DSE335 PC Software Manual
DSE335 PC Software Manual
057-237 ISSUE: 3
DSE335 Configuration Suite PC Software Manual
E-mail: [email protected]
Website: www.deepseaelectronics.com
The DSE logo and the names DSEGenset®, DSEAts®, DSEControl® and DSEPower® are UK
registered trademarks of Deep Sea Electronics Ltd.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Ltd. reserves the right to change the contents of this document without prior
notice.
Amendments List
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper case letter I with the numeral 1. The numeral
1 has a top serif to avoid this confusion.
TABLE OF CONTENTS
1 INTRODUCTION .............................................................................................. 5
1.1 CLARIFICATION OF NOTATION ........................................................................................5
1.2 GLOSSARY OF TERMS ......................................................................................................6
1.3 BIBLIOGRAPHY ..................................................................................................................7
1.3.1 INSTALLATION INSTRUCTIONS .................................................................................7
1.3.2 MANUALS .....................................................................................................................7
1.3.3 TRAINING GUIDES ......................................................................................................8
1.3.4 THIRD PARTY DOCUMENTS ......................................................................................8
1.4 INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE ............8
2 EDITING THE CONFIGURATION ................................................................... 9
2.1 SCREEN LAYOUT ...............................................................................................................9
2.2 MODULE ........................................................................................................................... 10
2.2.1 MODULE OPTIONS ................................................................................................... 10
2.2.2 MODULE TIMERS ..................................................................................................... 11
2.2.3 EVENT LOG ............................................................................................................... 12
2.2.4 DATA LOGGING ........................................................................................................ 12
2.3 APPLICATION OPTIONS ................................................................................................. 13
2.3.1 BREAKER SCHEME A .............................................................................................. 15
2.3.1.1 S1 / S2 LOAD INHIBIT ........................................................................................ 15
2.3.1.2 S1 AND S2 LOAD INHIBIT ................................................................................. 15
2.3.1.3 TIMING DIAGRAM .............................................................................................. 15
2.3.2 BREAKER SCHEME B .............................................................................................. 16
2.3.2.1 CHECK SYNC IS DISABLED ............................................................................. 16
2.3.2.2 CHECK SYNC IS ENABLED .............................................................................. 17
2.3.3 BREAKER SCHEME C .............................................................................................. 18
2.3.3.1 CHECK SYNC & BREAKER CLOSE TRANSITION DISABLED ........................ 18
2.3.3.2 CHECK SYNC IS ENABLED .............................................................................. 19
2.4 DIGITAL INPUTS .............................................................................................................. 23
2.4.1 INPUT FUNCTIONS ................................................................................................... 24
2.5 OUTPUTS.......................................................................................................................... 27
2.5.1 DIGITAL OUTPUTS ................................................................................................... 27
2.5.2 VIRTUAL LEDS .......................................................................................................... 28
2.5.3 OUTPUT SOURCES .................................................................................................. 29
2.6 S1....................................................................................................................................... 34
2.6.1 S1 OPTIONS .............................................................................................................. 34
2.6.2 S1 TIMERS................................................................................................................. 35
2.6.3 S1 ALARMS ............................................................................................................... 36
2.7 LOAD ................................................................................................................................. 38
2.7.1 LOAD CURRENT ....................................................................................................... 38
2.7.2 LOAD TIMERS ........................................................................................................... 39
2.8 S2....................................................................................................................................... 40
2.8.1 S2 OPTIONS .............................................................................................................. 40
2.8.2 S2 TIMERS................................................................................................................. 41
2.8.3 S2 ALARMS ............................................................................................................... 42
2.9 PLANT BATTERY ............................................................................................................. 43
2.10 COMMUNICATIONS ..................................................................................................... 44
2.10.1 BASIC ......................................................................................................................... 44
2.10.1.1 SERIAL PORT CONFIGURATION ..................................................................... 45
2.10.1.2 MODEM SETTINGS ........................................................................................... 45
2.10.1.3 RECOMMENDED MODEMS .............................................................................. 46
2.10.2 ADVANCED................................................................................................................ 47
2.10.2.1 INITIALISATION STRINGS................................................................................. 47
2.10.2.2 CONNECTION SETTINGS ................................................................................. 48
2.10.2.3 MODBUS............................................................................................................. 49
2.10.3 TROUBLESHOOTING MODEM COMMUNICATIONS.............................................. 49
2.10.3.1 MODEM COMMUNICATION SPEED SETTING ................................................ 49
2.10.3.2 GSM MODEM CONNECTION ............................................................................ 49
1 INTRODUCTION
NOTE: This manual details the configuration of the DSE335 module version 4.2 and later,
part of the DSEATS® range of products. A separate document covers the configuration of
DSE335 modules with firmware version prior to version 4.2.
