‘TRANSFORMER TEST EQUIPMENT
BIDDLE’
TTR’
Three-Phase Model
+ Microprocessor controlled,
automatic balancing
+ Reduces testing time
by 50%
+= Expanded ratio range
of 2700:1
+ Printer option
+ Eliminates the need for
manual setup changes
Transformer Turns Ratio Test Sets
DESCRIPTION
Biddle* TTR? Transformer Turns Ratio
Test Sets measure the turns ratio and
exciting current of windings In power,
potential and current transformers.
Deviations in turns ratio readings
indicate problems in one or both
‘windings or the magnetic core cireult,
‘The TTR test sets aid in identifying:
* Shorted coils
*+ Open circuits
* Incorrect connections
+ Internal faults of tap-changer
defects in step regulators as well as in
transformers,
Thethreephasemodelisafily automatic,
microprocessor-based system with an
expanded ratio range of 27001 to cover
‘most current and potential transformers
with unmatched accuracy of 4.1%,
‘The automatic operation reduces test
function time to under 10 seconds, pro-
viding dramatic cost savings to the user.
Additional time saving is gained from the
simple switch settings which eliminate
the need for manual setup changes,
An optional printer is available for
recording testing results,
The model is available in either hand-
cranked or line-operated versions and
measures highly sensitive turns ratios
of up to 129.99:1 with accuracy of
0.1%, An optional auxilary trans-
former extends the ratio range to
329.991
‘The TTRset operates on the principle that
the voltage ratio of the transformer at
no load is practically equal to the true
turns ratio.
‘Themalor source oferrorina transformer
is a primary impedance drop due to
‘magnetizing current, which Is kept to a
‘minimum by excitation ata fraction of
rated voltage. By employing a design
that meets both of these conditions
along with the use of a null balance
system, the turns ratio ofa transformer
can be determined accurately.
When measuring the tums ratio of
distribution and power transformers,
the accuracy is well within 0.1%.
APPLICATIONS.
* Threephase model: Fully automatic
units are used for testing single- and
three-phase transformers and voltage
regulators, for high-ratio readings
ranging from 0.8:1 to 2700:1
‘An RS-232C interface is provided
This singlephase TTR test set is oper:
ated by turning a crank,
for data transfer of for use with the
optional lid-mounted printer.
* Single-phase models: These models
are primarily used for testing
single-phase power and distribution
transformers, for low-ratio readings up
to 123.99:1, or up to 329.98:1 with an
auniliary transformer
‘They also can be used to test three-
phase transformers by connecting and
testing each phase separately.
FEATURES AND BENEFITS
‘Three-Phase Model
* Microprocessor-based control
provides fully automatic operation,
Test function takes less than
10 seconds.
* Digital readout displays ratio, exciting
current and self-diagnostic messages
for simplicity of operation,
+ Expanded ratio range of 2700:1
covers most current and potential
twansformers.
* The simple switch settings for all
‘combinations of transformer connections
tliminate the need for manual setup
changes.
+ 40 volt output voltage selection
allows testing current transformers.
+ Error messages reduce Incorrect
connections and incorrect settings.
+ R5.232C interface allows download
to an optional lid-mounted printer,
"AVO INTERNATIONAL‘SPECIFICATIONS
Range Dimensions
oat | Power [Tam] exeiing | Accuracy weit | SAT
Ratio | Current Hewxo
a WHxioswx14s0m, | 18
Single-phase | Hancherancod ororn 280% 260x370 mm | (2k) | 980008
fol sole
~ | a001 THe t5Wx29D in 2516
Line 120998 | gaue | sone |_280Hxs80wa737 Omm | crea) | 850027
Sinalephase | Linge THX 105 Wx 9D, 2b coon
rackmounioa | _ Une 2554x257 Wx483.D mm | (10k)
Three phase | {ag Joao 16] 070 TZSAxWx200 in 36 aa
fulomatie. 2700" | 1989 mA seo xs00wxsi00mm | (8.59)
+ 120,Vac, 6180 Hz. Te order 240 Vac, 50160 He, acd 47 to Cat. No
+ Dive by 5 switch for increased asatton
‘To corderinsrument wth printer mounted in, as -99 to Cat. Na
| To oder instrument with pnter i and 240 Vac, S060 He, add 89-47 to Cal No
FEATURES AND BENEFITS (cont) | + Line-operated model for shop or | Error Messages Indicate
ld testing is packaged In aT cttingcurent overloads
Single-Phase Models troodn cage PaCH#e4 IB 8 TUBBE | pret polalty
+ Avaliable In hand-ranked or line- Incorrect ead connections
Gperated models these unis provide | ‘Measures highly sensitive turn | [toma gutofealpration
unmatched accuracy (£0.1%) in a | Tatios up to in optional Ratio values beyond instrament range
