Basics of 3phase Induction Motor Part 4
Basics of 3phase Induction Motor Part 4
Any service factor greater than one 1.0 must be indicated on motor nameplate; in
some case the running current at service factor loading is also indicated on the
nameplate as service factor amperes or SFA.
In the above description, it’s the “certain conditions” where problems may occur.
The service factor is not intended as a general increase in the motor
horsepower rating. In most cases, a 10 kW motor with 1.15 service factor
should not be treated as an 11.5 kW motor and it is not considered acceptable
for application to a pump or fan with this service factor to operate continuously
at 11 kW.
National Electrical Manufacturer’s Association (NEMA) standard for motors,
NEMA MG-1, establishes the operating conditions required for proper
performance and normal life expectancy of ac motors. Motors are designed to
deliver their rated kW under voltage variation of 10% of rated and frequency
variation of 5% of rated. The combined variation of voltage and frequency is
limited to 10%.When operated under these limits, with shaft load at or less than
rated, the motor current and winding temperature will remain within rated
values, and normal motor life is expected. NEMA MG-1 also defines the limits
for operation of an ac motor within the service factor range. First of these is that
rated voltage and frequency must be maintained.
Many facilities may experience occasional periods of low voltage during peak
load periods. Under this condition a motor operating within its service factor
rating may experience an unacceptable increase in current and temperature.
The motor is permitted under the standard to operate at a 10 degrees C higher
winding temperature rise under service factor load than under its normal rated
load. As a rule of thumb life expectancy is halved for each 10 degree increase
in operating temperature.
The Protection applied to a particular machine depends on its size and the
nature of load to which it is connected.
All motors will have a thermal with stand curves which indicates the thermal
withstand time at various over load currents. The Heating of the machine is
because of the thermal current which can be derived from the positive and
negative sequence components of the Motor current as follows.
Ith = √ (Id2 + 3Is2 )
Where:
Ith = Thermal Current which causes the heating
Id = Positive Sequence Component of the Input Current
Is = Negative sequence Component of the Input Current.
It can be seen that the negative sequence plays proportionately more than
positive sequence current in the heating of the machine. The relay should
computes the positive and negative sequence components and calculate the
thermal current. The ideal relay should calculate sequence component on the
basis of vector calculation.
Locked Rotor Protection
The ideal relay should provide protection against both starting and running
locked rotor condition. In most of the relays the setting is selectable from 100%
to 500% of the motor full load current. The trip time delay is selectable from 1
to 120 seconds. Additionally the relay can accept a speed switch contact from
the field to detect the starting locked rotor condition.
No load running
This element provides the protection against no load running of motors. The
pickup level is selectable from 0.15 to 1Im and the trip time delay is adjustable.
Earth fault Protection
This protection provides the isolation of motors incase of earth faults. This
element can be connected in residual connection or by using a CBCT. Ideal
motor protection relay is provided with an earth fault pick up setting of 2% to
100% and a delay setting of 0.05secs to 5secs. Third harmonic filter should be
checked to avoid any mal operation because of unbalanced currents.
It is to be noted that, in case of residual connection, if the earth fault element is
provided with instantaneous protection, the earth fault element may cause
unwanted operation during the starting of the motor. This is because of the
unequal saturation characteristics of the CTs provided in the system. To avoid
the above problem a stabilizing resistor need to be provided in the earth fault
circuit.
References:
1. NEMA MG-1.
2. Industrial Power Engineering and Application Hand Book by K C Agarwaal.
3. Industrial Power System Hand Book by Shoaib Khan.
4. Theory and Calculation of Alternating Current Phenomena by Charles
Proteus Steinmetz
5. Motor protection relay (MM30) manual from L&T
Related electrical guides & articles
Troubleshooting the most typical winding problems of three phase electric motors
The facts about switchyards, incoming and outgoing feeder connections, CTs and
VTs
Premium Membership
Get access to premium HV/MV/LV technical articles, electrical engineering
guides, research studies and much more! It helps you to shape up your
technical skills in your everyday life as an electrical engineer.
