Fire Safety
Fire Safety
-\F ~<5'
~· ft ·-s
s ~ INSPECTION, TEST AND MAINTENANCE GUIDANCE
~
\~1zz&~
:-v/;"it.. FOR FIRE SAFETY SYSTEMS
"~
PROI'i::-0
June 1994
TABLE 01' CONTENTS
PAGE
l:NTRODUCTI:ON ...................... ............. 1
FIRE PUMPS . 11
HOUSEKBEPI:NG PRACTI:CES . . . . . . . . . . . . . . . . . . . . . . . • 16
- i -
\'
Fire safety systems (including fire suppression, detection and alarm) are crucial to
defend against fire. However, they are rendered useless if no routine maintenance or
testing is provided to assure their operation when needed. This document provides limited
guidance for periodic inspection, testing, and maintenance of fire safety systems commonly
found at EPA laboratory facilities. The document is intended as a starting point to help
safety personnel focus on key aspects of fire safety systems maintenance. The user will
need to evaluate their facilities to determine other specific system maintenance
requirements.
The document is divided in two portions. The first portion describes fire safety
components and their functions. The second portion is a Checklist of inspection, testing
and maintenance requirements of specific components. The Checklist can be used
independently to ensure that fire protection components are evaluated on a regular
scheduling basis, or it may be integrated into a facility preventive maintenance program.
It can be useful in developing a fire prevention plan for the facility. The following
systems and components are discussed: water supply, automatic sprinklers, standpipe and
hose, fire pumps, fixed and portable extinguishers, fire alarm, fire doors, dampers and
emergency lighting.
Records of all testing, maintenance and inspection activities should be kept on file for
periodic review. Attachment A provides examples of how inspection activities can be
recorded.
Although facility personnel can visually inspect various system components, many of the
testing and maintenance and some of the inspection procedures require handling of the
equipment or component. Those procedures requiring handling should be performed by
qualified fire protection contractors. Any test or maintenance procedure having a direct
connection to a central station or fire department should be made only after proper notice
is given to the signal receiving station. Fire protection systems are required to be
acceptance tested upon their installation. This document does not address acceptance
testing of new systems.
The following definitions provide the reader with generic fire protection terminology for
systems evaluation:
Each fire safety system component performs one or more functions of detection, suppres-
sion, or life safety. The water supply system is vital to fire suppression. Water which
may come from the city water system or water storage tanks, supplies automatic sprinklers,
standpipe and hose systems, and fire hydrants. A properly designed and maintained fire
alarm system will help limit loss of property and life by providing early warning. Life
safety features such as fire walls and enclosed stairways are normally designed into the
building construction. Several components of life safety systems need to be inspected and
maintained to ensure that people can escape a building safely. This portion of the
document describes key fire safety components and their operation.
Water for fire protection is conveyed to a facility by various methods, including water
storage tanks, public water mains, dedicated fire mains and public water hydrants. At EPA
facilities, water is commonly supplied through storage tanks and public fire mains. Fire
hydrants are normally publicly owned and the local jurisdiction is responsible for their
upkeep. Fire hydrants are used in emergencies to obtain water from the public water
supply. The most common type of hydrant is the dry barrel; it is used in locations
susceptible to freezing. Wet barrel hydrants are used where there is no danger of
freezing. Different portions of hydrants (e.g., piping, monitor nozzles, hose, hydrant
house) require routine inspection, test, and maintenance.
Water storage tanks hold a specified amount of water to augment water supply to the
facility or serve as the primary water source in remote areas. Tanks typically are
provided with control valves, check valves (which direct the flow of water), heaters (in
freezing climates), fire department connections, ladders, drain outlets, water level
alarms, and level indicators. Fire department connections, commonly referred to as .
"Siamese connections," usually consist of a dual 2 1/2-inch outlet outside the building.
The fire department connections are interconnected to standpipes or automatic sprinkler
systems. The fire department attaches hose lines to these connections to boost the water
capacity during a fire emergency.
Refer to NFPA 25, Standard for the Inspection, Testing and Maintenance of Water Based Fire
Prevention Systems, Chapter 6: Water Storage Tanks and Chapter 7: Private Fire Mains for
more detail.
