0% found this document useful (0 votes)
76 views

DSE335 PC Software Manual

Uploaded by

Walter Sánchez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views

DSE335 PC Software Manual

Uploaded by

Walter Sánchez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 82

DEEP SEA ELECTRONICS

DSE335 Configuration Suite PC Software


Manual
(Applicable to module version 4.2 and upwards)

Document Number: 057-237


Author: Fady Atallah

057-237 ISSUE: 3
DSE335 Configuration Suite PC Software Manual

Deep Sea Electronics Ltd.


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
England

Sales Tel: +44 (0) 1723 890099

E-mail: [email protected]
Website: www.deepseaelectronics.com

DSE335 Configuration Suite PC Software Manual

© Deep Sea Electronics Ltd.


All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
must be addressed to Deep Sea Electronics Ltd. at the address above.

The DSE logo and the names DSEGenset®, DSEAts®, DSEControl® and DSEPower® are UK
registered trademarks of Deep Sea Electronics Ltd.

Any reference to trademarked product names used within this publication is owned by their respective
companies.

Deep Sea Electronics Ltd. reserves the right to change the contents of this document without prior
notice.

Amendments List

Amd. No. Comments


1 Initial release
2 Added updates to Breaker Scheme C, Closed Transition operation.
3 Updated for v4.7 features. Manually updated to latest standard

Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper case letter I with the numeral 1. The numeral
1 has a top serif to avoid this confusion.

057-237 ISSUE: 3 Page 2 of 82


DSE335 Configuration Suite PC Software Manual

TABLE OF CONTENTS

1 INTRODUCTION .............................................................................................. 5
1.1 CLARIFICATION OF NOTATION ........................................................................................5
1.2 GLOSSARY OF TERMS ......................................................................................................6
1.3 BIBLIOGRAPHY ..................................................................................................................7
1.3.1 INSTALLATION INSTRUCTIONS .................................................................................7
1.3.2 MANUALS .....................................................................................................................7
1.3.3 TRAINING GUIDES ......................................................................................................8
1.3.4 THIRD PARTY DOCUMENTS ......................................................................................8
1.4 INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE ............8
2 EDITING THE CONFIGURATION ................................................................... 9
2.1 SCREEN LAYOUT ...............................................................................................................9
2.2 MODULE ........................................................................................................................... 10
2.2.1 MODULE OPTIONS ................................................................................................... 10
2.2.2 MODULE TIMERS ..................................................................................................... 11
2.2.3 EVENT LOG ............................................................................................................... 12
2.2.4 DATA LOGGING ........................................................................................................ 12
2.3 APPLICATION OPTIONS ................................................................................................. 13
2.3.1 BREAKER SCHEME A .............................................................................................. 15
2.3.1.1 S1 / S2 LOAD INHIBIT ........................................................................................ 15
2.3.1.2 S1 AND S2 LOAD INHIBIT ................................................................................. 15
2.3.1.3 TIMING DIAGRAM .............................................................................................. 15
2.3.2 BREAKER SCHEME B .............................................................................................. 16
2.3.2.1 CHECK SYNC IS DISABLED ............................................................................. 16
2.3.2.2 CHECK SYNC IS ENABLED .............................................................................. 17
2.3.3 BREAKER SCHEME C .............................................................................................. 18
2.3.3.1 CHECK SYNC & BREAKER CLOSE TRANSITION DISABLED ........................ 18
2.3.3.2 CHECK SYNC IS ENABLED .............................................................................. 19
2.4 DIGITAL INPUTS .............................................................................................................. 23
2.4.1 INPUT FUNCTIONS ................................................................................................... 24
2.5 OUTPUTS.......................................................................................................................... 27
2.5.1 DIGITAL OUTPUTS ................................................................................................... 27
2.5.2 VIRTUAL LEDS .......................................................................................................... 28
2.5.3 OUTPUT SOURCES .................................................................................................. 29
2.6 S1....................................................................................................................................... 34
2.6.1 S1 OPTIONS .............................................................................................................. 34
2.6.2 S1 TIMERS................................................................................................................. 35
2.6.3 S1 ALARMS ............................................................................................................... 36
2.7 LOAD ................................................................................................................................. 38
2.7.1 LOAD CURRENT ....................................................................................................... 38
2.7.2 LOAD TIMERS ........................................................................................................... 39
2.8 S2....................................................................................................................................... 40
2.8.1 S2 OPTIONS .............................................................................................................. 40
2.8.2 S2 TIMERS................................................................................................................. 41
2.8.3 S2 ALARMS ............................................................................................................... 42
2.9 PLANT BATTERY ............................................................................................................. 43
2.10 COMMUNICATIONS ..................................................................................................... 44
2.10.1 BASIC ......................................................................................................................... 44
2.10.1.1 SERIAL PORT CONFIGURATION ..................................................................... 45
2.10.1.2 MODEM SETTINGS ........................................................................................... 45
2.10.1.3 RECOMMENDED MODEMS .............................................................................. 46
2.10.2 ADVANCED................................................................................................................ 47
2.10.2.1 INITIALISATION STRINGS................................................................................. 47
2.10.2.2 CONNECTION SETTINGS ................................................................................. 48
2.10.2.3 MODBUS............................................................................................................. 49
2.10.3 TROUBLESHOOTING MODEM COMMUNICATIONS.............................................. 49
2.10.3.1 MODEM COMMUNICATION SPEED SETTING ................................................ 49
2.10.3.2 GSM MODEM CONNECTION ............................................................................ 49

Page 3 of 82 057-237 ISSUE: 3


DSE335 Configuration Suite PC Software Manual

2.10.3.3 SERIAL PORT INSTRUMENT DISPLAY ........................................................... 50


2.11 SCHEDULER ................................................................................................................. 52
2.11.1 SCHEDULER OPTIONS ............................................................................................ 52
2.11.2 BANK 1 ....................................................................................................................... 53
2.12 EXPANSION .................................................................................................................. 54
2.12.1 DSE2130 INPUT MODULES ..................................................................................... 54
2.12.1.1 DIGITAL INPUTS (A-D) ...................................................................................... 55
2.12.1.2 ANALOGUE INPUTS (E-H) ................................................................................ 56
2.12.2 DSE2157 RELAY MODULES .................................................................................... 57
2.12.3 DSE2548 LED EXPANSION ...................................................................................... 58
2.13 ADVANCED ................................................................................................................... 59
2.13.1 PLC ............................................................................................................................. 59
2.13.1.1 PLC LOGIC ......................................................................................................... 59
2.13.1.2 PLC FUNCTIONS ............................................................................................... 60
2.13.2 CONFIGURABLE GENCOMM PAGES ..................................................................... 61
3 SCADA ...........................................................................................................62
3.1 ATS IDENTITY .................................................................................................................. 63
3.2 MIMIC ................................................................................................................................ 64
3.3 LANGUAGES .................................................................................................................... 65
3.4 DIGITAL INPUTS .............................................................................................................. 65
3.5 DIGITAL OUTPUTS .......................................................................................................... 66
3.6 VIRTUAL LEDS................................................................................................................. 67
3.7 S1 & S2 ............................................................................................................................. 68
3.7.1 FREQUENCY, VOLTAGE AND CURRENT .............................................................. 68
3.7.2 POWER ...................................................................................................................... 69
3.8 LOAD ................................................................................................................................. 70
3.9 PLANT BATTERY ............................................................................................................. 70
3.10 ALARMS ........................................................................................................................ 70
3.11 STATUS ......................................................................................................................... 71
3.12 EVENT LOG .................................................................................................................. 72
3.13 MAINTENANCE............................................................................................................. 73
3.13.1 TIME ........................................................................................................................... 73
3.13.2 ACCUMULATED INSTRUMENTATION .................................................................... 74
3.13.2.1 S1 & S2 ............................................................................................................... 74
3.13.3 MODULE PIN ............................................................................................................. 75
3.14 DATA LOGGING ........................................................................................................... 76
3.15 PLC ................................................................................................................................ 77
3.16 EXPANSION .................................................................................................................. 78
3.16.1 2130 INPUT MODULE ............................................................................................... 78
3.16.2 2157 OUTPUT MODULE ........................................................................................... 79
3.16.3 2548 LED MODULE ................................................................................................... 80

057-237 ISSUE: 3 Page 4 of 82


Introduction

1 INTRODUCTION

NOTE: This manual details the configuration of the DSE335 module version 4.2 and later,
part of the DSEATS® range of products. A separate document covers the configuration of
DSE335 modules with firmware version prior to version 4.2.

This document details the use of the DSE Configuration Suite PC Software with the DSE8610 MKII
module, which is part of the DSEATS® range of products.

The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.

This is not a controlled document. DSE do not automatically inform on updates. Any future updates of
this document are included on the DSE website at www.deepseaelectronics.com

The DSE Configuration Suite PC Software allows the DSE8610 MKII module to be connected to a PC
via USB A to USB B cable (USB printer cable). Once connected, the software allows easy, controlled
access to various operating parameters within the module which can then be viewed and edited as
required.

The DSE Configuration Suite PC Software must only be used by competent, qualified personnel, as
changes to the operation of the module may have safety implications on the panel / generating set to
which it is fitted. Access to critical operational sequences and settings for use by qualified engineers,
may be barred by a security code set by the generator provider.

The information contained in this manual must be read in conjunction with the information contained
in the appropriate module documentation. This manual only details which settings are available and
how they may be used. Separate manuals deal with the operation of the individual module and its
ancillaries, refer to section entitled Bibliography elsewhere in this document for further information.

1.1 CLARIFICATION OF NOTATION


Clarification of notation used within this publication.

Highlights an essential element of a procedure to ensure correctness.


NOTE:

Indicates a procedure or practice, which, if not strictly observed, could


CAUTION! result in damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to personnel


WARNING! or loss of life if not followed correctly.

Page 5 of 82 057-237 ISSUE: 3


Introduction

1.2 GLOSSARY OF TERMS


Term Description
DSE3xx
All modules in the DSE3xx ATS range.
CT Current Transformer
An electrical device that takes a large AC current and scales it down by a fixed
ratio to a smaller current.
BMS Building Management System
A digital/computer based control system for a building’s infrastructure.
GSM Global System for Mobile communications. Cell phone technology used in most of
the World.
HMI Human Machine Interface
A device that provides a control and visualisation interface between a human and a
process or machine.
IDMT Inverse Definite Minimum Time
IEEE Institute of Electrical and Electronics Engineers
LED Light Emitting Diode
MSC Multi-Set Communication
SCADA Supervisory Control And Data Acquisition
A system that operates with coded signals over communication channels to
provide control and monitoring of remote equipment
SCR Selective Catalytic Reduction
A process that uses DEF with the aid of a catalyst to convert nitric oxide and
nitrogen dioxide into nitrogen and water to reduce engine exhaust emission.
SIM Subscriber Identity Module.
The small card supplied by the GSM/CDMA provider that is inserted into the cell
phone, GSM modem or DSEGateway device to give GSM/GPRS connection.
SMS Short Message Service
The text messaging service of mobile/cell phones.