MORE INFORMATION
Asif Eqbal
Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV
outdoor substation and coal fired thermal power plants for more than seven
years. Motto of joining EEP as a contributor is to share my little engineering
experience and help the budding engineers in bridging the conspicuous gap
between academics and Industrial practice. “If you have knowledge, let others
light their candles with it, so that people who are genuinely interested in helping
one another develop new capacities for action; it is about creating timeless
learning processes".
12 Comments
1.
SURAJ
MAR 26, 2022
How calculate Preheating current in LT motor?
Reply
2.
Partha
JUL 23, 2018
Starting current for Induction withstand for howmany times?
Reply
3.
Jayesh Purani
SEP 02, 2017
How much hot withstand time of 400VOLT 60hz motor 3phase
If any standard is applicable for the same if yes please lete know.
Reply
4.
Amer Abd Eltawab
AUG 17, 2016
what is the permissable under voltage value and time for MV motors
6.6KV
Reply
5.
Saqib Ali
APR 10, 2016
Dear sir
What does thermal time constant mean, that we give in units of minutes
and how it helps us to thermal overload protection of motors
Reply
6.
Md Saad
OCT 22, 2015
i want to know ind. Motor protection ckt against over n under
voltage,single phasing,over temperature,over loading,over n under
freq,phasr reversal
Reply
7.
Alan Chuah
NOV 05, 2014
Thank you for your time on the motor write out. May I know if it will cause
motor to breakdown if there is frequent start stop for blower as below?
Can you pls share your opinion?
Reply
8.
Pankaj Kumar
SEP 17, 2014
very nice sir,great!!!!!
please tell me the average life of three phase induction motor(especially
6600V,900kw,duty class s1,BHEL make),if it have DOL starting,fan cooled
tube ventilated in normal operating conditions and fitted with HSC pump,
Reply
9.
Asif Eqbal
OCT 24, 2012
If the motor is running and got tripped than to restart I think important
factor to be considered is:
Temperature of the motor when starting should be considered. If the motor
is continuous duty and running for some time than a restart after tripping is
basically hot start. Cold start is an initial start, after not having run for a
relatively long period of time.
Now after running for some time motor may have reached maximum
allowable temperature so when you restart, the motor will pull more
current during starting than when they run, and if you start during that time
the temperature may exceed the limit. How much time motor requires for
getting cool down depends upon cooling time constant.
Usually more than one hot start is permissible. This can be understood by
example:
10.
Ritesheie
OCT 23, 2012
sir,
if a HT(11kv) motor get tripped,can we start it immediately or should have
to wait for some time?
Reply
ANAND
FEB 22, 2014
Please refer detail of thermal damage (hot) and check it with
starting time of the the machine at present loading. If motor is very
important in respect of its functionality in your system and you
don’t want take risk, then restart it on reduced loading if possible.
Thanks
Anurag
Reply
DELL
SEP 05, 2015
Does anyone know where I can find a blank “Cause of
Action-Motor Vehicle Form” to fill out?
Reply
Leave a Comment
Tell us what you're thinking. We care about your opinion! Please keep in
mind that comments are moderated and rel="nofollow" is in use. So, please
do not use a spammy keyword or a domain as your name, or it will be deleted.
Let's have a professional and meaningful conversation instead. Thanks for
dropping by!
YOUR REAL NAME *
EMAIL ADDRESS *
Prove That You Are Not R2-D2. Solve Some Math:Ninety Seven − 92 =
© 2022 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms and Conditions
Electric Motor / Energy and Power
Site Conditions
2. Area Classification:
3. Temperature Class:
4. Gas Group:
5. Type of Protection:
Basic Data
2. Neutral:
5. Continuous Rating:
6. Service Factor:
7. Synchronous Speed:
8. Insulation Class:
Differential CT's
If yes then:
Required CT Ratio:
Accuracy Class:
CT Arrangement:
26. Cable Type:
Motor:
Heater:
Winding RTD:
Bearing Sensor:
CT:
27. Heater Terminal Box Entry:
M
otor view
1. Standard:
3. Starting Current:
4. Efficiency (100/75/50%):
28. Lubrication: Oil/Grease
29. Oil/Grease
Frequency ratio
Wherever possible the natural frequency of the foundation soil-system shall be
higher than the highest disturbing frequency and the frequency ratios shall not
be normally less than 0.4.Where this is not possible, the natural frequency of
the foundation-soil system shall be kept lower than the lowest disturbing
frequency. The frequency ratios in such cases shall not be lower than 1.50.
