0% found this document useful (0 votes)
100 views64 pages

NFS320 Installation Manual-52745 2012

This document provides a 3 sentence summary of a fire alarm control panel installation manual: The manual outlines installation precautions and limitations of a fire alarm system, noting that smoke and heat detectors have sensing limitations and may not detect all fires. It emphasizes the importance of proper installation, maintenance, and testing of the fire alarm equipment according to NFPA standards to ensure effective operation. Failure to properly install or maintain the system could result in equipment damage or limit the ability of the fire alarm to detect and respond to a fire.

Uploaded by

Erick Trejo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views64 pages

NFS320 Installation Manual-52745 2012

This document provides a 3 sentence summary of a fire alarm control panel installation manual: The manual outlines installation precautions and limitations of a fire alarm system, noting that smoke and heat detectors have sensing limitations and may not detect all fires. It emphasizes the importance of proper installation, maintenance, and testing of the fire alarm equipment according to NFPA standards to ensure effective operation. Failure to properly install or maintain the system could result in equipment damage or limit the ability of the fire alarm to detect and respond to a fire.

Uploaded by

Erick Trejo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

Fire Alarm Control Panel

NFS-320/E/C
Installation Manual

H1
Document 52745
09/09/2011 Rev:
P/N 52745:H1 ECN 12-0443
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guides for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which are made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. These documents can be found at http:// pling its ability to report a fire.
www.systemsensor.com/html/applicat.html. A study by the Audible warning devices such as bells may not alert people
Federal Emergency Management Agency (an agency of the if these devices are located on the other side of closed or
United States government) indicated that smoke detectors partly open doors or are located on another floor of a building.
may not go off in as many as 35% of all fires. While fire alarm Any warning device may fail to alert people with a disability or
systems are designed to provide early warning against fire, those who have recently consumed drugs, alcohol or medica-
they do not guarantee warning or protection against fire. A fire tion. Please note that:
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons: • Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on • Studies have shown that certain people, even when they
roofs, or on the other side of closed doors. Smoke detectors hear a fire alarm signal, do not respond or comprehend the
also may not sense a fire on another level or floor of a building. meaning of the signal. It is the property owner's responsi-
A second-floor detector, for example, may not sense a first- bility to conduct fire drills and other training exercise to
floor or basement fire. make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors • In rare instances, the sounding of a warning device can
because: cause temporary or permanent hearing loss.

• Barriers such as closed or partially closed doors, walls, or A fire alarm system will not operate without any electrical
chimneys may inhibit particle or smoke flow. power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
• Smoke particles may become “cold,” stratify, and not reach been properly maintained and replaced regularly.
the ceiling or upper walls where detectors are located.
Equipment used in the system may not be technically com-
• Smoke particles may be blown away from detectors by air patible with the control panel. It is essential to use only equip-
outlets. ment listed for service with your control panel.
• Smoke particles may be drawn into air returns before Telephone lines needed to transmit alarm signals from a
reaching the detector. premise to a central monitoring station may be out of service
The amount of “smoke” present may be insufficient to alarm or temporarily disabled. For added protection against tele-
smoke detectors. Smoke detectors are designed to alarm at phone line failure, backup radio transmission systems are rec-
various levels of smoke density. If such density levels are not ommended.
created by a developing fire at the location of detectors, the The most common cause of fire alarm malfunction is inade-
detectors will not go into alarm. quate maintenance. To keep the entire fire alarm system in
Smoke detectors, even when working properly, have sensing excellent working order, ongoing maintenance is required per
limitations. Detectors that have photoelectronic sensing the manufacturer's recommendations, and UL and NFPA stan-
chambers tend to detect smoldering fires better than flaming dards. At a minimum, the requirements of NFPA 72 shall be
fires, which have little visible smoke. Detectors that have ion- followed. Environments with large amounts of dust, dirt or
izing-type sensing chambers tend to detect fast-flaming fires high air velocity require more frequent maintenance. A main-
better than smoldering fires. Because fires develop in different tenance agreement should be arranged through the local man-
ways and are often unpredictable in their growth, neither type ufacturer's representative. Maintenance should be scheduled
of detector is necessarily best and a given type of detector monthly or as required by National and/or local fire codes and
may not provide adequate warning of a fire. should be performed by authorized professional fire alarm
Smoke detectors cannot be expected to provide adequate installers only. Adequate written records of all inspections
warning of fires caused by arson, children playing with should be kept. 
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of Limit-C1-2-2007

flammable materials, etc.).


2 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interference, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside aerial
energized. Do not attempt to install, service, or operate this wiring is not recommended, due to an increased susceptibility
unit until manuals are read and understood. to nearby lightning strikes. Consult with the Technical Ser-
CAUTION - System Re-acceptance Test after Software vices Department if any problems are anticipated or encoun-
Changes: To ensure proper system operation, this product tered.
must be tested in accordance with NFPA 72 after any pro- Disconnect AC power and batteries prior to removing or
gramming operation or change in site-specific software. Re- inserting circuit boards. Failure to do so can damage circuits.
acceptance testing is required after any change, addition or Remove all electronic assemblies prior to any drilling, filing,
deletion of system components, or after any modification, reaming, or punching of the enclosure. When possible, make
repair or adjustment to system hardware or wiring. All compo- all cable entries from the sides or rear. Before making modifi-
nents, circuits, system operations, or software functions known cations, verify that they will not interfere with battery, trans-
to be affected by a change must be 100% tested. In addition, former, or printed circuit board location.
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected Do not tighten screw terminals more than 9 in-lbs. Over-
by the change, up to a maximum of 50 devices, must also be tightening may damage threads, resulting in reduced terminal
tested and proper system operation verified. contact pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits
protection against such interference when devices are radioelectriques depassant les limites applicables aux
operated in a commercial environment. Operation of this appareils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.

HARSH™, NIS™, Notifier Integrated Systems™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®,
ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark
and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©Thursday, August 16, 2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 3


Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

4 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Table of Contents
Section 1: About This Manual.................................................................................................. 7
1.1: Standards and Other Documents....................................................................................................................7
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Related Documents ........................................................................................................................................8
1.4: Cautions and Warnings ..................................................................................................................................9
1.4.1: Typographic Conventions....................................................................................................................9
Section 2: System Overview .................................................................................................. 10
2.1: System Description ......................................................................................................................................10
2.1.1: Standard Features ..............................................................................................................................10
2.1.2: Options ..............................................................................................................................................11
2.1.3: System Limitations ............................................................................................................................11
2.2: System Components ....................................................................................................................................11
2.2.1: Standard Equipment ..........................................................................................................................11
2.2.2: Control Panel Circuit Board .............................................................................................................11
2.2.3: Main Power Supply CPS-24/E ..........................................................................................................12
2.2.4: Circuit Board Components ................................................................................................................13
2.2.5: System Cabinet ..................................................................................................................................15
2.3: Compatible Equipment ...............................................................................................................................16
Section 3: Installation............................................................................................................. 18
3.1: Preparing for Installation .............................................................................................................................18
3.1.1: Standards and Codes..........................................................................................................................18
3.2: Installation Checklist ...................................................................................................................................19
3.3: Mounting a Cabinet .....................................................................................................................................20
3.4: Installing Option Boards..............................................................................................................................20
3.5: Connecting the Power Cables ......................................................................................................................22
3.5.1: Overview ...........................................................................................................................................22
3.5.2: Connecting the Control Panel to AC Power......................................................................................23
3.5.3: Checking AC Power ..........................................................................................................................23
3.5.4: Installing and Connecting the Batteries ............................................................................................24
3.5.5: External DC Power Output Connections...........................................................................................24
3.5.6: Accessories DC Power Output Connections .....................................................................................25
3.6: NAC Connections and Releasing Circuits...................................................................................................26
3.7: Output Relay Connections ...........................................................................................................................27
3.8: Backup-Alarm Switches .............................................................................................................................27
3.9: UL Power-limited Wiring Requirements.....................................................................................................28
3.9.1: Labeling Modules and Circuits..........................................................................................................29
3.10: Installing EIA-485 Devices .......................................................................................................................29
3.11: Installing Remote Printers and/or CRT......................................................................................................29
3.11.1: Custom Cable Fabrication ...............................................................................................................29
3.11.2: Installing and Configuring the PRN Series Printer .........................................................................30
3.11.3: Installing and Configuring a CRT-2................................................................................................31
3.11.4: Connecting Multiple Printers, CRTs, or CRT/PRN Combination ..................................................32
3.12: Wiring a Signaling Line Circuit (SLC)......................................................................................................33
3.13: Connecting a PC for Off-Line Programming ............................................................................................34
Section 4: Applications .......................................................................................................... 35
4.1: Overview......................................................................................................................................................35
4.2: Devices Requiring External Power Supervision..........................................................................................35
4.3: NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) ..................................36
4.4: Central Station Fire Alarm System Canadian Requirements.......................................................................38
4.5: NFPA 72 Proprietary Fire Alarm Systems...................................................................................................39
4.6: Fire/Security Applications ..........................................................................................................................39

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 5


Table of Contents

4.6.1: General Operation..............................................................................................................................39


4.6.2: Installing a Security Tamper Switch..................................................................................................40
4.6.3: Receiving Unit ...................................................................................................................................40
4.6.4: Programming .....................................................................................................................................40
4.6.5: Wiring for Proprietary Security Alarm Applications ........................................................................41
4.7: Releasing Applications ................................................................................................................................42
4.7.1: Overview............................................................................................................................................42
4.7.2: Programming .....................................................................................................................................42
4.7.3: Wiring ................................................................................................................................................42
4.7.4: Connecting a Releasing Device to the Control Panel ........................................................................43
4.7.5: Connecting a Releasing Device to the FCM-1 Module.....................................................................45
4.7.6: Connecting a Releasing Device to the FCM-1-REL .........................................................................46
4.7.7: Connecting an NBG-12LRA Agent Release-Abort Station ..............................................................47
Section 5: Testing the System .............................................................................................. 49
5.1: Acceptance Test ...........................................................................................................................................49
5.2: Periodic Testing and Service........................................................................................................................49
5.3: Operational Checks ......................................................................................................................................49
5.4: Battery Checks and Maintenance.................................................................................................................50
Appendix A: Power Supply Calculations ............................................................................. 51
A.1: Calculating AC Branch Circuit Current......................................................................................................51
A.2: Calculating the System Current Draws ......................................................................................................51
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw..........................................54
A.3: Calculating the Battery Requirements ........................................................................................................55
A.3.1: Calculating the Battery Capacity ......................................................................................................55
A.3.2: Calculating the Battery Size .............................................................................................................56
Appendix B: Electrical Specifications .................................................................................. 57
B.1: Electrical Specifications ..............................................................................................................................57
B.2: Wire Requirements......................................................................................................................................59
Index ........................................................................................................................................ 61

6 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Section 1: About This Manual

1.1 Standards and Other Documents


 This Fire Alarm Control Panel complies with the following NFPA standards:
• NFPA 12 CO2 Extinguishing Systems
• NFPA 12A Halon 1301 Extinguishing Systems
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
• NFPA 17 Dry Chemical Extinguishing Systems
• NFPA 17A Wet Chemical Extinguishing Systems
• NFPA 72 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit (requires Notifier UDACT/UDACT-2).
• NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems.
• NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4).
• NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected
Premises Unit).
• NFPA 2001 Clean Agent Fire Extinguishing Systems

 The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 2017 Standard for General-Purpose Signaling Devices and Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• C22.1-98 The Canadian Electrical Code, Part 1

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 7


About This Manual UL 864 Compliance

1.2 UL 864 Compliance


1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the NFS-320/E/C with products not tested for UL 864 9th Edition
has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864.
These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
• For a complete list of all peripherals that can be used with this fire alarm control panel (FACP),
and which of those peripherals have not received UL 864, 9th Edition certification and may
only be used in retrofit applications, see Section 2.3, “Compatible Equipment”, on page 16.

1.3 Related Documents


Table 1.1 below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-NOT) provides the current
document revision. A copy of this document is included in every shipment.

Compatible Conventional Devices (Non-addressable) Document Number

Device Compatibility Document 15378

Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number

NFS-320/E/C Installation, Operations, and Programming Manuals 52745, 52746, 52747


NFS-320C Canadian Applications Addendum 52745CDN

SLC Wiring Manual 51253

Note: For individual SLC Devices, refer to the SLC Wiring Manual

Off-line Programming Utility Document Number

VeriFire® Tools CD help file VERIFIRE-TCD

Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number

ACPS-2406 Installation Manual 51304

ACPS-610 Instruction Manual 53018

APS-6R Instruction Manual 50702

APS2-6R Instruction Manual 53232

CHG-120 Battery Charger Manual 50641

FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Manual 51977

Networking Document Number

High-Speed Network Communication Module 54014

High-Speed Noti•Fire•Net Instruction Manual 54013

Noti•Fire•Net Manual, Network Version 5.0 & Higher 51584

ONYXWorks™ Workstation Hardware & Software Application: Installation and Operation Manual 52342

ONYXWorks™ NFN Gateway (PC Platform) Installation & Operation Manual 52307

Table 1.1 Reference Documentation (1 of 2)

8 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Cautions and Warnings About This Manual

ONYXWorks™ NFN Gateway (Embedded Platform) Installation & Operation Manual 52306

NCM-W/F Installation Document 51533

NCS ONYX® Network Control Station Manual, Network Version 4.0 & Higher 51658

NCA-2 Network Control Annunciator Manual 52482

NCA Network Control Annunciator Manual 51482

System Components Document Number

Annunciator Control System Manual 15842

ACM-8R Annunciator Control Module Manual 15342

FDU-80 Remote Annunciator Manual 51264

LCD-80 Liquid Crystal Display Annunciator 15037

LCD2-80 Liquid Crystal Display Annunciator 53242

LDM Series Lamp Driver Annunciator Manual 15885

SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712

DPI-232 Direct Panel Interface Manual 51499

TM-4 Installation Document (Reverse Polarity Transmitter) 51490

UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050

UDACT-2 Manual (Universal Digital Alarm Communicator/Transmitter) 54089

FireVoice-25/50 & FireVoice-25/50ZS Manual 52290

RA100Z Remote LED Annunciator Installation Document I56-0508

Table 1.1 Reference Documentation (2 of 2)

1.4 Cautions and Warnings


This manual contains cautions and warnings to alert the reader as follows:

CAUTION:
! Information about procedures that could cause programming errors, runtime errors, or equipment
damage.