057-237 ISSUE: 3 Page 6 of 82


Introduction

1.3 BIBLIOGRAPHY
This document refers to, and is referred by the following DSE publications which are obtained from
the DSE website: www.deepseaelectronics.com or by contacting DSE technical support:
[email protected].

1.3.1 INSTALLATION INSTRUCTIONS

Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.

DSE Part Description


053-136 DSE335 Installation Instructions
053-033 DSE2130 Input Expansion Installation Instructions
053-034 DSE2157 Output Expansion Installation Instructions
053-032 DSE2548 LED Expansion Annunciator Installation Instructions
053-049 DSE9xxx Battery Charger Installation Instructions
053-147 DSE9460 & DSE9461 Battery Charger Installation Instructions
053-185 DSE9473 & DSE9483 Battery Charger Installation Instructions

1.3.2 MANUALS

Product manuals are obtained from the DSE website: www.deepseaelectronics.com or by contacting
DSE technical support: [email protected].

DSE Part Description


057-151 DSE Configuration Suite PC Software Installation & Operation Manual
057-233 DSE335 Operator Manual
057-157 DSE335 Configuration Suite PC Software Manual – prior to v4.2
057-082 DSE2130 Input Expansion Operator Manual
057-083 DSE2157 Output Expansion Operator Manual
057-084 DSE2548 Annunciator Expansion Operator Manual
057-085 DSE9xxx Battery Charger Operator Manual
057-151 DSE Configuration Suite PC Software Installation & Operation Manual
057-175 PLC Programming Guide For DSE Controllers
057-176 DSE9460 & DSE9461 Battery Charger Operator Manual
N/A DSEGencomm (MODBUS protocol for DSE controllers)

Page 7 of 82 057-237 ISSUE: 3


Introduction

1.3.3 TRAINING GUIDES

Training guides are provided as ‘hand-out’ sheets on specific subjects during training sessions and
contain specific information regarding to that subject.

DSE Part Description


056-005 Using CTs With DSE Products
056-017 OC Configuration Interfacing
056-018 Negative Phase Sequence
056-019 Earth Fault Protection
056-021 Mains Decoupling
056-022 Switchgear Control
056-024 GSM Modem
056-026 kVA, kW, kvar and Power Factor
056-030 Module PIN Codes
056-036 DSE Module Expansion
056-047 Out of Sync and Failed To Close
056-051 Sending DSEGencomm Control Keys
056-053 Recommended Modems
056-069 Firmware Update
056-075 Adding Language Files
056-076 Reading DSEGencomm Alarms
056-079 Reading DSEGencomm Status
056-080 MODBUS
056-091 Equipotential Earth Bonding
056-092 Best Practices for Wiring Restive Sensors
056-097 USB Earth Loops and Isolation
056-099 Digital Output to Digital Input Connection
056-116 Underspeed and Overspeed

1.3.4 THIRD PARTY DOCUMENTS

The following third party documents are also referred to:

Reference Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device
ISBN 1-55937-879-4 Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc
ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J. Mahon
ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.

1.4 INSTALLATION AND USING THE DSE CONFIGURATION SUITE


SOFTWARE
For information in regards to installing and using the DSE Configuration Suite PC Software, refer to
DSE publication: 057-151 DSE Configuration Suite PC Software Installation & Operation
Manual which is found on the DSE website: www.deepseaelectronics.com

057-237 ISSUE: 3 Page 8 of 82


Editing the Configuration

2 EDITING THE CONFIGURATION


The software is broken down into separate sections to provide simple navigation whilst editing the
module’s configuration to suit a particular application.

2.1 SCREEN LAYOUT


The type of module
configuration file Click to move to the
being edited Previous or Next section

The coloured shading


shows the currently Click to close the
selected page/section opened configuration file

Click + or – to expand
or collapse the section

Click to step Forward or Back through Click to return to the Home


previously viewed configuration sections section shown below

Click to view /
edit the section

Page 9 of 82 057-237 ISSUE: 3


Editing the Configuration

2.2 MODULE
The Module section allows the user to edit options related to the module itself and is subdivided into
smaller sections.

Click to view /
edit the section

2.2.1 MODULE OPTIONS

Allows the user to Free entry boxes to allow the


select the function user to give the configuration
of the modules file a description. Typically this
user configurable is used to enter the job number,
LED indicators. customer name, engineers
For details of name etc.
possible
selections, please
see section
entitled Output
Sources
elsewhere in this
document.

Allows the user


to create logo
and text insert
cards

Parameters are described overleaf…

057-237 ISSUE: 3 Page 10 of 82


Editing the Configuration

Parameter Description
Lamp test at power  = Lamp test at power up is disabled.
up  = All module lamps illuminate when power is first applied.
Power Up in Auto  = The module enters START INHIBIT mode when DC power is applied.
 = The module enters AUTO mode when DC power is applied.
Transfer by buttons  = Fascia load control buttons are disabled.
 = Fascia load control buttons are enabled when the module is in Manual
Mode.
Support right-Left Determines the direction of text input where supported (i.e. configurable input
Languages in text)
Module Strings  = Left to right language support
 = Right to left language support
Enable Backlight  = The LCD Backlight stays On at all times.
Power Saving Mode  = DC power saving mode by turning off the LCD Backlight when the module
is not operated for the duration of the Backlight Timer.
Display Source  = Source Summary Screens are not shown on the module display
Summary Screens  = Additional screens for the two sources are shown the module display.
Disable Stop Mode  = Pressing the Stop Button changes the operating mode to Stop mode
(therefore removing the S2 Start and Run output).
 = Pressing the Stop Button does not change the operating mode to Stop
mode (the S2 Start and Run output remains active).
This allows the user to select the Stop button to enter the FPE and clear
alarms without changing the Modules Operating Mode

2.2.2 MODULE TIMERS

Parameter Description
Page Timer The amount of time before the module reverts to show the Status page when it
is left unattended
Scroll Timer The amount of time for automatic scroll between parameters on a selected
page.
Backlight Timer When the module is not operated for the duration of the Backlight Timer, the
LCD backlight turns off

Page 11 of 82 057-237 ISSUE: 3


Editing the Configuration

2.2.3 EVENT LOG

The event log is configured to allow users to select which events are stored.

Parameter Description
Power Up  = Power up events are not logged in the module’s event log
 = Power up events are logged when the DC Supply is applied to the
module or whenever the module is rebooted
S1 Return  = The S1 Return events are not logged in the module’s event log
 = Logs the S1 Return events
S1 Fail  = The S1 Fail events are not logged in the module’s event log
 = Logs the S1 Failure events
S2 Return  = The S2 Return events are not logged in the module’s event log
 = Logs the S2 Return events
S2 Fail  = The S2 Fail events are not logged in the module’s event log
 = Logs the S2 Failure events
Electrical Trip  = The Electrical Trip Alarms are not logged in the module’s event log
Alarms  = Logs the Electrical Trip alarms
Latched Warnings  = The Latched Warning Alarms are not logged in the module’s event log
 = Logs the Latched Warning Alarms
Unlatched Warnings  = The Unlatched Warning Alarms are not logged in the module’s event log
 = Logs the Unlatched Warning Alarms
Breaker Auxiliary  = The Breaker Auxiliary Failures are not logged in the module’s event log
Failures  = Logs the Breaker Auxiliary Failures

2.2.4 DATA LOGGING

Select the instrument / item


to be logged. Twenty (20)
selection points are
possible.

057-237 ISSUE: 3 Page 12 of 82


Editing the Configuration

2.3 APPLICATION OPTIONS

Parameters are detailed overleaf…

Page 13 of 82 057-237 ISSUE: 3


Editing the Configuration

Parameter Description
Breaker Type See overleaf for description of the Breaker Type.
Check Sync This option is only available when Scheme B is selected. See overleaf for
description of the Check Sync options
 = None check sync operation
 = During load transfer, the module only closes its breaker within the check
sync window. See overleaf for description of the Check Sync options.
Return to This option is only available when Check Sync is enabled. See overleaf for
programmed description of the Check Sync options
transition  = Normal operation
 = During load transfer if the check sync of the supplies does not occur within
two minutes, a ‘break’ or ‘open transition’ transfer occurs.
Elevator Post  = Normal operation
Transfer  = Any configurable output set to elevator control remains active for the
duration of the elevator delay after a load transfer has taken place.
Breaker Close This option is only available when Scheme C is selected. See overleaf for
Transition description of the Scheme C options
 = Break before make operation
 = During load transfer, the module only closes its breaker within the check
sync window. See overleaf for description of the Check Sync options.
Inhibit Retransfer to  = When the S1 supply is reinstated after a failure, the re-transfer back to S1
S1 takes place.
 = This prevents the load being transferred back to the S1 supply, even in
the event of the S2 supply failing.
Fail to Close This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
When the Close S1 or Close S2 output is activated, if the configured S1
Closed Auxiliary or S2 Closed Auxiliary digital input respectively do not
become active within the Fail To Close timer, the alarm is activated
Paralleling This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
This timer dictates how long the two supplies are closed in parallel for during
the Close Transition.
Fail to Open This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
When the Close S1 or Close S2 output is de-activated, if the configured S1
Closed Auxiliary or S2 Closed Auxiliary digital input respectively do not de-
activate within the Fail To Open timer, the alarm is activated
S1 Identity Enter a text string to identify the module’s S1 source.
S1 Source Type Select the function of the module’s S1 sensing terminals:
Mains
Generator
S1 Source Priority Select the S1 priority
Available options to choose from:
Priority
Standby
S1 Phase Display Choose which phase voltage to show on the module display
S2 Identity Enter a text string to identify the module’s S2 source.
S2 Source Type Select the function of the module’s S2 sensing terminals:
Mains
Generator
S2 Source Priority Select the S2 priority
Available options to choose from:
Priority
Standby
S2 Phase Display Choose which phase voltage to show on the module display

057-237 ISSUE: 3 Page 14 of 82


Editing the Configuration

2.3.1 BREAKER SCHEME A

Breaker scheme A is suitable for contactors or ACBs.

NOTE: S1 Closed Auxiliary and S2 Closed Auxiliary inputs do not affect the operation of
the load switching in Breaker Scheme A

2.3.1.1 S1 / S2 LOAD INHIBIT

Activation of an input configured to S1 Load Inhibit or S2 Load Inhibit inputs cause the corresponding
breaker to be opened immediately. No other change in function occurs.
When the input is deactivated the breaker is closed again if appropriate.

2.3.1.2 S1 AND S2 LOAD INHIBIT

If an input configured to S1 and S2 Load Inhibit is activated, outputs set to Open S1 and Open S2
energise, and inputs configured to Close S1 and Close S2 de-energise. Open S1 Pulse and Open S2
Pulse outputs only energise if the corresponding supply was on load before application of the S1 and
S2 Load Inhibit input.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.

2.3.1.3 TIMING DIAGRAM

Open S1

Close S2

Open S2

Close S1

Open S1 Pulse

Close S2 Pulse

Open S2 Pulse

Close S1 Pulse

Transfer Time Transfer time

Page 15 of 82 057-237 ISSUE: 3


Editing the Configuration

2.3.2 BREAKER SCHEME B

Breaker Scheme B is intended only for use with certain designs of transfer switch. For example, rotary
transfer switches with very short changeover time.
This scheme is only suitable for breakers which require pulse signals for opening and closing.