Unmatched ac Say ttanstomer extenge ths |
* Rackinounted model is suitable for s ‘Single-Phase Models
routine production testing bytransformer | SPECIFICATIONS Output
Ianulacturers or epale shops, This 8, 50/601
Uti ineoperated, Three-Phase Model
ie Line-operated models supply up
tors Aor testing specially power
+ 120.0, 0/60 Hestandardtestfor | transformers havingagh ato and
poweranddlstebutontanstomers | stow secondary voage
*+40V,50/60Hzfor currenttransformers | Metering: Four decade dials
Selectorswitehes provideautomatic | Oo siouaL aecESSORIES
election of transformer winding
{ype and phase under tes. Thermal printer and protective interlocks
RATIO are available for use with the three
7 Metering phase TTR test set.
The insirument displays error messages | Turns Ratio: Sig LCD
iftest connections are incorect. Exciting Current: 3digit Lc Printer
Test results can be documented with a
thermal printer
‘A header can be printed that provides
spaces to record the TTR serial number,
test date, operator name, transformer
Information, temperature, test voltage,
relative humidity and comments/notes.
The header automatically includes the
type of transformer (single- or three
Select the transformer winding type and phase under test, press a button, and ratios | An optional printer provides hard-copy
‘are displayed automatically. documentation
24 AVO INTERNATIONAL, TenorAucaliary transformer for single phase TTR
phase) and the configuration of the
high- and low-voltage windings.
‘The three-phase TTR automatically
identifies whether three-phase or
single-phase leads are being used and
sends the test results to the printer In
the proper format
‘The test result printout includes
ratio, exciting current and polarity.
Aspace'is included for the transformer
tap number.
Protective interlocks
An interlock shorting plug is supplied
with the test set. Both a foot-switch and
a hand switch interlock are available
as optional accessories.
Auniliary Transformer
An aunillary transformer extends the
ratio range of singlephase models to
329,99:1. Turns ratio is 100:1 and 200:1,
land is accurate to within £0.1%,
The auxiliary transformer includes all
the necessary cables for connection
Calibration reference transformer
Pind
‘TRANSFORMER TEST EQUIPMENT
to the TTR set and the transformer
under test
Dimensions
BHx13W x 10D in,
203 Hx 330 W x 254 D mm.
Weight: 13 1b (5.9 kg)
Calibration Reference
Transformer
Calibration reference transformers
are available for both single- and
three-phase test sets. They provide a
relerence standard for periodic cali
bration checks to document proof of
calibration.
A Calibration Certificate of Turn
Ratio Accuracy traceable to the NIST
is furnished with each calibration
reference translormer, providing
accuracies of 10.05%,
Dimensions (single- and three.
phase)
BHx M4 Wx 10D in,
203 H x 356 W x 254 D mm
Weight
Single-Phase: 11 Ib (6.0 kg) approx
‘ThreePhase: 16 Ib (7:3 kg) approx
tem (@ty)
‘Three-phase automatic TTR, line,
120 Vac, 50/60 Hz
240 Vac, 50/60 Hz
‘Three-phaseTTR with printe
mounted in lid
120 Vac, 50/60 Hz
240 Vac, 50/60 Hz
Single-phase TTR, hand-cranked
Single-phase TTR, line, 120 Vac, 50/60 Hz.
Single-phase TTR, line, 240 Vac, 50/60 Hz
Single-phase TTR, rack-mounted, line,
120 Vac, 50/60 Hz 550022
Single-phase TTR, rack-mounted, line,
240 Vac, 50/60 Hz 350022-47
Included Accessories
‘Three-Phase Models:
Cables
Power cord, 8 ft (2.5 mi [1] 17032
Grounding cord, 15 (45 m) {1} ‘47025
With heavy-duty clips for one-phase connections
toH winding, 10 f @ m) [1] 28549-1H
to X winding, 10 @ mi) (1) 28550-1X
With heavy-duty clips for three-phase connections
toH winding, 30 fm) [1] 2854 1-111
to X winding, 30 ft @ m) [1] 28542-1X
Shorting plug for interlock receptacie [1]. 28552
Al cables are supplied in a canvas bag with an
adjustable shoulder strap. Longer cable lengths
are also available,
Instruction manual
AVTMS5-U1
Cat. Mo, tem (ty) Cat. No.
Single-Phase Models
vn 550100 Cable assembly 19494
35010047 With Cclamps for X (low-voltage) winding,
108 Gm) [2]
55010039 With spring clips for H (high-voltage) winding,
1384 m) [2]
Al cables are permanently connected to the test set
Instruction manual |AVTMS5ID
Optional Accessories
‘ThreePhase Models
Printer with cable 550105
Case, shipping and storage,
heavy-duty, padded
Calibration reference transformer
Printer paper [1 roll] 2705-1
Carrying case
For cables 2187441
Soft pack for TTR 246010
Extension cable for high- and low-voltage
cables, 15 ft (45 m). 550110
Foot switch interlock 102295
Hand switch interlock 279802
Single-Phase Models
Auiliary transformer, extends the ratio
range to 323,99
Calibration reference transformer
Note:The cables have been designed for use with the
TTR test sets. Any substitution may cause errors
in reading and may be dangerous to the operator.
"AVO INTERNATIONAL