BULK MAIN~
!RISER I
l• I ALARM VALVE
MAIN
Figure 1: Typical Automatic Wet Pipe Sprinkler System (Reprinted by permission of NfPA)
,., RISER
2" MAIN
DRAIN VALVE
SPRINKLER RISER
WATER
2" MAIN MOTOR----
DRAIN GONG INCOMING
WATER
PRESSURE
GAUGE
TO RETARDING
CHAMBER
PRESSURE SWITCH
AND WATER MOTOR
ALARM
NOH V I\LVP; NOS 1P., 2 NORMALLY OPEN CLOSE NO. 1 TO SHUT OFF WATER .
CLOSE NO . 2 TO SILENCE ALARM.
Figure 2: Schematic of Wet Pipe Sprinkler Valve Figure 3: Photograph of Wet l'ipe Vi!lve
(Reprinted by permission of NFPA) (Reprinted by permission of NI:PJ\)
D~ Pipe Sprinkler Systems
Unheated buildings which are subject to freezing have dry pipe sprinkler systems instead
of wet pipe systems. However, the enclosure which houses the valves for dry pipe systems
must be heated. Dry pipe systems have their piping filled with air or nitrogen under
pressure. When the heat from a fire causes the sprinkler to open, the air pressure is
released. This permits the water pressure to push open the dry pipe valve. Water then
flows into the piping system and out the opened sprinkler. Dry pipe systems are often
less reliable than wet pipe systems due to additional maintenance requirements. Figures 4
and 5 show details of a dry pipe sprinkler and valve. Figure 6 is a schematic of a dry
pipe system.
Deluge Systems
In this system, the sprinklers are open; the water is held back by a deluge valve on the
system riser. When the fire detection system in the protected area activates, it trips
the deluge valve. This causes water to flow through all the sprinklers. These systems
are used in small areas such as cooling towers where water damage is not a concern.
Pre-action Systems
Pre-action syst·ems are similar to deluge systems, except that the sprinklers are closed.
If water damage is a concern, as in computer rooms, a pre-action system is employed.
When the fire detection system trips the deluge valve, water enters the sprinkler pipi ng .
However, water only discharges through the sprinklers which opened .
It is imperative to keep all records of sprinkler system evaluations on file. Records of
testing, if compared over a few years, will help determine if the system capacity has
diminished. Attachment A is an example of inspection activities that should be recorded.
, . - - - - - T O SPRINKLERS
PllfSSURF SWITCH-------.
PRIMING FUNNEL
/\Ill fl[Lifr V/\l.VF------,
CIIFU: V/\l V F - - - - - ,
IIJW/\lFFl
' .11lTOil GONr;----..t
t--..,.--'WMI....-1--+--~
PRIMING CHAMBER
II /\llt\1 ()fl/\lr~ "'I
I ll(lM 1\lrt
·:lll'f'l \
'I 1\l/\RMTESTCOCK
I'IIIMIN(i WATF II
I I Vf I lFO,I ~
V /\IVf WATER
7" MAIN DRAIN SUPPLY
Ill! If' r:II[(Y. V/\LVF------if'
FIRE DEPARTMENT
PRESSURE
GAUGE
CONNECTION~
WATFR l'f1EC.C.URF.
(;1\IJrif - - - - - <: I:r--1 t::I{).----
1w ;ci iAil<;r 1 o 0111 :.111r \cHEcK VALVE W / BALL
I Iff 1·K V/\1 V f - DRIP. PIPE BALL DRIP
TO OUTSIDE
., . . flfi/\IN V/\LVE
\___-TAMPER SWITCH
Figure ·1: Schematic of Dry Pipe Sprinkler figure 5: !'holograph of Dry l'ipe V,1lvc
(Reprinted by permission of NfPA) (l{eprinted by pcrmis.c;ion of NFI';\)
}d!
(i i_!