2.3.2.1 CHECK SYNC IS DISABLED

TRANSFERRING TO S1

To open the S1 breaker the Open S1 output energises, it then de-energises when the S1 Closed
Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the ‘S1 Closed Auxiliary’ indicates the S1 breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the S2 breaker by energising the Open
S1 and Close S2 outputs simultaneously, it then de-energises these outputs when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

TRANSFERRING TO S2

To open the S2 breaker the Open S2 output energises, it then de-energises when the S2 Closed
Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the ‘S2 Closed Auxiliary’ indicates the S2 breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the S1 breaker by energising the Open
S2 and Close S1 outputs simultaneously, it then de-energises these outputs when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first

S1 AND S2 LOAD INHIBIT INPUT

When the S1 and S2 Load Inhibit input is activated while S2 is closed the Open S2 output energises,
it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully opened, or
after 1s whichever occurs first.

When the S1 and S2 Load Inhibit input is activated while S1 is closed the Open S1 output energises,
it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully opened, or
after 1s whichever occurs first.

When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.

TIMING DIAGRAM
S1 has
opened S2 has closed
Open S1

Close S2

Open S2

Close S1

S1 has opened
Non-Sync Non-Sync
S2 has
Transfer Time Transfer Time closed

057-237 ISSUE: 3 Page 16 of 82


Editing the Configuration

2.3.2.2 CHECK SYNC IS ENABLED

NOTE : The module waits indefinitely for synchronisation unless the ‘Return to
programmed transition’ function is active in which case after 2 minutes it performs a non-sync
transfer as described in the previous section.

NOTE: The transfer time is ignored during a check-sync but is used if the transfer fails
and it performs a non-sync transfer.

TRANSFER TO S2

When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S1 and Close S2 outputs simultaneously. These outputs are de-energised when the S2 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

TRANSFER TO S1

When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S2 and Close S1 outputs simultaneously. These outputs are de-energised when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.

S1 AND S2 LOAD INHIBIT

When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.

When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.

When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.

TIMING DIAGRAM
In Sync
S2 has closed
Open S1

Close S2

Open S2

Close S1

In Sync
S1 has
closed

Page 17 of 82 057-237 ISSUE: 3


Editing the Configuration

2.3.3 BREAKER SCHEME C

Breaker scheme C supports open transition, open transition with check-sync and closed transition
with check-sync.

2.3.3.1 CHECK SYNC & BREAKER CLOSE TRANSITION DISABLED

S1 / S2 LOAD INHIBIT

Activation of an input configured to S1 Load Inhibit or S2 Load Inhibit inputs cause the corresponding
breaker to be opened immediately. No other change in function occurs.
When the input is deactivated the breaker is closed again if appropriate.

S1 AND S2 LOAD INHIBIT

If an input configured to S1 and S2 Load Inhibit is activated, outputs set to Open S1 and Open S2
energise, and inputs configured to Close S1 and Close S2 de-energise. Open S1 Pulse and Open S2
Pulse outputs only energise if the corresponding supply was on load before application of the S1 and
S2 Load Inhibit input.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.

TIMING DIAGRAM

Open S1

Close S2

Open S2

Close S1

Open S1 Pulse

Close S2 Pulse

Open S2 Pulse

Close S1 Pulse

Transfer Time Transfer time

057-237 ISSUE: 3 Page 18 of 82


Editing the Configuration

2.3.3.2 CHECK SYNC IS ENABLED

NOTE : The module waits indefinitely for synchronisation unless the ‘Return to
programmed transition’ function is active in which case after 2 minutes it performs a non-sync
transfer as described in the previous section.

NOTE: The transfer time is ignored during a check-sync but is used if the transfer fails
and it performs a non-sync transfer.

TRANSFER TO S2

When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S1 and Close S2 outputs simultaneously. The Close S2 Output Pulse is de-energised when the
S2 Closed Auxiliary input indicates the source has successfully closed, or after 1s whichever occurs
first.

TRANSFER TO S1

When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S2 and Close S1 outputs simultaneously. The Close S1 Output Pulse is de-energised when the
S1 Closed Auxiliary input indicates the source has successfully closed, or after 1s whichever occurs
first.

S1 AND S2 LOAD INHIBIT

When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.

Page 19 of 82 057-237 ISSUE: 3


Editing the Configuration

TIMING DIAGRAM

Open S1

Close S2

Open S2

Close S1

Open S1 Pulse

Close S2 Pulse

Open S2 Pulse

Close S1 Pulse

Transfer Time Transfer time

057-237 ISSUE: 3 Page 20 of 82


Editing the Configuration

BREAKER CLOSE TRANSITION IS ENABLED

NOTE: When Breaker Close Transition is enabled, the module performs a sync transfer
without the need for enabling the Check Sync feature.

TRANSFER TO S2

When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window, the module energises the
Close S2 output and checks for the S2 Closed Auxiliary input activating. If the S2 Closed Auxiliary
activates within the Fail to Close time, the Paralleling timer begins. If the S2 Closed Auxiliary does not
activate within the Fail to Close time, the Open S2 output is activated and the S2 Fail to Close alarm
activates.

At the end of the Paralleling timer, the module de-energises the Close S1 output and checks for the
S1 Closed Auxiliary input de-activating. If the S1 Closed Auxiliary does not de-activate within the Fail
to Open time, the Open S1 and Open S2 outputs are activated and the S1 Fail to Open alarm
activates.

TRANSFER TO S1

When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window, the module energises the
Close S1 output and checks for the S1 Closed Auxiliary input activating. If the S1 Closed Auxiliary
activates within the Fail to Close time, the Paralleling timer begins. If the S1 Closed Auxiliary does not
activate within the Fail to Close time, the Open S1 output is activated and the S1 Fail to Close alarm
activates.

At the end of the Paralleling timer, the module de-energises the Close S2 output and checks for the
S2 Closed Auxiliary input de-activating. If the S2 Closed Auxiliary does not de-activate within the Fail
to Open time, the Open S1 and Open S2 outputs are activated and the S2 Fail to Open alarm
activates.

S1 AND S2 LOAD INHIBIT

When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is de-energised the load is returned to the supply that was
disconnected, providing that supply is healthy.

Page 21 of 82 057-237 ISSUE: 3


Editing the Configuration

TIMING DIAGRAM

Paralleling S1 Fail to S1 Fail to Paralleling


Timer Open Close Timer
Timer Timer

Close S1

Close S1 Pulse

Open S1

Open S1 Pulse

S1 Closed
Auxiliary

Close S2

Close S2 Pulse

Open S2

Open S2 Pulse

S2 Closed
Auxiliary

S2 Fail to S2 Fail to
Close Timer Open Timer

057-237 ISSUE: 3 Page 22 of 82


Editing the Configuration

2.4 DIGITAL INPUTS


The Digital Inputs section is subdivided into smaller sections.
Select the required section with the mouse.

NOTE: The module’s digital inputs are configured as either negative or positive switching
in groups of three, this is determined in the modules configuration.

Configure input group to:


Close to Ground (-ve DC
Input Supply)
Group Close to Supply (+ve DC
supply)

Select the type of alarm


required.
For details of these, see the
section entitled Alarm Types
elsewhere in this document.

Configures if the input is


active or not active.

This is the text displayed on


the module screen when the
alarm is triggered.

Click and drag to change the


setting. This is used to give a
delay on acceptance of the
input. Useful for liquid level
switches or to mask short
term operations of the
external switch device.

Input function. See section


entitled Input Functions for
details of all available
functions

Close or Open To
Activate

As this example shows a


predefined function, these
parameters are greyed out
as they are not applicable.

Page 23 of 82 057-237 ISSUE: 3


Editing the Configuration

2.4.1 INPUT FUNCTIONS

Under the scope of IEEE 37.2, function numbers are also used to represent functions in
microprocessor devices and software programs. Where the DSE input functions are represented by
IEEE 37.2, the function number is listed below.

Function Description
Not used The input is disabled
Alarm Mute This input is used to silence the audible alarm from an external source,
such as a remote mute switch.
Alarm Reset This input is used to reset any latched alarms from a remote location. It is
also used to clear any latched warnings which may have occurred (if
configured) without having to stop/unload S2.
Auto Restore Inhibit In the event of a remote start/S1 failure, S2 is instructed to start and take
IEEE 37.2 - 3 Checking Or load. On removal of the remote start signal/S1 return the module continues
Interlocking Relay to run S2 on load until the Auto Restore Inhibit input is removed. This input
allows the controller to be fitted as part of a system where the restoration
to S1 is controlled remotely or by an automated system.
Auto start Inhibit This input is used to provide an over-ride function to prevent the controller
IEEE 37.2 - 3 Checking Or from starting S2 in the event of a remote start/S1 out of limits condition
Interlocking Relay occurring. If this input is active and a remote start signal/S1 failure occurs
the module does not give a start command to the S2. If this input signal is
then removed, the controller operates as if a remote start/S1 failure has
occurred, starting and loading S2. This function is used to give an ‘AND’
function so that S2 is only called to start if S1 fails and another condition
exists which requires S2 to run. If the ‘Auto start Inhibit’ signal becomes
active once more it is ignored until the module has returned the S1 supply
on load and shutdown.
This input does not prevent starting of the engine in MANUAL or TEST
modes.
Auxiliary S1 Fail The module monitors the incoming single or three phase supply for Over
voltage, Under Voltage, Over Frequency or Under frequency. It may be
required to monitor a different S1 supply or some aspect of the incoming
S1 not monitored by the controller. If the devices providing this additional
monitoring are connected to operate this input, the controller operates as if
the incoming S1 supply has fallen outside of limits, S2 is instructed to start
and take the load. Removal of the input signal causes the module to act if
S1 has returned to within limits providing that the S1 sensing also indicates
that the S1 is within limits.
Auxiliary S1 Ready Allows an external device (such as the engine control module) to instruct
the controller that S1 is healthy and available to take load. The controller
then monitors the voltage and frequency to check they are within
acceptable limits before performing the load transfer function.
Auxiliary S2 Fail The module monitors the incoming single or three phase supply for Over
voltage, Under Voltage, Over Frequency or Under frequency. It may be
required to monitor a different S2 supply or some aspect of the incoming
S2 not monitored by the controller. If the devices providing this additional
monitoring are connected to operate this input, the controller operates as if
the incoming S2 supply has fallen outside of limits, S1 is instructed to start
and take the load. Removal of the input signal causes the module to act if
S2 has returned to within limits providing that the S2 sensing also indicates
that the S2 is within limits.
Parameter descriptions are continued overleaf…

057-237 ISSUE: 3 Page 24 of 82


Editing the Configuration

Function Description
Auxiliary S2 Ready Allows an external device (such as the engine control module) to instruct
the controller that S1 is healthy and available to take load. The controller
then monitors the voltage and frequency to check they are within
acceptable limits before performing the load transfer function.

