Dnp3 Control Relay Output Block Command
Dnp3 Control Relay Output Block Command
RX 05 | 64 | 1A | 44 | 00 | 00 | 0A | 00 | 47 | 9F | F9 | C9 | 81 | 00 | 00 | 0C | 01 | 17 | 01
| 64 | 41 | 01 | 20 | 03 | 00 | 00 | 08 | 09 | 00 | 00 | 00 | 00 | 04 | 87 | 26 |
*This bit must be set whenever one of the slave’s output points is in local operation mode.
This indication is not intended to inhibit or prevent controls from the master: it is a
warning that controls might not succeed. The system implementer must provide suitable
lockouts that disable control operation from the master when points are in local mode. If
the master directs a control command to a point in local mode, the slave shall return a
status code indicating failure due to the point being in local mode. Masters may send
control requests to slaves that set IIN1.5 because this bit does not necessarily mean that all
points are disabled for operation from the master. For example, in a data concentrator
application, only one IED may be in the local mode. This requires the data concentrator to
set IIN1.5; however, control commands to the other IEDs should succeed. Slaves that have
a local-remote switch or logic are responsible for preventing control actions on those
points that it places in local mode.