While the above criteria shall be applied to all possible modes of vibration, it
may be permitted to operate machines closer to the resonance in certain modes
of vibration provided the resulting amplitudes do not exceed the permissible
limit.
Even though machine may be balanced, minor disturbing forces can occur due
to manufacturing tolerances and other causes, for sensitive installations, the
frequencies arising from these may have to be considered.
Permisible Amplitudes
Limitations of Vibration Amplitude to Avoid Damage to Machinery
This shall be specified by the manufacturer and shall in no cases be exceeded.
Where no specific limit has been stated by the manufacturer, it may be taken
that foundation satisfying the following amplitude criteria shall provide a
satisfactory base for machinery.
Limitations of Vibration Amplitude to Avoid Damage to Machinery
the damage in neighboring buildings due to resonance will be negligible if the
amplitude vibration of the foundation is less than 200 microns at frequencies
below 20 Hz, where the disturbing frequency exceed 20 Hz, a lower amplitude
may be necessary for certain installations.
Limitation of Vibration Amplitude to Avoid Discomfort of Persons
for low speed machines, it is unlikely that foundations which satisfy the previous
point will produce vibrations of sufficient amplitude to be disturbing to persons.
In special cases where there are particular reasons to avoid discomfort to
personnel
Limitations of Amplitude to Avoid Settlement
for most soil types, foundations for low speed machines designed to limiting
amplitude of 200 microns will not suffer undue settlement due to dynamic loads.
In case of some soils like loose sands and silts in conjunction with high water
table, there is a possibility of significant settlement to occur. In all such cases, it
shall be preferable to consolidate the soil underneath the foundation.
Anti-Vibration Mountings
Where it is found to be impracticable to design a foundation consisting of a
simple concrete block resting on the natural soils to give satisfactory dynamic
characteristics, it may be possible to reduce the transmitted vibrations to
acceptable levels by means of anti-vibration mounting. Depending upon the
nature of the machinery and the installation, the anti-vibration mounting may be
used:
a) Between machinery and foundation, and
b) Between a foundation block and a supporting system.
Free vibration analysis
Free vibration analysis shall be carried out to calculate the natural frequencies
and mode shapes of the foundation. The highest natural frequency calculated
should be at least 10 percent higher than the operating frequency of the
machine. Damping may be neglected for the purpose of free vibration analysis.
Frequency criteria
The following frequency criteria shall be checked:
The fundamental natural frequency shall be at least 20perccnt away from the
machine operating speed.
That is, fn < 0.8 fm or fn > 1.2 fm
Where
fn = fundamental natural frequency of the foundation, and
fm = operating speed of the machine.
However, it is preferable to maintain a frequency separation of 50 percent.
Conclusion
The foundation of any rotating electrical machine operating at 50 Hz should be
such that the natural frequency of vibration is either less than 40 Hz or greater
than 60 Hz.
References:
1. NEMA MG-1.
2. Industrial Power Engineering and Application Hand Book by K C Agarwaal.
3. Industrial Power System Hand Book by Shoaib Khan.
4. Theory and Calculation of Alternating Current Phenomena by Charles
Proteus Steinmetz
5. Motor protection relay (MM30) manual from L&T
Related electrical guides & articles
Guidelines for selecting the proper Variable Frequency Drive (VFD) for motor
applications
Troubleshooting the most typical winding problems of three phase electric motors
The essentials of power-generation systems you MUST know in the middle of the
night!
Premium Membership
Get access to premium HV/MV/LV technical articles, electrical engineering
guides, research studies and much more! It helps you to shape up your
technical skills in your everyday life as an electrical engineer.
MORE INFORMATION
Asif Eqbal
Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV
outdoor substation and coal fired thermal power plants for more than seven
years. Motto of joining EEP as a contributor is to share my little engineering
experience and help the budding engineers in bridging the conspicuous gap
between academics and Industrial practice. “If you have knowledge, let others
light their candles with it, so that people who are genuinely interested in helping
one another develop new capacities for action; it is about creating timeless
learning processes".
