Example Distance Distance
Example Distance Distance
2
Preface
This paper describes how to test distance protection zones. It contains an application example which will be
used throughout the paper. The theoretical background of the distance protection function will be explained.
This paper also covers the definition of the necessary Test Object settings as well as the
Hardware Configuration for distance protection tests. Finally the Distance or Advanced Distance test
modules are used to perform the tests which are needed for the distance protection zones.
t/s
1.6
220 kV 1.2
S²sc=15 GVA 0.8
0.4
0.0
Z Z
t t
32.5 km 20.1 km 10 km
110 kV
Protection functions
(21)
Characteristic of distance zones: Quadrilateral or Mho
Note: Testing of associated functions (e.g., Automatic Reclosure, Switch on to Fault), are not part of this
document.
110 kV 600 A
1A Z´line 0.404 Ω64, 32.5 km
110kV 110 V
BB A 3 3
t/s
1.6
220 kV 1.2
S²sc=15 GVA 0.8
Zone 2 0.4
Zone 1 0.0
Z
t
Zone 3
110 kV 110 kV
BB A BB B
There are different types of impedance characteristics. For this example only the Quadrilateral and Mho
types will be used.
1
2
1
3
1
4
1
5
1. Settings of zone 1
2. Settings of zone 2
3. Settings of zone 3
1
4 1
2 4. Setting of the line angle (it depends on the
type of relay, whether this setting exists or
not)
5. Setting of the distance characteristic angle
6. Directional characteristic (the directional
characteristic depends on the type of relay)
1
1
1
5
1
6
1
3
1
2 1
5
1
3 1
6
1
7
1
7
1
5
1
4 1. Setting of zone 1 for phase faults
2. Setting of zone 2 for phase faults
1
2 3. Setting of zone 3 for phase faults
4. Setting of zone 1 for ground faults
1
1 5. Setting of zone 2 for ground faults
6. Setting of zone 3 for ground faults
7. Setting of the line angle
1
3
1
6
Note: For the logic of the Ground Distance Elements see chapter 2.3 .
1105 1211
Relay Relay
Zline 1- Zline Zline 1- Zline
Zline = Line impedance
= Fault loop
Zg 1- Zg Zg 1- Zg
Zloop 2 Zline
Zloop Zline Zg
Zloop Zloop
2Zline Zline Zg
For phase to phase faults the distance between the relay and the fault can be calculated from the loop
impedance by just using the line impedance. However, for phase to ground faults the ground impedance is
also needed. To take the ground impedance into account, a zero sequence compensation factor (grounding
factor) is used. The definition of this factor depends on the manufacturer of the relay:
Figure 10: Zero sequence compensation factor for distance protection devices from SIEMENS
Setting this factor will influence the resulting zone for phase to ground faults as shown below.
X/
1 kL Z1 Zone setting
Resulting zone
Z1
R/
Figure 11: Influence of the zero sequence compensation factor on the zone
Note: The functionality of the Advanced Distance test module and the Distance test module is
different!
Figure 12: Test View of the Advanced Distance test module and Distance test module
For all following discussions, the Advanced Distance test module is used. This test module
incorporates the functionality of the Distance test module.
The test module can be found on the Start Page of the OMICRON Test Universe. It can also be inserted into
an OCC File (Control Center document).
Note: The parameters V max and I max limit the output of the currents and voltages to prevent
damage to the device under test. These values must be adapted to the respective
Hardware Configuration when connecting the outputs in parallel or when using an amplifier.
The user should consult the manual of the device under test to make sure that its input rating
will not be exceeded.
Note: Once an Advanced Distance / Distance test module is inserted, this RIO function is available.
System Settings
The first tab contains the definition of the system data, the relay behavior as well as the relay tolerances.
4
6
1
1 4
7
3
2
4
3
2
1
4
4
4
5
Z
R jX
jX
Protected Line R
If the line reactance X is set in the relay, then the impedance Z has to be calculated out of the reactance
Ω
X X l 0.218 km 32.5 km
X and the line angle . Line length = Z 7.88 Ω (see Table 1).
sin sin sin 64
2. Regarding the feeder connection diagram (Figure 2) the PT is placed at line. If at busbar is chosen, the
voltage will have the nominal value after tripping.
At line At busbar
Protected Protected
object; object;
e.g. line e.g. line
Busbar Busbar
3. The CT starpoint has to be set according to the connection of the secondary windings of the CT. For this
example the feeder connection diagram (Figure 2) shows that the CT grounding is towards the line.
Protected Protected
object; object;
Busbar Relay e.g. line Busbar Relay e.g. line
Protected Protected
object; object;
Busbar Relay e.g. line Busbar Relay e.g. line
4. The impedance and time tolerances are found in the relay manual.
5. The grounding factor compensates the effect of the ground impedance on the distance zones (see
chapter 2.3 ). For further information on the settings of the grounding factor the Help function should be
used.