WARNING:
! Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.

1.4.1 Typographic Conventions


NOTE: The term NFS-320 is used in this manual to refer to the NFS-320, and the NFS-320E
and the NFS-320C, unless otherwise noted.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 9


Section 2: System Overview

2.1 System Description


The NFS-320/E/C control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is mounted in its cabinet to create a complete fire alarm control system. The
panel supports FlashScan® and CLIP mode; the board provides an integral signalling line circuit
(SLC) that can support up to 318 addressable points (159 detectors and 159 monitor/control
modules). The panel is networkable, and can be monitored across a network by other networked
panels.
Modular devices mount in the cabinet or in auxiliary backboxes to provide additional circuits. This
system is available in either a 120 VAC or 240 VAC configuration. Cabinetry can be ordered in
black or in red. The NFS-320/E/C chassis is removable, allowing work to be done outside the
cabinet.

2.1.1 Standard Features


• Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or Classic Loop
Interface Protocol (CLIP) families of detectors and modules
• Integral power supply with battery charger
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Releasing service using on-board NACs or FCM-1 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports ONYX® Intelligent Sensing algorithms
• Network operation
• Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT, printer/CRT, or network operation
• VeriFire Tools® off-line programming utility
• Autoprogram feature for faster device programming
• The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection (0 ohm impedance)
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Disconnect of deeply-discharged battery (low battery disconnect)
• Programmable for strobe synchronization
• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs

10 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


System Components System Overview

2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• Optional devices include: Wire and Fiber versions of the NCM or HS-NCM connection to the
Noti•Fire•Net and High-Speed Noti•Fire•Net, UDACT/UDACT-2 Universal Digital Alarm
Communicator/Transmitter, and ACM-8R remote relay module to increase point capacity.
• Optional annunciators connected through the EIA-485 interface allow remote system
monitoring.

2.1.3 System Limitations


System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries). (Note that batteries larger than
26 AH will require a separate battery backbox.)

2.2 System Components


2.2.1 Standard Equipment
The standard, factory-assembled NFS-320/E/C system includes the following components:
• The control panel with integral power supply, and cabinet. NFS-320 (120V operation) or NFS-
320E (220-240V operation), and CPS-24/E. NFS-320/E is the “control panel” itself and the
heart of the system; it ships with a grounding cable, battery interconnect cables, and document
kit. CPS-24/E mounts directly on the control panel. The system ships pre-installed in its
cabinet.

NOTE: The CPS-24/E is an integral part of the NFS-320 and is not available separately.

• A primary display KDM-R2 keypad/display.


Batteries are ordered separately; refer to Appendix A.3 “Calculating the Battery Requirements” for
system current-draw calculations.
Up to two option boards can be installed within the FACP’s cabinet; additional optional peripherals
can be mounted in auxiliary backboxes. Refer to Section 2.3, “Compatible Equipment” for
equipment listed for use with this FACP.

2.2.2 Control Panel Circuit Board


The control panel electronics are contained in NFS-320 and its built-in power supply. The printed
circuit board incorporates a signaling line circuit (SLC) and the central processing unit; the power
supply has an integral battery charger. A keypad/display unit is installed over the power supply as
shown Figure 2.1. Wiring is shown in Figure 2.2, “NFS-320 and Power-Supply: Wiring
Connections” and Figure 2.3, “NFS-320 and Power-Supply: Jumpers, LEDs and Switches”.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 11


System Overview System Components

Figure 2.1 NFS-320/E/C System, Shown with Door Open

2.2.3 Main Power Supply CPS-24/E


The main power supply is an integral part of the NFS-320/E/C and mounts directly over the control
panel’s circuit board. It provides a total of 3.9 A (7.4 A in alarm) and contains an integral battery
charger. This can be used for many functions including:
• Powering the NFS-320/E/C
• Powering a variety of UL-listed 24 VDC notification appliances from four built-in NAC
outputs
• Providing up to 1.25 A of resettable power for four-wire smoke detectors
• Providing up to 1.25 A of non-resettable power for external devices such as the TM-4
Transmitter Module
• Providing auxiliary 24 VDC power @ 0.5 A and 5 VDC power @ 0.15 A
• Fuse: 8 amps, 250 V, 5 x 20 mm, Fast Acting, ceramic, p/n 12117
See Figure 2.2, “NFS-320 and Power-Supply: Wiring Connections” and Figure 2.3, “NFS-320 and
Power-Supply: Jumpers, LEDs and Switches” for details.

12 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


TB10 - DC Power TB11 - EIA-485 Terminal Mode Connection (supervised) 
(24 VDC power-limited) (Figure 3.13 on page 29)
Resettable TB11 - EIA-485 ACS Mode Connection (supervised)
Non-resettable
(See Figure 3.6 on page 24) TB12 - EIA-232 Printer Connection (Figure 3.14 on page 30)
TB12 - EIA-232 PC/Terminal Connection (CRT)
(Figure 3.15 on page 31)
J1 - Network/Service Connection (NUP) 
System Components

(power-limited, supervised)

J2 - USB A VeriFire Tools Connection


J3 - USB B VeriFire Tools Connection
TB13 - SLC Loop #1 
All NAC Circuits: power- (supervised, power-
limited, supervised limited)
(Figure 3.9 on page 26) (Figure 3.17)

TB9 - NAC#1

TB3 - Battery Connection 


TB8 - NAC#2
(over-current protected, non-power-limited)
(+) (-)

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


2.2.4 Circuit Board Components

TB7 - NAC#3
TB2 - Secondary Power Auxiliary Outputs
(power-limited)
(Larger images are referenced on these drawings.)

TB6 - NAC#4

TB1 - AC Power Connection (non-


Hot power-limited)
Neutral
Earth
Ground

TB5 - 

Figure 2.2 NFS-320 and Power-Supply: Wiring Connections


Supervisory Relay
Security Relay

TB4 - 
CPU320-KAPS-291809.wmf

Alarm Relay
Trouble Relay
LEDs on the NFS-320 and its power supply. Figure 2.2 shows wiring connections; Figure 2.3

Output Relays - power-limited only if connected to a power-limited


source. (See Figure 3.10 on page 27 for details.) J7 - KDM-R2
Connection J5 - Security Tamper Switch
The following three figures illustrate the location of the various connections, switches, jumpers and

shows jumpers, LEDs and switches. See Section 3 “Installation” for larger images and more details.

13
System Overview

J6 - Auxiliary Trouble Input


JP1 - SLC Ground

14
JP2 - Cut for 200MA Operation Fault Jumper
NAC
LEDs
System Overview

LED5 - +24V Aux LED

LED6 - +5V Aux LED


LED6
LED1 -- +5V
LogicAux
Power
LEDLED

LED2 - Trouble LED


LED3 - Earth Fault LED (general board ground fault)
SW1 - Ground Fault Detection Enable/Disable

LED4 - AC Power LED


LED10 – SLC Loop
Ground Fault LED
F4- AC Fuse
CPU320-KAPS-291809.wmf, CPU2-640-LEDs.wmf

Disable - Enable Switches System Switches - ‘No


for Backup Alarm Keyboard Operation’
(Figure 3.11 on page 27) SW5 - Acknowledge
SW6 - Silence
SW7 - Reset

Figure 2.3 NFS-320 and Power-Supply: Jumpers, LEDs and Switches


LED1 - Power-on LED (AC or battery)
LED2 - Signals Silenced LED
LED3 - Point Disabled LED
LED4 - System Trouble LED
LED5 - Supervisory LED
LED6 - Security LED
LED7 - Pre-Alarm LED

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


System Components

LED8 - Fire Alarm LED


System Components System Overview

2.2.5 System Cabinet


The control panel is factory installed in its backbox. The lockable door is hinged on the left and
opens a full 180 degrees. Mounting methods include surface-mounting or semi-flush mounting on a
wall between 16 inch (40.64 cm) on-center studs. A trim ring option is available for semi-flush
mounting.
External measurements:
• Backbox: 18.12 in. (46.025 cm) width; 
18.12 in. (46.025 cm) height; 
5.81 in. (14.76 cm) depth.
• Door: 18.187 in. (46.195 cm) width;
18.40 in. (46.736 cm) height; 
0.75 in. (1.905 cm) depth.
When using trim ring TR-320, mount backbox with at least 1 inch (2.54 cm) between wall surface
and front of backbox, to allow door to open fully past the trim ring. The TR-320 molding width is
0.905 in. (2.299 cm).

 Additional Options

The NFS-320/E/C control panel provides space for one or two additional option boards to be
installed, as shown in Figure 3.3 on page 21. The NFS-320C fulfills ULC annunciation
requirements; see NFS-320C Canadian Applications Addendum for details. A variety of compatible
annunciators are available with their own backboxes; see Section 2.3, “Compatible Equipment”.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 15


System Overview Compatible Equipment

2.3 Compatible Equipment


These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-
addressable equipment see the Device Compatibility Document. These devices are UL and ULC
listed unless marked otherwise (in parentheses next to the product). Other control panels and their
equipment can also be connected in a network, via Noti•Fire•Net version 5.0 or the High-Speed
Noti•Fire•Net; refer to the Noti•Fire•Net Version 5.0 & Higher Installation Manual or High-Speed
Noti•Fire•Net Installation Manual for details. For products documented separately, see Section 1.3
“Related Documents”.

WARNING: UL 9th Edition Compliance


! This product has been certified to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of the NFS-320/E/C with
products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72
and/or the latest edition of UL 864. These applications will require the approval of the local Authority
Having Jurisdiction (AHJ). 
Peripheral devices in the second list were listed under UL 8th Edition and may only be used in retrofit
applications (see Section 1.2, “UL 864 Compliance”, on page 8).

Notifier Compatible Equipment


NOTE: Products marked with a checkmark “” have not received UL 864 9th Edition certification
and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8).

ABF-1B Annunciator Flush Box FCO-851 Photo/CO Detector


ABF-1DB Annunciator Flush Box with Door FCPS-24S6/8 Field Charger Power Supply
ABF-2B Annunciator Flush Box FDM-1 Dual Monitor Module
ABF-2DB Annunciator Flush Box with Door FDX-551 Intelligent Thermal Sensor
ABF-4B Annunciator Flush Box FDU-80 Remote Fire Annunciator
ABM-16AT Annunciator Blank Module FMM-1 Monitor Module
ABM-32A Annunciator Module Blank FMM-101 Mini Monitor Module
ABS-1TB Annunciator Surface Box FSC-851 IntelliQuad Multi-Criteria Detector
ABS-1B Annunciator Surface Box FSB-200S Single-ended beam smoke detector with
ABS-2B Annunciator Surface Box sensitivity testing
ABS-4D Annunciator Surface Box FSB-200 Single-ended beam smoke detector.
ABS-8RB Annunciator Backbox for ACM-8R FSD-751P Photoelectric Duct Detector
ACM-24AT Annunciator Control Module FSD-751RP Photoelectric Duct Detector with alarm
ACM-48A Annunciator Control Module relay
ACM-8R Annunciator Control Module FSD-751PL Low-flow Duct Detector
ACPS-610 Addressable Charger/Power Supply FSD-751RPL Low-flow Duct Detector with alarm
AEM-24AT Annunciator Expander Module relay
AEM-48A Annunciator Expander Module FSI-751, FSI-851 Ion Detector
AKS-1B Annunciator Key Switch FAPT-751, FAPT-851 Acclimate Plus™
BAT-12180 Battery 12-volt, 18 amp-hour Combination Photoelectric/Heat Detector
BAT-12250 Battery 12-volt, 25 amp-hour FSH-751 HARSH™ Smoke Detector
BAT-12260 Battery 12-volt, 26 amp-hour FSL-751 VIEW® Low Profile Laser Detector
BAT-12550 Battery 12-volt, 55 amp-hour FSM-101 Pull Station Monitor Module
BAT-12600 Battery 12-volt, 60 amp-hour FPJ Firefighter’s Phone Jack
BAT-121000 Battery 12-volt, 100 amp-hour FRM-1 Relay Module
BX-501 Intelligent Detectors/Sensors Base FSP-751, FSP-851 Photo Detector
B501 Intelligent base FSP-751T, FSP-851T Photo/Thermal Detector
B200SR Sounder base FST-751, FST-851 Thermal Detector
B710LP Intelligent detector base FST-751R, FST-851R Thermal Detector (rate of rise)
CCM-1 Communication Converter Module FST-851H High Temperature Detector
CHG-120 Battery Charger FTM-1 Telephone Module
CMX-1 Addressable Control Module FZM-1 Monitor and Zone Interface Module
CMX-2 Addressable Control Module FV-25/50 FireVoice 25/50
NFS-320/E/C Control Panel Circuit Board FV-25/50ZS FireVoice 25/50 Zone Splitter
CPX-551 Ionization Smoke Detector HPX-751Intelligent HARSH™ Detector (CLIP)
CPX-751 Intelligent Ionization Smoke Detector HS-NCM-MF High-Speed Network Communications
CRT-2 Video Display Monitor with Keyboard Module (Multi-Mode Fiber)
DPI-232 Direct Panel Interface HS-NCM-MFSF High-Speed Network
DHX-501, DHX-502 Duct Detectors Communications Module (Multi-Mode Fiber to Single-
FCM-1 NAC Module Mode Fiber)
FCM-1-REL Releasing Control Module HS-NCM-SF High-Speed Network Communications

Continued on next page...