4 Comments
1.
Jhon
NOV 12, 2014
Hi, I like to know what means “Type IKK”…Thanks
Reply
2.
Edvard
AUG 04, 2012
Excellent Asif, congratulations!
Reply
Leave a Comment
Tell us what you're thinking. We care about your opinion! Please keep in
mind that comments are moderated and rel="nofollow" is in use. So, please
do not use a spammy keyword or a domain as your name, or it will be deleted.
Let's have a professional and meaningful conversation instead. Thanks for
dropping by!
YOUR REAL NAME *
EMAIL ADDRESS *
Prove That You Are Not R2-D2. Solve Some Math:Twenty Nine − = Twenty
Seven
© 2022 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms and Conditions
The voltages for three phases, 50 Hz motors are: 415 V, 3.3 kV, 6.6 kV and
11 kV.
As per Motor voltage ratings are defined by NEMA MG 1, Motors and
Generators (Ref. 1), and ANSI C50.41, Polyphase Induction Motors for Power
Generating Stations (Ref.2). According to ANSI C50.41, Section 6.3, preferred
voltage ratings are as follows:
460V; 2300V; 6600
575V; 4000V; 13,200V
Note that these ratings do not correspond exactly to the standard ANSI C84.1
(Ref. 16) nominal system voltages of 480, 600, 2400, 4160, 6900, and 13,800V.
Instead, each of these ratings is roughly 4 percent lower than the nominal
system voltage. The reason for this is to provide some allowance for voltage
drop.
For Coordination of Voltages and Output of three-phase induction motors it is
recommended that the minimum rated output should be greater than the limits
given below in terms of the rated voltage:
2 < Voltage < 3.3 for and up to 100kW
3.3 < Voltage < 6.6 for and up to 200kW
6.6 < Voltage < 11 for and up to 1000kW.
This is the voltage rating given by IS-325 Three phase induction motor
Specification but this cannot be followed in all cases as there have been cases
where motors of 150kW being supplied by 415V and 160kW to 4500kW being
supplied by 11kV.Now here comes the application of motor in picture & the load
torque requirement of the concerned motor. Torque developed in Induction
motor is directly proportional to the square of EMF induced in rotor. At standstill
the EMF induced in rotor is almost equal to applied voltage to stator and in
running condition the EMF induced in rotor is slip times the applied voltage to
stator.
Why anti condensation heating or space heaters are employed when a three
phase induction motor is not under operation?
Often the motors are kept in a store for some time or they are transported under
very damp conditions and in such cases, the insulation resistance generally
becomes low and it is dangerous for the motor to he connected up before the
condition has been rectified.
IEEE 43 places special emphasis on determining the insulation condition of
such machines before energizing and even before conducting a high-voltage
test. This can be determined by the insulation test as noted below.
Rm=kV+1
Where:
R = recommended minimum insulation resistance in MR (mega ohms) of the
entire machine windings, at 40°C or 1 MR per 1000 V plus 1 M Ω, and
kV = rated machine voltage in kV
At the site, when commissioning a new or an existing motor after a long
shutdown, it must have a minimum insulation level according to the above
equation. An 11 kV motor, for instance, must have a minimum insulation of 12
MΩ. In normal practice, it is observed that when first measured the resistance
reading may show more than the minimum value and may mislead the operator,
while the winding condition may not be adequate for a high voltage test or an
actual operation.
One must therefore ensure that the winding condition is suitable before the
machine is put into operation. For this purpose, the polarization index (PI),
which is determined from the insulation test data only as noted below, is a
useful pointer. It must be evaluated at site while conducting the insulation test
then compared with the manufacturer’s reference data for the machine to
assess the condition of insulation at site and its suitability for operation.
This is usually a site test, but to establish a reference record of the machine, it
is also carried out at the works on the completed machine and test records
furnished to the user.
Drying Out
If the measured insulation resistance of the motor is less than 1 MΩ/kV with a
minimum of 1 MΩ when the machine is cold, it should first be dried out by anti
condensation heater before full voltage is applied to the terminals of the motors.