External Panel Lock This input is used to provide security to the installation. If the External
Panel lock input is active, the module does not respond to operation of the
Mode select or start buttons. This allows the module to be placed into a
specific mode (such as Auto) and then secured. The operation of the
module is not affected and the operator is still able to view the various
instrumentation pages etc. (Front panel configuration access is still
possible while the system lock is active).
Force Transfer To S1 Activating this input causes the module to open S2 and transfer the load to
S1 disregarding the status of S1.
When S1 is not available, the load remains off until the supply is back
within limits.
Force Transfer To S2 Activating this input causes the module to open S1 and transfer the load to
S2 disregarding the status of S2.
When S2 is not available, the load remains off until the supply is back
within limits.
Inhibit Scheduled Run This input is used to provide a means of disabling a scheduled run.
IEEE 37.2 - 3 Checking Or
Interlocking Relay
Lamp Test This input is used to provide a test facility for the front panel indicators
fitted to the module. When the input is activated all LED’s illuminate.
Open / Close S1 Allows connection of an external signal to control open and closing of the
IEEE 37.2 - 52 AC Circuit S1 load switch device.
Breaker
Open / Close S2 Allows connection of an external signal to control open and closing of the
IEEE 37.2 - 52 AC S2 load switch device.
Circuit Breaker
Remote Start off load If this input is active, operation is similar to the ‘Remote Start on load’
function except that S2 is not instructed to take the load. This function is
used where an engine only run is required e.g. for exercise.
Remote Start on load When in auto mode, the module performs the start sequence and transfers
load to S2.
In Manual mode, the load is transferred to S2 if the supply is already
healthy, however in manual mode, this input does not generate start/stop
requests of S2.
Reset Breaker Alarms This input is used to reset any of the Fail to Open or Fail to Close alarms
when using Breaker Scheme C without pressing the Stop Button.
S1 and S2 Load Inhibit This input is used to prevent the module from loading the S1 and S2
IEEE 37.2 - 3 Checking Or supplies. If the S1 or S2 supply is already on load activating this input
Interlocking Relay causes the module to unload that supply. Removing the input allows the
supply to be loaded again.

Parameter descriptions are continued overleaf…

Page 25 of 82 057-237 ISSUE: 3


Editing the Configuration

Function Description
S1 Closed Auxiliary This input is used to provide feedback to allow the controller to give true
IEEE 37.2 - 3 Checking Or indication of the contactor or circuit breaker switching status. It must be
Interlocking Relay connected to the S1 load switching device auxiliary contact.
(Breaker Scheme B)
In ‘Breaker Scheme A’, Incorrect application of this signal does not trigger
an alarm condition, it is used solely for indication of the breaker status.

In ‘Breaker Scheme B’ this feedback is used for internal interlocking of the


breaker outputs.

In ‘Breaker Scheme C’ this feedback is used for ensuring a closed


transition has occurred within the Breaker Close Transition timer.
S1 Load Inhibit This input is used to prevent the controller from loading S1. If S1 is already
IEEE 37.2 - 52 AC Circuit on load, activating this input causes the controller to unload S1. Removing
Breaker the input allows S1 to be loaded again.

NOTE: This input only operates to control the S1 switching


device if the module’s load switching logic is attempting to load S1. It
does not control the S1 switching device when the S2 supply is on
load.
S2 Closed Auxiliary This input is used to provide feedback to allow the controller to give true
IEEE 37.2 - 3 Checking Or indication of the contactor or circuit breaker switching status. It must be
Interlocking Relay connected to the S2 load switching device auxiliary contact.
(Breaker Scheme B)
In ‘Breaker Scheme A’, Incorrect application of this signal does not trigger
an alarm condition, it is used solely for indication of the breaker status.

In ‘Breaker Scheme B’ this feedback is used for internal interlocking of the


breaker outputs.

In ‘Breaker Scheme C’ this feedback is used for ensuring a closed


transition has occurred within the Breaker Close Transition timer.
S2 Load Inhibit This input is used to prevent the controller from loading S2. If S2 is already
IEEE 37.2 - 52 AC Circuit on load, activating this input causes the controller to unload S2. Removing
Breaker the input allows S2 to be loaded again.

NOTE: This input only operates to control the S2 switching


device if the module’s load switching logic is attempting to load S2. It
does not control the S2 switching device when the S1 supply is on
load.
Simulate S1 Available This function is provided to override the module’s internal monitoring
function. If this input is active, the module does not respond to the state of
the incoming AC S1 supply and behaves as if the supply is healthy.
Simulate S2 Available This function is provided to override the module’s internal monitoring
function. If this input is active, the module does not respond to the state of
the incoming AC S2 supply and behaves as if the supply is healthy.
Transfer To S1 Activating this input causes the module to open S2 and transfer the load to
S1, only when S1 is available.
When S1 is not available, S2 remains on load until S1 is back within limits.
Transfer To S2 Activating this input causes the module to open S1 and transfer the load to
S2, only when S2 is available.
When S2 is not available, S1 remains on load until S2 is back within limits.

057-237 ISSUE: 3 Page 26 of 82


Editing the Configuration

2.5 OUTPUTS
The Outputs section is subdivided into smaller sections.
Select the required section with the mouse

2.5.1 DIGITAL OUTPUTS

Select what
the output is
to be used to
control

Select if the relay is to


energise or de-
energise upon
activation of the
source

The output sources


are sorted into
groups or searched
for by typing part of
These labels the name into the
match the typical source box.
wiring diagram

The list of output sources available for configuration of the module outputs is listed in the section
entitled Output Sources.

Page 27 of 82 057-237 ISSUE: 3


Editing the Configuration

2.5.2 VIRTUAL LEDS

Allows configuration of ‘status’


items.
These items are not available for
viewing on the module itself but is
seen in the SCADA section of the
PC software, or read by third party
systems (ie BMS or PLCs) using
the Modbus protocol.

Select if the LED is to


active or de-active the
LED upon activation of
the source

The output sources are


sorted into groups or is
searched for by typing its
name into the source
box.

The list of output sources available for configuration of the module outputs is listed in the section
entitled Output Sources.

057-237 ISSUE: 3 Page 28 of 82


Editing the Configuration

2.5.3 OUTPUT SOURCES

The list of output sources available for configuration of the module relay outputs also applies to the
LED configuration and expansion relay outputs.

Under the scope of IEEE 37.2, function numbers are also used to represent functions in microprocessor devices
and software programs. Where the DSE output functions are represented by IEEE 37.2, the function number is
listed below.

Output Source Activates… Is Not Active….


Not Used The output does not change state (Unused)
Alarm Mute Active when a configured Alarm Mute digital input is active
Alarm Reset Active when a configured Alarm Reset digital input is active
Audible Alarm This output indicates that the Inactive if the internal sounder is
IEEE 37.2 – 74 Alarm Relay internal sounder is operating to not operating.
allow it to feed an external
sounder. Operation of the Mute
pushbutton resets this output
once activated.
Auto Restore Inhibit Active when the Auto-Restore Inhibit function is active.
Auto Start Inhibit Active when the Auto-Start Inhibit function is active.
Auxiliary S1 Fail Active when a configured Auxiliary S1 Fail digital input is active
Auxiliary S1 Ready Active when a configured Auxiliary S1 Ready digital input is active
Auxiliary S2 Fail Active when a configured Auxiliary S2 Fail digital input is active
Auxiliary S2 Ready Active when a configured Auxiliary S2 Ready digital input is active
Battery High Voltage This output indicates that a Inactive when battery voltage is
IEEE 37.2 – 59 DC Over Voltage Battery Over voltage alarm has not High
Relay occurred.
Battery Low Voltage This output indicates that a Inactive when battery voltage is
IEEE 37.2 – 27 DC Under Battery Under Voltage alarm has not Low
Voltage Relay occurred.
Breaker Alarm Reset Active when a configured Breaker Alarm Reset digital input is active
Close S1 Output Used to control the load The output is inactive whenever
IEEE 37.2 – 52 AC Circuit switching device. Whenever the S1 is not required to be on load
Breaker module selects S1 to be on load,
this control source is active.
Close S1 Output Pulse Used to control the load switching device. Whenever the module
IEEE 37.2 – 52 AC Circuit selects S1 to be on load this control source is active for the duration
Breaker of the Breaker Close Pulse timer, after which it becomes inactive
again.
Close S2 Output Used to control the load The output is inactive whenever
IEEE 37.2 – 52 AC Circuit switching device. Whenever the S2 is not required to be on load
Breaker module selects S2 to be on load
this control source is active.
Close S2 Output Pulse Used to control the load switching device. Whenever the module
IEEE 37.2 – 52 AC Circuit selects to be on load this control source is active for the duration of
Breaker the Breaker Close Pulse timer, after which it becomes inactive again.
Close to N Output Used to control the load The output is inactive when S1
IEEE 37.2 – 52 AC Circuit switching device. Whenever the or S2 are required to be on load
Breaker module selects S1 and S2 to not
supply the load this control
source is active.
Close to N Output Pulse Used to control the load switching device. Whenever the module
IEEE 37.2 – 52 AC Circuit selects ATS to be in the neutral position, this control source is active
Breaker for the duration of the Breaker Close Pulse timer, after which it
becomes inactive again.
Close Transition in Progress Active only when a closed transition is in progress. The output goes
inactive after the transfer is complete.
Parameter descriptions are continued overleaf…

Page 29 of 82 057-237 ISSUE: 3


Editing the Configuration

Output Source Activates… Is Not Active….


Common Alarm Active when one or more alarms The output is inactive when no
(of any type) are active alarms are present
Common Electrical Trip Active when one or more The output is inactive when no
Electrical Trip alarms are active shutdown alarms are present
Common warning Active when one or more The output is inactive when no
IEEE 37.2 – 74 Alarm Relay warning alarms are active warning alarms are present
Cooling Down Active when the Cooling timer is The output is inactive at all other
in progress times
Digital Input A – L Active when the digital input is Inactive when :
active • the input is not active
• the input is active but
conditioned by activation
delay or arming
requirements.
Elevator Control Active during the elevator delay Inactive at all other times
time before a load transfer takes
place and remains active for the
duration of the elevator delay
after a transfer takes place
(when elevator post transfer is
enabled.
External Panel Lock Active when the module’s panel lock function is active.
Fail to Start Active when the S2 is configured as generator and no voltage or
frequency is measured for S2 within the Start Delay timer.
Fail to Stop Active when the S2 is configured as generator and the generator
fails to stop within the Fail to Stop Delay timer.
Force Transfer to S1 Active when the Force Transfer To S1 digital input is active.
Force Transfer to S2 Active when the Force Transfer To S2 digital input is active.
Inhibit Scheduled Run Active when the Inhibit Scheduled Run digital input is active.
Lamp Test Active when the Lamp Test digital input is active or the Mute/Lamp
Test push button is pressed.
Load Shedding Control (1-5) Becomes active when the engine Inactive when the engine kW
kW exceeds Load Shedding returns to below the Load
Control Trip Setting. Shedding Control Return setting.
Loading Frequency Not Active when S2 has failed to reach the loading frequency after the
Reached ‘Safety on Delay’ timer.
Loading Voltage Note Active when S2 has failed to reach the loading voltage after the
Reached ‘Safety on Delay’ timer.
Open S1 Output Used to control the load The output is inactive whenever
IEEE 37.2 – 52 ac circuit breaker switching device. Whenever the S1 is required to be on load
module selects S1 to be off load
this control source is active.
Open S1 Output Pulse Used to control the load switching device. Whenever the module
IEEE 37.2 – 52 ac circuit breaker selects S1 to be off load this control source is active for the duration
of the Breaker Open Pulse timer, after which it becomes inactive
again.
Open S2 Output Used to control the load Inactive whenever S2 is required
IEEE 37.2 – 52 ac circuit breaker switching device. Whenever the to be on load
module selects S2 to be off load
this control source is active.
Open S2 Output Pulse Used to control the load switching device. Whenever the module
IEEE 37.2 – 52 ac circuit breaker selects S2 to be off load this control source is active for the duration
of the Breaker Open Pulse timer, after which it becomes inactive
again.
Open/Close S1 Active when a configured Open/Close S1 digital input is active
Open/Close S2 Active when a configured Open/Close S2 digital input is active
Parameter descriptions are continued overleaf…

057-237 ISSUE: 3 Page 30 of 82


Editing the Configuration

Output Source Activates… Is Not Active….