16 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Compatible Equipment System Overview

Module (Single-Mode Fiber) NFS-LBB Battery Box


HS-NCM-W High-Speed Network Communications NFS-LBBR Red Battery Box
Module (Wire) ONYXWorks Graphical Workstation
HS-NCM-WMF High-Speed Network PRN-6 80-Column Printer
Communications Module (Wire to Multi-Mode Fiber) R-120 120 Ohm End-of-Line Resistor
HS-NCM-WSF High-Speed Network R-2.2K 2.2K End-of-Line Resistor
Communications Module (Wire to Single-Mode Fiber) R-27K 27K End-of-Line Resistor
ISO-X Loop Fault Isolator Module R-470 470 End-of-Line Resistor
KDM-R2 Keypad/Display Unit R-47K 47K End-of-Line Resistor
LCD-80 Liquid Crystal Display Module RPT-485W EIA-485 Repeater (Wire)
LDM-32 Lamp Driver Module RPT-485WF EIA-485 Repeater (Wire/Fiber)
LDM-E32 Lamp Driver Module A77-716B End-of-Line Resistor Assembly
LDM-R32 Lamp Driver Module RA100Z Remote Annunciator with diode
LPX-751 VIEW® Low Profile Laser Detector (CLIP SCS-8, SCE-8 Smoke Control Station
mode) SCS-8L, SCE-8L Smoke Control Lamp Driver
MMX-1 Addressable Monitor Module SDX-551 Intelligent Photoelectric Detector
MMX-2 Addressable Monitor Module SDX-751 Intelligent Photoelectric Detector
MMX-101 Addressable Mini Monitor Module STS-1 Security Tamper Switch
NBG-12LRA Agent Release-Abort Station TM-4 Transmitter Module
NBG-12 Series Manual Pull Station UDACT/UDACT-2 Universal Digital Alarm
NBG-12LX Addressable Manual Pull Station Communicator Transmitter
NCA-2 Network Control Annunciator XP6-C Supervised Control Module
NCM-F Network Control Module (Fiber) XP6-R Six Relay Control Module
NCM-W Network Control Module (Wire) XP6-MA Six Zone Interface Module
NCS Network Control Station XP10-M Ten Input Monitor Module
N-ELR Assortment ELR Pack with Mounting Plate

System Sensor Equipment


A2143-00 End of Line Resistor Assembly EOLR-1 End-of-Line Resistor Assembly

Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous


Editions of UL 864
NOTE: The products in this list have not received UL 864 9th Edition certification and may only be
used in retrofit applications (see Section 1.2, “UL 864 Compliance”, on page 8).
ACM-16AT Annunciator Control Module PRN-4, PRN-5 80-Column Printer
ACM-32A Annunciator Control Module RA400 Remote Annunciator
ACPS-2406 Auxiliary Charger/Power Supply RA400Z Remote Annunciator with diode
AEM-16AT Annunciator Expander Module XP5-C Transponder Control Module
AEM-32A Annunciator Expander Module XP5-M Transponder Monitor Module
APS-6R Auxiliary Power Supply XPC-8 Transponder Control Module
BGX-101L Addressable Manual Pull Station XPDP Transponder Dress Panel
CHG-120 Battery Charger XPM-8 Transponder Monitor Module
FCPS-24 Field Charger Power Supply XPM-8L Transponder Monitor Module
IPX-751Advanced Multi-Sensor Intelligent Detector XPP-1 Transponder Processor
(Discontinued) XPR-8 Transponder Relay Module
NCA Network Control Annunciator

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 17


Section 3: Installation

3.1 Preparing for Installation


Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and
maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors
needed for all devices and find the appropriate knockouts. (Refer to Section 3.9 “UL Power-limited
Wiring Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual, including temperature and
humidity limits for the system (Page 3).
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.

CAUTION:
! Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.

WARNING:
! This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.

3.1.1 Standards and Codes


In addition, installers should be familiar with the following standards and codes:
• NEC Article 300 Wiring Methods.
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
• C22.1-98 The Canadian Electrical Code, Part 1.
• CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.

18 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Installation Checklist Installation

3.2 Installation Checklist


Table 3.1 provides an installation checklist for installing, wiring, and testing the NFS-320/E/C
system. It has references to installation information included in manuals listed in Section 1.3
“Related Documents”.

Seq Task Refer to


1. Mount the cabinet backbox to the wall. Section 3.3 “Mounting a Cabinet”
2. If adding option boards such as such as wire and/or fiber Section 3.4 “Installing Option Boards”, 
version of the NCM/HS-NCM or TM-4: Section 1. “Remove and re-install KDM-R2 as shown in
• Remove keypad. Figure 3.2. It may be convenient to do some basic field-
• Install option boards wiring before reinstalling KDM-R2.”, and Section 3.4
• Replace keypad “Installing Option Boards”
Also see option board documentation for board-specific
details.
3. Optional: Install auxiliary power supply and/or external Auxiliary power manuals, Section 3.8 “Backup-Alarm
battery charger; set backup-alarm switches. Switches”
4. Connect AC wiring, place batteries into backbox without Section 3.5 “Connecting the Power Cables”
connecting them, and run cable to optional power supplies,
DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
5. Optional: Install output devices such as a printer, or CRT Section 3.11 “Installing Remote Printers and/or CRT”
terminal.
6. Wire annunciators and network connections. Relevant product manuals
7. Wire the Signaling Line Circuits. Section 3.12 “Wiring a Signaling Line Circuit (SLC)”
8. Terminate wire shielding as instructed. SLC Wiring Manual
9. Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries.
10. Check AC power. Table 3.2 in Section 3.5 “Connecting the Power Cables”
11. Connect the batteries using interconnect cable, P/N 75560 and 75561.
12. Program the control panel. NFS-320/E/C Programming Manual and VeriFire Tools
Online Help.
13. Field test the system. Section 5 “Testing the System”

Table 3.1 Installation Checklist


Top two
mounting holes

Location for 1 or 2
option boards

Two lower
mounting holes
are behind
batteries.

Figure 3.1 NFS-320/E/C in Cabinet

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 19


Installation Mounting a Cabinet

3.3 Mounting a Cabinet


This section provides instructions for mounting the NFS-320/E/C backbox to a wall. The NFS-
320/E/C is assembled with a removable chassis that can be removed to provide easier access to the
backbox’s mounting holes, or to allow the electronics to be worked on outside the cabinet.
Follow these guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the
finished floor.
• Access to the cabinet shall be provided in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.2.5 “System
Cabinet”.)
• Use the four holes in the back surface of the backbox to provide secure mounting. (See
Figure 3.1 on page 19.)
• Mount the backbox on a surface that is in a clean, dry, vibration-free area.

CAUTION:
! Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.

Follow the instructions below:


1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use
mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test
Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.9
“UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6. Feed wires through appropriate knockouts.

3.4 Installing Option Boards


The NFS-320/E/C ships fully assembled with in its cabinet. One or two option boards can be
mounted inside the NFS-320 cabinet, under the keypad, as shown in Figure 3.3. Option boards that
can be installed internally include the wire and/or fiber versions of the NCM or HS-NCM, TM-4,
and UDACT or UDACT-2. See Section 2.3, “Compatible Equipment” for a complete list. When
installing option boards, temporarily remove the KDM-R2 keypad/display unit to provide full
access to hardware connections. It may be convenient to do some basic field-wiring before
reinstalling KDM-R2.

NOTE: UDACT or UDACT-2 only: 


If using UDACT or UDACT-2 inside the cabinet, do not install a second option board. 
See the UDACT Manual or UDACT-2 Manual for instructions on using the mounting bracket.

20 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Installing Option Boards Installation

1. Remove and re-install


KDM-R2 as shown in
Figure 3.2. It may be
convenient to do some
basic field-wiring before

320_assembly_tech_pubs_5-2.wmf
reinstalling KDM-R2.
2. Lay the first option board
over the four stand-offs
already installed on the
CPU, so that the holes and
stand-offs align.

Figure 3.2 Removing and Reinstalling KDM-R2

3. If attaching a second
option board, use its standoffs to
secure the first option board, then lay
the second option board over the
standoffs. Two sizes of standoffs are
shipped with the option boards; select

320_assembly_tech_pubs_3-2.wmf
standoffs that allow sufficient
clearance for electronics on the lower
option board.
4. Secure the top option board with four
#4-40 screws (supplied).
5. Re-attach KDM-R2.

Figure 3.3 Installing Option Boards

CAUTION:
! It is critical that all mounting holes of the NFS-320/E/C are secured with a screw or standoff to insure
continuity of Earth Ground.

NOTE: It may be convenient to field-wire the SLC loop before installing any option boards, and
to make wiring connections on the first option board before installing a second option board in
front of it.

Installing a Transmitter Module TM-4


TM-4 is power-limited. Connections are on TB10 nonresettable output and TB11 EIA-485 ACS
Mode. Refer to the Transmitter Module TM-4 installation document for installation details.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 21


Installation Connecting the Power Cables

Network Communications Module


If networking two or more control panels or network control annunciators, each unit requires a
Network Communications Module (NCM) or a High-Speed Network Communications Module
(HS-NCM); wire and fiber versions are available for each. The wire and/or fiber versions of the
NCM or HS-NCM can be installed in any standard option-board position (see Section 3.4,
“Installing Option Boards”; the default position is immediately to the right of the control panel.
1. Mount the NCM/HS-NCM in the selected position and screw firmly in place.
2. Connect J1 on the control panel to J3 on the NCM or J6 of the HS-NCM using the network
cable provided (P/N 75556) as described in the NCM Installation Document and the HS-NCM
Installation Document. Do not connect two NCM/HS-NCMs via NUP ports (“NUP to NUP”).
3. When installing the NCM: Connect Channel A and/or Channel B as described in the NCM
Installation Document.
When installing the HS-NCM: Connect Channel A to Channel B as described in the HS-
NCM Installation Document.

NOTE: See the Noti•Fire•Net Manual or the High-Speed XLS-NET Manual and NCM Installation
Document or the HS-NCM Installation Document for wiring diagrams and system configuration
information. See the BMP-1 Product Installation Drawing if considering mounting the module
behind blank module plate in a dress plate or annunciator backbox.

NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm)
minimum bend radius.

NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on
the same network.

3.5 Connecting the Power Cables


WARNING:
! Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the entire system is complete.

WARNING:
! Several sources of power can be connected to the control panel. Before servicing the control panel,
disconnect all sources of input power including the battery. While energized, the control panel and
associated equipment can be damaged by removing and/or inserting cards, modules, or
interconnecting cables.

3.5.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 5.0 A from line voltage source (with NFS-
320E use 220-240 VAC, 50/60 Hz, 2.5 A). Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.31
mm2) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system during
loss of primary power.

22 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Connecting the Power Cables Installation

• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
• Auxiliary power source – 24 VDC power @ 0.5 A and 5 VDC power @ 0.15 A from TB2 on
the CPS-24/E.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.

3.5.2 Connecting the Control Panel to AC Power


Connect primary power as follows (see
TB1 - AC Power Connection
Figure 3.4):
1. Turn off the circuit breaker at the main
power distribution panel. Hot
Neutral
2. Open the hinged insulating cover on TB1.

CPS-24_TB1.wmf
Ground
3. Connect the service ground to terminal (Earth)
marked Ground (Earth).
4. Connect the primary neutral line to terminal
marked NEUTRAL and the primary Hot line Figure 3.4 CPS-24/E:
to terminal marked HOT. AC Power Connections
5. Close the hinged insulating cover over TB1.

3.5.3 Checking AC Power


Table 3.2 contains a checklist for checking the system with AC power applied:

CAUTION:
! While checking AC power, make sure batteries are not connected. 
Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 10.

Component Status
Control panel The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
circuit board
Each option board In an unconfigured system, the yellow Trouble indicator may come on for approximately 10 seconds after
applying AC power.
Each auxiliary power The yellow Trouble indicator comes on because batteries are not connected.
supply

Table 3.2 AC Power Checklist

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 23


Installation Connecting the Power Cables

3.5.4 Installing and Connecting the Batteries


w

WARNING:
! Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.

