The document discusses control fundamentals for HVAC systems. It defines key terms like controlled variables, control loops, sensors, controllers and final control elements. It describes characteristics of open and closed loop control systems. It also outlines different control methods like pneumatic, analogue and digital controls. Finally, it discusses various control modes like two-position, step, proportional, proportional-integral and proportional-integral-derivative controls.
The document discusses control fundamentals for HVAC systems. It defines key terms like controlled variables, control loops, sensors, controllers and final control elements. It describes characteristics of open and closed loop control systems. It also outlines different control methods like pneumatic, analogue and digital controls. Finally, it discusses various control modes like two-position, step, proportional, proportional-integral and proportional-integral-derivative controls.
Control Fundamentals Introduction Definitions Control System Characteristics Control System Components Characteristics and Attributes of Control Methods
29-Aug-17 K H Ng, ES & BMS 2
Introduction Controls are essential to the proper system operation It should be considered in the early design process
29-Aug-17 K H Ng, ES & BMS 3
Introduction In a HVAC system, automatic controls regulate the system output in response to varying indoor and outdoor conditions To maintain general comfort conditions in offices; and To provide narrow temperature and humidity limits for product quality
29-Aug-17 K H Ng, ES & BMS 4
Introduction Automatic controls Optimize system operation, e.g. adjust temperature and pressures automatically; Limit energy usage
29-Aug-17 K H Ng, ES & BMS 5
HVAC Systems Characteristics All the processes in HVAC system require automatic controls These processes include heating, cooling, dehumidification, humidification, ventilation and filtration
29-Aug-17 K H Ng, ES & BMS 6
Control System Characteristics Automatic controls are used wherever a variable condition must be controlled In HVAC systems, the most commonly controlled conditions or variables are pressure, temperature, humidity and flow rate
29-Aug-17 K H Ng, ES & BMS 7
Control System Characteristics In control systems, the following terms need to be clarified: Controlled variables; Control loop; Control methods; and Control modes
29-Aug-17 K H Ng, ES & BMS 8
Control Variables An automatic control system control the variable by manipulating a second variable For example, air in a room moves through a hot water coil The thermostat measures the temperature (controlled variable) of the room air (controlled medium)
29-Aug-17 K H Ng, ES & BMS 9
Control Variables As the room cools, the thermostat operates a valve which regulates the flow (manipulated variable) of hot water (control agent) through the coil The coil supplies heat to warm the room air
29-Aug-17 K H Ng, ES & BMS 10
Control Loop A control loop consists of a sensing element (sensor傳感器) which receives an input, e.g. temperature sensor ; a controller控制器 that processes the input and produces an output signal; and a final control element that operates according to the output signal from the controller, e.g. valve
29-Aug-17 K H Ng, ES & BMS 11
Sensor Measures the value of the controlled valuable, e.g. temperature Sends the resulting signal to the controller
29-Aug-17 K H Ng, ES & BMS 12
Controller Receives the sensor signal Compare it with the desired value or set- point, e.g. temperature Generates a correction signal to direct the operation of the controlled device or the final control element, e.g. valve
29-Aug-17 K H Ng, ES & BMS 13
Final Control Element The final control element varies the control agent, e.g. hot water to device, to regulate the output (e.g. flow rate) of the control equipment (e.g. valve) The desired condition is achieved
29-Aug-17 K H Ng, ES & BMS 14
Control Loop Open or closed
29-Aug-17 K H Ng, ES & BMS 15
Open Loop The system assumes a fixed relationship between a controlled condition and an external condition, e.g. control of perimeter heating based on outdoor temperature sensor It does not take into account changing space conditions from other changing variables in the building 29-Aug-17 K H Ng, ES & BMS 16 Open Loop Does not provide close control May result deviation from the targeted values of the measurable variables Thus, it is not common in residential or commercial applications
29-Aug-17 K H Ng, ES & BMS 17
Close Loop Relies on measurement of controlled variable to vary the controller output Example: temperature of discharge air in a heating system Sensor measures the discharge air temperature Sends a feedback signal to the controller
29-Aug-17 K H Ng, ES & BMS 18
Close Loop Controller compares the feedback signal to the set-point Based on the difference (deviation), the controller issues a corrective signal to a valve The valve regulates the hot water flow to meet the demand
29-Aug-17 K H Ng, ES & BMS 19
Close Loop Changes in the controlled variable (temperature) reflect the demand Sensor continues to measure changes in discharge air temperature and feeds the new condition back to the controller for continuous comparison and correction Feedback reduce the magnitude of deviation and produce system stability
29-Aug-17 K H Ng, ES & BMS 20
Control Methods Automatic control system is classified by Type of energy transmission; and Type of control signal (A or D) used to perform its functions Most common forms of energy are electricity and compressed air Systems may comprise one or both forms of energy
