker: 600 W
Total: 5270 W
Total Demand Load:
7379.2 W + 5270 W = 12649.2 W
12649.2W
=57.49 A
220 V

Use 100 A Frame, 60 A Trip circuit breaker with 14 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.

Service Entrance Sizing for PPD


A. General Lighting & Required Circuits
Floor Area: 391 m2
VA
391 m2 x 32 2 = 12512 VA
m
No. of General-Purpose Circuits: 4 Branch Circuits
1500 VA x 8 branch Circuits = 6000 VA
Total Load: 12512 VA + 6000 VA = 18512 VA
Applying Demand System:
3000 VA x 100% = 3000 VA
(18512 VA – 3000 VA) x 0.35 = 5429.2 VA
Total: 3000 VA + 5429.2 VA = 8429.2 W
B. Heating and Air Conditioning
Air Conditioner Size Estimation for bedroom A:
1. Floor Area (bedroom A): 33 m2
2
1 ft
42 m2 x ( ) =355.21 ft 2
0.3048 m
2 Btu
355.21 ft x 30 2
=10656.27 BTU
ft
2. Windows
North Facing:
(0.9 m x 1.2 m) x 1 x 166 = 179.28 BTU
South Facing: N/A
3. Person Load:
1 person x 400 = 400 BTU
4. Lighting Load:
lamps Btu
2 fixtures x 2 x 75 W x 4.25 = 1275 BTU
fixtures W
5. Appliance Load:
Desktop: 300 W x 3.15 = 945 BTU
Stand Fan: 60 W x 3.15 = 189 BTU
Total:
(10656.27 BTU + 179.28 BTU+ 400 BTU + 1275 BTU + 945 BTU
+ 189 BTU)
= 13644.55 BTU
Air conditioning capacity: 13644.55 BTU
Air conditioning wattage: 1070 W

Air Conditioner Size Estimation for bedroom B:


1. Floor Area (bedroom B): 33 m2
2
1 ft 2
42 m x (
2
) =355.21 ft
0.3048 m
2 Btu
355.21 ft x 30 =10656.27 BTU
ft 2
2. Windows
North Facing:
(0.9 m x 1.2 m) x 1 x 166 = 179.28 BTU
South Facing: N/A
3. Person Load:
1 person x 400 = 400 BTU
4. Lighting Load:
lamps Btu
2 fixtures x 2 x 75 W x 4.25 = 1275 BTU
fixtures W
5. Appliance Load:
Desktop: 300 W x 3.15 = 945 BTU
Stand Fan: 60 W x 3.15 = 189 BTU
Total:
(10656.27 BTU + 179.28 BTU+ 400 BTU + 1275 BTU + 945 BTU
+ 189 BTU)
= 13644.55 BTU
Air conditioning capacity: 13644.55 BTU
Air conditioning wattage: 1070 W
C. Other Appliances
Fixed:
Water Heater = 3500 W
2 x 3500 W = 7000 W
Total Demand Load:
8429.2 W + 1070 W + 1070 W + 7000 W = 17569.2W
17569.2W
=79.86 A
220 V

Use 100 A Frame, 90 A Trip circuit breaker with 22 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.

Service Entrance Sizing for Main Panelboard


79.86 A + 90.72 A + 57.49 A + 79.86 A = 307.93 A

Use 400 A Frame, 350 A Trip circuit breaker with 200 mm2 Copper Conductor with
THHW @ 90°C insulation in 65 mm diameter conduit.
Appendices
Table 1. Recommended illumination for residences.

Table 2. Coefficient of utilization.

Table 3. Light of Loss Factor


Table 4. Typical Molded Case Circuit Breaker Characteristics.

Table 5. Allowable ampacities of insulated conductors.


Table 6. Rigid PVC Conduit Allowable Sizes.