WARNING:
! Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this
connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2
“Installation Checklist”, Table 3.1; this is Step 11.

Batteries are installed in the control panel cabinet TB3 - Battery Connection
or in a separate battery cabinet which can be
mounted below the control panel or up to 20 feet Battery (+) Battery (-)
(6.096 m) away from the control panel, in conduit
in the same room.
Connect the battery as follows (see Figure 3.4

+24V AUX COM COM +5V AUX


above):
1. Install batteries into bottom of cabinet or into
separate battery cabinet.
2. Connect the red cable from TB3(+) on the Figure 3.5 CPS-24/E:
CPS-24/E power supply to the positive (+) DC Power Connections
terminal of one battery.
3. Connect the black cable from TB3(–) on the
CPS-24/E power supply to the negative (–) terminal of the other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the
positive (+) terminal on the second battery.

3.5.5 External DC Power Output Connections


Terminal TB10 provides two (2) power outputs, resettable and non-resettable. Each output is
power-limited. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is
part of Step 4.
Non-resettable Resettable
Power Power
CPU-320-DCOut.wmf

Figure 3.6 Power Supply DC Outputs - TB10

24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply
provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require
resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be
supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as
the EOLR-1) after the last device. Connect the power supervision relay normally open contact in
series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power
supervision relay. When you reset the system, the control panel removes power from these
terminals for approximately 15 seconds.

24 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Connecting the Power Cables Installation

Connect external field wires to the power supply terminals TB10 RESET(+) and (–) to provide up
to 1.25 A of current for powering four-wire smoke detectors. See Figure 3.6 above. TB2 (on CPS-
24), TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
24 VDC Non-resettable Power Circuit The power supply provides one 24 VDC filtered,
power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power
devices that require low-noise 24 VDC power (such as Notifier annunciator model ACM-24AT or
the transmitter module TM-4).
Connect external field wires to power supply terminals TB10 NONRESET (+) and (–) to provide
up to 1.25 A of non-resettable current for powering external devices such as annunciators. See
Figure 3.6 above. TB2 (on CPS-24), TB10 and all 4 NACs share a maximum of 3.0 A in standby
and 6.0 A in alarm.

CAUTION:
! During system reset, power remains at terminals TB10 NONRESET (+) and (–).

3.5.6 Accessories DC Power Output Connections


Terminal TB2 supplies one (1) non-resettable, power-limited 24 VDC circuit and one
nonresettable, power-limited 5 VDC circuit available to power external devices. Applications that
require a 5V connection to the Accessories Output, such as an UZC-256, must be within 10 feet
(3.658 meters) of the power supply. The distance from the power supply to the accessory requiring
power must not extend past the length of the supplied cable, P/N 75657, which is 10 feet long. Do
not splice or otherwise extend P/N 75657. Refer to section B.2, "Wire Requirements" of this
manual for all applications requiring a 24V connection. Connect wiring with all power sources off.
• 24 VDC (nominal) @ 0.5 A max
• 5 VDC (nominal) @ 0.15 A max

24V - Blue Wire


AMPS24_TB2access.wmf

COM - Black Wire

COM - Black Wire

5V - Red Wire

Figure 3.7 Connecting to the Accessories Output TB2 on CPS-24/E

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 25


Installation NAC Connections and Releasing Circuits

3.6 NAC Connections and Releasing Circuits


The control panel provides four NAC terminals as shown in Figure 3.9. Each can be configured as
Style Y (Class B) or Style Z (Class A) as shown in Figure 3.8. Each circuit can provide 1.5 A of
current, but the total current drawn from the main power supply cannot exceed 7.4 A in alarm
condition (refer to Table A.2). Additionally, TB2 (on CPS-24), TB10 and all 4 NACs share a
maximum of 3.0 A in standby and 6.0 A in alarm. NAC circuits are supervised and power-limited.
Use UL-listed 24 VDC notification appliances only (refer to the Device Compatibility Document).

A–
TB9 - NAC#1 A+
B–
UL-listed ELR-2.2K,
B+
1/2 W (supplied)
A–
TB8 - NAC#2 A+
B–
B+

nfs640-nacout.cdr
B+ B– A+ A– B+ B– A+ A– B+ B– A+ A–

A–
TB7 - NAC#3 A+
B–
Unused Circuits Style Y (Class B) Style Z (Class A) B+
Connection Connection

Figure 3.8 Notification Appliance Circuit (NAC) A–

CPU-320-NACS.wmf
Connections TB6 - NAC#4 A+
B–
B+

Figure 3.9 NAC Terminals and NAC LEDs

NOTE: Any NAC can be programmed as a releasing circuit, and the releasing circuit must
be supervised; For more information, refer to Section 4.7 “Releasing Applications” in this manual
and the NFS-320/E/C Programming Manual. Refer to the Device Compatibility Document for UL-
listed compatible releasing devices. Sample connections for NAC terminals are shown in
Figure 3.8. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part
of Step 4.

26 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Output Relay Connections Installation

3.7 Output Relay Connections


The panel provides a set of Form-C relays. These
are rated for 2.0 A at 30 VDC (resistive):
• Alarm - TB4
• Trouble - TB4
• Supervisory - TB5
• Security - TB5
These are power-limited only if connected to a
power-limited source.
Using VeriFire Tools, the Supervisory and

CPU-320-relays.wmf
Security contacts can also be configured as Alarm
contacts. Follow instructions in the VeriFire Tools
online help.

Figure 3.10 Form-C Relay


Connections

3.8 Backup-Alarm Switches


WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

Backup alarm switches are provided that enable NACs


and the alarm relay to activate during a backup alarm
condition. If the main board’s microcontroller fails and

CPU-320-bckalm.wmf
an alarm is reported by any detector or a monitor
module that has backup reporting enabled, the NAC
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure
regardless of the settings of switches SW1-SW4.
Figure 3.11 Backup Alarm
• SW1 - NAC#1 Switches
• SW2 - NAC#2
• SW3 - NAC#3
• SW4 - NAC#4
So, for example, if SW1 and SW4 were enabled at the time of an alarm during microcontroller
failure, NAC#1 and NAC#4 would activate. Follow sequence of steps in Section 3.2 “Installation
Checklist”, Table 3.1.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 27


Installation UL Power-limited Wiring Requirements

3.9 UL Power-limited Wiring Requirements


Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any nonpower-
limited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter and exit
the cabinet through different knockout and or conduits. To maintain separation, group non-power
limited modules together, i.e., group modules on the same side of the enclosure or in separate rows.
Figure 3.12 shows one configuration that meets these UL requirements. Equipment is configured
with at least a 0.25 inch (6.35 mm) separation between power-limited and nonpower-limited
wiring; AC and battery wiring is routed away from power-limited wiring.

Power-limited Circuits*

Power-
limited
circuits

Maintain vertical
separation where NPL
circuits appear to
“cross”

NPL
Nonpower-
limited

640-2-PWRLMTWIR-ISO2.wmf
circuits

To cabinet-mounted batteries
(nonpower-limited)

Figure 3.12 Typical Wiring for UL Power-limited Wiring Requirements


(Shown with relays as connected to power-limited modules)

NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares
to secure the wiring. Use a power-limited source for relay output on terminals 
TB5 and TB4.
See Figure 2.2, “NFS-320 and Power-Supply: Wiring Connections” on page 13 to identify power-
limited and non-powerlimited circuits.

NOTE: Drawing is not to scale; proportions and angles are exaggerated to show wire-placement
more clearly.

28 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Installing EIA-485 Devices Installation

3.9.1 Labeling Modules and Circuits


At the time of installation, each nonpower-limited circuit connected to ACM-8R, and LDM-R32
modules must be identified in the space provided on the cabinet door label when connected to a
non-power-limited source of power.
The label lists all compatible power-limited modules and circuits; also see Figure 2.2 on page 13.
The LDM-R32 is power-limited only when connected to power-limited sources. When connected
to a non-power-limited source, the power-limited marking must be removed.

3.10 Installing EIA-485 Devices


Figure 3.13 provides a closer view of the EIA-485 connections provided on TB11. Because specific
connections can vary by the type of device being connected, refer to the product installation manual
for details.

cpu2-640tb200.wmf
Figure 3.13 EIA-485 Connections

3.11 Installing Remote Printers and/or CRT


3.11.1 Custom Cable Fabrication
A custom cable needs to be fabricated to connect the PRN Printer or the CRT-2 Monitor to the
system. Length of the cable will vary with each installation, but should not exceed a maximum
length of 20 feet (6.1 m). Printer must be installed in the same room as the panel, and the cable be
installed in conduit. Construct cable as follows:
1. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25
Connector using the wiring specifications shown in the table below. (Custom cable kit 
P/N 90106 is provided.)
2. Tighten clamp on connector to secure cable.

DB-25 Connector 
TB12 on Control Panel
(Custom cable kit 90106)

Pin 3 TX

Pin 2 RX

Pin 7 REF

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 29


Installation Installing Remote Printers and/or CRT

3.11.2 Installing and Configuring the PRN Series Printer


When connected to the Control Panel via an EIA-232 interface, the PRN prints a copy of all status
changes within the control panel and time-stamps the printout with the time of day and date the
event occurred. It provides 80 columns of data on standard 9" by 11" tractor-feed paper.

NOTE: You can also use the EIA-232 printer interface with UL-listed information technology
equipment, such as personal computers, to monitor the control panel for supplementary
purposes.

This section contains information on connecting a printer to the control panel and for setting the
printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided, use a
separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You
may use your building emergency power supply, so long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control
panel as shown in Figure 3.14.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
Tighten securely.

Note: Outputs are power-limited


but are not supervised.
DB-25 connector on PRN
series printer (female
socket shown)
Terminate one end of
shield at backbox

CPU-320-prn.wmf

Control Panel

Figure 3.14 Remote Printer Connections

Setting Printer Options


Refer to the documentation supplied with the PRN series printer for instructions on using the
printer menu controls. Set the printer options (under the menu area) according to the settings listed
in Table 3.3.

30 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Installing Remote Printers and/or CRT Installation

Option Setting Option Setting


Font HS Draft CPI 10 CPI
LPI 6 LPI Skip 0.5
ESC Character ESC Emulate Epson FX-850
Bidirectional Copy ON I/O
CG-TAB Graphic Buffer 40K
Country E-US ASCII Serial
Auto CR OFF Baud 9600, 4800, or 2400
Color Option Not Installed Format 7 Bit, Even, 1 Stop
Protocol XON/XOFF
Formlen
Character Set Standard
Lines 6LPI=60
Standard Exec 10.5 Sl.Zero On
Auto LF Off
PAPER
BIN 1 12/72"
BIN 2 12/72"
SINGLE 12/72"
PUSH TRA 12/72"
PULL TRA 12/72"
PAP ROLL 12/72"

Table 3.3 PRN Setup Options

3.11.3 Installing and Configuring a CRT-2


A CRT-2 can only be used in a non-networked application when used with the NFS-320/E/C. For
further details on setting up the CRT-2, refer to the NFS-320/E/C Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control
panel as shown in Figure 3.15.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten
securely.
3. Set parameters as discussed in Table 3.15.
DB-25 connector
on CRT-2
(female socket shown)

Terminate one end of


shield at backbox
nfs640-crt2conn.cdr

Control
Panel

Figure 3.15 Connecting a CRT-2

Setting CRT-2 Parameters


The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of
parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown
in Table 3.4 below. You can then program parameters in each group.
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll
Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar
to view the options for each parameter. When finished programming all setup groups, press the
<Pause> key. To save all changes, press <Y>.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 31


Installation Installing Remote Printers and/or CRT

Table 3.4 shows the standard settings for using the CRT-2 with the NFS-320/E/C; for one instance
where these settings may change slightly see Section 3.11.4 “Connecting Multiple Printers, CRTs,
or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-320/E/C are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.

NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the NFS-320/E/C Operations Manual.

NOTE: The CRT cannot be connected at the same time as the network.