29-Aug-17 K H Ng, ES & BMS 21
Control Methods Electromechanical, electronic or microprocessor control systems use electrical energy Pneumatic control systems use varying air pressure from the sensor to a controller which output a pneumatic signal to a final control element
29-Aug-17 K H Ng, ES & BMS 22
Control Methods Pneumatic, electromechanical and electronic systems performed limited, pre- determined control functions and sequences Microprocessor-based controllers use digital control for a wide variety of control sequences
29-Aug-17 K H Ng, ES & BMS 23
Control Methods Self-powered systems use power of measured variable to induce necessary corrective action Many complete control systems use a combination of external power and self- power
29-Aug-17 K H Ng, ES & BMS 24
Analogue Control Analogue devices are traditionally used in HVAC control In a pneumatic controller, the sensor sends a continuous pneumatic signal (pressure) to controller The signal (pressure) is proportional to the value of the variable being measured
29-Aug-17 K H Ng, ES & BMS 25
Analogue Control The controller compares the sent signal with the desired value of air pressure as determined by the set-point An output signal is sent based on the comparison
29-Aug-17 K H Ng, ES & BMS 26
Digital Control The digital controller receives electronic signals from sensors The signals are converted into digital pulses (values) and mathematical operations are performed on these pulses Controller re-converts the output value to a signal to operate an actuator
29-Aug-17 K H Ng, ES & BMS 27
Digital Control The digital controller periodically updates the process as a function of a set of measured control variables and a given set of control algorithms The controller works out the entire computation, including the control algorithm Sends a signal to an actuator
29-Aug-17 K H Ng, ES & BMS 28
Digital Control In most commercial control systems, an electronic-pneumatic transducer converts the electric output to a variable pressure output The variable pressure output is responsible for the pneumatic actuation of the final control element
29-Aug-17 K H Ng, ES & BMS 29
Control Modes Control systems use different control modes to accomplish their purposes.
29-Aug-17 K H Ng, ES & BMS 30
Control Modes These include Two-position Step; Floating; Proportional (P); Proportional-integral (PI); Proportional-integral-derivative (PID); and Adaptive
29-Aug-17 K H Ng, ES & BMS 31
Two-position Control The final control element occupies one of two possible positions Used in simple HVAC systems to start and stop fan coil units and refrigeration machines Two values of the controlled variable determine the position of the final control element
29-Aug-17 K H Ng, ES & BMS 32
Two-position Control Between these values is a zone called “differential gap” or “differential” When the controlled variable is within this differential, the controller cannot initiate an action of the final control element For close temperature control, the cycling must be accelerated or timed
29-Aug-17 K H Ng, ES & BMS 33
Basic Two-position Control Cyclical operation of the control equipment The controlled variable cycles back and forth between 2 values (‘on’ and ‘off’ points) Influence by the lag in the system The differential is the minimum possible swing of the controlled variable
29-Aug-17 K H Ng, ES & BMS 34
Basic Two-position Control Overshoot and undershoot conditions are caused by the lag of the system It is best used in systems where Minimal total system lag (including transfer, measuring and final control element lags) Close control is not required
29-Aug-17 K H Ng, ES & BMS 35
Timed Two-position Control Anticipates requirements and delivers measured quantities of heating or cooling on a percentage on-time basis Reduce control point fluctuations Timing is accomplished by a timer The controller responds to gradual changes in the average value of the controlled variable rather than to cyclical fluctuations
29-Aug-17 K H Ng, ES & BMS 36
Timed Two-position Control Overshoot and undershoot are reduced or eliminated Faster cycling rate of mechanical equipment Closer control of the variable than basic two-position control
29-Aug-17 K H Ng, ES & BMS 37
Timed Proportioning Control Provides more effective two-position control Available with sophisticated electromechanical thermostats and electronic and microprocessor-based controllers
29-Aug-17 K H Ng, ES & BMS 38
Step Control Step controllers operate switches or relays in sequence to enable or disable multiple outputs, or stages, of two-position devices Uses a proportional signal to attempt to obtain proportional output from equipment that is typically either on or off
29-Aug-17 K H Ng, ES & BMS 39
Step Control Stages may be arranged to operate with or without overlapping operating (on/off) differentials Typical two-position differentials still exist Total output is proportioned
29-Aug-17 K H Ng, ES & BMS 40
Floating Control A variation of two-position control Often called “three-position control” Available in most microprocessor-based control systems Requires a slow-moving actuator and a fast responding sensor Keeps the control point near the set-point at any load level
29-Aug-17 K H Ng, ES & BMS 41
Floating Control Can only be used on systems with minimal lag between the control medium and the control sensor Used primarily for discharge control systems where the sensor is immediately downstream from the coil, damper or device that it controls
29-Aug-17 K H Ng, ES & BMS 42
