Datasheet Kabel Power Prysmian N2RXY E22 PCI 002 Issue3 CSI 19.05.22 Halaman 7 8

This technical specification document provides details on the construction, materials, dimensions, electrical properties, and testing requirements for an XLPE/PVC/SWA/PVC-FR-UV cable with voltages of 600/1000V. The cable uses a stranded copper conductor, XLPE insulation, PVC-FR inner and outer sheaths, and a galvanized steel wire armour. Dimensional and electrical data is provided for cable sizes from 3Gx2.5mm2 to 3Gx6mm2, including conductor diameters, insulation/sheath thicknesses, resistance values, current ratings, and other specifications.

Uploaded by

Joko Schumacher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views2 pages

Datasheet Kabel Power Prysmian N2RXY E22 PCI 002 Issue3 CSI 19.05.22 Halaman 7 8

This technical specification document provides details on the construction, materials, dimensions, electrical properties, and testing requirements for an XLPE/PVC/SWA/PVC-FR-UV cable with voltages of 600/1000V. The cable uses a stranded copper conductor, XLPE insulation, PVC-FR inner and outer sheaths, and a galvanized steel wire armour. Dimensional and electrical data is provided for cable sizes from 3Gx2.5mm2 to 3Gx6mm2, including conductor diameters, insulation/sheath thicknesses, resistance values, current ratings, and other specifications.

Uploaded by

Joko Schumacher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

No : E22-PCI-002

TECHNICAL Issue :3
Date : 19-05-2022
SPECIFICATION Pages : 7 of 15

CONSTRUCTION
Cable Type : XLPE/PVC/SWA/PVC-FR-UV
Voltage : 600/1000V
Design Standard : IEC 60502-1
Conductor Standard : IEC 60228, BSEN 60228
Flame Propagation : IEC 60332-3-22

CABLE DESCRIPTION:

1
2
3
4
5

Part Description No.


Conductor Cu Plain annealed stranded circular copper conductor, Class 2 1
Insulation XLPE Cross-linked polyethylene compound
Assembly Multiple cores are cabled together, supplied with non-hygroscopic filler
2
when necessary to obtain a circular construction and covered with a
polyester tape wrapping
Inner Covering PVC-FR Flame retardant polyvinyl chloride compound. Black 3
Armouring SWA Galvanised steel wire armour 4
Outer Sheath PVC-FR Flame retardant polyvinyl chloride compound with UV stabilizer. Black
UV
5

CABLE MARKING:
PRYSMIAN ELECTRIC CABLE 600/1000V XLPE/PVC/SWA/PVC RFP-UV _G x _MM2
Wording
IEC60502-1, IEC 60332-3-22 YR-YYYY
Height of text Min. 3 mm
Type of Marking Ink-jet
Length marking Sequential length marking at 1 metre interval printed on outermost surface

CORE IDENTIFICATION:
3-G : Brown, Blue, Green/Yellow
4-G : Brown, Black. Grey, Green/Yellow

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed
as a result of our efforts to improve the quality of our products.
No : E22-PCI-002

TECHNICAL Issue :3
Date : 19-05-2022
SPECIFICATION Pages : 8 of 15

TECHNICAL DATA TABLE

XLPE/PVC/SWA/PVC-FR-UV 600/1000V

DIMENSIONAL DATA LV LV LV LV

Voltage Uo/U KV 0.6/1 0.6/1 0.6/1 0.6/1


Size Nominal mm2 3Gx2.5 4Gx2.5 3Gx4 3Gx6
Conductor Type (Phase) Non Compact Non Compact Non Compact Non Compact
Conductor Diameter Approx mm 1.98 1.98 2.51 3.08
Insulation Thickness Min.Ave mm 0.7 0.7 0.7 0.7
Min.Spot mm 0.53 0.53 0.53 0.53
Insulation Diameter Approx mm 3.3 3.3 3.8 4.4
Inner Covering Thickness Min.Spot mm 0.6 0.6 0.6 0.6
Inner Covering Diameter Approx mm 9.0 9.8 10.1 11.3
Armour Wire diameter Nominal mm 0.9 0.9 0.9 0.9
Diameter Over Armour Approx mm 10.7 11.6 11.8 13.1
Oversheath Thickness Min.Spot mm 1.24 1.24 1.24 1.24
External diameter of cable Approx mm 13.9 14.8 15.0 16.3
Diameter Tolerance ±1.0 mm ±1.0 mm ±1.0 mm ±1.0 mm
Mass of cable Approx Kg/Km 376 430 462 559
Standard Length Nominal M 1000 1000 1000 1000
Drum Size mm 1200 1200 1200 1400
Bending Radius Minimum mm 140 150 150 165
Pulling Tension
Eye on Conductor Maximum Kgf 52.5 70 84 126
Stocking on Cable Maximum kN 0.7 0.8 0.8 0.9
Side Wall Pressure Maximum kN/m 5 5.4 5.3 5.5

ELECTRICAL DATA
DC Resistance at 20 ºC (Phase) Maximum Ω/km 7.41 7.41 4.61 3.08
AC Resistance at 90 ºC Maximum Ω/km 9.448 9.448 5.878 3.927
Reactance at 50 Hz Approx Ω/km 0.093 0.093 0.087 0.083
Capacitance Approx µF/km 0.153 0.135 0.173 0.193
Impedance Approx Ω/Km 9.448 9.448 5.879 3.928
Inductance Approx mH/km 0.301 0.295 0.283 0.269
Conductor Fault at 1s [Phase] kA 0.4 0.4 0.6 0.9
Current rating in Ground *) A 43 47 55 69
Current Rating in Air *) A 34 37 44 56
Voltage Drop mV/A/m 16.364 16.364 10.183 6.803
Insulation Resistance MΩ.km 2000 2000 2000 2000
Conductor Operating Temperature Maximum °C 90 90 90 90
AC Voltage Test for 5 minute KV 3.5 3.5 3.5 3.5

*) Air Temp.=30°C ,Ground Temp.= 20°C,Soil Thermal Resistivity =1.0K.m/W,Depth of Laying =500mm

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed
as a result of our efforts to improve the quality of our products.