23BTVE
23BTVE
PROTHERM 23 BTVE
User, Installation
and Servicing Instructions
6187
PROVITHERM 23 BTVE
The boiler serial number is marked on the label attached to the inside of the drop down
door. Refer to the ‚Introduction‘ section for a description of the basic functions
of the boiler. The ‚Users‘ section describes how to safely operate the boiler.
PROVITHERM 23 BTVE 1
Dear Customer,
You have become an owner of a wall-hung combination boiler. The boiler PROVITHERM 23 BTVE with forced
flue gas removal is designed for heating up the central heating water (CH) in central-heating systems in flats, family
houses, workshops, offices, etc. and as a flow heater of domestic hot water (DHW). We believe it will serve you
to your full satisfaction – certain minimum requirements must be fulfilled to that end. That is why we are asking
you to study and follow these instructions carefully.
In practice, situations may occur in which the users must apply necessary precautions:
• Preventing the boiler from switching on (also accidental) when inspecting the flue-gas duct, water and gas piping
– i.e., electricity supply to the boiler must be stopped (e.g., by unplugging) in addition to using the boiler switch;
• Stopping the boiler whenever flammable or explosive vapours appear (even if temporarily) – such as vapours of
flooring glue, paints when surface finishing, gas leaks, etc.);
• If it is necessary to discharge water from the heating system, it must not be dangerously hot;
• If water has leaked from the boiler exchanger, or if the exchanger is filled with ice, no attempts to start the boiler
should be made until normal operating conditions prevail;
• If there is a (whether confirmed or suspected) gas leak or stoppage in the gas supply, switching off the boiler,
shutting down the gas supply and calling gasworks or a specialised service centre.
2 PROVITHERM 23 BTVE
USER INSTRUCTIONS
Diagram 1
Control Panel
1 - On/Off switch
2 - Central heating temperature selector
3 - Domestic hot water temperature selector
4 - Pressure gauge (bar) and temperature gauge (°C)
5 - Fault display (faults indicated by a red flashing light)
PROVITHERM 23 BTVE 3
BOILER START AND SWITCH-OFF
The preparation for and commencing of the boiler operation may only be carried out by a specialised service
centre!
Before starting the boiler when it has been put into operation, check the following facts:
– The power cord must be plugged into the socket.
– The gas valve that feeds the boiler must be open.
– The water pressure in the heating system should be between 1 and 2 bar.
Now the boiler is ready to be started.
Cleaning
The boiler can be cleaned with a wet cloth and then dried and polished with a dry cloth. Never use any abrasives
or thinners.
WARRANTY CONDITIONS
The warranty on PROVITHERM 23 BTVE boilers is provided as specified in the Guarantee Certificate, Service
Booklet and under conditions specified in these Instructions for Use and Instructions for Installation (in chapters
Introduction, Boiler installation).
4 PROVITHERM 23 BTVE
INSTALLATION INSTRUCTIONS
Introduction
The Provitherm 23 BTVE boiler is a wall mounted modulating combination boiler with electronic ignition providing
central heating and instantaneous hot water.
The boiler is of the I2H category for use with Natural Gas (G20). The boiler has a fan assisted balanced flue which
both discharges the products of combustion to and draws the combustion air from the outside of the room. The
boiler is suitable for top outlet flue connection only but can be fitted with horizontal flue, vertical flue or twin-
pipe flue. Refer to flue options guide for further information, this is available from your nearest stockist. Both
the central heating and domestic hot water temperature are user adjustable from the boiler control panel. Domestic
hot water demand always has priority over heating demand. The pump, expansion vessel and associated safety
devices are all fitted within the boiler. The boiler can be installed against either an external wall or on an adjacent
inside wall, that is, the flue system will pass directly to the rear or to either side to the terminal fitted on the
outside wall face. The installation must be carried out by a qualified registered person in accordance with the
relevant requirements of The Building Regulations, The Water Byelaws, The Building Standards Regulations and
any applicable local regulations. These instructions should be carefully followed for the safe and economical
use of your boiler.
Electrical Supply
WARNING: This boiler must be earthed.
All system components shall be of an approved type and shall be connected in accordance with the current
issue of appropriate norm and any applicable local regulations. All external wiring between the appliance and the
electrical supply and earthing requirements shall comply with the current IEE Regulations.