PLC Output Flag 1-20 Active when the PLC Output Flag (1-20) becomes active.
Remote Control 1-10 Active when the corresponding Remote Control is active
Remote Start Off Load Active when the Remote Start Off Load input function is active
Remote Start On Load Active when the Remote Start On Load input function is active
Return Delay in Progress Indicates that S2 is on load, and S1 is available, during the return
delay timers.
S1 and S2 Closed Active when the S1 and S2 Closed Auxiliary inputs are active at the
same time, indicating the two supplies are closed in parallel.
S1 and S2 Load Inhibit Active when a configured S1 and S2 Load Inhibit digital input is
active
S1 and S2 Open Active when the S1 and S2 Closed Auxiliary inputs are not active at
the same time.
S1 Available Active when the S1 supply is available and within limits
S1 Breaker Auxiliary Fail Active when a configured S1 Breaker Auxiliary Fail digital input is
active
S1 Closed Active when the Close S1 output function is active
S1 Closed Auxiliary Active when a configured S1 Closed Auxiliary digital input is active
S1 Fail to Close Active when the Close S1 output has activated but the S1 Closed
Auxiliary input has not activated within the Fail to Close time.
S1 Fail to Open Active when the OpenS1 output has activated but the S1 Closed
Auxiliary input has not de-activated within the Fail to Open time.
S1 Failure Latched Activates when the S1 failure alarm is active. Reset by digital input
configured to Alarm Reset
S1 Failure Unlatched Activates when the S1 failure alarm is active. Reset automatically
when S1 becomes available
S1 High Frequency Becomes active if S1’s frequency goes higher than the configured
trip setting.
S1 High Voltage Becomes active if S1’s voltage goes higher than the configured trip
setting.
S1 In Limits Activates when S1 becomes available and is within configured limits.
S1 Load Inhibit Active when the S1 Load Inhibit digital input is active.
S1 Load Inhibited Indicates that an input configured to S1 Load Inhibit is active,
preventing the supply from taking load.
S1 Low Frequency Becomes active if S1’s frequency goes lower than the configured trip
setting.
S1 Low Voltage Becomes active if S1’s voltage goes lower than the configured trip
setting.
S1 Phase Rotation Alarm Active when the S1 Phase Rotation Alarm is active.
S1 Ready Active when a configured S1 Ready digital input is active
S1 Transient Delay Active during the Transient Delay time when S1 is not within limits
S2 Available Active when the S1 supply is available and within limits
S2 Breaker Auxiliary Fail Active when a configured S2 Breaker Auxiliary Fail digital input is
active
S2 Closed Active when the Close S2 output function is active
S2 Closed Auxiliary Active when a configured S2 Closed Auxiliary digital input is active
S2 Fail to Close Active when the Close S2 output has activated but the S2 Closed
Auxiliary input has not activated within the Fail to Close time.
S2 Fail to Open Active when the OpenS2 output has activated but the S2 Closed
Auxiliary input has not de-activated within the Fail to Open time.
S2 Failure Latched Activates when the S2 failure alarm is active. Reset by digital input
configured to Alarm Reset
S2 Failure Unlatched Activates when the S2 failure alarm is active. Reset automatically
when S1 becomes available
Parameter descriptions are continued overleaf…

Page 31 of 82 057-237 ISSUE: 3


Editing the Configuration

Output Source Activates… Is Not Active….


S2 Gen High Frequency When S2 is configured to Gen, this output becomes active if S2’s
frequency goes above the configured trip setting.
S2 Gen Low Frequency When S2 is configured to Gen, this output becomes active if S2’s
frequency falls below the configured trip setting.
S2 Gen High Voltage When S2 is configured to Gen, this output becomes active if S2’s
voltage goes above the configured trip setting.
S2 Gen Low Voltage When S2 is configured to Gen, this output becomes active if S2’s
voltage falls below the configured trip setting.
S2 In Limits Activates when the S2 becomes available, is within configured limits
and the Auxiliary S2 Ready input is active.
S2 Load Inhibit Indicates that an input configured to S2 Load Inhibit is active,
preventing the supply from taking load.
S2 Load Inhibited Indicates that an input configured to S2 Load Inhibit is active,
preventing the supply from taking load.
S2 Mains High Frequency When S2 is configured to Mains, this output becomes active if S2’s
frequency goes above the configured trip setting.
S2 Mains High Voltage When S2 is configured to Mains, this output becomes active if S2’s
voltage goes above the configured trip setting.
S2 Mains Low Frequency When S2 is configured to Mains, this output becomes active if S2’s
frequency falls below the configured trip setting.
S2 Mains Low Voltage When S2 is configured to Mains, this output becomes active if S2’s
voltage falls below the configured trip setting.
S2 Phase Rotation Alarm Active when the S2 Phase Rotation Alarm is active.
S2 Ready Activates when S2 becomes available and both the warming and
cooldown time are not active. Ignores alarm conditions and the S2
transient delay
S2 Start and Run Active when the controller has requested for S2 to start and run.
S2 Transient Delay Active during the Transient Delay time when S1 is not within limits
Scheduled Run Active when the controller is requesting the set to run under control
of the inbuilt Scheduler.
Scheduled Do Not Transfer Active when a configured Do Not Transfer scheduler event is active.
Scheduled Event In Progress Active when any configured scheduler event is active.
Scheduled Start S1 Off-load Active when a configured S1 Start Off Load scheduler event is
active.
Scheduled Start S2 Off-load Active when a configured S2 Start Off Load scheduler event is
active.
Scheduled Transfer to S1 Active when a configured Transfer To S1 scheduler event is active.
Scheduled Transfer to S2 Active when a configured Transfer To S2 scheduler event is active.
Simulated S1 Available Active when the Simulated S1 Available digital input is active.
Simulated S2 Available Active when the Simulated S2 Available digital input is active.
Start Delay in Progress Active when the controller is in the start delay timer, after which the
set is called to start.
System in Auto Mode Active when unit is in Auto mode
System in Manual Mode Active when unit is in Manual mode
System in Prohibit Return Active when unit is in Prohibit Return Mode
Mode
System in Stop Mode Active when unit is in Stop Mode
System in Test Off-Load Active when unit is in Test Off-Load Mode
Mode
System in Test On-Load Active when unit is in Test On-Load Mode
Mode
Parameter descriptions are continued overleaf…

057-237 ISSUE: 3 Page 32 of 82


Editing the Configuration

Output Source Activates… Is Not Active….


Transfer To S1 Active when the Transfer to S1 digital input is active
Transfer To S2 Active when the Transfer to S2 digital input is active
Waiting For Manual Restore Becomes active when S2 is on load and the S1 supply is healthy but
an input configured to Manual Restore is active.
This is used to signal to an operator that action is required before the
set transfers back to the S1 supply.
Waiting For S1 Active when the controller has requested for S1 to start and is
waiting for it to become available.
Waiting For S2 Active when the controller has requested for S2 to start and is
waiting for it to become available.
Warming Up Active when S2 is running off load, during the warming timer, before
taking load.

Page 33 of 82 057-237 ISSUE: 3


Editing the Configuration

2.6 S1
The S1 section is subdivided into smaller sections. Select the required section with the mouse.

2.6.1 S1 OPTIONS

When three phase loads are


present, it is usually desirable
to enable the Immediate S1
Dropout feature.

Parameter Description
Open When
S2 Available NOTE: Active when S1 source is set to Standby. For further details see
section entitled Application Options elsewhere in this document

NOTE: S1/S2 Closed Auxiliary must be configured to enable this


Parameter. For further details, see section entitled Digital Inputs elsewhere in
this document.
 = The S1 breaker can be requested to open regardless if S2 is available. This is
useful when using DC controlled opening signals.
 = The S1 breaker is only requested to open when S2 is available. This is required
when S1’s breaker’s opening signals are supplied by S2’s supply.
Immediate S1
Dropout NOTE: This feature cannot be enabled when Open When S2 Available is
enabled.
 = Upon S1 failure, the S1 Breaker remains closed until a transfer to S2 is
initiated.
 = Upon S1 failure, the S1 Breaker opens immediately.
AC System This defines the topology of the alternator/source and the connections to the DSE
module sensing terminals.

057-237 ISSUE: 3 Page 34 of 82


Editing the Configuration

Parameter Description
VT Fitted  = The voltage sensing to the controller is direct from the alternator
 = The voltage sensing to the controller is via Voltage Transformers (VTs or PTs)
This is used to step down the generated voltage to be within the controller voltage
specification.
By entering the Primary and Secondary voltages of the transformer, the controller
displays the Primary voltage rather than the actual measured voltage.

This is typically used to interface the DSE module to high voltage systems (ie 11kV)
but also used on systems such as 600V ph-ph.

2.6.2 S1 TIMERS

Click and drag to change the


setting.
Timers increment in steps of
1second up to one minute,
then in steps of 30seconds up
to 30minutes, then in steps of
30minutes thereafter (where
allowed by the limits of the
timer).

Timer Description
Start Delay Used to give a delay before starting in AUTO mode. This timer is activated
upon the respective start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start
signals or short term S2 failures.
Return Delay A delay, used in auto mode only, that allows for short term removal of the
request to unload the supply before action is taken. This is usually used to
ensure the supply remains on load before accepting that the start request has
been removed.
Transient Delay Used to delay the detection of S1 failure. This is normally used to prevent
short term transients or brownout conditions from being classified as a S1
Failure and opening the breaker.