References:
1. NEMA MG-1.
2. Industrial Power Engineering and Application Hand Book by K C Agarwaal.
3. Industrial Power System Hand Book by Shoaib Khan.
4. Theory and Calculation of Alternating Current Phenomena by Charles
Proteus Steinmetz
5. Motor protection relay (MM30) manual from L&T
Related electrical guides & articles
The art of predicting the fate of a power transformer by looking into a cup of oil
The ground is not just ground! At least not in hospitals, medical, and dental
practices
Key points on how to design a fault-tolerant and reliable facility distribution system
Learn how to prepare for transformer acceptance tests and final inspections
Premium Membership
Get access to premium HV/MV/LV technical articles, electrical engineering
guides, research studies and much more! It helps you to shape up your
technical skills in your everyday life as an electrical engineer.
MORE INFORMATION
Asif Eqbal
Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV
outdoor substation and coal fired thermal power plants for more than seven
years. Motto of joining EEP as a contributor is to share my little engineering
experience and help the budding engineers in bridging the conspicuous gap
between academics and Industrial practice. “If you have knowledge, let others
light their candles with it, so that people who are genuinely interested in helping
one another develop new capacities for action; it is about creating timeless
learning processes".
8 Comments
1.
Oluwaseun Temitope
JUL 15, 2022
Thanks. The write-up is helpful
Reply
2.
Shoukat Ali
DEC 25, 2019
We required different induction motors, please advise us, how we will
send you requirements.
Reply
3.
Tahir Hussain
NOV 23, 2019
Is there any guideline for voltage level utilization with respect to motor
rated power while employing VFDs?
Reply
4.
Edison
JUL 02, 2019
What are the HV motor starting methods?
Reply
5.
Askar
MAR 05, 2017
hi everbody . would i know about requirment space heater for LV motors/
Where it is specified as IEC or etd?
thak all!!
Reply
6.
NISCHAL JAIN
JUN 01, 2015
Sir,
I have a 1 HP , 1100 RPM , 60 HZ motor.
Is it possible for me to increase the HP of the motor to say 2HP but
maintaining the SPEED of 1100 RPM at 50 Hz.
Pls reply.
Reply
7.
Adlin Shajan K
SEP 21, 2014
11kv motor will using how much insulation . What are the various types of
transformers.
Reply
8.
Krunal Dandhare
APR 02, 2014
Is it possible that 3 phase induction motor will start with 2 phase supply?
reason?
Reply
Leave a Comment
Tell us what you're thinking. We care about your opinion! Please keep in
mind that comments are moderated and rel="nofollow" is in use. So, please
do not use a spammy keyword or a domain as your name, or it will be deleted.
Let's have a professional and meaningful conversation instead. Thanks for
dropping by!
YOUR REAL NAME *
EMAIL ADDRESS *
×Get Notifications
This article will deal with those concepts of 3 phase induction motor which are
essential prerequisite for proper selection, procurement, installation and
maintenance of the same.
Basics of 3-phase Induction Motor (part 1)
Before any actual discussion on motor is started It will better to have a
comparison of starting behavior of induction motor and transformer because as
per the equivalent circuit representation a 3 phase induction motor is
generalized transformer.
It is assumed that readers are already familiar with the elementary concept of
principle of operation and construction of three phase induction motor.
What is the fundamental difference in working principle of induction
motor and transformer? That is even though the equivalent circuit of motor
and transformer is same rotor of motor rotates where as secondary of
transformer do not.
Induction motor is a generalized transformer. Difference is that transformer is an
alternating flux machine while induction motor is rotating flux machine. Rotating
flux is only possible when 3 phase voltage (or poly phase) which is 120 degree
apart in time is applied to a three phase winding (or poly phase winding) 120
degree apart in space then a three phase rotating magnetic flux is produced
whose magnitude is constant but direction keeps changing. In transformer the
flux produced is time alternating and not rotating.
There is no air gap between primary and secondary of transformer where as
there is a distinct air gap between stator and rotor of motor which gives
mechanical movability to motor. Because of higher reluctance ( or low
permeability) of air gap the magnetizing current required in motor is 25-40% of
rated current of motor where as in transformer it is only 2 -5 % of rated primary
current.