Connection of the boiler and system controls to the mains supply must be through a common isolator and must
be fused 3A, maximum. This method of connection must be by a fused double pole isolating switch, with a
minimum contact separation of 3 mm on both poles. The switch should be readily accessible and preferably
adjacent to the appliance. It should supply the appliance only and be easily identifiable as so doing.
Overheating safety
In the event of a problem, the overheating safety devices cause safety shutdown of the boiler. If this happens,
call your Installation/Servicing company.
Boiler controls
The control panel, located at the lower front of the boiler casing, see diagram 1, allows the boiler to be started,
shut down, controlled and monitored during use.
Flue
Do not obstruct the outside terminal of the flue.
Ancillary equipment
A range of flue accessories are available including vertical flues, twin-pipe flues, bends etc.
For further information contact your supplier.
PROVITHERM 23 BTVE 5
DIMENSIONS AND PRESSURE AVAILABLE
5
16
740
Net lift weight (boiler only) . . . . . . . . . . . . . . . 36 kg 410 0
2
3
Gross lift weight (boiler and packaging) . . . . 37 kg
Diagram 3
Diagram 4
6 PROVITHERM 23 BTVE
TECHNICAL DATA – PROVITHERM 23 BTVE
Heating
Heat input (max) NET Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 kW / 85,300 BTU/H
Heat input (min) NET Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,4 kW / 35,490 BTU/H
Heat output (max) NET P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 kW / 78,480 BTU/H
Heat output (min) NET P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,7 kW / 29,670 BTU/H
Heat output (adjusted in manufacture) NET P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 kW *
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91%
Maximum heating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 °C
Expansion vessel effective capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 l
Expansion vessel charge pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,5 bar
Maximum system capacity at 75°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 l
Safety valve, maximum service pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 bar
Hot water
Heat input (max) NET Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 kW / 85,300 BTU/H
Heat input (min) NET Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,4 kW / 35,490 BTU/H
Heat output (max) NET P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 kW / 78,480 BTU/H
Heat output (min) NET P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,7 kW / 29,670 BTU/H
Maximum hot water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 °C
Minimum hot water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 °C
Specific flow rate (for 30°C temp rise) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11L/min.
Threshold flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,7 L/min.
Maximum supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 bar
Minimum supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,5 bar
Combustion
Products outlet diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 mm
Fresh air inlet diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 mm
Electrical
Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 V ~ 50 Hz
Electrical rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 W fused at 3 A
Level of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IPX4D
Fuse rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 mA
PROVITHERM 23 BTVE 7
BOILER SCHEMATIC
Diagram 5
8 PROVITHERM 23 BTVE
)OXHWHUPLQDOVSRVVLELOLWLHV
'LDJUDP2YHUKDQJ
places opened to public
another places
'LDJUDP3RVLWLRQLQJRQWKHIDFDGH
'LDJUDP4XLHWFRUQHU
PROVITHERM 23 BTVE 9
HEATING SYSTEM DESIGN
Heating System Design
• The Provitherm 23 BTVE is compatible with any type of installation.
• Heating surfaces may consist of radiators, convectors or fan assisted convectors.
• Pipe sectional areas shall be determined in accordance with normal practices, using the output/pressure curve
(diagram1). The distribution system shall be calculated in accordance with the output requirements of the actual
system, not the maximum output of the boiler. However, provision shall be made to ensure sufficient flow so that
the temperature difference between the flow and return pipes be less than or equal to 20°C. The minimum flow is
500 l/h.
• The piping system shall be routed so as to avoid any air pockets and facilitate permanent venting of the instal-
lation. Bleed fittings must be provided at every high point of the system and on all radiators.
• The total volume of water permitted for the heating system depends, amongst other things, on the static head in
the cold condition. The expansion vessel on the boiler is pressurised at 0.5 bar and allows a maximum system
volume of 70 litres for an average temperature of 75°C and a maximum service pressure of 3 bar. This pressure
setting can be modified at commissioning stage if the static head differs. An additional expansion vessel can be
fitted to the system if required.
• Provision shall be made for a drain valve at the lowest point of the system.