~ . ~=::; ~ ~~ ~ ~~ ~ I~··
(ii) I J 7}
J.-lifi,
~
I II (lQI
~
(2~_,
l
(77)~ (7<!) (Jo1
~) @
I .___ _- t t _ 64.1
~ill
2 rwnpP.r-type fuP. hydrant 13 Anti -llnod dP.vicP. lnruinnr.ll 14 ChP.r.lr v-.lvr
3 UndP.rQrnuncl lirP. main 14 Accelrq;:~torfoptiullill l 25 A i'iP.r to ~prirddr11 w~;trrn
4 t<rv v;:~lvl! Anrl road hn• 15 WatP.r motm rtl;urn rl•ilin 16 Thru~lil hlork
5 Pnu inrliLa tm valvr. 16 WatP.r moun illttrot 27 Orain ,.,;nlvr ;tnrl pltuJ
6 M;:~m dram 17 Crn~J main 28 Orumrfrip
7 Anll cfrip 18 0. v pipP. valve hou<:P. 29 Urutqht ~;prinldrr
(76) 8 rirP dr•p;utmPnl conner. l ion 19 W<ttPr motor nl alfn lin~ 30 Dry JlPtH1t•nt 'SPrinklrr
9 ChPd valvP. 20 PrP.1i,UtP. swi trh 31 lrispPcrm ·s teu villve
21 Alarm line strainrr 32 lno;pt•r: tnr · ~ tr•tl dram
10 Or ;tin cup
11 Main dr;ain valvP. n Alarm teSI vttlvP
CIIF.CK VALVE
l lrlliOIIFinE~
lfiiFCTION PIPING
figure 7: Typical Fire Department Siamese Connection Figure 8: Photograph of Fire flose Cabinet
(Reprinted by permission of NFPA) (Reprinted by permission of NFPA)
Standpipe and Hose Systems for complete guidance. Figure 8 illustrates a fire hose
cabinet.
FIRB PUMPS
Fire pumps are provided to fire protection systems to boost the pressure of an existing
water supply. Fire pumps are designed to operate at various flows and pressures: rated
pressure (pump design), churn pressure (no flow), and overflow pressure (150% of designed
flow) . When the fire pumps are tested, performance at these flow rates is observed.
The pump may be housed in a cut - off room in the facility, or in a detached pump house.
The engine for operating the pump is typically a diesel engine or an electric motor.
Pumps can operate manually, as well as automatically if provided with pump controllers.
Pumps which provide primary protection for the facility normally start automatically.
A preventive maintenance program which complies with the manufacturer's recommendations
must be established and implemented. Maintain records on all work performed on the pump,
engine, controller, and auxiliary equipment. A routine review of test records can provide
clues to water supply or pump deficiencies. Refer to NFPA 20, Standard for the
Installation of Centrifugal Fire Pumps and NFPA 25, Chapter 5: Fire Pumps for additional
information.
Many types of automatic extinguishing systems other than sprinklers are available for fire
suppression. They are typically selected based on the hazard type that will be protected.
For protection of electronic equipment, EPA normally selects C0 2 extinguishing systems and
pre - action sprinkler systems. Foam water systems are selected to protect areas using
large amounts of flammable liquids.
Carbon Dioxide Extinguishing Systems (C02 )
C0 2 systems have C0 2 agent under pressure in cylinders and tanks. The tanks are accessed
through hoses to nozzles in the protected area. The systems apply C0 2 gas to fill an
entire room (total flooding systems), or to a specific area (local application) ~
Portable fire extinguishers are required in most EPA facilities. Portable extinguishers
are selected according to the hazard they protect. The multipurpose dry chemical and
carbon dioxide extinguishers are most common at EPA facilities. The multipurpose dry
chemical can normally protect against most types of fires including electrical, ordinary
combustibles and flammable materials. C0 2 extinguishers are effective on electrical and
flammable liquid fires. The label on the extinguisher cylinder indicates what types · of
fires it can extinguish.
TIT DISCHARGE
NOZZLE
PIPING
ACTUATION LINE
DISCHARGE CONTROL
VALVE- ~
NAMEPLATE WITH
SYSTEM DATA
I .. I
D D CYLINDER
WALL MOUNTING
BRACKET
Figure 9:
Typical Carbon Dioxide High Pressure System (Reprinted by permission of NFPA)
central station, upon receiving an alarm signal, will make attempts to verify the alarm.
If it cannot verify a false alarm, the Fire Department responds to the installation. Fire
alarm systems are connected to emergency power supplies, which must be inspected and
maintained, as well.
Smoke Detector•
Fires produce detectable quantities of smoke before any significant rise in heat. Smoke
detection devices respond when smoke particles enter the units~ Duct smoke detectors
cause the air handling systems of a buildings ventilation system to shut down, thereby
preventing the recirculation of smoke within the building. Magnets or artificial smoke
can be used to test smoke detectors. It is recommended that artificial smoke be applied
from a distance of at least 12 feet to avoid damage to the unit.