Function Key CRT-2 Parameters


F1: Quick  Emulation=CRT-2 EIA Baud Rate=9600 EIA Data Format=8/1/N
(“Read Status” key) Comm Mode=Full Duplex Aux Baud Rate=9600 Aux Data Format=8/1/N
Enhanced=On Language=U.S. Host/Printer=EIA/Aux
F2:Genrl Emulation=CRT-2 Enhanced=On Auto Wrap=Off
(“Alter Status” key) Auto Font Load=On Auto Page=Off Auto Scroll=On
Monitor Mode=Off Bell Volume=09 Warning Bell=On
Host/Printer=EIA/Aux
F3: Displ Page Length=24 Screen Length=26 Lines Screen Video=Normal
(“Prog” key) Display Cursor=On Cursor=Blink Line Auto Adjust Cursor=On
Columns=80 Width Change Clear=Off Speed=Normal
Scroll=Jump Refresh Rate=60 Hz Overscan Borders=Off
F4: Kybd Language=U.S. Char Set Mode=ASCII Key Mode=ASCII
(“Spl Funct” key) Keyclick=Off Key Repeat=Off Margin Bell=Off
Key Lock=Caps Keyboard Present=Yes
F5: Keys  Enter Key=<CR> Return Key=<CR> Backspace=<BS>/<DEL>
(“Prior” key) Alt Key=Meta Disconnect=Pause Desk Acc=Disabled
Pound Key=U.S.
F6: Ports EIA Baud Rate=9600 EIA Data Format=8/1/N EIA Parity Check=On
(“Next” key) Aux Baud Rate=9600 Aux Data Format=8/1/N Aux Parity Check=On
EIA Xmt=Xon-Xoff EIA Recv=Xon-Xoff(XPC) EIA Xmt Pace=Baud
Aux Xmt=Xon-Xoff Aux Recv=Xon-Xoff(XPC) Aux Xmt Pace=Baud
EIA Break=Off EIA Modem Control=Off EIA Disconnect=2 sec
Aux Break=Off Aux Modem Control=Off Aux Disconnect=2 sec
F7: Host Comm Mode=Full Duplex Local=Off Recv <CR>=<CR>
(“Auto Step” key) Recv <DEL>=Ignore Send ACK=On Send Line Term=<CR><LF>
Send Block Term=<CR> Null Suppress=On
F8: Print  Prnt Line Term=<CR><LF> Prnt Block Term=<CR> Secondary Recv=Off
(“Activ Signal” key)
F9: Emul Attribute=Page Bright Video=Off Page Edit=Off
WPRT Intensity=Dim WPRT Reverse=Off WPRT Underline=Off
WPRT Blink=Off Display NV Labels=Off Save Labels=On
Status Line=Off Fkey Speed=Normal
F10 Setup Group F10 does not affect communications with the control panel.
F11 Setup Group F11 does not affect communications with the control panel.
F12: Prog Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G 
(“Ack Step” key) F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q

Table 3.4 Standard CRT-2 Settings for Use with NFS-320/E/C

3.11.4 Connecting Multiple Printers, CRTs, or CRT/PRN


Combination
Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
• Set Host/Printer=EIA/AUX.
• Set EIA Data Format=8/1/N.
• If the AUX device is a printer, set the Printer and AUX Data Format=7/1/E.
• If the AUX device is a second CRT-2, set the AUX Data Format=8/1/N.

32 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Wiring a Signaling Line Circuit (SLC) Installation

Connect multiple devices as shown in Figure 3.16.


To Control Panel
TB12-PC/CRT REF
TB12-PC/CRT TX
7 3 2 7 3 2 TB12- PC/CRT RX

To AUX Port of CRT-2 To EIA-232 port of CRT-2


(female socket shown) (female socket shown)

prncrt-conn.cdr
7 3 2
To EIA-232 port of next 
CRT-2 or PRN (female socket shown)

Note: For wire requirements, see Table B.1 in Appendix B “Electrical Specifications”.

Figure 3.16 Connecting Multiple Devices on the EIA-232 Circuit

3.12 Wiring a Signaling Line Circuit (SLC)


 Overview

Communication between the control panel and intelligent and addressable initiating, monitor, and
control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet
the requirements of NFPA Style 4, Style 6, or Style 7 circuits.
This manual provides requirements and performance details specific to this control panel; for
installation information and general information, refer to the SLC Wiring Manual.

 Wiring

Maximum wiring distance of an SLC using 12 AWG (3.31 mm2) wire is 12,500 feet (3810 meters)
total twisted-pair for Style 4, Style 6 and Style 7 circuits.

 Capacity

The NFS-320/E/C provides one (1) SLC, with a total capacity of 318 intelligent/addressable
devices:
• 01-159 intelligent detectors
• 01-159 monitor and control modules
Units employing multiple detector operation shall include a minimum of two detectors in each
protected space and reduce the detector installation spacing to 0.7 times the linear spacing in
accordance with National Fire Alarm Code, NFPA. For spacing requirements refer to the detector’s
installation instructions.

NOTE: To meet the ten-second response time required by UL 864, 9th edition, when SLC loops
are configured to run in CLIP mode, all input modules must be mapped to address 19 and lower.
There are no limits to detectors or output modules.

 Installation

This control panel supports one SLC loop, which connects to TB13 on the control panel. For details
on designing, installing and configuring SLC loops, see the SLC Wiring Manual.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 33


Installation Connecting a PC for Off-Line Programming

SLC B SLC A

nfs640-slcloops.cdr, CPU-320-SLC-TB.wmf
SLC B (output loop)

SLC A (loop return)

SLC Loop Connections


on FACP’s main circuit board

B+ A+ B- A- TB13 on B+ A+ B- A-
NFS-320/E/C
Style 4 SLC Loops Style 6 SLC Loops
Note: T-Tapping is not allowed on a four-wire SLC.

Figure 3.17 SLC Loop Connections and Wiring

3.13 Connecting a PC for Off-Line Programming


A PC can be hooked up to the control panel to allow the VeriFire Tools programming utility to
upload and download the operating program. Refer to the insert in the VeriFire Tools CD and to the
program’s on-line help function for instructions. There are two options for connection:
Two options are available.
1. For PCs with USB Ports, connect the PC to USB B via a standard USB B cable.
2. For PCs without USB Ports, connect the PC’s serial port to the Control Panel’s
Network/Service Connection (J1, NUP).

NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72.

34 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Section 4: Applications

4.1 Overview

Chapter Covers the following topics

Section 4.3 “NFPA 72 Central or How to install UDACT/UDACT-2 with the control panel for use as a
Remote Station Fire Alarm System NFPA Central or Remote Station Fire Alarm System (Protected
(Protected Premises Unit)” Premises Unit)

Section 4.5 “NFPA 72 Proprietary How to set up a Protected Premises Unit to communicate with a listed
Fire Alarm Systems” compatible Protected Premises Receiving Unit.

Section 4.6 “Fire/Security How to use the control panel as a combination Fire/Security system,
Applications” including the following:
• Installing a Security Tamper Switch into the cabinet
• Circuit Wiring

Section 4.7 “Releasing How to install the following releasing applications:


Applications” • Releasing Device to the Control Panel (NAC integral circuits)
• Releasing Device to the FCM-1 Module
• NBG-12LRA Agent Release-Abort Station

Municipal Box (Auxiliary)


Municipal Box applications require a TM-4 Transmitter module. Refer to the TM-4 Transmitter
Module installation document for installation details.

4.2 Devices Requiring External Power Supervision


With version 12.0 and higher, certain type codes have external power supervision (FlashScan only)
built into the software. An external power-supervision relay is required (see Figure 4.1) unless one
of the following typecodes is selected for the device:

• Control • (Blank) • Nonreset Ctl • Gen Supervis


• Strobe • Release Ckt • Alarms Pend • Gen Trouble
• Horn • Rel Ckt Ulc • Gen Alarm • Gen Pend
• Trouble Pend

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 35


Applications NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)

Power Supervision
Relay (EOLR-1)
(Not required for
FlashScan type codes
that provide built-in SLC from FACP
power supervision.)

+

Non-resettable 24
VDC Power from –
a listed source +
Device to be
Supervised

3030-external-power-suptpH.wmf
*If the SLC device does
not match the one in this
N.C. Supervision  figure, refer to the SLC
FCM-1
Relay Contact  manual appendix, which
contains wiring conversion
Part of EOLR-1 
charts for type V and type
(Not required for H modules.
FlashScan type codes
that provide built-in
power supervision.)

Figure 4.1 Enabling External Power Supervision Using Relays

4.3 NFPA 72 Central or Remote Station Fire Alarm System


(Protected Premises Unit)
Figure 4.2 shows typical wiring diagram for a NFPA 72 Central Station Fire Alarm System
(Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using
the Universal Digital Alarm Communicator/Transmitter (UDACT or UDACT-2) and control panel.
This provides typical wiring only; connect and program the UDACT or UDACT-2 according to the
directions given in the UDACT Instruction Manual or UDACT-2 Instruction Manual.

NOTE: An NFPA 72 Central Station or Remote Station requires 24 hours of standby power and 5
minutes in alarm.

NOTE: This application can also be done with the TM-4 Transmitter; refer to the TM-4
Transmitter Module installation document for more details.

NOTE: For additional setup information for the UDACT-2, refer to the UDACT-2 Instruction
Manual.

36 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) Applications

Ferrite cores
FACP Cabinet P/N 29090

To supervised Solid earth


phone lines ground

24 VDC  EIA-485
Nonresettable power (ACS Mode)

Supervised and power-limited


EIA-485 and power wiring

CPU-320-udact.wmf
UDACT in ABS-8RB
(shown with cover removed)

Figure 4.2 Typical Wiring Diagram for a Central Station Fire Alarm System

NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 37


Applications Central Station Fire Alarm System Canadian Requirements

4.4 Central Station Fire Alarm System Canadian


Requirements
For Canadian applications requiring a second dial-out option, refer to the following illustration for
UDACT/UDACT-2 and TM-4 setup:
NOTES:

EIA-485
• Drawing is not to scale.
• The UDACT/UDACT-2 should
PRI SEC
LINE SEIZE
LED 3 LED 15
LED 4 LED 16
LINE FAIL
LED 5 LED 17
NO TONE TB2 TB1
LED 6 LED 18
KISS OFF ACS + ACS - REF REMOTE REMOTE REMOTE MUNICIPAL
LED 7 LED 19 BOX
STATION STATION STATION

be set for “Receive Only” for


COMM FAIL
TB3 SW1 ALARM TROUBLE SUPERVISORY

UDACT-2
+24VDC REF ELR

TM-4
+ 24V this configuration. For
+ 24V {
EIA-485 COMM LOSS
LED 1
REAL TIME
LED 2

+ 24V
_ 24V
LED 8

{ _ additional UDACT/UDACT-2
POWER
LED 9 TXACS RXACS

COMMON
LED 13

+
LED 14
LED2 LED1
LED 20

_
Relay EIA-485 +{ setup information, refer to the
Drive _
EIA-485 {
INPUT 5

TRANS TEST POWER


UDACT Installation Manual. or
INPUT 4

CLEAR REPORT RESET

LED4 SW6

NON-ISOLATED
UDACT-2 Instruction Manual.

ISOLATED
SW2 SW3 SW4

SW4
DISABLE
SW2
INPUT 3

ENABLE
INPUT 2

SW3

• This illustration is show with


LED3
TONE DETECT
LED21
TROUBLE SW5

1
INPUT 1

1
the NCM-W. For other NCM or
SW1 ON
OPTION ON
SELECT
SWITCH
1 2 3 4 OFF

HS-NCM setup, refer to the


NCM Installation or HS-NCM
ON
NO
Installation documents.
0 C
18/24
115
NC
• For additional setup information
on the TM-4, refer to the TM-4
230

MR-101/C
Instruction Manual.
FMM-1
EIA-485
_ + _
+ SLC
To Previous
Node on
Network

24V + EF B TERM B EF A TERM A


OFF

OFF
SW101

SW103
SW102

SW100

_
ON

ON

NFS-320
LED101 LED100
J3 J2

A HI B HI
LED6 LED7
NUP2

NUP1

RCDA RCDB
LED4 LED2

STATA STATB
LED3 LED5

RECON PULSE1
LED1 LED8
LCM A

RESET POWER

NCM-W
LCM B

LCMTERM
A A

OFF
ON
SW1

SW2

To Next Node
on Network
EF B TERM B EF A TERM A
OFF

OFF
SW101

SW103
SW102

SW100
ON

ON

NCA-2
LED101 LED100
J3 J2

A HI B HI
LED6 LED7
NUP2

NUP1

RCDA RCDB
LED4 LED2

STATA STATB
LED3 LED5

RECON PULSE1
LED1 LED8
LCM A

RESET POWER

NCM-W
LCM B

LCM TERM
A A

OFF
ON
SW1

SW2

Figure 4.3 Central Station Canadian Requirements for Second Dial-Out Connection

38 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


NFPA 72 Proprietary Fire Alarm Systems Applications

4.5 NFPA 72 Proprietary Fire Alarm Systems


When connected and configured as a protected premises unit with UDACT or UDACT-2, the NFS-
320/E will automatically transmit General Alarm, General Trouble, and General Supervisory
signals to a listed compatible Protected Premises Receiving Unit. See the UDACT Manual or
UDACT-2 Manual for compatible receiving units. A simplified drawing of connections between the
receiving unit and the NFS-320/E protected premises unit is shown in Figure 4.4.
Connect the receiving unit to the protected premises unit as shown in Section 4.3 “NFPA 72 Central
or Remote Station Fire Alarm System (Protected Premises Unit)”.
For information on installing and programming the Receiving unit, refer to the documentation for
that control panel.

Telephone line and backup

UDACT
or UDACT-2

Compatible Receiving Unit


(see UDACT Manual or UDACT-2 NFS-320/E
Manual)
NFS-320/E
Protected Premises Unit

Figure 4.4 Typical Proprietary Fire Alarm Systems Wiring Connections

4.6 Fire/Security Applications


NOTE: NFS-320/E/C is not approved for use in security applications in Canada.

4.6.1 General Operation


The control panel can be used as a combination Fire/Security system when installed and operated
according to the instructions in this section.
For security applications, program one or more monitor modules (listed for security applications)
with the SECURITY Type Code, and wire as shown in Figure 4.6. Activating this type of module
lights the SECURITY LED, and displays a security alarm condition on the control panel LCD display.
The panel sounder will sound until the Security alarm is acknowledged. You can also program
additional sounders or output devices to activate with the security alarm initiating device. The
SECURITY Type Code is designed to indicate an alarm as follows: (a) on an open or short circuit; or
(b) on a ±50% change in resistance value from the End-of-Line resistor value.
A tamper switch installed in the cabinet door will indicate a door tamper condition whenever the
door is open. If the control panel indicates a Security alarm, you can acknowledge, silence, and
reset the condition from the control panel.
When the system resets, a 30-second exit timer starts. During this time the tamper switch and all
Security alarms are ignored. There is no entrance delay timer.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 39


Applications Fire/Security Applications

For bypass of security zones, use the DISABLE routine (covered in the Status Change section of
the NFS-320/E/C Operations Manual) for Security type devices.

