0% found this document useful (0 votes)
52 views4 pages

CO2 Salida Analogax3

This document summarizes a carbon dioxide transmitter that measures and transmits measurements of carbon dioxide, temperature, and relative humidity. It uses a non-dispersive infrared sensor to accurately measure carbon dioxide levels. It can provide up to three analog outputs to transmit the measurements. Additional features include optional LCD display, Modbus communication, and wall mounting. It is suitable for use in building ventilation systems and other applications to monitor indoor air quality.

Uploaded by

Tomas Velasquez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views4 pages

CO2 Salida Analogax3

This document summarizes a carbon dioxide transmitter that measures and transmits measurements of carbon dioxide, temperature, and relative humidity. It uses a non-dispersive infrared sensor to accurately measure carbon dioxide levels. It can provide up to three analog outputs to transmit the measurements. Additional features include optional LCD display, Modbus communication, and wall mounting. It is suitable for use in building ventilation systems and other applications to monitor indoor air quality.

Uploaded by

Tomas Velasquez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Carbon Dioxide Transmitter

with Temperature and RH% Option

Model#: G01-CO2-B10C/30C

 Real time carbon dioxide detection and transmitting


 High accuracy Temperature and humidity detection
 NDIR infrared CO2 sensor with patented self calibration
 Provide 3xanalog linear outputs for measurements
 Optional LCD display of all measurements
 Modbus communication
 CE-approval

 Features
 Design for real time measuring ambiance carbon sensors seamlessly with the digital auto
dioxide level and temperature +RH% compensation
 NDIR infrared CO2 sensor inside with special  Provide up to three analog linear outputs for
Self Calibration. It makes CO2 measurement measurements
more accurate and more reliable.  LCD is optional to display CO2 and temperature
 More than 10 years lifetime of CO2 sensor &RH measurements
 High accuracy temperature and humidity  Optional Modbus communication
measurement  24VAC/VDC power supply
 Combined both humidity and temperature  EU standard and CE-approval

 Application
 Building ventilation systems
 Industry ventilation systems
 Airport, train station, shopping mall, office, classroom and
other public places for air quality measurement and
indication
 Lab., warehouse, and other places to detect
CO2+Temp. +RH%

1
 Specifications

Carbon Dioxide

Sensing element Non-Dispersive Infrared Detector (NDIR)

CO2 measuring range 0~2000ppm/ 0~5,000ppm optional

CO2 Accuracy @22℃(72℉) ±40ppm + 3% of reading or ±75ppm (whichever is greater)

Temperature dependence 0.2% FS per℃

Stability <2% of FS over life of sensor (15 year typical)

Pressure dependence 0.13% of reading per mm Hg

Calibration ABC Logic Self Calibration Algorithm

Response time <2 minutes for 90% step change typical

Signal update Every 2 seconds

Warm-up time 2 hours (first time) / 2 minutes (operation)

Temperature Humidity

Measuring range 0℃~50℃(32℉~122℉) (default) 0 ~100%RH

Accuracy ±0.4℃ (20℃~40℃) ±3%RH (20%-80%RH)

Display resolution 0.1℃ 0.1%RH

Stability <0.04℃/year <0.5%RH/year

General Data

Power supply 24VAC/VDC

Consumption 1.8 W max. ; 1.2 W avg.


1~3 X analog outputs
Analog outputs 0~10VDC(default) or 4~20mA (selectable by jumpers)
0~5VDC (selected at placing the order)
RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic
Modbus communication (optional)
protection, independent base address.
Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing

Storage conditions 10~50℃(50~122℉), 20~60%RH non condensing

Net Weight 240g

Dimensions 130mm(H)×85mm(W)×36.5mm(D)

Installation wall mounting with 65mm×65mm or 2”×4”wire box

Housing and IP class PC/ABS fireproof plastic material, protection class: IP30

Standard CE-Approval

2
 Models Guide

G01-CO2-B X 0 C –Y 0 Z –U 02/05 –T/TH –Txx

X: LCD or no LCD
1- Without LCD, 24VAC/VDC power supply
3- LCD display, 24VAC/VDC power supply

C: 24VAC/VDC power supply

Y: analog output quantity


3-3Xanalog outputs (for CO2, temperature, humidity)
2-2Xanalog outputs (for CO2, temperature)
1-1xanalog output (for CO2)
0-no analog output

Z: Modbus communication
1-with Modbus communication
0-no Modbus

U: type of analog output


V- 0~10VDC (default)
A- 4~20mA
V5- 0~5VDC (not be changed)

02/05: CO2 range


02- 0~2000ppm
05- 0~5000ppm

T/TH: temperature option/ temperature and humidity option

Txx: temperature scaling


T05: 0℃~50℃(32℉~122℉) default (without the postfix indicates the default)
T06: 0℃~60℃(32℉~140℉)
T26: -20℃~60℃(-4℉~140℉)

Accessory (selectable at placing the order)


921: back plate for wall mounting
921+922: desktop bracket

3
 Mounting and Dimensions
85.00 36.50

TONGDY

A1 A2 4.20
9.50

130.00 84.00

60.00 60.00

24Vac/dc GND AN1 AN2 AN3 B A


RS-485
AC/DC

1 2 3 4 5 6 7
CO2 Transmitter/Controller

B1 B2