• Where thermostatic radiator valves are fitted, not all radiators must be fitted with this type of valve, and in
particular, where the room thermostat is installed.
• In the case of an existing installation, it is ESSENTIAL that the system is thoroughly flushed prior to installing
the new boiler, using a proprietary product such as Fenox or Sentinel. Contact the product manufacturers for
specific details.
Gas connection
The supply from the governed gas meter must be of ade- Diagram 7
quate size to provide a constant inlet working pressure DISCHARGE
of 20 mbar. SAFETY VALVE (3 bar)
To avoid low gas pressure problems, it is recommended
that the 15 mm gas supply on the boiler is connected to
using 22 mm pipe (as close as possible to the boiler within 1 metre).
• On completion, the gas installation must be tested using the pressure drop method and purged in accordance
with the current issue of appropriate norm.
Important
When cutting the flue hole and when extending the flue centre line to a side wall, remember that the flue system
must have a fall of about 35 mm per metre of flue DOWNWARD towards the terminal. There must NEVER be a
downward incline towards the boiler.
Water connection
Connect the system pipework to the copper connections on the fixing jig observing the correct flow and return
format as shown in diagram 9. Do not subject the isolating valves to heat.
Additional
expansion
Boiler vessel
(if required)
Filling device Domestic
water
Cold supply in
Bypass
valve
Control
valve
Return
Drain
Flow
point
Heating
circuit Diagram 9
12 PROVITHERM 23 BTVE
HORIZONTAL FLUE INSTALLATION
Diagram 10
• Fit gasket (E) onto underside of flue elbow (D).
• Carefully insert ‘O’ ring (J) into upper and lower parts of inner elbow.
• Fit elbow onto fan outlet.
• Fit external rubber sealing collar (G) onto air inlet pipe (A).
• Fit flue through hole in wall and pull up so that external collar (G) is flush against outside wall.
• Fit seal and clamp (C) to flue and assemble into elbow (D) making sure that both inner and outer pipes are sealed
properly.
Note: Maximum horizontal length with no bends is 4 m. For horizontal flue lengths up to 1 m the restrictor must be
left in the fan outlet, see diagram 11. For horizontal flue lengths between 1 and 4 m, remove the restrictor (R).
• Tighten up clamp using screws provided.
Note: Should it be necessary to cut the flue, always cut equal amounts from both inner and outer pipes.
Always cut the end furthest from the terminal.
For each 90° flue bend fitted, reduce overall flue length by 1 m.
For each 45° flue bend fitted, reduce overall flue length by 1/2 m.
Diagram 11
Standart top
outlet flue
Standart top
outlet flue
90° elbow
Extension
pipe
PROVITHERM 23 BTVE 13
VERTICAL FLUE INSTALLATION
• Fit gasket (E) onto underside of vertical adaptor (O) – see diagram 12.
• Carefully insert ‘O’ ring (J) into vertical adaptor inner spigot.
• Fit vertical adaptor (O) onto fan outlet.
• For flat roof installation, fit flat roof flashing collar (part no. 85107)
• Fit extension pipes (M) as required.
• For pitch roof installation, fit pitch roof flashing (part no. 85105).
• Fit flue terminal (L) onto roof ensuring flashing makes a watertight joint.
Note: Maximum vertical height with no bends is 9 m.
Should it be necessary to cut the flue, always cut equal amounts from both inner and outer pipes.
Connect condensate trap (supplied) to vertical flue adaptor when flue length exceeds 3 m.
Connect 15 mm plastic pipe (not supplied) to a suitable drain.
For vertical flue lengths up to 4 m the restrictor must be left in the fan outlet, see diagram 11.
For vertical flue lengths between 4 and 9 m, remove the restrictor (R).
For each 90° flue bend fitted, reduce overall flue height by 1 m.
For each 45° flue bend fitted, reduce overall flue height by 1/2 m.
Diagram 12
14 PROVITHERM 23 BTVE
FLUE CONFIGURATIONS
Diagram 13
PROVITHERM 23 BTVE 15
ELECTRICAL PART
Pr
P2
3
P1
2 1
H L
Diagram 17
16 PROVITHERM 23 BTVE
COMMENCING BOILER OPERATION
The commissioning and first firing of the boiler must only be
done by a qualified registered person.