WARNING:
! Damage can result from incorrect wiring connections.

4.6.2 Installing a Security Tamper Switch


To wire the cabinet with a Security Tamper Switch kit model STS-200, refer to Figure 4.5:
1. Install the STS-200 Tamper Switch into the location shown in Figure 4.5. Push the switch
through the opening until it snaps into place.
2. Connect the STS-200 connector to J5 (Security Tamper) on the Control Panel. (As shown in
Figure 4.5, J5 is located on the circuit board, underneath the edge of KDM-R2.)

STS-200 mounting
location

Connect to
J5 “Security Tamper”

320_STS1.wmf

Figure 4.5 Installing the STS-200 Security Tamper Switch

4.6.3 Receiving Unit


For applications requiring transmission of security alarm information to a central receiving unit, the
control panel may be connected via the UDACT or UDACT-2 to a compatible receiving unit (see
the UDACT Manual or UDACT-2 Manual). For information on configuring the Receiving unit for
Combination Fire/Security applications, refer to the documentation for that control panel.

4.6.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.

40 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Fire/Security Applications Applications

2. Select the Type Code SECURITY.

NOTE: For detailed instruction on programming Type Codes, refer to the NFS-320/E/C
Programming Manual.

4.6.5 Wiring for Proprietary Security Alarm Applications


Table 4.6 shows typical wiring for proprietary security alarm applications with modules. Note the
following:
• The module is programmed with software SECURITY Type Code.
• For use with UL listed systems only; application not for ULC security usage.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
• All monitor modules used for security application must be installed in the NFS-320/E cabinet
with STS-1 Security Tamper Switch.

NFS-320/E Protected Premises Unit

SLC
UL-listed,  Channel
UL-listed 47K  A or B
End-of-Line Resistor  normally-open
(provided with module) security switch

CPU2-640-burgtpH.wmf
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
UL-listed, normally-closed contains wiring conversion
security switch FlashScan Monitor Module charts for type V and type
H modules.

Figure 4.6 Wiring Diagram for Proprietary Security Alarm Applications

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 41


Applications Releasing Applications

4.7 Releasing Applications


WARNING:
! When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12.
Do not enter the protected space unless physical lockout and other safety procedures are fully
completed. Do not use software disable functions in the panel as lockout.

WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

4.7.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
Standard Covers
NFPA 12 CO2 Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems

Table 4.1 NFPA Standards for Releasing Applications

4.7.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
Control Panel releasing outputs and FCM-1 modules. Program the FCM-1 module for the
appropriate type code according to the chart below:

Type Code: RELEASE CKT Type Code: REL CKT ULC


• For use in UL applications. • For use in UL or ULC applications.
• Do not use REL device at the solenoid. • Requires REL device at solenoid.
• Cannot use power-limited wiring. • Power-limited wiring.
• Supervised for open circuit only. • Supervised for open circuit and shorts.
• Supervised for power loss with power- • Supervised for power loss with power-
supervision relay. supervision relay.

For more information, refer to the NFS-320/E/C Programming Manual.

4.7.3 Wiring
References to wiring diagrams for releasing applications:
To connect Refer to
A releasing device to the control panel. Section 4.7.4 “Connecting a Releasing Device to the Control Panel”.
A releasing device to the FCM-1 Module. Section 4.7.5 “Connecting a Releasing Device to the FCM-1 Module”.
An NBG-12LRA Agent Release-Abort Station. Section 4.7.7 “Connecting an NBG-12LRA Agent Release-Abort Station”.

42 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Releasing Applications Applications

4.7.4 Connecting a Releasing Device to the Control Panel


Use TB6 (NAC#4), TB7 (NAC#3), TB8 (NAC#2), or TB9 (NAC#1) on the control panel for
NAC⁄Releasing Circuits. The releasing circuit must be supervised and use listed, compatible
releasing devices.

B+ NAC/Releasing output (source)


B– NAC/Releasing output (source)
A+ Class A (return for NAC only)
A– Class A (return for NAC only)
Compatible UL-listed
24 VDC releasing device

CPU-320-RELCONN1.wmf
Control
Panel

REL-2.2K (Use with Type Code


Rel Ckt ULC, or see Circuit
Note: See text below for circuit requirements. Requirement 4.)

Figure 4.7 Typical Style 4 Connection of a Releasing Device to Control Panel

WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

Circuit Requirements. When connecting a releasing device, note the following:


1. The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each circuit can
provide 1.5 A. Total current drawn from the power supply cannot exceed 7.4 A in an alarm
condition (refer to Table A.2, “System Draw Current Calculations,” on page 53). Use
compatible UL-listed 24 VDC appliances only. For more information on compatible
appliances, refer to the Device Compatibility Document.
2. Refer to the Releasing Applications appendix in the NFS-320/E/C Programming Manual for
configuration details (such as setting the Soak Timer).
3. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-2.2K) with control panel releasing circuits.
Connect the End-of-Line device as shown in Figure 4.7.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
4. For applications not requiring power-limited circuits – 
a) If the application does not require supervising the releasing device against shorts, in-line
supervisory devices (P/N REL-2.2K) are not required.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.)

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 43


Applications Releasing Applications

5. The releasing circuit must be programmed with a releasing type code listed in the NFS-
320/E/C Programming Manual.

NOTE: As per UL 864 9th Edition, a supervisory signal must be indicated at the panel whenever
a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the
switch. See 4.11.

IQActuatorsa.wmf
Figure 4.8 Releasing Circuits (Option 1)

IQActuatorsb.wmf
Figure 4.9 Releasing Circuits (Option 2)

IQActuatorsb.wmf

Figure 4.10 Releasing Circuits (Option 3)

44 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Releasing Applications Applications

GasDisconnect.wmf
Figure 4.11 Release Circuits (Mechanical Disconnect Switch)

4.7.5 Connecting a Releasing Device to the FCM-1 Module


The module can control 1 A of current. Make sure to keep total system current within the limits of
the power supply. You can power the module from the power supply of the Control Panel or any
UL/ULC listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For
more information, refer to the Device Compatibility Document.

Power Supervision SLC from FACP


Non-resettable Relay (EOLR-1) –
– 24 VDC Power +

+ –

Compatible UL-listed
24 VDC releasing device

Relconn-fcmtpH.wmf
*If the SLC device does
+ not match the one in this
Brown Red figure, refer to the SLC
manual appendix, which
REL-47K contains wiring conversion
(Use with Type Code charts for type V and type
N.C. Supervision
Rel Ckt ULC, FCM-1 H modules.
or see Circuit Relay Contact
Requirement 3.) Part of EOLR-1

Note: See text for circuit requirements.

Figure 4.12 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module

Circuit Requirements When connecting a releasing device to the FCM-1 module, note the
following:
1. Refer to the Releasing Applications appendix in the NFS-320/E/C Programming Manual for
configuration details (such as setting the Soak Timer).
2. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the FCM-1 module. Connect the in-
line supervisory device as shown in Figure 4.12.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits:
a) In-line supervisory devices (P/N REL-47K) are not required; however, the releasing device
circuit is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 45


Applications Releasing Applications

c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.

WARNING:
! The XP6-C is not listed for releasing applications and cannot be substituted for FCM-1.

4.7.6 Connecting a Releasing Device to the FCM-1-REL


Typical Connections Figure 4.13 shows typical connections for wiring a releasing device to the
FCM-1-REL. Refer to the Device Compatibility Document for compatible releasing devices.

Non-resettable
24 VDC power

(-)

SLC (-)
Module polarities are shown in alarm condition. (+)
All wiring shown is supervised and power-limited. SLC (+)

Compatible UL-listed

fcm-1-rel-y.wmf
24 VDC releasing device.
One (1) device maximum.

FCM-1-REL

Figure 4.13 NPFA Style Y (Class B) Wiring of the FCM-1-REL

Non-resettable When using the FCM-1-REL for


24 VDC power Style Y (Class B) applications,
remove jumper J1.

Module polarities are shown in alarm condition.


All wiring shown is supervised and power-limited. (-)
(+)
SLC (-)
SLC (+)

Compatible UL-listed
fcm-1-1rel-z.wmf

24 VDC releasing device.


One (1) device maximum.
FCM-1-REL

Figure 4.13 NPFA Style Z (Class A) Wiring of the FCM-1-REL

NOTE: With software version 14.0 or higher ALL new FlashScan Mode SLC releasing
applications require the FCM-1-REL control module. The V-type FCM-1 control module may be
used in SLC releasing applications with software version 14.0 or higher. H-type FCM-1 control
modules do not support FlashScan Mode releasing applications with software version 14.0 or
higher. Use H-type FCM-1 for CLIP mode releasing applications.

46 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Releasing Applications Applications

Critical Requirements. When connecting a releasing device to the FCM-1-REL module, note
the following:
1. See “Power Considerations” on page 52 for information on monitoring 24 VDC power.
2. Do not T-tap or branch a Style Y or Style Z circuit.
3. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1-
REL.
4. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of
connections.
5. All applications using the FCM-1-REL are power-limited:
a. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
b. Circuits are supervised against opens and shorts.
6. Refer to the NFS-320/E/C Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the
NFS-320/E/C Programming Manual.

4.7.7 Connecting an NBG-12LRA Agent Release-Abort Station


SLC loop to 
NBG-12LRA FMM-101 FACP
See Document 51369 Manual Abort Yellow Black
for installation details.

Violet Red

FMM-1
Manual Release Black

Red

Normal Non-resettable +24 VDC


NFS640-NBG12LRAtpH.wmf

ELR mode R-47K Release from main power supply


supervised and
FRM-1
power-limited

C.
N.C. N.O.
System
Common (–)

Power Supervision
Relay (EOLR-1)
FCM-1
24 VDC power
from FACP’s
main power supply
*If the SLC device does
24 VDC UL-listed
not match the one in this
releasing device figure, refer to the SLC
Brown Red manual appendix, which
N.C. Supervision contains wiring conver-
Relay Contact Polarity shown in
REL-47K an energized sion charts for type V and
(use with Type Code state. type H modules.
Rel Ckt ULC)

Figure 4.14 Typical Connections for an NBG-12LRA Agent Release-Abort Station

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 47


Applications Releasing Applications

NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.7.4 “Connecting a
Releasing Device to the Control Panel” on page 43. If using FCM-1, see Circuit Requirements for
Section 4.7.5 “Connecting a Releasing Device to the FCM-1 Module” on page 45.

48 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Section 5: Testing the System

5.1 Acceptance Test


When finished with the original installation and all modifications, conduct a complete operational
test on the entire installation to verify compliance with applicable NFPA standards. Testing should
be conducted by a factory-trained fire alarm technician in the presence of a representative of the
Authority Having Jurisdiction and the owner’s representative. Follow procedures outlined in NFPA
Standard 72’s section on Inspection, Testing and Maintenance.

5.2 Periodic Testing and Service


Periodic testing and servicing of the control panel, all initiating and notification devices, and any
other associated equipment is essential to ensure proper and reliable operation. Test and service the
control panel according to the schedules and procedures outlined in the following documents:
• NFPA Standard 72’s section on Inspection, Testing and Maintenance.
• Service manuals and instructions for the peripheral devices installed in the system. Correct any
trouble condition or malfunction immediately.

5.3 Operational Checks


Between formal periodic testing and servicing intervals, the following operation checks should be
performed monthly, or more frequently when required by the Authority Having Jurisdiction.
• Before proceeding: a) notify the fire department and the central alarm receiving station if
transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding
devices are disregarded during the test period; and c) when necessary, disable activation of
alarm notification appliances and speakers to prevent their sounding.
• Disconnect all releasing devices to prevent accidental activation in accordance with NFPA
2001 and NFPA 12A releasing agents.

WARNING:
! Do not rely on disable/enable software settings to lockout releasing devices.

• Check that the green POWER LED lights.


• Check that all status LEDs are off.
• Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work.
• Activate an Initiating Device Circuit using an alarm initiating device or an addressable
initiating device on the SLC and check that all programmed active notification appliances
function. Reset the alarm initiating device, the control panel, and any other associated
equipment. Select the paging function and confirm that the message can be heard in the
affected fire zones. Repeat the above step with each Initiating Device Circuit and each
addressable device.
• Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or
an addressable initiating device on the SLC, and check that programmed active notification
appliances sound, and alarm indicators illuminate. Measure the battery voltage with
notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC
and reapply AC Power

Continued on next page...

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 49


Testing the System Battery Checks and Maintenance

NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.

• Return all circuits to their pretest condition.


• Check that all status LEDs are off and the green POWER LED is on.
• Notify fire, central station and/or building personnel when you finish testing the system.

