1.access Control
1.access Control
The AMC2 (Access Modular Controller) is used as an independent authorization on access points, takes
access controller in the access control systems: access decisions, controls closing/opening elements
• BISACE (Access Engine) from version 2.0 onward and registers movement events.
• AMS (Access Management System)
• APE (Access Professional Edition). System overview
Components and features • Integrated Microcontroller Dimension (H x W x D) (in) 9.13 in x 3.54 in x 2.48 in
u Overvoltage protection
The PSU-60 is a power supply unit with an integrated The following applies to the battery mode:
battery charging device. • If the input voltage is less than 85 VAC, the power
supply switches to “Battery operation” mode and the
Functions yellow LED lights up next to BOP.
• The OFF button is only activated in “Battery
operation” mode. Press this button to switch off the
PSU-60.
• Restart is only possible when the alternating current
supply is restored.
• This power supply unit can be switched to 12 V or 24
V mode. To do this, the switch must be configured as
shown below, when there is no voltage input on the
power supply.
Notice
The power supply must only be installed by
qualified personnel.
Installation/configuration notes
Technical specifications The power supply switches to normal operation as soon as the AC
incoming voltage has normalized.
Power Supply Output is Class 2 Power Limited.
Temperature equalization is performed by an external NTC resistor.
Output values
Reverse polarity protection.
Output voltage: 12V mode 10-15V
24V mode 20-30V Environment variables
Output current: 12V mode max 5A Working temperature: -20°C to 60°C (-4°F to 140°F)
24V mode max. 2.5A
Working temperature (UL 0°C to 49°C (32°F to 120°F)
Output power: 60 W (constant) installations only):
Over voltage 12V mode 16.5V Storage temperature: -40°C to 85°C (-40°F to 185°F)
protection at: 24V mode 33V
Relative humidity: 5% to 95%
Input values
Ordering information
Input voltage: AC 100-240V~, 50-60Hz
APS-PSU-60 Power supply unit
Input current (AC): Max. 2A, to the specified max. load at A power supply unit with an integrated battery
85 VAC charging device, that supports 12 V/7 Ah, 12 V/14 Ah
Inrush current for 1ms: AC 100-240V 30A and 24 V/7 Ah batteries, with selectable 12 VDC or 24
VDC voltage output.
Input protection in case of a failure, the primary voltage is cut off from Order number APS-PSU-60
the power supply by a fuse.
Represented by:
System overview 10 mm
0,394 in
outs. 352,5 mm
13,878 in
Installation/configuration notes
Parts included
The external dimensions and the securing screw holes
are shown in this diagram: Quantity Component
1 Cable set
Input voltage 100-240 VAC API-AMC2-16IOE Extention board with 16-input 16-
output
Input current 2A 16 input/output extension board, up to three per AMC,
can be combined with the AMC2 16I-EXT and the
Ordering information AMC2 8I-8O-EXT
Order number API-AMC2-16IOE
AEC-AMC2-UL01 AMC enclosure with 1 DIN rail
Compliant with UL294 system certification for AMC2. API-AMC2-16IE Extention board with 16-input
Order number AEC-AMC2-UL01 16 input extension board, up to three per AMC, can be
Accessories combined with the AMC2 16I-16O-EXT and the AMC2
APS-PSU-60 Power supply unit 8I-8O-EXT
A power supply unit with an integrated battery Order number API-AMC2-16IE
charging device, that supports 12 V/7 Ah, 12 V/14 Ah D126 Battery, 12V 7Ah
and 24 V/7 Ah batteries, with selectable 12 VDC or 24 A rechargeable sealed lead‑acid power supply used as
VDC voltage output. a secondary power supply or in auxiliary or ancillary
Order number APS-PSU-60 functions.
APC-AMC2-4WCF Door controller Wiegand with CF Order number D126
card
Four Wiegand interfaces for up to 4 card readers,
network connection to the host system and Compact
Flash memory (2 GB). Host data transfer encrypted.
Order number APC-AMC2-4WCF
Represented by:
Installation/Configuration Notes
Installation Technical Specifications
Housing
External dimensions (W x H x D) 79.6 x 43 x 16.8 mm
Material Polycarbonate (UL 94)
Color Black
Weight 75 g
Connections
Display Multicolored LED
Interfaces Wiegand 26-bit
Environmental conditions
Operating temperature -30° to 65° C
Humidity 10 to 95% no condensation water
Environment class IP 65
• Four Wiegand interfaces for connecting readers.
• Up to four readers can be installed per entrance. Electrical parameters
Please follow the general mounting instructions for the Power supply 5 to 16 VDC
proximity reader regarding the distance between readers Reading process HID - PROX
and metallic surfaces.
www.boschsecurity.com
2 | ARD-ProxPointPlus - Proximity Reader
Housing
Operating/modulation frequency 125 kHz
Reading distance 4 cm to 6 cm with ISO card
Ordering Information
ARD-ProxPointPlus - Proximity Reader ARD-PROX-PPL
Small reader with beeper and multicolored
LED display.
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1923269643 | Cur: en-US, V10, 14 Jul 2010
Engineered Solutions | Access Management System V3.0
Access Importer/Exporter (3) BVMS Client workstation for access and video management
This tool facilitates data import and export from
(4) Optional MAC servers (one MAC license is always included, on
external systems for 1-time data migration, such as
the AMS server)
from Access PE systems, or regular data transfer from
Active Directory via the LDAP protocol. (5) AMCs
Topology diagrams (6) Entrances with cameras
The following diagrams illustrate AMS configurations
without and with BVMS. Functions
The following tables specify the dimensions of an AMS Intrusion integration Maximum 25 panels B and G Series
access control system from two aspects:
License bundle PRO
• As per the respective license bundle: LITE, PLUS or
PRO. PRO Licensed Maximum
• As a maximum, if the necessary licenses are number number
purchased.
Number of doors (with 1 or 2 32 10,000
License bundle LITE readers):
Number of guard tours 200 Intrusion integration Maximum 25 panels B and G Series
5 | Access Management System V3.0
AMS-XCLI-1V30 License for 1 operator client AMS-FUPG-TOPR30 License from Plus to Pro
License for 1 operator client Upgrade from Plus to Pro
Order number AMS-XCLI-1V30 Order number AMS-FUPG-TOPR30