0% found this document useful (0 votes)
188 views2 pages

Summary of Nfpa 13 13r 13d Differences

This document summarizes the key differences between NFPA 13, NFPA 13R, and NFPA 13D sprinkler system standards. NFPA 13R targets life safety in residential occupancies by focusing sprinklers in high risk areas, unlike NFPA 13 which aims for both life safety and property protection. NFPA 13D has the least restrictive requirements and applies to one- and two-family homes. The document provides a table outlining differences in permitted building heights, occupancy types, and areas allowed to be omitted from sprinkler coverage between the three standards.

Uploaded by

Geovanny Portero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
188 views2 pages

Summary of Nfpa 13 13r 13d Differences

This document summarizes the key differences between NFPA 13, NFPA 13R, and NFPA 13D sprinkler system standards. NFPA 13R targets life safety in residential occupancies by focusing sprinklers in high risk areas, unlike NFPA 13 which aims for both life safety and property protection. NFPA 13D has the least restrictive requirements and applies to one- and two-family homes. The document provides a table outlining differences in permitted building heights, occupancy types, and areas allowed to be omitted from sprinkler coverage between the three standards.

Uploaded by

Geovanny Portero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SUMMARY 

OF DIFFERENCES 
NFPA 13, NFPA 13R, & NFPA 13D 
Unlike NFPA 13, NFPA 13R works to make the installation of the sprinkler system more affordable and accessible for 
residential occupancies by targeting the areas of highest fire risk to life safety with sprinkler systems. Swapping NFPA 13 
and NFPA 13R is not simply a one‐for‐one exchange, as their goals are overall quite different. NFPA 13D, by extension, is 
the least restrictive standard and intended for one or two family residential properties. 

References to the building code are to the International Building Code, as it's typically the most prevalent used in the US. 
As always, there's far more detail to many of these requirements than can be summarized in two pages ‐ so be sure to 
use the supplied section references to gather more information on specifics for your project. 

Find many more articles and resources like this at www.MeyerFire.com. 

CODE PLANNING       
  NFPA 13  NFPA 13R  NFPA 13D 
Life Safety   Life Safety Only 
Life Safety Only 
Objective  + Property Protection   [NFPA 13D 2002‐2019 
[NFPA 13R 2002‐2019 1.2] 
[NFPA 13 2002‐2019 1.2.1]  1.2.1] 
Yes 
Considered “Fully‐Sprinklered” for 
[IBC ref. section 903.1.1 as  No  No 
Code Purposes? 
fully‐sprinklered] 
Yes  Only for R‐Occupancy 
Building Height Increases Permitted?  No 
[IBC Table 504]  [IBC Table 504] 
Permitted in One & Two‐Family, or 
Yes  Yes  Yes 
Group R‐3 & R‐4 Condition 1 and 
[IBC 903.1.1]  [IBC 903.1.2]  [IBC 903.3.1.3] 
townhouse R‐Occupancies?  
Permitted in R‐Occupancies up to 4  Yes  Yes 
No 
stories?  [IBC 903.1.1]  [IBC 903.1.2] 
Permitted in Mixed Use /   Yes  No 
No 
Non‐Residential Occupancies?  [IBC Table 508.4, 508.3.1]  [IBC 903.1.2] 
       
   