Page 35 of 82 057-237 ISSUE: 3


Editing the Configuration

2.6.3 S1 ALARMS

Alarm Description
Under Voltage  = S1 Under Voltage detection is disabled
IEEE 37.2 – 27 AC  = S1 Under Voltage gives an alarm in the event of the mains voltage
Undervoltage Relay falling below the configured Under Voltage Trip value. The Under Voltage
Trip value is adjustable to suit the application. The alarm is reset and the
S1 is considered within limits when the S1 voltage rises above the
configured Under Voltage Return level.
Over Voltage  = S1 Over Voltage detection is disabled
IEEE 37.2 – 59 AC  = S1 Over Voltage gives an alarm in the event of the S1 voltage rising
Overvoltage Relay above the configured Over Voltage Trip value. The Over Voltage Trip
value is adjustable to suit the application. The alarm is reset and the S1 is
considered within limits when the S1 voltage falls below the configured
Over Voltage Return level.
Under Frequency  = S1 Under Frequency detection is disabled
IEEE 37.2 – 81 Frequency  = S1 Under Frequency gives an alarm in the event of the S1 frequency
Relay falling below the configured Under Frequency Trip value. The Under
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S1 is considered within limits when the S1 frequency rises
above the configured Under Frequency Return level.
Over Frequency  = S1 Over Frequency detection is disabled
IEEE 37.2 – 81 Frequency  = S1 Over Frequency gives an alarm in the event of the S1 frequency
Relay rising above the configured Over Frequency Trip value. The Over
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S1 is considered within limits when the S1 frequency falls
below the configured Over Frequency Return level.

057-237 ISSUE: 3 Page 36 of 82


Editing the Configuration

Alarm Description
Phase Rotation  = The phase rotation is not checked
Detection  = An Electrical Trip alarm is generated when the phase rotation of S1
IEEE 37.2 – 47 Phase supply is not matching the configurerd Phase Rotation setting.
Sequence Relay

Page 37 of 82 057-237 ISSUE: 3


Editing the Configuration

2.7 LOAD
The Load section is subdivided into smaller sections. Select the required section with the mouse.

2.7.1 LOAD CURRENT

Type the value or click


the up and down arrows
to change the settings

Click and drag to


change the setting.

Timer Description
CT Primary Primary rating of the Current Transformers
CT Secondary Secondary rating of the Current Transformers
Full Load Rating Full load rating (100% rating) of the load current
Max kW Rating Full load rating (100% rating) of the load kW

Click to enable or
disable the option.
The relevant values
below appears
greyed out if the
alarm is disabled.

Setting Description
Enable Provides control of configurable outputs set to Load Shedding Control.
 = Load Shedding Control is disabled.
 = The module monitors the load and control any outputs configured to
Load Shedding Control (1-5)
Outputs in Scheme The number of outputs (max 5) that is included in the function.
Outputs at Start The number of outputs configured to Load Shedding Control 1-5 that is
energised when the set is required to take load. The Transfer Delay / Load
Delay timer begins. At the end of this timer, the load switch is closed – S2 is
placed on load.
Trip / Trip Delay When the load level is above the Trip setting for the duration of the Trip
Delay, then the ‘next’ output configured to Load Shedding Control is activated
(max 5)
Return / Return Delay When the load level is below the Return setting for the duration of the Return
Delay, then the ‘highest numbered’ output configured to Load Shedding
Control is de-activated and the timer is reset.
Transfer Time / Load The time between closing the Load Shedding Control outputs (Outputs at
Delay Start) and closing the load switching device.

057-237 ISSUE: 3 Page 38 of 82


Editing the Configuration

2.7.2 LOAD TIMERS

Timer Description
Non-sync Transfer The time between one supply’s load switch being opened and the other
Time supply’s load switch being closed. Used to give time for the load switches to
move to their correct positions and to prevent the mechanical interlock from
“jamming”.
This timer is also used to give a ‘dead time’ to ensure that any machinery
stops fully after removal of the supply, before applying the new supply to the
equipment (for instance directly driven AC motors).
Check-Sync Transfer The time allowed for the Sync Transfer to be completed. If the two supplies
Time do not come in sync during this time, the module reverts to perform a Non-
Sync Transfer.
Breaker close pulse The amount of time that Breaker Close Pulse signals are present when the
request to close a breaker is given.
Breaker Trip pulse The amount of time that Breaker Open Pulse signals are present when the
request to open a breaker is given.
Elevator Delay Use to delay the Elevator Control output before and after load transfer takes
place. See section entitled Application for details of Elevator Control.

Page 39 of 82 057-237 ISSUE: 3


Editing the Configuration

2.8 S2
The S2 section is subdivided into smaller sections. Select the required section with the mouse.

2.8.1 S2 OPTIONS

When three phase loads are


present, it is usually desirable
to enable the Immediate S2
Dropout feature.

This is ‘read only’ for


information purposes. The
AC system is configured in
the ‘S1 Options’ page.

Parameter Description
Open When
S1 Available NOTE: Tick box shown for read only purpose. To configure the tick box
see section entitled S1 Options elsewhere in this document.

NOTE: Active when S2 source is set to Standby. For further details see
section entitled Application Options elsewhere in this document
 = The S2 breaker can be requested to open regardless if S1 is available. This is
useful when using DC controlled opening signals.
 = The S2 breaker is only requested to open when S1 is available. This is required
when S2’s breaker’s opening signals are supplied by S1’s supply.
Immediate S2
Dropout NOTE: This feature is not enabled when Open When S1 Available is
enabled or when S2 is set to Standby. For further details see
section entitled Application Options elsewhere in this document.
 = Upon S2 failure, the S2 Breaker remains closed until a transfer to S1 is
initiated.
 = Upon S2 failure, the S2 Breaker opens immediately.
AC System This defines the topology of the alternator/source and the connections to the DSE
module sensing terminals.

057-237 ISSUE: 3 Page 40 of 82


Editing the Configuration

Parameter Description
VT Fitted  = The voltage sensing to the controller is direct from the alternator
 = The voltage sensing to the controller is via Voltage Transformers (VTs or PTs)
This is used to step down the generated voltage to be within the controller voltage
specification.
By entering the Primary and Secondary voltages of the transformer, the controller
displays the Primary voltage rather than the actual measured voltage.

This is typically used to interface the DSE module to high voltage systems (ie 11kV)
but also used on systems such as 600V ph-ph.

2.8.2 S2 TIMERS

Click and drag to change the


setting.
Timers increment in steps of
1second up to one minute, then
in steps of 30seconds up to
30minutes, then in steps of
30minutes thereafter (where
allowed by the limits of the
timer).

Timer Description
Start Delay Used to give a delay before starting in AUTO mode. This timer is activated
upon the respective start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start
signals or short term S2 failures.
Return Delay A delay, used in auto mode only, that allows for short term removal of the
request to unload the supply before action is taken. This is usually used to
ensure the supply remains on load before accepting that the start request has
been removed.
Transient Delay Used to delay the detection of S1 failure. This is normally used to prevent
short term transients or brownout conditions from being classified as a S1
Failure and opening the breaker.
Warming Up Time The amount of time that the set runs BEFORE being allowed to take load.
This is used to warm the engine to prevent excessive wear.
Fail Delay The module instructs that S2 is to start and waits for the period of this timer
for S2 to become available. If it is not available when the timer expires, the
S2 failure alarm is triggered.
Cooling time The amount of time that the set runs OFF LOAD before being stopped. This
is to allow the set to cool down and is particularly important for engines with
turbo chargers.
Fail to Stop Delay  = Alarm is disabled
 = If the supply is called to stop and is still running after the configurable
Fail to Stop delay time expires, a Fail to Stop alarm is generated.

Page 41 of 82 057-237 ISSUE: 3


Editing the Configuration

2.8.3 S2 ALARMS

Alarm Description
Under Voltage  = S2 Under Voltage detection is disabled
IEEE 37.2 – 27 AC  = S2 Under Voltage gives an alarm in the event of the mains voltage
Undervoltage Relay falling below the configured Under Voltage Trip value. The Under Voltage
Trip value is adjustable to suit the application. The alarm is reset and the
S2 is considered within limits when the S2 voltage rises above the
configured Under Voltage Return level.
Over Voltage  = S2 Over Voltage detection is disabled
IEEE 37.2 – 59 AC  = S2 Over Voltage gives an alarm in the event of the S2 voltage rising
Overvoltage Relay above the configured Over Voltage Trip value. The Over Voltage Trip
value is adjustable to suit the application. The alarm is reset and the S2 is
considered within limits when the S2 voltage falls below the configured
Over Voltage Return level.
Under Frequency  = S2 Under Frequency detection is disabled
IEEE 37.2 – 81 Frequency  = S2 Under Frequency gives an alarm in the event of the S2 frequency
Relay falling below the configured Under Frequency Trip value. The Under
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S2 is considered within limits when the S2 frequency rises
above the configured Under Frequency Return level.
Over Frequency  = S2 Over Frequency detection is disabled
IEEE 37.2 – 81 Frequency  = S2 Over Frequency gives an alarm in the event of the S2 frequency
Relay rising above the configured Over Frequency Trip value. The Over
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S2 is considered within limits when the S2 frequency falls
below the configured Over Frequency Return level.
Phase Rotation  = The phase rotation is not checked
Detection  = An Electrical Trip alarm is generated when the phase rotation of S2
IEEE 37.2 – 47 Phase supply is not matching the configured Phase Rotation setting.
Sequence Relay

057-237 ISSUE: 3 Page 42 of 82


Editing the Configuration

2.9 PLANT BATTERY

Click to enable or disable the


option. The relevant values
below appears greyed out if
the alarm is disabled.

Click and drag to


change the setting.

Type the value or click


the up and down arrows
to change the settings

Parameter Description
Plant Battery Undervolts The alarm activates when the battery voltage drops below the configured Pre-
IEEE 37.2 -27 DC Alarm level for the configured Delay time. When the battery voltage rises above the
Undervoltage Relay configured Return level, the alarm is de-activated.
Plant Battery Overvolts The alarm activates when the battery voltage rises above the configured Pre-
IEEE 37.2 -59 DC Alarm level for the configured Delay time. When the battery voltage drops below
Overvoltage Relay the configured Return level, the alarm is de-activated.

Page 43 of 82 057-237 ISSUE: 3


Editing the Configuration

2.10 COMMUNICATIONS
The module includes an RS232 port for connection to a modem and an RS485 ports for connection to
another device. The protocol used is Modbus RTU.

The Communications page is subdivided into smaller sections.


Select the required section with the mouse.

2.10.1 BASIC

Free text entries to identify the


module.
This text is displayed on the
SCADA screen when the
module is connected to the PC.

Modbus Slave
ID
Baud rate adjustable
from 1200-115200

Selects how the


port is to be used

These items are


greyed out until a
relevant option in Port
Usage is selected.

Click to enable or disable a


GSM modem. The relevant
features below appears
greyed out if the GSM
modem is disabled.

057-237 ISSUE: 3 Page 44 of 82


Editing the Configuration

2.10.1.1 SERIAL PORT CONFIGURATION

Timer Description
Port usage Only one of the two serial ports is used at any one time (RS232 or RS485)
The options are :
No Modem – RS232 ports is used for direct RS232 connection to PLC, BMS
etc
Incoming modem calls – RS232 port connected to modem, used to accept
incoming calls only.
Incoming and outgoing modem (Sequence) – RS232 port connected to
modem used to accept incoming calls and also make calls upon shutdown
alarms.
Outgoing modem alarms (Sequence) - RS232 port connected to modem,
used to make calls upon shutdown alarms.
Incoming and outgoing modem (Cyclic) – RS232 port connected to
modem used to accept incoming calls and also make calls upon shutdown
alarms.
Outgoing modem alarms (Cyclic) - RS232 port connected to modem, used
to make calls upon shutdown alarms.