The following documents provide additional information: NFPA 101, Life Safety Code; NFPA
72 H, Guide for Testing.
Heat Detectors
A heat detector works when the fusible elements within the unit melt or when air or metal
in the unit expands in response to a predetermined heat level. Heat detectors are
provided on the initiating device circuits~ EPA facilities have fixed temperature, rate-
of-rise, or rate compensation heat detectors. Fixed temperature heat detectors must be
replaced if they are tested using heat. Other restorable detectors can be safely tested
with a hair-dryer, or shielded heat lamp. Rate-of-rise and rate compensation detectors
can reset themselves after testing. Any detectors which fail to operate during tests must
be properly replaced. Records for testing, inspection, and maintenance must be kept on
file.
Manual Stations, Bells, and Horns
Basically, manual stations are electrical switches housed in a red-colored box. They
operate upon breaking glass, pulling a lever, or using a key. Bells and horns generate
loud noises to indicate emergencies. Sometimes visual signals such as strobes and lights
are provided.
Power supply to the alarm system can be provided by either commercial light and power
supply or an engine-driven generator. Secondary power supply to the alarm system must be
provided. It can consist of a storage battery and charger, or an engine-driven generator.
Secondary power supplies normally support other systems as well, including fire pumps,
exhaust hoods and emergency lighting. All power supplies, including uninterrupted power
supplies (UPS), have inspection, test and maintenance requirements. A routine maintenance
and operational testing program must be developed and implemented based on manufacturer's
recommendations.
NFPA 110, Emergency and Standby Power Supply and NFPA 72, National Electrical Code discuss
power supply requirements in detail.
Fire Doors
Fire doors are used to protect openings in fire-rated walls and partitions. They are
required to be self-closing or automatic closing (i.e., close upon activation of detection
systems). It is imperative that fire doors are not kept open with wood jambs or door
chocks. Doing so compromises fire safety and the design flow rates of ventilation
systems. NFPA 80, Standard on Doors and Windows provides details on door testing.
DamPers
Fire dampers are provided on some air distribution systems to limit the migration of heat
or flame across a fire barrier. They close automatically when they detect excessive heat
in the air distribution duct. Smoke dampers restrict the movement of smoke.
NFPA 90A, Installation of Air Conditioning and Ventilating Systems and NFPA 101, Life
Safety Code discuss fire and smoke dampers.
Emergency Lights
Emergency lighting is required at most EPA facilities. Laboratory work units require at
least 10 candles of illumination on the face of the hood during emergencies. Emergency
lighting must operate automatically in the event of any interruption of normal lighting.
Refer to NFPA 101, Chapters 5 and 31 for more information. Written records of testing
must be kept on file.
HOUSEKEEPXNG PRACTXCES
hydrant semi-annually & after each annually: Fully open ·and annually a
operation: Check all hydrants close private hydrants to lubricate private
near the facility for signs of ensure water flows hydrants and
damage or obstructions. Verify properly. provide other
that private hydrants are services according
visible and accessible and that to manufacturer.
caps are in place. Wet hydrants
require annual insoection.
hydrant annually: Inspect exposed 5 years: Perform flow
piping piping for leaks, damage, or tests; determine
corrosion. deterioration.
hose/hydrant monthly: Inspect for Test hoses per NFPA 1962. annually: Ensure
house accessibility, physical damage, all fire hose and
and missing equipment. other components
are in usable
condition.
hydrant semi-annually: Check for annually: Test similarly annually:
monitor leakage, physical damage, to hydrants. Lubricate to
nozzle corrosion. semi-annually: Oscillate ensure proper
and move nozzles through operation.
their full range.
antifreeze
loop
- 21 - - _JUNJ: 19U
building annually: Before the onset of
heating freezing weather, verify that
sprinklei piping will not be
exposed to freezing and that
adequate heat will be provided.
- 23 - DRAF'l' - JUNJ: 19 9 t
pre-action weekly: Ensure that the valve annually: During the annually: Clean
valve is free of physical damage and spring, trip test dry the interior and
that all trim valves are in the pipe valve with control replace or repair
appropriate (open or closed) valve partially open. parts during
position. Check that electrical every 3 years: Perform a annual trip test.
components are in service. full flow trip · test with
annually: Inspect interior the supply control valve
during annual trip test. fully open.
valve daily: Inspect enclosure
enclosure heating equipment daily during
cold weather. Maintain
temperature to at least 40°F.
weekly: Inspect if low
temperature alarms are present.
detection semi-annuallya Test fire
systems detection associated with
the sprinkler system for
proper operation.
date inspector hydraulic test of alarm test of 2" test water flow
(initials) name plate devices main drain alarm
- - -- --~
Attatchment A
650 gpm at 45psi. System has 100 sprinklers.
Attatchment A