 
Page 1 of 2 | Updated December 2019                                                                                              More Resources at www.MeyerFire.com 
OMITTED AREAS       
  NFPA 13  NFPA 13R  NFPA 13D 
If non‐comb., small, or filled 
Yes  Yes 
with non‐comb. insulation 
Omit in Attics?  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
[NFPA 13 2002 8.14.1.2, 
2007 6.9.6, 2010‐19 6.6.6]  8.6.5, 2019 8.3.5] 
2007‐2016 8.15.1.2] 
Yes  Yes  Yes 
Bathrooms in Units less than 55 sqft w/ 
 [NFPA 13 2002 8.14.8.1,  [NFPA 13R 2002 6.8.2,  [NFPA 13D 2007‐10 
15‐min. Non‐Combustible Lining? 
2007‐16 8.15.8.1.1]  2007 6.9.2, 2010‐19 6.6.2]  8.6.2, 2013‐19 8.3.2] 
Closets in Hotel or Motel w/ Non‐ Yes  Yes 
Combustible Surface less than 24 sqft,  [NFPA 13 2002 8.14.8.2,  [NFPA 13R 2002 6.8.3,  N/A 
or Hospital Less than 6 sqft?1  2007‐16 8.15.8.2]  2007 6.9.3, 2010‐19 6.6.3] 
Yes  Yes 
Closets w/ Non‐Combustible Surface 
No, Required  [NFPA 13R 2002 6.8.3,  [NFPA 13D 2007‐10 
less than 24 sqft?1 
2007 6.9.3, 2010‐19 6.6.3]  8.6.3, 2013‐19 8.3.3] 
Yes  Yes 
Closets on Exterior Balconies or 
No, Required  [NFPA 13R 2002 6.8.6,  [NFPA 13D 2013‐19 
Breezeways & Exterior Access?1 
2007 6.9.7, 2010‐19 6.6.7]  8.3.8] 
Yes if non‐comb., filled with 
Yes  Yes 
non‐comb. insulation1 
Concealed Spaces?  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
[NFPA 13 2002 8.14.1.2, 
2007 6.9.6, 2010‐19 6.6.6]  8.6.5, 2013‐19 8.3.5] 
2007‐2016 8.15.1.2] 
Yes  Yes 
Concealed Spaces with only Ventilation 
No, Required  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
Equipment?1 
2007 6.9.6, 2010‐19 6.6.6]  8.6.5, 2013‐19 8.3.5] 
Yes  Yes 
Elevator Machine Rooms?  No, Required  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
2007 6.9.6, 2010‐19 6.6.6]  8.6.5, 2013‐19 8.3.5] 
Yes 
Garages, Carports?  No, Required  No, Required  [NFPA 13D 2007‐10 
8.6.3, 2013‐19 8.3.4] 
Yes  Yes 
Penthouse Equipment Rooms?  No, Required  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
2007 6.9.6, 2010‐19 6.6.6]  8.6.5, 2013‐19 8.3.5] 
Yes  Yes 
Porches?  No, Required  [NFPA 13R 2002 6.8.5,  [NFPA 13D 2007‐10 
2007 6.9.6, 2010‐19 6.6.6]  8.6.3, 2013‐19 8.3.4] 
 
     
HYDRAULIC CALCULATIONS 
  NFPA 13  NFPA 13R  NFPA 13D 
Four1 
Four1  Two1 
Max Number of Adjacent Calculated  [NFPA 13R 2007 6.7.1.2, 
[NFPA 13 2002 11.2.3.5.1,  [NFPA 13D 2002‐10 
Residential Sprinklers  2007 6.8.1.2, 2010‐19 
2007‐16 11.3.1.1]  8.1.2, 2013‐19 10.2] 
7.1.1.3] 
Yes 
No 
[NFPA 13 2002 11.2.3.5.5, 
Hose Allowance Required?  [NFPA 13R 2007 A.6.8.2,  No 
2007 11.3.1.5, 2010‐16 
2010‐19 A.7.2] 
11.3.1.6] 
New: 0.10 gpm/sqft  0.05 gpm/sqft or listing of 
0.05 gpm/sqft or listing 
Existing: Listing of Sprinkler  sprinkler 
of sprinkler 
Minimum Residential Density  [NFPA 13 2002 11.2.3.5.2,  [NFPA 13 2002 6.7.1.1.2.2, 
[NFPA 13D 2002‐10 
2007 11.3.1.2, 2010‐16  2007 6.8.1.1.1.2, 2010‐19 
8.1.1, 2013‐19 10.1.1] 
11.3.1.3]  7.1.1] 
NFPA 13 Hydraulic  NFPA 13 Hydraulic  NFPA 13D Worksheet 
Calculation Method 
Calculations  Calculation  Calculations 
1
 Refer to the applicable code section(s) for specifics on requirements   
 
Page 2 of 2 | Updated December 2019                                                                                              More Resources at www.MeyerFire.com 