5.4 Battery Checks and Maintenance


Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water
or electrolyte. These batteries are charged and maintained in a fully charged state by the main
power supply’s charger during normal system operation. A discharged battery typically reaches the
voltage of 27.6 VDC within 48 hours; the charge rate depends on the battery size (2.0A for 18-
26AH; 5.0A-5.7A for 26AH-200AH).
Immediately replace a leaking or damaged battery. Batteries should be replaced in accordance with
the battery manufacturer’s recommendations.

WARNING:
! Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.

• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or
eyes with water for at least 15 minutes. Water and household baking soda provides a good
neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools,
bracelets, rings, and coins.

WARNING:
! Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.

50 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Appendix A: Power Supply Calculations
Calculations must be done to determine standby and alarm DC current loads. Ampere-hour
requirements must be calculated as well to determine battery size.
The CPS-24/E power supply provides filtered 24VDC power that may be used for operating
external devices. Use Table A.2 to determine if external loading is within the capabilities of the
power supply.

A.1 Calculating AC Branch Circuit Current


Use Table A.1 below to determine the total amount of current, in AC amperes, that a 120 VAC,
50/60 Hz service must be able to supply to the fire alarm system. Devices rated for 220-240 VAC
operation will draw approximately one-half the current listed in Table A.1.

Device Type No. of Devices Current (amps) Total Current


CPS-24 Power Supply [ 1 ] X 5.0 = 5.0
CPS-24/E Power Supply [ ] X 2.5 =
FCPS-24S6/S8 [ ] X 3.2 =
ACPS-2406 [ ] X 2.7* =
ACPS-610 [ ] X 5.0* =
ACPS-610/E [ ] X 2.5* =
APS-6R [ ] X 2.5 =
CHG-120 [ ] X 2.0 =
Sum column for AC Branch Current required=amps

Table A.1 120 VAC Fire Alarm Circuit


* Separate calculations are required for any devices powered by the ACPS-
610 or ACPS-2406. They have their own integral battery charger and
batteries can be connected directly to them. Refer to the ACPS-2406 or
ACPS-610 Installation Manuals for battery calculations.

AC Branch Circuit Installation


For guidelines on wiring the AC branch circuit current, see “Operating Power: AC Branch Circuit”
on page 59 in Appendix B.1 “Electrical Specifications”.

A.2 Calculating the System Current Draws


The control panel’s main power supply must be able to power all internal system devices (and
several types of external devices) continuously during non-fire alarm conditions. Use column 1 in
Table A.2 to calculate the Non-Fire Alarm Load on the power supply regulator when applying
primary power. The main power supply must also provide a finite amount of additional current
during a fire alarm condition. Use column 2 in Table A.2 to calculate the additional current needed
during fire alarms. The requirements for non-fire alarm and fire alarm current loads cannot exceed
the capabilities of the power supply as listed below:
• 3.9 A at 24 VDC during Standby; and
• 7.4 A at 24 VDC during Alarm.
The current draw from all NACs plus DC output from TB10 and TB2 is 3.0 A during standby, and
6.0 A in alarm.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 51


Power Supply Calculations Calculating the System Current Draws

How to Use the Calculating Tables


As used in this section, “Primary” refers to the control panel’s on-board power supply, its primary
source of AC power. “Secondary” refers to the control panel’s backup batteries (or any other 24
VDC power supply listed for Fire Protective Signaling and connected in place of the batteries). The
term “standby” refers to the output current required when no fire alarm is present. The term “alarm”
refers to the output current required when a fire alarm is present.
The Primary Power Source Non-Alarm Current and Alarm Current columns are DC current
calculations. These calculations confirm that the power supply can provide enough current to
support the system during Primary Non-Fire Alarm and Fire Alarm conditions.
Quantities List the number of devices powered by the FACP and its power supply. Devices
powered by the Accessories Output (TB10 and TB2) draw current directly from the panel. Devices
powered by the Panel Output draw current through the fire panel’s connection to the power supply.
Use these quantities to calculate total current draw of each set of devices in calculation columns 1,
2, and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of
calculation column 1 to get the current drawn from the power supply during a non-alarm condition,
with AC power applied. This current draw cannot exceed 3.9 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets
the system designer determine the current load that the power supply must support during a fire
alarm. The total current draw during a fire alarm cannot exceed 7.4 A without an auxiliary power
supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support
fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the
Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device
Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire
alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the
system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire
alarm condition during AC power loss.The non-fire alarm current is required to complete the
standby battery calculations. After summing all current draws, insert the total in Table A.3.

52 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Calculating the System Current Draws Power Supply Calculations

Calculation Column 1 Calculation Column 2 Calculation Column 3


Category Primary, Non-Fire Alarm Primary, Fire Alarm  Secondary, Non-Fire Alarm
Current (amps) Current (amps) Current (amps)
Qty X [current draw]= Total Qty X [current draw]= Total Qty X [current draw]= Total
NFS-320/E  1 x [0.250] = 1 x [0.250] = 1 x [0.250] =
# NACs in use (0, 1, 2, 3 or 4)* [ ] x [0.035] [ ] x [0.035] [ ] x [0.035]
CPS-24/E n/a n/a n/a n/a 1 x [0.040]
KDM-R2 (Backlight on) [ ] x [0.100]= [ ] x [0.100]= [ ] x [0.100]=
SLC loop†: 1 1 1
with jumper JP2 cut on CPU x [0.200]= x [0.200]= x [0.200]=
or without jumper JP2 cut on CPU x [0.400]= x [0.400]= x [0.400]=
NCA, NCA-2 Back-light ON [ ] x [0.400]= [ ] x [0.400]= [ ] x [0.400]=
NCA, NCA-2 Back-light OFF [ ] x [0.200]= [ ] x [0.200]= [ ] x [0.200]=
NCM-W/F [ ] x [0.110]= [ ] x [0.110]= [ ] x [0.110]=
HS-NCM-W/MF/SF/WMF/WSF/MFSF [ ] x [0.400]= [ ] x [0.400]= [ ] x [0.400]=
TM-4 [ ] x [0.110]= [ ] x [0.175]= [ ] x [0.110]=
DPI-232 (Refer to manual**) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
APS-6R [ ] x [0.025]=
ACPS-2406, ACPS-610 [ ] x [0.0013]=
ACM-24AT [ ] x [0.016]= [ ] x [0.070]= [ ] x [0.016]=
ACM-48A [ ] x [0.016]= [ ] x [0.070]= [ ] x [0.016]=
AEM-24AT [ ] x [0.002]= [ ] x [0.056]= [ ] x [0.002]=
AEM-48A [ ] x [0.002]= [ ] x [0.056]= [ ] x [0.002]=
Maximum number of LEDs illuminated on [ ] x [0.0054]= [ ] x [0.0054]=
these annunciators during non-fire
conditions:
AFM-16AT, AFM-32A [ ] x [0.040]= [ ] x [0.056]= [ ] x [0.040]=
ACM-16AT, ACM-32A [ ] x [0.040]= [ ] x [0.056]= [ ] x [0.040]=
AEM-16AT, AEM-32A [ ] x [0.002]= [ ] x [0.018]= [ ] x [0.002]=
AFM-16A [ ] x [0.025]= [ ] x [0.065]= [ ] x [0.025]=
ACM-8R (refer to manual**) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
LDM (refer to manual**) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
FDU-80 [ ] x [0.0643]= [ ] x [0.0643]= [ ] x [0.0643]=
LCD-80 [ ] x [0.100]= [ ] x [0.100]= [ ] x [0.050]=
FZM-1, MMX-2 Auxiliary power [ ] x [0.0115]= [ ] x [0.090]= [ ] x [0.0115]=
RPT-W, RPT-WF, RPT-F [ ] x [0.017]= [ ] x [0.017]= [ ] x [0.017]=
RPT-485W, RPT-485WF
UDACT Communicator [ ] x [0.040]= [ ] x [0.100]= [ ] x [0.040]=
UDACT-2 Communicator [ ] x [0.052]= [ ] x [0.087]= [ ] x [0.052]=
NFV-25/50 (see manual**) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Four-Wire Smoke Detectors‡ [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
[ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Power Supervision Relay  [ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
EOLR-1
Notification Appliance powered from Main [ ] x[ ]=
Power Supply** [ ] x[ ]=
DHX-501, FSD-751RPFSD-751RPL(Duct [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Detectors with internal relays) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Refer to installation document
CHG-120 Battery Charger [ ] x [0.060]=
Local Energy Municipal Box [ ] x[ ]=
Compatible Devices not listed above†† [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
[ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Sum each column for totals Primary, non-alarm: Primary, alarm: Secondary, non-alarm:

Table A.2 System Draw Current Calculations


* Maximum current draw for all NACs plus DC output from TB10 and TB2 is 3.0 A during standby.
† Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current draws. If jumper JP2 is cut, total device current cannot
exceed 200 mA; if jumper JP2 is not cut, total device current cannot exceed 400 mA.
‡ The total regulated load current supplied to four-wire smoke detector and power supervision relays cannot exceed 1.25 A.
** Enter the total notification appliance draw from the Main Power Supply, excluding the current from APS-6R supplies. Refer to Device Compatibility Document.
†† Refer to manual and/or Device Compatibility Document. See Table 1.1, “Reference Documentation,” on page 8 for specific documentation part numbers.

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 53


Power Supply Calculations Calculating the System Current Draws

A.2.1 Calculating the Maximum Secondary Power Fire Alarm


Current Draw
Use Table A.3 below to determine the maximum current requirements of secondary power source
during fire alarm conditions. The result obtained is the amount of current that the batteries must be
able to supply to the fire alarm system. Use the result in Table A.4 to determine the size of the
batteries needed for the fire alarm system.
Results taken from Table A.3 below assume that, while in a fire alarm condition, batteries must
feed the main power supply (and any additional supplies such as the APS2-6R) with the maximum
rated power each supply can provide.

Current
Device Quantity Total Current/Type
(in amps)
Alarm Current, from Table A.2, col 2 =
*
APS2-6R [ ] X 6 =
Sum Column for Secondary Fire Alarm Load =

Table A.3 Maximum Secondary Power Fire Alarm Current Draw


* Actual load current may be used in place of maximum rated supply
current. To calculate actual load current, sum the current draws for each
appliance connected to APS-6R supplies.

NOTE: The Secondary Fire Alarm Load cannot exceed the following: 
• 12 A with BAT-12260 batteries (12 V, 26 AH). 
• 20 A with BAT-12550 batteries (12 V, 55 AH).

54 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Calculating the Battery Requirements Power Supply Calculations

A.3 Calculating the Battery Requirements


A.3.1 Calculating the Battery Capacity
Use this table to determine the battery capacity needed for the system:
Current (amps) X Time (hours) = AH

Secondary Non-Fire Alarm Current  Required Secondary Non-Fire Alarm  


(from column 3 in Table A.2)  Standby Time (24 or 60 hours)  
(see Note 8)    
 X ________________ = _________AH
________________
APS-6R  Required Secondary Non-Fire Alarm  
Standby Load Current  Standby Time (24 or 60 hours)  
    
________________ X ________________ = _________AH

Secondary Fire Alarm Load   Required Fire Alarm Standby Time:  


(from Table A.3)  (for 5 minutes, enter 0.084; for 15  
(see Note 8)  minutes, enter 0.25)  
    
________________ X ________________ = _________AH

Sum Column for Total Secondary Amp Hours calculated = _________AH

Multiply by the derating factor x 1.2 (see Note 7) = _________AH

Battery Size – Total Secondary Amp Hours Required = _________AH


1. NFPA 72 Local, Proprietary, and Central Station systems requires 24 hours of standby power followed by
5 minutes in alarm.
2. NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes
in alarm.
3. Batteries installed in a system powered by an automatic starting engine generator need to provide at
least 4 hours of standby power.
4. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
5. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition.
Due to the sporadic nature of voice operation, however, NFPA 72 permits 15 minutes of operation at a
maximum connected load to equal 2 hours of normal use.
6. If the total exceeds 26 AH, the system requires a separate NFS-LBB, BB-100 or BB-200 battery
enclosure for two larger capacity batteries.
7. The following battery derating factors must be used for Canadian installations using NFS-320C charger:
• For a 26 AH battery, use derating factor of 1.5
• For a 55 AH battery, use derating factor of 1.8
• For a 100 AH battery, use derating factor of 2.5
• For a 200 AH battery, use derating factor of 2.5
8. For 26 AH batteries: maximum standby current cannot exceed 0.65A; maximum alarm current cannot
exceed 6.75A

Table A.4 Secondary Power Standby and Fire Alarm Load

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 55


Power Supply Calculations Calculating the Battery Requirements

A.3.2 Calculating the Battery Size


Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system.
The CPS-24/E can charge batteries from 18 to 200 AH. Select batteries that meet or exceed the
Total Amp-Hours calculated in Table A.4 and that are within the acceptable battery charger range.
Write the amp-hours requirements on the Protected Premises label.
The maximum battery size that can be mounted inside the NFS-320’s cabinet is 26AH.