Gas installation
It is recommended that any air is purged from the supply at the
GAS INLET
gas inlet test point on the gas valve, see diagram 18
TEST POINT
2. Undo cap ( A ) on automatic air vent on top of pump and leave undone,
see diagram 19.
A
3. Turn the switch ON ( I )
Open the tap ( § ) on the filling device (see
diagram 20) and fill the system until the pres-
sure indicated on the display is 2 bar. Close fill-
ing device.
Diagram 19
4. Bleed each radiator to remove air, ensure all bleed screws are re-
tightened. Diagram 20
If necessary repressurise the system, refer to procedure 3.
5. Leave cap ( A ) on automatic air vent on top of pump open, see dia-
gram 19.
Diagram 23
PROVITHERM 23 BTVE 17
Installation filling:
• If the boiler loses water: the pressure gauge (a) and
fault display (b) will flash. Fill the system by the fill-
(a) (b) (c)
ing device (c) at the bottom of the boiler until the
pressure gauge reads 1.5 bar (see diagram 23).
Warning: Take care not to overfill the boiler. At a pres-
sure of 2.5 bar or above indicating over pressure, the
fault display (b) will flash. The pressure must be re-
duced to 1.5 bar by bleeding a radiator. If the fault
continues call your Installation/Servicing company or
Heatcall.
Diagram 23
Warning: When purging the boiler, do not use the
valve on the expansion vessel – it is NOT a purging valve!!!
Boiler start
Before starting the boiler, check whether:
• The main gas valve is open;
• The gas valve on the boiler is open;
• Water valves (DHW, heating) are open;
• The boiler’s cord is plugged in.
Bypass
The Provitherm 23 BTVE boiler has a built-in bypass. This
must be adjusted according to the requirements of the sys-
tem, refer to the flow rate pressure curve (diagram 1). The
boiler is supplied with the built-in bypass open a half a turn.
It is adjusted by turning the bypass screw (A), see dia-
gram 24. Turn the screw clockwise to close the bypass.
When using thermostatic radiator valves (TRV’s) on all of
the radiators, it is essential that a separate, adjustable by-
pass of 15 mm minimum diameter is fitted between the
flow and return of the heating circuit, see diagram 8. Any
bypass must be fitted before system controls.
Diagram 24
18 PROVITHERM 23 BTVE
SAFETY DEVICES
The Provitherm 23 BTVE incorporates a visual fault display that indicates certain-
fault conditions, (red flashing light, see diagram 25) should they occur.
Should the boiler fail to operate during Commissioning, themost likely fault is that the
gas supply to the boiler has not been turned on or purged sufficiently or that there is
no pressure in the heating system.
Diagram 25
Air in pipes
Important: A central heating system can not operate correctly unless it is filled with water and air bled from the
system. If these conditions are not met the system may be noisy. Bleed the air in the radiators and adjust the
pressure if system requires. If the system requires filling to often this may be due to minor leaks or corrosion in
the system. Call a qualified service engineer.
Frost protection
The Provitherm 23 BTVE has a built in frost protection device that protects the boiler from freezing. If the boiler is
to be left and there is a risk of frost, ensure that the gas and electrical supplies are left connected. The frost
protection device will light the boiler when the temperature of the boiler water falls below 4°C. When the temper-
ature reaches 8°C, the boiler stops.
Note: This device works irrespective of any room thermostat setting and will protect the complete heating system.
PROVITHERM 23 BTVE 19
SERVICING INSTRUCTIONS
Diagram 26
ROUTINE CLEANING AND INSPECTION
• Operate boiler and check for any faults that need to be put right.
• Isolate boiler from the gas and electrical supplies.
• On completion check all gas carrying parts for soundness with leak detection fluid.
REMEMBER, when replacing a part on this appliance, use only spare parts that you can be assured conform to the
safety and performance specification that we require. Do not use reconditioned or copy parts. To ensure the
continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular
intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in
general once a year should be enough. It is the law that any servicing is carried out by a qualified registered
person.
20 PROVITHERM 23 BTVE
Side panels (for ease of access if required).
• Support the side panels as you remove them.
