Pump Room Submersible Pumps Calc

This document provides sizing specifications for submersible sewage pumps (SP-1) located in a pump room. It determines: 1. The maximum estimated influent flow is 0 L/S based on the drainage fixture units calculation. 2. The recommended pump capacity is 54 GPM for each of two duplex pumps (one lead and one lag), to provide a total pump capacity of 54.34 GPM. 3. The total dynamic head is 15m based on calculations of static head, discharge pressure, pipe friction loss, and miscellaneous losses. The document then provides specifications for pump start/stop levels within the sump and recommends dimensions for an effective sump volume of 2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Pump Room Submersible Pumps Calc

This document provides sizing specifications for submersible sewage pumps (SP-1) located in a pump room. It determines: 1. The maximum estimated influent flow is 0 L/S based on the drainage fixture units calculation. 2. The recommended pump capacity is 54 GPM for each of two duplex pumps (one lead and one lag), to provide a total pump capacity of 54.34 GPM. 3. The total dynamic head is 15m based on calculations of static head, discharge pressure, pipe friction loss, and miscellaneous losses. The document then provides specifications for pump start/stop levels within the sump and recommends dimensions for an effective sump volume of 2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SUBMERSIBLE PUMPS SIZING

SEWAGE SUBMERSIBLE PUMPS (SP-1) :- (location: pump room)


A.) SYSTEM CAPACITY :-
Estimated Max Influent Flow

D.F.U.V
Fixture Number
Unit Total ABBREVIATIONS :-
WC-1 / EWC-1 0 4 0 FLUSH VALVE / PRIVATE USE
WC-2 / EWC-2 0 6 0 FLUSH VALVE / PUBLIC USE
WC-3 / EWC-3 0 3 0 FLUSH TANK / PRIVATE USE
LAV-1/LAVE-2 0 1 0 LAVATORY/PUBLIC OR PRIVATE USE
FD 0 2 0 FLOOR DRAIN/PUBLIC OR PRIVATE USE
AHUD & FCU (AD) 0 2 0 AIR HANDLING/FANCOIL UNITS
DWF 0 0.5 0 DRINKING WATER FOUNTAIN
PD / TD 0 2 0 PARKING / TRENCH DRAIN
J.S 0 3 0 JANITOR SINK
SH 0 2 0 SHOWER
KS 0 2 0 KITCHEN SINK
UR 0 4 0 URINAL
Total Drainage Fixture Units Value = 0 D.F.U
Drainage Design Discharge Qd = 0 GPM= 0 L/S
IN CASE OF TANK EMPTYING
VOLUME OF TANK (M3)= 305
AREA OF TANK (M2)= 112
DURATION REQUIRED TO EMPTY 10 CM TANK HEIGHT=0.5 HRS
FLOW DISCHARGE PER SUBMERSIBLE PUMP Qsp = = 49.4 GPM
3.11 L/S

TAKE THE LARGEST CAPACITY QIN = 49.4 GPM 1.92 L/S

B.) SYSTEM'S TOTAL DYNAMIC HEAD :-


Static Head = 4.00 m ( 5.69 ) psi

Discharge Pressure = 3.00 m ( 4.27 ) psi

Pipe Friction Loss = 5.00 m ( 7.11 ) psi

Miscellaneous Losses = 3.00 m ( 5.00 ) psi


Total = 15.00 m ( 22.07 ) psi

Chosen = 15 m ( 22.00 ) psi

C.) RECOMMENDED PUMP CAPACITY :-


USE DUPLEX TYPE SUBMERSIBLE SUMP PUMPS
(1 Lead + 1 Lag), each 100% is flow.
Total PUMP CAPACITY 54.34 GPM
PUMP CAPACITY ( FOR EACH ) = 54 GPM & 22.00 psi
= 3.43 L / Sec & 15 m
12.34 m3/h & 1.5 bar

Sump Dimension
Effective volume
assume pump start on 5 minutes & shut off 5 minutes.
So,pump will operating 6 times per hour

V =[ TIME(SEC)*FLOW (LITERS/SEC) ] /4
V= 514.2 LITERS Pump stop = Pump depth
Effective sump pit depth 0.25 M Pump lead start = stop level + Effective Level
Inlet pipe invert level 0.40 ACCORDING TO THE PLAN Pump lag start = pump lead start + 0.15m
Pump stop level 0.30 High level = pump lag start + 0.10m
Pump lead start level 0.55 Total depth= high level + invert level
Pump lag start level 0.70 0.1 m between inlet pipe and high level
Pump high level 0.8
TOTAL DEPTH 1.30
Volume OF SUMP
Dimensions
LENGTH = 1.5 m
WIDTH = 1.5 m
DEPTH = 1.30 m
TOTAL VOLUME = 2.9 m3