Voltage Number Part


Battery Size
Rating Required Number* Backbox Part Number†
18 AH 12 volts two BAT-12180 NFS-320 enclosure, BB-25
26 AH 12 volts two BAT-12260 NFS-320 enclosure, BB-25
100 AH 12 volts four for 100 AH BAT-121000 BB-100
two for 200 AH BB-200
*Manufactured to our specifications.
†Red version available; add “R” to part number listed here

Table A.5 Selecting Battery and Battery Backbox

56 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Appendix B: Electrical Specifications

B.1 Electrical Specifications


AC Power

Component Values

Main Power Supply 120 VAC, 50/60 Hz, 5.0 A; or 


220-240 VAC, 50/60 Hz, 2.5 A

Wire size Maximum 12 AWG (3.31 mm2) with 600 VAC insulation

NOTE: If using an auxiliary power supply such as FCPS-24S6/S8 or APS-6R, refer to the
documentation for that equipment.

Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum bat-
tery capacity for the CPS-24/E main power supply is 200 AH. The NFS-320 enclosure provides
space for up to two 26 AH batteries. Use external battery boxes if the installation requires larger
capacity batteries; see Table A.5, “Selecting Battery and Battery Backbox,” on page 56.
When AC Power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts.
The power supply will be disconnected from the batteries. The power supply’s normal operation
will be restored when AC power returns.
The table below contains battery charger specifications.
Charger Description Specifications
CPS-24/E  An internal battery charger Normal Charge: 27.6 VDC +/- 0.24 VDC
Main Power Supply for 18 AH to 200 AH Charging Current: 2.0 A or 5.7 A (Software selectable)
CHG-120 An external battery charger Dual Rate: High Charge: 28.1 VDC
Battery Charger designed to charge lead-acid Normal Charge: 27.6 VDC
batteries between 26 AH and Charging Current: 4.5 A
120 AH
ACPS-2406 An internal battery charger Normal Charge: 27.6 VDC
Auxiliary for 7 AH to 26 AH Charging Current: 1.1 A max (0.750 A typical)
Charger/Power
Supply
ACPS-610 An internal battery charger Normal Charge: 27.6 VDC +/- 0.24 VDC
Addressable for 12 AH to 200 AH Charging Current: 2A, 5A, or OFF (Software Selectable)
Charger/Power
Supply

Signaling Line Circuit (SLC)


Item Value
Voltage 24 VDC nominal, 27.6 VDC maximum
Maximum length 12,500 ft. (3810 m) per channel (NFPA Style 4) or 10,000 ft. (3048 m) total
loop or circuit length (NFPA Style 6 and 7)
Note: Refer to Appendix B.2 “Wire Requirements” for limitations.
Maximum current 400 mA peak, (max short circuit; circuit will shut down until short is fixed)
Maximum resistance 50 ohms (supervised and power-limited)

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 57


Electrical Specifications Electrical Specifications

Notification Appliance Circuits and Releasing Circuits


Item Value
Max. wiring voltage drop 2 VDC 
(Retrofit note: SLCs with old CMX modules are restricted to 1.2 VDC.)
NAC Nominal operating 24 VDC regulated; 1.5 A max.
voltage
Special Applications for 20.16 - 26.42 VDC
Releasing Circuits
Current for all external 7.4 A in alarm (3.9 A continuous)
devices connected to the TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
control panel’s power supply
Optional ACPS-2406 Total 6 A in alarm (5 A continuous)
Optional ACPS-610 Total 6 A in alarm (1.5 A single output)
Optional APS-6R Total 6 A in alarm (4 A continuous)
Maximum signaling 1.5 A
current/circuit per NAC Note: Some devices have maximum draws less than this; refer to the device’s
documentation.
End-of-Line Resistors Control Panel NACs (TB6, TB7, TB8, TB9): 2.2K, 1/2 watt
(ELRs) XP6-C, FCM-1 Modules: 47K, 1/2 watt
NOTE: For a list of compatible Notification Appliance Circuits and Releasing Circuits see Notifier Device
Compatibility Document 15378.

Output Relays (common)


Output relays for Alarm and Trouble are common on TB4; Supervisory, and Security are program-
mable on TB5. See Figure 3.10, “Form-C Relay Connections” on page 27).
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB10 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
• Nominal voltage: 24 VDC special applications.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB10 NONRESET (+) and (–) supply one (1) power-limited circuit avail-
able to power external devices, such as notification appliances and annunciators.
• Nominal voltage: 24 VDC regulated, special applications, 1.5 A max.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10, TB2, and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible devices and notification appliances.

NOTE: The Control Panel provides a total of 7.4 A of power in alarm (3.9 A in standby), shared
by all internal circuitry and external provisions (24 V resettable and non-resettable). TB10 and all
4 NACs share a maximum of 3.0 A in standby and 6.0 in alarm. For power requirements, refer to
the power supply calculation tables in Appendix A.

58 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Wire Requirements Electrical Specifications

Operating Power: AC Branch Circuit


The control panel requires connection to a separate dedicated AC branch circuit. Follow these
guidelines when connecting the AC branch circuit:
• Label the branch circuit “Fire Alarm”. This must be a separate dedicated AC fire alarm circuit.
• Connect the branch circuit to the line side of the main power feed of the protected premises.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices except for
overcurrent protection, from the power source to the fire alarm control panel.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the National
Electrical Codes, as well as local codes.
• Use 12 AWG (3.31 mm2) wire with 600 VAC insulation for the AC branch circuit.
Connect the ground terminal (TB1-Earth) to a solid earth ground (a metallic, cold water pipe may
be suitable in some installations). This connection is vital in reducing the panel’s susceptibility to
transients generated by lightning and electrostatic discharge.
Operating Power: Secondary Power Source (Batteries)
The battery charger is current-limited and can recharge sealed lead-acid type batteries. The battery
charger shuts off when the control panel is in alarm.

B.2 Wire Requirements


Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to
ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that
circuit and the current traveling through it. Use Table B.1 below to determine the specific wiring
requirements for each circuit.
Compliance with the Federal Communications Commission (FCC) and Canadian Department of
Communication regulations on electrical energy radiation requires the following: Use twisted-pair
shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in
conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.

NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the SpectrAlert, SpectrAlert Advanced
or MA/SS-24 Series) instead of more electronically noisy notification appliances (such as
electromechanical bells or horns).

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 59


Electrical Specifications Wire Requirements

Circuit Distance
Circuit Type Wire Requirements Typical Wire Type
Function (feet/meters)
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 12,500 ft. (3,810 m) 12 AWG (3.31 mm2) 
(power limited) intelligent and (3.31 to 0.82 mm2). 50 ohms maximum per 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
addressable length of Style 6 and 7 loops. 50 ohms per 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
modules. branch maximum for Style 4 loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
Twisted-shielded pair 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 to
NOTE: 1.31 mm2)
• Shields must be isolated from ground. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
• Shields should be broken at each
device.
Untwisted, unshielded wire, in conduit or 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 to
outside of conduit. 1.31 mm2)
3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
Note: Maximum total capacitance of all
SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 mircofarads.
EIA-485 Connects to Twisted-shielded pair with a characteristic 6,000/1829 16 AWG (1.31 mm2)
(power limited) FDU-80, ACS impedance of 120 ohms. 18 AWG (0.82 (max)
modules, LCD- mm2) minimum.
80, or TM-4
Transmitter
EIA-232 Connects to Twisted-shielded pair in conduit.  20 feet (6.1 m)  16 AWG (1.31 mm2)
(power limited) Printers, CRT, 18 AWG (0.82 mm2) minimum. (without modem)
or PC.
IDC FMM-1, 12-18 AWG (3.31 to 0.82 mm2). 12 to 18 AWG (3.31 to
Initiating Device FMM-101, Maximum circuit resistance is 20 ohms. 0.82 mm2)
Circuit FDM-1, XP10-
M, XP6-MA
(power limited)
NAC FCM-1*, XP6-C 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 V drop, 12 to 18 AWG (3.31 to
Notification (power limited) At alarm current level, no more than a 1.2 or sized to provide 0.82 mm2)
Appliance V drop at the end of the circuit, or sized to the minimum rated
Circuit provide the minimum rated operating operating voltage of
voltage of the appliances used. the appliances used.
Releasing FCM-1-REL 12-18 AWG (3.31 to 0.82 mm2). To meet 5 ohms 12 to 18 AWG (3.31 to
Module 5 ohms maximum per circuit for class A or maximum current 0.82 mm2)
class B, or sized to provide the minimum resistance, or sized
rated operating voltage of the appliances to provide the
used. minimum rated
operating voltage of
the appliances used.
24 VDC Power To TM-4 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 volt drop 12 to 18 AWG (3.31 to
Runs Transmitter, Size wire so that no more than 1.2 V drop 0.82 mm2)
(power-limited) Annunciator and across wire run from supply source to end
FCM-1 modules of any branch.
CHG-120 External battery 12 AWG (3.31 mm2) in conduit 20/6.1 (max) 12 AWG (3.31 mm2)
charger
*FCM-1 can not be used for synchronized strobe/sounder applications.
Table B.1 Wire Requirements

NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 60950.

60 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Index
Numerics F
24 VDC, see Power (DC) FCM-1, also see Releasing Applications
Circuit Requirements 45
A FCM-1-REL, also see Releasing Applications 46
Connections 46
A77-716B, see Power Supervision Relay
Fire/Security Applications 39–41
(Replaced by EOLR-1)
Form-C relays 27, 58
AC, see Power 23, 24
Four-wire Smoke Detector
Acceptance Test 49
Specifications 58
ACM-8R
Labeling Requirements 29
Agent Release-Abort Station 47 I
Alarm Relays, see Form-C Relays 27 Installation
Checklist 19
B Preparation 18
Backup-Alarm Switches 27
Batteries, also see Power: DC 24 J
Battery Calculations 51, 52, 53, 54, 55, 56 Jumper Locations 13, 14
Battery Checks and Maintenance 50
Battery Specifications 57 K
Connections 24
KDM-R2 11
Removal/Installation 21
C
Cabinets L
Dimensions 15
LDM-R32
Mounting 20
non-power-limited circuits 29
Central Receiving Unit, also see UDACT Manual
lockout 49
40
Circuit Board, see CPU
Compatible Equipment 16, 17 M
Components 13, 14 Main Power Supply, see Power Supply
Control Panel Circuit Board, see CPU Maintenance 49
CPS-24/E, see Power Supply microcontroller failure 27
CPU Multiple Detector Operation 33
Drawing 11, 13, 14
Overview 11
CRTs 32
N
CRT/PRN Combination 32 NACs (Notification Appliance Circuits)
CRT-2 Configuration 31 Backup option 27
CRT-2 Function Keys and Parameters 32 NAC Connections 26
Installation 29–33 Releasing applications 26, 27, 42, 43
Specifications 58
NBG-12LRA 47
D NCM, Also see Networking
DC, see Power 23, 24 Installation 20
Networking 22
E NFPA Applications
NFPA 72 Central or Remote Station Fire
Electrical connections 22
Alarm System 36
Electrical Specifications 57
NFPA Applications (Overview) 35
EOLR-1, see Power Supervision Relay
NFS-320 (120V Operation), see Basic Equipment
External Power Supervision 35
Packages 11

NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011 61


O–W Index

NFS-320 (120V operation), see Basic Equipment Connections 43


Packages 13 FCM-1-REL Connections 46
NFS-320 (120Voperation), see Basic Equipment
Packages 14 S
NFS-320E (220-240V Operation) 11
Security Relays, see Form-C Relays 27
Nonpower-limited circuits
Security Tamper Switch 40, 41
UL wiring requirements 28, 29
Service 49
Notification Appliance Circuits, see NACs
SLC
Device Capacity 33
O Installation 33
Operating Power 59 Maximum Wiring Distance 33
Operational Checks 49 specifications 57
Option boards SLC See also SLC Wiring Manual 33
Installation steps 20 Specifications 57, 58
Output relays Standard equipment 11
Connections 27, 58 STS-1, also see Security Tamper Switch 41
Specifications 58 Supervisory and Security contacts
configuring as Alarm contacts 27
P Supervisory Relays, see Form-C Relays 27
Supplemental Documentation 8
Periodic Testing 49
Switches
Power
Backup-Alarm 27
AC Power Checklist 23
Switch Locations 14
AC Power Connections 23, 24
System
AC power connections 23
Description of features 10
AC specifications 57
Limitations 11
DC Power Connections 23, 24
Options 11
DC power connections 24
System Current Draws 51, 53, 54, 55, 56
Installation steps 22
System current draws 52
Non-resettable 25
Power specifications 22, 58
Resettable 24 T
Power Supervision Relay 47 Terminal Block Locations 13, 14
power supply 12 Testing 49
Power Supply Calculations 51, 53, 54, 55, 56 TM-4
Power supply calculations 52 see TM-4 Transmitter Module Installation
Power-limited Wiring Requirements 28 Document 21
Printers 32 Trouble Relays, see Form-C Relays 27
Installation 29–33
PRN series connections 30 U
PRN settings 30
UDACT also see Central Receiving Unit
PRN/CRT Combination 32
and the UDACT Manual 36
Remote PRN 30
UL nonpower-limited wiring requirements 28
Proprietary Security Alarm Applications
UL Requirements 28
Wiring 41
Protected Premises Unit 36
V
R VeriFire 34
Related Documentation 8
Relays, see Form-C Relays 27 W
Releasing Circuits Wiring
Connections 26 Proprietary Security Alarm Applications
Releasing Applications 42–48 41
Specifications 58 Wire Requirements 59
Releasing Device
Circuit Requirements 43

62 NFS-320/E/C Installation Manual — P/N 52745:H1 09/09/2011


Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replaces all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will prevent any loss
by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.