• Unscrew and remove the three retaining screws from front of each side panel.
• Left hand side panel only disconnect the control panel retaining strap at the control panel.
• Pull each panel forward from the rear retaining pins to remove.
To Drain the central heating circuit
• Open drain valve fitted at the lowest point in the system.
• Allow air into the system by opening a radiator bleed screw or the boilers drain valve (a), see diagram 30.
Diagram 30 (a)
(d) (c)
HEATING Note: Isolating cocks water and gas (b)
COLD HEATING
FLOW are shown
not partin of
the: OFF position
boiler WATER IN RETURN
PROVITHERM 23 BTVE 21
Combustion chamber cover
• Unscrew and remove the four screws securing combus-
tion chamber cover to combustion chamber.
• Remove combustion chamber cover from boiler.
• Take care not to damage the insulation.
SENSE GAP
4 mm
Diagram 32
BURNER
RETAINING
SCREWS
POWER EARTH
BURNER SUPPLY LEAD
GUIDE LEADS
Diagram 34
AIR PRESSURE
SWITCH
SENSING TUBE
FAN RETAINING
SCREW
PULL DOWN
Diagram 33
22 PROVITHERM 23 BTVE
Heat exchanger.
• Remove the two flue hood retaining screws to remove
the flue hood.
• Use a soft brush or vacuum clean the heat exchanger.
Diagram 36
FILTER
RETAINING CLIP
FLAT
FILTER
Diagram 37
PROVITHERM 23 BTVE 23
REPLACEMENT OF PARTS
IMPORTANT INFORMATION
WARNING: Before commencing the replacement of any component, isolate appliance from electrical supply and
turn off gas at service cock. Replacement of parts must be carried out by a competent person. When replacing
components it may be necessary to renew sealing washers, gaskets and ‚O‘ rings. If new ones are supplied with
replacement components they must be used. All parts are replaced in reverse order to removal. If any gas-
carrying components are disturbed, removed or replaced it will be necessary on completion to check for gas
soundness with leak detection fluid.
Central heating thermistor
Before starting refer to the front of Section Impor-
tant information.
• Remove the front panel.
CENTRAL
• Lower the control panel.
HEATING
• Remove the sealed chamber cover.
THERMISTOR
• Locate central heating thermistor on the top left hand
side of the heat exchanger, see diagram 38.
24 PROVITHERM 23 BTVE
Burner, refer to Section Routine cleaning and inspec-
tion.
Before starting refer to the front of Section Impor-
tant information.
PROVITHERM 23 BTVE 25
Overheat thermostat Diagram 43
Before starting refer to the front of Section Important ELECTRICAL
information. LEAD
• Remove the front panel. CENTRAL
• Lower the control panel. HEATING
• Remove the sealed chamber cover. THERMISTOR
• Locate overheat thermostat on left hand side of heat ex- OVERHEAT
changer, see part of diagram 43. ELECTRICAL
LEADS THERMOSTAT
• Disconnect electrical connections from thermostat
• Unclip thermostat from heat exchanger.
• When refitting electrical connections to replacement ther-
mostat the polarity is not important.
Ignition electrode
Before starting refer to the front of Section Important
information.
• Remove burner.
• Remove the left hand side panel. HEAT EXCHANGER
• Undo and remove screw securing electrode assembly to
the burner injector assembly, see diagram 41.
• Disconnect the electrical connections at the igniter unit,
see diagram 57. Note the routing of the cables.
26 PROVITHERM 23 BTVE
• Remove the flue hood, retained by two screws lift up and off.
• Remove the electrical leads from the overheat thermostat, refer to diagram 43.
• Disconnect the four union nuts.
• Lift to remove the heat exchanger taking, care not to damage the insulation.
CONTROL
BOARD
COVER
PROVITHERM 23 BTVE 27
Diagram 46
230 V CONTROLS
INTERFACE
BOARD
MAINS
CONTROL PANEL SWITCH
PUMP HEAD
HEX HEAD
SCREW
Diagram 47
28 PROVITHERM 23 BTVE
• Disconnect pump cable from pump (avoid straining ca- REDUCED PRESSURE ZONE VALVE (RPZ)
bles).
• Connect electrical connection to replacement pump head.
