ABP 22 Ab Eelectrification and Control Systems
ABP 22 Ab Eelectrification and Control Systems
Submitted by:
De Austria, Manny M.
Submitted to:
Engr. Mark Keylord S. Onal
The project involved designing an electrical plan for a 1-storey residential house in
Alcate, Victoria, Oriental Mindoro. The house has a floor area of approximately 391 square
meters and consists of a living room, dining area, kitchen, bathroom, garage, scullery, two
bedrooms, and a master bedroom.
The following assumptions were made for the computations:
Air
CS-PU12VKH-8
Conditioner Panasonic 1070
Microwave
Samsung MC35R8088LC 2850
Oven
Rice
Panasonic SRY18G 600
Cooker
Exhaust
Asahi EF-24 600
Fan
Washer
LG FV1208D4W 1200
and Dryer
SON-CMT-
Audio
Sony MAINSB40BT-
System 50
KSP
Water
Ingco VPM3708 370
Pump
Desktop ACER
TC1750-I78G 300
Computer ASPIRE
Water
Asahi WD-107 500
Dispenser
Recommended
Area Area Lumens No. of No. of
CU LLF Illumination
Description (m2) Produced Lamps Fixtures
(lux)
Living
43.45 0.45 0.80 100 12069.44 10.06 5.03
Room
Dining
51.1 0.45 0.80 150 21291.67 17.74 8.87
Room
Kitchen 73.54 0.45 0.80 1500 3064146.67 255.34 127.67
Master’s
42.35 0.45 0.80 500 58819.44 49.02 24.51
Bedroom
Room A 33 0.45 0.80 500 45833.34 38.2 19.1
Room B 33 0.45 0.80 500 45833.34 38.2 19.1
Wardrobe 8 0.35 0.70 500 16326.53 13.60 6.8
Master’s
11.25 0.35 0.70 500 22959.18 19.13 9.565
Bathroom
Bathroom A 6.6 0.35 0.70 500 13469.38 11.22 5.61
Bathroom B 6.6 0.35 0.70 500 13469.38 11.22 5.61
Main
9.88 0.35 0.70 500 20163.26 16.80 8.4
Bathroom
Scullery 16.72 0.35 0.70 500 33510.20 27.92 13.96
Garage 39 0.25 0.60 100 26000 21.67 10.835
Table 2. Summary of lighting computations.
Kitchen
Living Room
(spare) 9 20 A 20 A
AAc AAc
2mm2 THHW Cu 7 8 2mm2 THHW Cu
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu 1 2 2mm2 THHW Cu
(spare) 9 20 A
AAc
2mm2 THHW Cu 7 8 (spare)
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu
1 2 2mm2 THHW Cu
(spare) 9 20 A
AAc
2mm2 THHW Cu 7 8 (spare)
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 1 2 2mm2 THHW Cu
(spare) 9 20 A 20 A
AAc AAc
2mm2 THHW Cu 7 8 2mm2 THHW Cu
20 A 20 A
AAc
2mm2 THHW Cu 5 6 2mm2 THHW Cu
20 A 20 A
AAc AAc
2mm2 THHW Cu 3 4 2mm2 THHW Cu
15 A 20 A
AAc AAc
2mm2 THHW Cu
1 2 2mm2 THHW Cu
(spare) 9
(spare) 7 8 (spare)
(spare)
5 6 (spare)
60 A 90 A
AAc AAc
14mm2 THHW Cu 3 4 22mm2 THHW Cu
90 A 100
AAc A
22mm2 THHW Cu 1 AAc 2 30mm2 THHW Cu
50 A Frame 20 A Trip
Branch Circuit:
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Branch Circuit No. 8
Conductor Size: 2 mm2
Conduit Size: 15 mm
Power Panelboard B (PPB)
Branch Circuit No. 1
8 receptacles x 1.5 estimated load = 12 A
Branch Circuit No. 2
6 outlets x 1.5 estimated load = 9 A
Branch Circuit No. 3
Air conditioning unit wattage: 1070 W
1070W
=4.86 A
220 V
Branch Circuit No. 4
Microwave oven wattage: 2850 W
2850W
=12.95 A
220 V
Branch Circuit No. 5
Electric range wattage: 3300 W
Applying demand system, Nameplate rating up to 3.3kW, demand factor = 80%
3300 W x 0.80 = 2640 W
2640W
=12 A
220 V
Branch Circuit No. 7
Refrigerator wattage: 160 W
50 A Frame 20 A Trip
Branch Circuit No. 2
Branch Circuit No. 3
Branch Circuit No. 4
Branch Circuit No. 5
Branch Circuit No. 6
Branch Circuit No. 7
Conductor Size: 2 mm2
Conduit Size: 15 mm
Main Panelboard
Service Entrance Sizing for PPA
A. General Lighting & Required Circuits
Floor Area: 391 m2
VA
391 m2 x 32 2 = 12512 VA
m
No. of General-Purpose Circuits: 4 Branch Circuits
1500 VA x 4 branch Circuits = 6000 VA
Total Load: 12512 VA + 6000 VA = 18512 VA
Applying Demand System:
3000 VA x 100% = 3000 VA
(18512 VA – 3000 VA) x 0.35 = 5429.2 VA
Total: 3000 VA + 5429.2 VA = 8429.2 W
B. Heating and Air Conditioning
Air Conditioner Size Estimation for master’s bedroom:
1. Floor Area (master’s bedroom): 42.35 m2
2
1 ft
42.35 m2 x ( ) =455.85 ft 2
0.3048 m
2 Btu
455.85 ft x 30 2
=13675.5 BTU
ft
2. Windows
North Facing: N/A
South Facing:
(0.9 m x 1.2 m) x 2 x 871 = 1881.36 BTU
3. Person Load:
2 persons x 400 = 800 BTU
4. Lighting Load:
lamps Btu
2 fixtures x 2 x 75 W x 4.25 = 1275 BTU
fixtures W
5. Appliance Load:
Desktop: 300 W x 3.15 = 945 BTU
Stand Fan: 60 W x 3.15 = 189 BTU
Total:
(13675.5 BTU + 1881.36 BTU + 800 BTU + 1275 BTU + 945 BTU + 189
BTU)
= 18765.86 BTU
Air conditioning capacity: 18765.86 BTU
Air conditioning wattage: 1070 W
B. Other Appliances
Fixed:
Water Heater = 3500 W
2 x 3500 W = 7000 W
Total Demand Load:
8429.2 W + 1070 + 1070 + 7000 W = 17569.2 W
17569.2W
=79.86 A
220 V
Use 100 A Frame, 90 A Trip circuit breaker with 22 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.
Use 100 A Frame, 60 A Trip circuit breaker with 14 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.
Use 100 A Frame, 90 A Trip circuit breaker with 22 mm2 Copper Conductor with THHW
@ 90°C insulation in 25 mm diameter conduit.
Use 400 A Frame, 350 A Trip circuit breaker with 200 mm2 Copper Conductor with
THHW @ 90°C insulation in 65 mm diameter conduit.
Appendices
Table 1. Recommended illumination for residences.