This document provides specifications for the Micrologic 6.0 A trip unit, including that it is an electronic trip unit used for distribution circuit breakers. It lists the trip unit's ratings up to 6300A and 50/60Hz frequency, and describes its adjustable protections settings for long time overload, short circuit, instantaneous, and ground fault protections. Environmental specifications are provided for operating temperatures from -25 to 70°C.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views

MicroLogic 33073

This document provides specifications for the Micrologic 6.0 A trip unit, including that it is an electronic trip unit used for distribution circuit breakers. It lists the trip unit's ratings up to 6300A and 50/60Hz frequency, and describes its adjustable protections settings for long time overload, short circuit, instantaneous, and ground fault protections. Environmental specifications are provided for operating temperatures from -25 to 70°C.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Product datasheet

Specifications

Micrologic 6.0 A trip unit - LSIG - for


NT, NW
33073

Training Objectives : Compliant

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Control unit

Trip unit name MicroLogic 6.0 A

Trip unit technology Electronic

Range compatibility MasterPact NT


MasterPact NW
Compact NS
Masterpact MT
PowerPact P-Frame
PowerPact R-Frame

Device application Distribution

Number of poles 3P
4P

Protected poles description 4t


3t
3t + N/2

Trip unit protection functions Selective + earth-fault protection

Protection type for overload protection (long time)


for short time short-circuit protection
for instantaneous short-circuit protection
for earth fault

Trip unit rating 630 A at 50 °C


800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
4000 A at 50 °C
5000 A at 50 °C
6300 A at 50 °C

Network type AC

Network frequency 50/60 Hz

Circuit breaker mounting mode Fixed


Drawout

Complementary
Long-time pick-up adjustment Adjustable 9 settings
type Ir (thermal protection)

[Ir] long-time protection pick-up 0.4...1 x In


adjustment range

Long-time protection delay Adjustable 9 settings


adjustment type tr

Apr 26, 2023 1


[Tr] long-time protection delay 0.7…16.6 s at 7.2 x Ir
adjustment range 0.7…24 s at 6 x Ir
12.5…600 s at 1.5 x Ir

Thermal memory 20 mn

Short-time protection pick-up Adjustable 9 settings


adjustment type Isd

[Isd] Short-time protection pick- 1.5...10 x Ir


up adjustment range

Short-time protection delay Adjustable


adjustment type tsd

[Tsd] Short-time protection 0…0.4 s I²t=off


delay adjustment range 0.1…0.4 s I²t=on

Instantaneous protection pick- Adjustable 9 settings


up adjustment type Ii

[Ii] instantaneous protection 2...15 x In


pick-up adjustment range Off

Ground-fault protection pick-up Adjustable 9 settings


adjustment type Ig

[Ig] ground-fault protection 0.2...1 x In for 400 A < In < 1250 A


pick-up adjustment range 0.3...1 x In for In <= 400 A
500...1200 A for In >= 1250 A

Ground-fault protection time Adjustable


delay adjustment type tg

[Tg] ground-fault protection 0…0.4 s I²t=off


time delay adjustment range 0.1…0.4 s I²t=on

Earth-leakage protection Without

Zone selective interlocking ZSI With

Local signalling 3 LEDs (red) for electrical fault


1 LED (red) for internal error

Display type Digital display

Type of measurement Ammeter

Communication of data Measurement readout


Protection and alarm settings

Environment
Ambient air temperature for -25…70 °C
operation

Ambient air temperature for -40…85 °C


storage

Offer Sustainability
REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information Yes

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

PVC free Yes

Contractual warranty
Warranty 18 months

2
Apr 26, 2023
Recommended replacement(s)

Apr 26, 2023 3