• Fit replacement pump head in reverse order to removal.
• Check for leaks. Diagram 48
Filling system tap, refer to diagram 48.
Before starting refer to the front of Section Important
information.
• Remove the front panel.
• Lower the control panel.
• Drain down the boiler only.
• Pull out slotted metal clip securing tap into housing, re-
move tap.
• Pull out slotted metal clip and remove pipe from tap.
PROVITHERM 23 BTVE 29
System water pressure sensor, refer to diagram 51.
Before starting refer to the front of Section Important infor-
mation.
• Remove the front panel, refer to Section Routine cleaning
and inspection.
• Lower the control panel, refer to Section Routine cleaning
and inspection. SYSTEM
• Drain down the boiler. WATER
• Remove electrical connections from water pressure sensor. PRESSURE
• Pull off slotted metal clip and remove water pressure sensor. SENSOR
STEPPER
MOTOR
ELECTRICAL
CONNECTION
GAS
CONTROL
VALVE
30 PROVITHERM 23 BTVE
Gas control valve stepper motor Diagram 55
Before starting refer to the front of Section Important infor-
mation.
• Remove the front panel.
• Lower the control panel. STEPPER
• Disconnect the electrical connection from stepper motor, see MOTOR
diagram 54.
• Remove the two screws securing stepper motor to the gas
control valve, see diagram 55.
• Fit replacement gas control valve stepper motor.
• Note: Take care not to damage the ‚O‘ ring.
Diagram 57
Diagram 56
DISCHARGE
SAFETY
VALVE
PROVITHERM 23 BTVE 31
32 PROVITHERM 23 BTVE
PROVITHERM 23 BTVE - Electrical diagram
92/7$*()5((+($7,1*&21752/6&211(&7,213/8*
Diagram 59
PROVITHERM 23 BTVE 33
DEFECTS
Before trying to operate the boiler make sure that:
• All gas supply cocks are open and that the gas supply has been purged of air.
• The heating system pressure is at least 1 bar.
• There is a permanent mains supply to the boiler.
• The fuse on the PCB is intact.
WARNING. Always isolate the boiler from the electrical supply before carrying out any electrical replacement work.
Always check for gas soundness after any service work. Should there be any doubt about the voltage supply to
any of the components, it is possible to carry out a simple electrical test to ensure all is operational in that area.
To carry out the electrical test, gain access to the main Printed Circuit Board (PCB), as described previously, and
measure the voltages according to table 2.
IMPORTANT: On completion of the fault finding task which has required the breaking or remaking of the electrical
connections, the continuity, polarity, short circuit and resistance to earth checks must be repeated using a
suitable multimeter.
Table 2
Voltage Measured value Measuring point
230 Volt 230 V AC Between terminals H8.1 and H8.2
24 Volt maximum 33 V DC Between terminals J5.3 and J15.1
minimum 20 V DC
18 Volt 18 V ± 1 V Between terminals J2.9 and J2.10
Display 5 V ± 0.5 V Between terminals J13.4 and J13.1
The electrical resistance of the thermal sensors corresponds to temperature changes as follows:
15 °C . . . . . . . . . . 16 kΩ
20 °C . . . . . . . . 12.7 kΩ
25 °C . . . . . . . . . . 10 kΩ
FAULTY WATER
PRESSURE SENSOR
It is possible to replace
the sensor with two 1kΩ
resistors as shown in the OVERHEAT
diagram. THERMOSTAT
RESET BUTTON
Diagram 60 Diagram 61
34 PROVITHERM 23 BTVE
TYPE OF FAULT CHECK
No domestic hot water or central heating • 230V supply
(No flashing warning light on control panel) • Is fuse blown
• Loose connections on control board (PCB)
• Faulty control or interface board (PCB’s)
No hot water but central heating ok • Loose connections at hot water flow sensor.
• Faulty hot water flow sensor.
• Faulty control board (PCB).
Adjustment valve Close the gas inlet: If the valve does not move:
(step motor) Dismantle the step motor (screw not Check the connections at both
sealed in). Trigger a demand and check motor and control board (PCB).
that the valve opens during the ignition. Change the motor. Replace the
control board (PCB).
PROVITHERM 23 BTVE 35