6. Select this checkbox to enter all impedances in primary values.
7. This checkbox must be activated, if a 5 A relay is tested which uses 1 A as reference for the impedance
calculation..
As shown above, no zone is set by default. Click New to insert a zone. Afterwards the characteristic editor
can be opened by clicking edit. Here the distance zone can be entered.
Click Add to add a new element to the Element list. The element can be either a line or an arc.
> A line has to be set with an angle and a point on the line. This point can be set either in cartesian or in
polar coordinates. Therefore, the options Line cartesian and Line polar exist.
> A circle has to be set with a center point, a radius, a start angle, an end angle as well as a direction. As
the center can be set in cartesian as well as in polar coordinates, the options Arc cartesian and
Arc polar can be used.
1
1 2 3
1. Mho shape
2. Lens/Tomato shape 2
3. Quadrilateral
Note: The shape of a distance zone depends on the type of relay as well as on the settings in the
relay. The shape can be found in the relay manual. The elements for one quadrilateral as well
as for one mho shape are shown below.
X/ X/
Z1
X1
R/ R/
R1
If additional zones are required the first zone can be copied (1) and appended to the list (2). Afterwards the
settings of the other zones can be adapted. After all the zones have been entered the list could look like this:
3 4 5 6 7 3 5 6
Note: In this example different starting zones have been defined. The zones ZS1 are only in the
forward direction. Therefore, the forward directional end time is set as the tripping time for these
zones. The zones ZS2 cover the complete impedance plane and, therefore, have the non-
directional end time as the tripping time (see Table 1).
3.2.1 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A
VA VC
VB VN
IA
IB
IC
IN
VA VC
VB VN
IA IC
IB IN
Note: Make sure that the rating of the wires is sufficient when connecting them in parallel.
The following explanations only apply to protection relays with a secondary nominal current of
1 A.
The analog outputs, binary inputs and outputs can all be activated individually in the local Hardware
Configuration of the specific test module (see chapter 3.3 ).
4
4
3
3
1
1
2
2
1. The start command is optional (it is needed if Starting is selected as a time reference in the test).
2. The trip command has to be connected to a binary input. BI1 … BI10 can be used.
3. For wet contacts adapt the nominal voltages of the binary inputs to the voltage of the circuit breaker trip
command or select Potential Free for dry contacts.
4. The binary outputs and the analog inputs etc. will not be used for the following tests.
Start
Trip
Protection
Relay
VA
VB
VC
(-) (-)
IA
IB
IC
IN
Trip
(+)
optional
Start
(+)
Protection
Relay
VA
VB
VC
(-) (-)
IA
IB
IC
IN
Trip
(+)
optional
Start
(+)
> Pick-up Test: The respective pick-up function (e.g., Overcurrent starting) is tested. This test is not
explained in this document.
> Trip time test: The trip times of the distance protection function are verified.
> Zone reach test: The zone reaches of the distance protection are verified.
The trip time test, as well as the zone reach test, is performed with the Advanced Distance test module.
2
6
1
The trip times are tested with the shot test. With this test method test shots can be placed in the impedance
plane. These test shots can either be set manually by entering R and X or |Z| and Phi values or an angle
can be entered (1) and the values can be set relative to the respective zone (2). To do so, the option
|Z| relative has to be selected. If this option is used, the test shots will be adapted whenever the zone
settings change. The Follow line angle change option can also be selected in which the angle of the test
shots will be adapted whenever the line angle changes.
For this test, test shots are placed both inside and outside of the tripping zones. Hence, it is possible to test
the trip times of all the tripping zones, as well as the directional and non-directional end time.
For the zone reach test the Search Test is used. With this tab the user can define search lines. The test
module applies test shots along these lines to search for the reach of each zone. It is also possible to use
the Check Test. With this test lines are again defined. However, this time test shots will be placed along
these lines outside the tolerance bands. This confirms if the zone reach is within the defined tolerances.
3
6
1
1
4 4
6
3
1. Search lines can be defined either by dragging a line in the impedance plane or by setting a start point,
an angle and the length. After a line has been defined, Add is clicked to add them to the list of test lines.
2. By activating Follow line angle change and Relative test lines can be defined in a way that they adapt
to changes of the zone settings or the line angle.
3. In the forward and reverse direction, one search line is defined to test the reactance settings X of the
zones.
4. The resistance settings R of the zones are tested in the same way.
5. Using search lines in parallel to the resistance search lines, the characteristic angle is confirmed.
6. Test lines along the line angle can also be set. This confirms that the relay works correctly in the area
where faults normally occur.