1. NEMA MG-1.
2. Industrial Power Engineering and Application Hand Book by K C Agarwaal.
3. Industrial Power System Hand Book by Shoaib Khan.
4. Theory and Calculation of Alternating Current Phenomena by Charles
Proteus Steinmetz
5. Motor protection relay (MM30) manual from L&T
Related electrical guides & articles
Design Knowhow: Low voltage substation layouts, earthing, fire protection and
tests
How to design the power supply for data centres and airports while megawatts of
loads rise fast
How to select grounding point(s) and how many generator or transformer neutrals
to use
Premium Membership
Get access to premium HV/MV/LV technical articles, electrical engineering
guides, research studies and much more! It helps you to shape up your
technical skills in your everyday life as an electrical engineer.
MORE INFORMATION
Asif Eqbal
Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV
outdoor substation and coal fired thermal power plants for more than seven
years. Motto of joining EEP as a contributor is to share my little engineering
experience and help the budding engineers in bridging the conspicuous gap
between academics and Industrial practice. “If you have knowledge, let others
light their candles with it, so that people who are genuinely interested in helping
one another develop new capacities for action; it is about creating timeless
learning processes".
37 Comments
1.
Stanley Ogidi
MAY 04, 2019
Have an idea to invent an electric power generating machine but I need
you assistance, thanks ,please you can whatsap me on this line for
discussion +2348034681128
Reply
2.
Rajaram Maity
JAN 18, 2018
sir,
please explin how much i set the derived earth fault both idmt and
instantaneous .600 kw 3.3kv induction motor .there are a relay siemens
argus 7sr17
Reply
3.
Yadav Rishikesh
NOV 10, 2017
What happens if we use silicon steel core in induction motor for path of
flux instead of air gap?
Reply
4.
Mehdi
DEC 31, 2016
Hello;
I want to know how we can defined the turn ration between the primary
and secondary in induction motors.
thanks
Reply
IBRAHIM MURTAZA
JAN 14, 2017
please guide me that how much an LT 3 phase induction motor
will consume current in star configuration at start
Reply
Yadav Rishikesh Balasaheb
NOV 10, 2017
What happens if we use silicon steel core in induction motor for
path of flux instead of air gap?
Reply
5.
Pankaj
AUG 15, 2016
hey!!
Can anyone tell me, how to find the winding data of fresh stator. if slots &
HP is known
Reply
6.
John Stewart
NOV 07, 2015
Hi Asif,
There’s a slight misunderstanding in your explanation on the reason for
Star and Delta connections.
In fact the reason we use Star connection on higher voltage machines is
to drop the Volts per pole.
The motor performance doesn’t need to change at all because the turns
per coil and conductor sizes are changed to suit the changed phase volts.
Star connection reduces the volts per phase, so in design, the turns are
reduced proportionately and the conductor size increased proportionately.
That means the flux density in the iron remains the same, so shaft torque
and starting curve is the same.
There is no real commercial advantage either. There is the same total
amount of copper in the slot.
Reply
7.
Michael
OCT 02, 2015
Could you please explain/ draw how to connect a three pole two way with
off rotary switch to a three phase motor in order to obtain two speeds with
off between.
Reply
8.
Virender Singh
SEP 11, 2015
Hllo
sir
give me ac motor winding data calculator and ac motor winding data list
0.5 hp to350hp
Reply
9.
Saroj
SEP 05, 2015
Can you please explain Steinmetz equivalent circuit of induction motor,
mainly the relationship between frequency of supply and equivalent
resistance across the rotor side??
Reply
« Older Comments
Leave a Comment
Tell us what you're thinking. We care about your opinion! Please keep in
mind that comments are moderated and rel="nofollow" is in use. So, please
do not use a spammy keyword or a domain as your name, or it will be deleted.
Let's have a professional and meaningful conversation instead. Thanks for
dropping by!
YOUR REAL NAME *
EMAIL ADDRESS *
Prove That You Are Not R2-D2. Solve Some Math:96 − = Eighty Seven
© 2022 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms and Conditions
×Get Notifications