RS485 – The RS485 port is active. This is often used to connect to PLC’s,
building management systems and other third party equipment.

2.10.1.2 MODEM SETTINGS

Timer Description
Alarm Number The phone number that the module dials upon an alarm condition. This
number must be connected to a PC modem on a PC running the
Configuration Suite Software.
GSM Modem  = The connected modem is a fixed line telephone modem
 = The connected modem is a GSM (cellular) modem. The GSM signal
strength meter and GSM operator are shown on the module display.
SMS Message The Message centre used to send SMS messages. This number is usually
Centre Modem stored on the SIM card and need not be entered here.
A number is only needed here if it is not stored on the SIM card.
SMS Recipient Numbers of the cell phones to send SMS messages to.
Numbers Leave blank if SMS function is not required.

Page 45 of 82 057-237 ISSUE: 3


Editing the Configuration

2.10.1.3 RECOMMENDED MODEMS

DSE stock and supply the following recommended modems:

PSTN (FIXED LINE) MODEM

Description DSE Part Number


Multitech ZBA Global Modem 020-252
Modem Localisation kit for Europe 020-253
Modem Localisation kit for Iceland/Sweden 020-254
Modem Localisation kit for New Zealand 020-264
Modem Localisation kit for Netherlands 020-265
Modem Localisation kit for USA 020-286

Other Localisation Kits are obtained from www.multitech.com

GSM MODEM

DSE do not stock or supply SIM cards for the modem, these must be obtained from your local GSM
provider.

DSE Part
Description
Number
0830-001-01
NOTE: This modem is supplied ready configured to operate with the
DSE module. When purchasing from a third party, the modem is not
configured to communicate with the module.

Sierra Fastrack Xtend GSM Modem supplied with power supply cable, RS232
connection cable and GSM antenna. Suitable for GSM operating on 900/1800
MHz bands.

057-237 ISSUE: 3 Page 46 of 82


Editing the Configuration

2.10.2 ADVANCED

Modem initialisation
strings. These set up the
modem to perform the
functions required.

2.10.2.1 INITIALISATION STRINGS

The initialisation strings are commands that are sent to the modem upon powering up the DSE
module and additionally at regular intervals subsequently, whenever the module initialises (resets) the
modem.

FACTORY SET INITIALISATION STRINGS

Setting Description
E0 Echo off
S7=60 Wait for carrier time 60s
S0=0 (not auto answer) Do not answer
S0=2 (auto answer) Answer after two rings
&S0 DSR always on
&C1 DCD is active if modem is online
&D3 Reset (ATZ) on DTR-drop
H0 Hang up (disconnect)

SILENT OPERATION

The modem connected to the module usually makes dialling noises and ‘squeal’ in the initial stages of
making a data call. To control this noise, add the following command to the end of the initialisation
string :

Setting Description
M0 Silent operation
M1 Sounds during the initial stages of making a data call
M2 Sounds always when connected (not recommended for normal use but is also of use for
troubleshooting)

Page 47 of 82 057-237 ISSUE: 3


Editing the Configuration

MULTITECH ZBA GLOBAL MODEM INITIALISATION STRINGS

The factory settings for the initialisation strings are suited to the Multitech ZBA Global Modem :

SIERRA FASTRACK XTEND GSM MODEM INITIALISATION STRINGS

When connected to the Sierra Fastrack Xtend GSM modem, the initialisation strings must be altered
by changing the factory set &D3 to &D2.

Setting Description
&D2
Hang up on DTR-drop
(required for Sierra Fastrack Xtend)
&D3
Reset on DTR-drop
( factory settings)

OTHER MODEMS

When using modems not recommended by DSE first try either of the options shown above. If
problems are still encountered, you must contact your modem supplier for further advice.

2.10.2.2 CONNECTION SETTINGS

Timer Description
Master inactivity The module looks by default at the USB port for communications.
timeout When activity is detected on the RS232 or RS485 port, the module switches
to look at the relevant port for further data. If no data activity is detected on
the port for the duration of the master inactivity timer, it reverts to looking at
the USB port.
This must be set longer than the time between modbus polls from the
master.
Connect delay The amount of time that is allowed to elapse between the alarm being
registered and the controller dialling out with the fault.
Retries The number of times the module attempts to contact the remote PC by
modem.
Retry delay The amount of time between retries.
Repeat cycle delay The amount of time between cycles.

057-237 ISSUE: 3 Page 48 of 82


Editing the Configuration

2.10.2.3 MODBUS

Parameter Description
Inter-frame Delay Set the time delay between the DSE module receiving a MODBUS RTU
request and the DSE module’s response.
Parity Checking Set the Modbus string Parity

2.10.3 TROUBLESHOOTING MODEM COMMUNICATIONS

2.10.3.1 MODEM COMMUNICATION SPEED SETTING

First ensure the modem is set to communication with the DSE module at 9600 baud – Modems
supplied by DSE are factory adjusted to operate with the module. Only modems purchased from a
third party may require adjustment.

To change the modems RS232 baud rate you need a command line terminal program (Hyperterminal
by Microsoft is a good solution). Operation of this terminal program is not supported by DSE, you
must contact your terminal program supplier.

Connect the modem RS232 port to your PCs RS232 port. You may need an additional card in your
PC to provide this facility.

Use Hyperterminal (or similar) to connect to the modem at its current baud rate. You may need to
contact your modem supplier to obtain this detail. If this is not possible, use ‘trial and error’ methods.
Select a baud rate, attempt connection, press <ENTER> a few times. If the modem responds with OK>
then you are connected at the correct baud rate. Any other response (including nothing) means you
are not connected so select another baud rate.

When connected. enter the following command:

AT+IPR=9600 and press <ENTER>

This sets the modem to 9600 baud.

Close the Hyperterminal connection (do not remove power from the modem) then open a new
connection to the modem at 9600 baud.

Enter the following command:

AT&W and press <ENTER>

This saves the new setting in the modem. Power is now safe to be removed. The next time power is
applied, the modem starts with the new settings (Baud rate = 9600), suitable to communicate with the
module.

2.10.3.2 GSM MODEM CONNECTION

Most GSM modems have a Status LED. The Sierra Fastrack Xtend modem as recommended and
supplied by DSE has a RED Status LED, operating as follows.

LED STATE Description


Off Modem is not powered
On Continuous Not connected to GSM network
Flashing Slow (approx once every two
Connected to GSM network
seconds)
Flashing Fast (approx twice per second) Connected to GSM network data transmission in
progress.

Page 49 of 82 057-237 ISSUE: 3


Editing the Configuration

2.10.3.3 SERIAL PORT INSTRUMENT DISPLAY

The following section is an excerpt from the operator manual (DSE Publication 057-158) and details
the Serial Port instrument, used for monitoring operation of the module serial port.

NOTE: Factory Default settings are for the RS232 port to be enabled (no modem
connected), operating at 19200 baud, modbus slave address 10.

Example 1 – Module connected to a RS232 telephone modem.

Indicates that a modem is configured.


Shows ‘RS232’ if no modem is configured
or ‘RS485’ if the RS485 port is selected

Modem Setup Sequence

1)

If the Modem and the module communicate successfully :

2)

In case of communication failure between the modem and module, the modem is automatically reset
and initialisation is attempted once more :

3)

In the case of a module that is unable to communicate with the modem, the display continuously
cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and
attempts to communicate with it again. This continues until correct communication is established with
the modem.
In this instance, you must check connections and verify the modem operation.

Example 2 – Module connected to a modem.

057-237 ISSUE: 3 Page 50 of 82


Editing the Configuration

Example 3 – Modem status of a GSM modem

Currently connected GSM


operator and signal
strength

Example 4 - Module RS485 port configured for


connection to a modbus master.

Page 51 of 82 057-237 ISSUE: 3


Editing the Configuration

2.11 SCHEDULER
The scheduler is used to automatically start S2 on a configured day and time and run for the set
duration.
The S2 supply made to run on load or off load depending upon the configuration:

The scheduler allows for the configuration of two different banks, this offers the possibility of having
monthly scheduled events or weekly events. See overleaf for more information on Monthly and
Weekly events.

2.11.1 SCHEDULER OPTIONS

Click to enable or disable the


Scheduler.
 = Scheduled transfers are
disabled
 = Scheduled transfers are
enabled

057-237 ISSUE: 3 Page 52 of 82


Editing the Configuration

2.11.2 BANK 1

Function Description
Schedule Period Determines the repeat interval for the scheduler bank.
Weekly: Provides the ability to select certain days of the week when the
scheduler is needed

Monthly: Provides the ability to select the weeks of the month when the
scheduler is needed

In case both Monthly and Weekly scheduled run intervals are required,
two Banks are provided.
Week The option is available when the Schedule Period is configured as
Monthly.
Select the number of the week the schedule is required in each month.
Day Specify the day of week the scheduled run takes place
Transfer Mode Determines the transfer action when the scheduled event occurs.
Do Not Transfer: the existing supply remains on load and the transfer is
inhibited even when this supply fails

Off Load: the Target supply is taken forced off load. If the other supply is
available this then supplies the load

Transfer: the load is transferred to the Target supply. If the Target does
not become available, the load remains on the existing supply.
Target Choose the Target supply for the Transfer Mode action.
Start Time Determines at what time of day the scheduled run starts
Duration Determines the duration of time for the scheduled run
Clear Resets the values for the Week, Day, Start Time and Duration to defaults

Page 53 of 82 057-237 ISSUE: 3


Editing the Configuration

2.12 EXPANSION
The Expansion page is subdivided into smaller sections.
Select the required section with the mouse.

2.12.1 DSE2130 INPUT MODULES

Select the DSENet ID of the input expansion you wish to configure. The ID of the expansion input
module is set by rotary decimal switch accessible under the removable cover of the device.

Click to enable or disable


the option. The relevant
The following is then shown: values below appears
greyed out if the alarm is
disabled.

Select the alarm type of the


link lost alarm. This alarm
takes action if the expansion
module is not detected by the
host module.

Select which of the


expansion inputs you wish
to configure.

057-237 ISSUE: 3 Page 54 of 82


Editing the Configuration

2.12.1.1 DIGITAL INPUTS (A-D)

Select the required function of the


input and whether it is open or close
to activate.

Select the required alarm


type of the input and when it
is active.

Type the text that is to appear on the


module’s display when the alarm is
active.

Gives a delay upon activation of the input to


allow the input to be used as a level switch
for example.

Page 55 of 82 057-237 ISSUE: 3


Editing the Configuration

2.12.1.2 ANALOGUE INPUTS (E-H)

Configured as an Analogue Input

Edit the sensor


curve if required.

Click and drag to


change the setting.

Click to enable or disable the


option. The relevant values
below appears greyed out if
the alarm is disabled.