Floating Control The farther the control point moves beyond the dead-band, the faster the actuator moves to correct the deviation
29-Aug-17 K H Ng, ES & BMS 43
Proportional Control Proportions the output capacity of the equipment to match the heating or cooling load Unlike two-position control, the mechanical equipment is neither full on nor full off Achieves the desired heat replacement or displacement rate
29-Aug-17 K H Ng, ES & BMS 44
Proportional Control The final control element moves to a position proportional to the deviation of the value of the controlled variable from the set-point The position of the final control element is a linear function of the value of the controlled variable
29-Aug-17 K H Ng, ES & BMS 45
Proportional Control The final control element is seldom in the middle of its range The set-point is typically the middle of the throttling range There is usually an offset between the control point and the set-point
29-Aug-17 K H Ng, ES & BMS 46
Proportional Control The throttling range is the amount of change in the controlled variable required for the controller to move the controlled device through its full operating range For some controllers, throttling range is referred as “proportional band”
29-Aug-17 K H Ng, ES & BMS 47
Proportional Control Output of the controller is proportional to the deviation of the control point from set- point The control point is rarely at set-point and offset may be acceptable Compensation is the resetting of the set- point to compensate for varying load conditions
29-Aug-17 K H Ng, ES & BMS 48
Proportional Control Compensation reduces the effect of offset for more accurate control Compensation is also called “reset control” or “cascade control”
29-Aug-17 K H Ng, ES & BMS 49
Compensation Control A control technique in proportional control A secondary, or compensation, sensor resets the set-point of the primary sensor Compensation can either increase or decrease the set-point Positive or summer compensation Negative or winter compensation
29-Aug-17 K H Ng, ES & BMS 50
Compensation Control Most commonly used for temperature control But can also be used with humidity
29-Aug-17 K H Ng, ES & BMS 51
PI Control Reset of control point is automatic Also called “proportional-plus- reset” control Virtually eliminates offset and makes proportional band nearly invisible The controlled variable may deviate from the set-point and offset develops
29-Aug-17 K H Ng, ES & BMS 52
PI Control Proportional band gradually and automatically shifts The controlled variable is brought back to the set-point P control is limited to a single final control element position for eachvalue of the controlled valuable
29-Aug-17 K H Ng, ES & BMS 53
PI Control PI controls changes the final control element position to accommodate load changes The control point is kept at or very near the set-point
29-Aug-17 K H Ng, ES & BMS 54
PI Control Reset action of the integral component shifts the proportional band as necessary around the set-point as the load on the sysem changes Shifting of proportional band keeps the control point at set-point by making further corrections in the control signal
29-Aug-17 K H Ng, ES & BMS 55
PI Control Offset is eliminated Proportional band is usually set fairly wide to ensure system stability under all operating conditions Reset of control point is not instantaneous Whenever the load changes, the controlled variable changes
29-Aug-17 K H Ng, ES & BMS 56
PI Control The proportional control makes an immediate correction, which usually results in an offset The integral function of the controller makes control correction to bring the control point back to set-point Has a reset time adjustment that determines the rate at which the proportional band shifts 29-Aug-17 K H Ng, ES & BMS 57 PI Control Under steady state conditions, the control point and set-point are the same for any load conditions Integral windup, or an excessive overshoot condition, can occur in PI control
29-Aug-17 K H Ng, ES & BMS 58
PID Control Adds the derivative function to PI control Derivative function opposes any change and is proportional to the rate of change The more quickly the control point changes, the more corrective action PID system provides
29-Aug-17 K H Ng, ES & BMS 59
Adaptive Control Available in some microprocessor-based controllers Its algorithms enable a controller to adjust its response for optimum control under all load conditions A controller tuned to control accurately under one set of conditions cannot always respond well when conditions change
29-Aug-17 K H Ng, ES & BMS 60
Adaptive Control An adaptive control algorithm monitors the performance of a system and attempts to improve the performance One measurement of performance is the response time towards disturbance The shorter the time, the better the performance
29-Aug-17 K H Ng, ES & BMS 61
Adaptive Control The methods used to improve are determined by the type of adaptive algorithm Used in energy management programmes such as optimum start
29-Aug-17 K H Ng, ES & BMS 62
Application Guidelines Considerations for control requirements The degree of accuracy required and the amount of offset, if any, that is acceptable The type of load changes expected, including their size, rate, frequency and duration The system process characteristics, such as time constants, number of time lag elements and reaction rate
29-Aug-17 K H Ng, ES & BMS 63
Application Guidelines The simplest mode of control that meets application requirements is best to use, both for economy and for best results