Type the value or click


the up and down arrows
to change the settings.

Configured as a Digital Input

Select the required function


of the input and whether it is
open or close to activate.

Select the required alarm type of


the input and when it is active.

Type the text that is to appear


on the module’s display when
Gives a delay upon activation of the alarm is active.
the input to allow the input to be
used as a liquid level switch for
example.

057-237 ISSUE: 3 Page 56 of 82


Editing the Configuration

2.12.2 DSE2157 RELAY MODULES

Select the DSENet ID of the relay expansion you wish to configure. The ID of the relay board is set by
rotary decimal switch accessible under the removable cover of the device.

The following is then shown:

Click to enable or disable the


option. The relevant values below
appears greyed out if the alarm is
disabled.

Select the alarm type of the


link lost alarm. This alarm
takes action if the expansion
module is not detected by the
host module.

Select the output source


and the polarity required.
For example this output
energises when the
module is in the Auto
mode.

Page 57 of 82 057-237 ISSUE: 3


Editing the Configuration

2.12.3 DSE2548 LED EXPANSION

Select the DSENet ID of the LED expansion you wish to configure. The ID of the Annunciator is set by
rotary decimal switch accessible on the back of the device.

The following is then shown:

Click to enable or disable the option. The relevant


values below appears greyed out if the alarm is
disabled.

Select the alarm type of the link lost


alarm. This alarm takes action if the
expansion module is not detected by
the host module.

 - If the Mute / Lamp Test


button is pressed, other
DSE2548 modules
Enable or disable the configured to Follow Main
expansion module’s internal Unit and the host module
sounder. also perform Lamp Test /
Mute their alarm and vice-
versa.
 - If the Mute / Lamp Test
button is pressed, other
DSE2548 modules and the
host module does not
respond to this.

Select the configuration


for the LED. For instance
this LED is configured to
be Unlit when in Auto
mode. Hence this is a Not
in Auto LED.

057-237 ISSUE: 3 Page 58 of 82


Editing the Configuration

2.13 ADVANCED
The Advanced page is subdivided into smaller sections.
Select the required section with the mouse.

2.13.1 PLC

The PLC Logic adds comprehensive PLC functionality to the DSE controller.
This is an advanced section, used entirely at your own risk.

2.13.1.1 PLC LOGIC

NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com

The PLC Logic adds comprehensive PLC functionality to the DSE controller.
This is an advanced section, used entirely at your own risk.
PLC Logic Conditions
PLC Logic
Actions
PLC Logic Counters and Timers configuration
Add Label, Import Rung, Search counter /
timer

In PLC logic, the ladder of logic is made up of a series of rungs.


The ladder is the complete PLC program. This program may perform a single task, or multiple tasks.
Each rung contains a number of conditions and actions.

For instance if the conditions in the rung are met, the action takes place.

Condition (example Check Action (example Start timer)


Flag)

PLC Ladder made of two rungs

Click the to A condition with a diagonal line through it


erase the entire means NOT. (example Timer has Not expired)
rung

Page 59 of 82 057-237 ISSUE: 3


Editing the Configuration

2.13.1.2 PLC FUNCTIONS

NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com

PLC Functions allow the PLC logic to create alarm conditions or drive ‘virtual inputs’ on the controller.
A PLC function is configured in the same way as a module digital input.

057-237 ISSUE: 3 Page 60 of 82


Editing the Configuration

2.13.2 CONFIGURABLE GENCOMM PAGES

For advanced Modbus users of the controller, configurable Gencomm pages are available.
The intention is to allow the user to create personal collections of data in subsequent registers to
minimise the number of modbus reads required by the master, and hence speed up data collection.

All configurable Gencomm registers are 32-bit unsigned format.

The configurable modbus pages are:

Page Hex address Decimal address


166 A600 42496
167 A700 42752
168 A800 43008
169 A900 43264

Example of Gencomm page configuration:

The register address is obtained from the formula:


register_address=page_number*256+register_offset.
To read the Plant Battery Volts from the above register, the Modbus master device needs to read the
data in two registers and then combine the data from the Most Signficant Bit and the Least Significant
Bit.
MSB address in Decimal = (166 * 256) + 2 = 42498
LSB address in Decimal = (166 * 256) + 3 = 42499

Page 61 of 82 057-237 ISSUE: 3


SCADA

3 SCADA
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool
and also as a means of monitoring and control.
As a service tool, the SCADA pages is to check the operation of the controller’s inputs and outputs as
well as checking the system parameters.
Click to connect
to the module

When connection is made…


Click to close
the connection
to the module

Module’s firmware
revision number

The SCADA page is subdivided into smaller sections.


Select the required section with the mouse.

057-237 ISSUE: 3 Page 62 of 82


SCADA

3.1 ATS IDENTITY


Shows the module’s current settings for Site Identity, ATS Identity, S1 Identity and S2 Identity.

Page 63 of 82 057-237 ISSUE: 3


SCADA

3.2 MIMIC
This screen provides a mimic of the control module and allows the operator to change the control
mode of the module.
Only the mode control and load switch buttons are operational in the mimic display. The menu
navigation buttons are inoperable.

Module status information.


This is not an exact Hint: Before
the mimic
duplicate of the module’s buttons operate, ensure
own display. you have this enabled
under TOOLS |
Click the ‘Accept ACCESS
Button’ to accept a PERMISSIONS
mode change

The load switch


buttons are also
operable (in manual
mode as with the
module’s own fascia
buttons)
Click to change
module mode Click the mode button to
change between Test on
load, Test off load & Prohibit
Return modes

057-237 ISSUE: 3 Page 64 of 82


SCADA

3.3 LANGUAGES

Current language
in the module

Select new
language

Click to send
the new
language to the
module

During language upload, the progress is


shown. Total transfer time is less than
one minute.
During this process:

• DO NOT DISCONNECT THE USB


LEAD

• DO NOT TURN OFF YOUR PC

• DO NOT DISCONNECT THE


MODULE’s DC POWER SUPPLY

3.4 DIGITAL INPUTS

Shows if the input channel is State of the input


active or not. This input is (open or closed to
open but is active. The input is battery negative
configured to be open to or positive)
activate

Page 65 of 82 057-237 ISSUE: 3


SCADA

3.5 DIGITAL OUTPUTS

Shows if the output channel is active or not. This State of the output
output is Close but is active. The output is (open or closed)
configured to be Close S1 Output de-energise.
As relay is normally closed (N/C) and the Close
S1 source is present, the output is activated to
close the N/C relay.

057-237 ISSUE: 3 Page 66 of 82


SCADA

3.6 VIRTUAL LEDS


Shows the state of the virtual LEDs. These LEDs are not fitted to the module or expansion modules,
they are not physical LEDs. They are provided show status and appear only in the SCADA section of
the configuration suite, or is read by third party PLC or Building Management Systems (for example)
using the modbus RTU protocol.

Shows if the
Virtual LED is
active or not

Shows what the Virtual LED


is configured for (shows the
LED number if not
configured)

Page 67 of 82 057-237 ISSUE: 3


SCADA

3.7 S1 & S2
The S1 and S2 pages are subdivided into smaller sections.
Select the required section with the mouse.

3.7.1 FREQUENCY, VOLTAGE AND CURRENT

Shows the modules measurements of the S1 or S2 supply.

057-237 ISSUE: 3 Page 68 of 82


SCADA

3.7.2 POWER

Shows the modules measurements of the S1 or S2 supply power.

Page 69 of 82 057-237 ISSUE: 3


SCADA

3.8 LOAD
Shows the measurement of the load current.

3.9 PLANT BATTERY


Shows the measurement of the plant battery

3.10 ALARMS
Shows any present alarm conditions.

057-237 ISSUE: 3 Page 70 of 82


SCADA

3.11 STATUS
Shows the module’s current status.

Page 71 of 82 057-237 ISSUE: 3


SCADA

3.12 EVENT LOG


Shows the contents of the module’s event log

The recorded events


in the module’s Event
log.

Click to save the log


to an Excel or csv file
for use in an external
spreadsheet program
Click to save the
log to a pdf
(Adobe Acrobat)
file

Click to print the


log

057-237 ISSUE: 3 Page 72 of 82


SCADA

3.13 MAINTENANCE
The Maintenance page is subdivided into smaller sections.
Select the required section with the mouse.

3.13.1 TIME

Display of the
module’s
current date
and time

Type the new date / time


or click the up and down
arrows to change the
settings

Click Set to adjust


Click Set to the module to the
adjust the module selected date/time.
to the date/time
that your PC is
set to.

Page 73 of 82 057-237 ISSUE: 3


SCADA

3.13.2 ACCUMULATED INSTRUMENTATION

The Accumulated Instrumentation page is subdivided into smaller sections.


Select the required section with the mouse.

3.13.2.1 S1 & S2

Display of the
module’s
current value
for the Type the new value or
parameter click the up and down
arrows to change the
settings

Click Set to
adjust the
module to the
selected value

Click to reset all


the accumulated
instrumentation
counters to zero.

057-237 ISSUE: 3 Page 74 of 82


SCADA

3.13.3 MODULE PIN

NOTE: If the PIN is lost of forgotten, it is not possible to access the module!

Allows a PIN (Personal Identification Number) to be set in the controller. This PIN must be entered to
either access the front panel configuration editor or before a configuration file is sent to the controller
from the PC software.

Enter the desired


PIN number and
reconfirm.

Page 75 of 82 057-237 ISSUE: 3


SCADA

3.14 DATA LOGGING


Allows the user to view a live feed of the module’s Data Log (if configured).

NOTE: Data logging is a ‘live’ function – Maximum 8hrs duration is shown so long as the
PC is left connected to the controller.

Navigation
sliders

Zoom
slider

The data is automatically


collated and presented in
the graphs.
For exampled Voltages
are displayed in the same
graph, but not mixed with
battery voltage

Selects the timescale of the


displayed graphs.
Scroll bars on the graphs ‘x’ axis
are also used to scroll the graph
backwards and forwards in time.

057-237 ISSUE: 3 Page 76 of 82


SCADA

3.15 PLC

NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com

Allows monitoring of the PLC functions within the controller.


Green highlighting
shows the condition is
True.

Live timer and counter


display subject to the
speed of update over
the communications
link

Flag State –
Clear means
the flag is not
set.

Page 77 of 82 057-237 ISSUE: 3


SCADA

3.16 EXPANSION
The Expansion page is subdivided into smaller sections.
Select the required section with the mouse.

3.16.1 2130 INPUT MODULE

Shows if the input channel is State of the


active or not. This input is closed input (open or
but is active. The input is closed to battery
configured to be Close To negative)
Activate

057-237 ISSUE: 3 Page 78 of 82


SCADA

3.16.2 2157 OUTPUT MODULE

Shows if the output channel is active or not.


This output is closed and not active. The
output is configured to be Open To Activate State of the
output (open or
closed)

Page 79 of 82 057-237 ISSUE: 3


SCADA

3.16.3 2548 LED MODULE

Shows if the LED is active or not.

057-237 ISSUE: 3 Page 80 of 82


This Page Intentionally Blank
This Page Intentionally Blank

You might also like