This document details the use of the DSE Configuration Suite PC Software with the DSE8610 MKII
module, which is part of the DSEATS® range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. DSE do not automatically inform on updates. Any future updates of
this document are included on the DSE website at www.deepseaelectronics.com
The DSE Configuration Suite PC Software allows the DSE8610 MKII module to be connected to a PC
via USB A to USB B cable (USB printer cable). Once connected, the software allows easy, controlled
access to various operating parameters within the module which can then be viewed and edited as
required.
The DSE Configuration Suite PC Software must only be used by competent, qualified personnel, as
changes to the operation of the module may have safety implications on the panel / generating set to
which it is fitted. Access to critical operational sequences and settings for use by qualified engineers,
may be barred by a security code set by the generator provider.
The information contained in this manual must be read in conjunction with the information contained
in the appropriate module documentation. This manual only details which settings are available and
how they may be used. Separate manuals deal with the operation of the individual module and its
ancillaries, refer to section entitled Bibliography elsewhere in this document for further information.
1.3 BIBLIOGRAPHY
This document refers to, and is referred by the following DSE publications which are obtained from
the DSE website: www.deepseaelectronics.com or by contacting DSE technical support:
[email protected].
Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.
1.3.2 MANUALS
Product manuals are obtained from the DSE website: www.deepseaelectronics.com or by contacting
DSE technical support: [email protected].
Training guides are provided as ‘hand-out’ sheets on specific subjects during training sessions and
contain specific information regarding to that subject.
Reference Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device
ISBN 1-55937-879-4 Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc
ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J. Mahon
ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.
Click + or – to expand
or collapse the section
Click to view /
edit the section
2.2 MODULE
The Module section allows the user to edit options related to the module itself and is subdivided into
smaller sections.
Click to view /
edit the section
Parameter Description
Lamp test at power = Lamp test at power up is disabled.
up = All module lamps illuminate when power is first applied.
Power Up in Auto = The module enters START INHIBIT mode when DC power is applied.
= The module enters AUTO mode when DC power is applied.
Transfer by buttons = Fascia load control buttons are disabled.
= Fascia load control buttons are enabled when the module is in Manual
Mode.
Support right-Left Determines the direction of text input where supported (i.e. configurable input
Languages in text)
Module Strings = Left to right language support
= Right to left language support
Enable Backlight = The LCD Backlight stays On at all times.
Power Saving Mode = DC power saving mode by turning off the LCD Backlight when the module
is not operated for the duration of the Backlight Timer.
Display Source = Source Summary Screens are not shown on the module display
Summary Screens = Additional screens for the two sources are shown the module display.
Disable Stop Mode = Pressing the Stop Button changes the operating mode to Stop mode
(therefore removing the S2 Start and Run output).
= Pressing the Stop Button does not change the operating mode to Stop
mode (the S2 Start and Run output remains active).
This allows the user to select the Stop button to enter the FPE and clear
alarms without changing the Modules Operating Mode
Parameter Description
Page Timer The amount of time before the module reverts to show the Status page when it
is left unattended
Scroll Timer The amount of time for automatic scroll between parameters on a selected
page.
Backlight Timer When the module is not operated for the duration of the Backlight Timer, the
LCD backlight turns off
The event log is configured to allow users to select which events are stored.
Parameter Description
Power Up = Power up events are not logged in the module’s event log
= Power up events are logged when the DC Supply is applied to the
module or whenever the module is rebooted
S1 Return = The S1 Return events are not logged in the module’s event log
= Logs the S1 Return events
S1 Fail = The S1 Fail events are not logged in the module’s event log
= Logs the S1 Failure events
S2 Return = The S2 Return events are not logged in the module’s event log
= Logs the S2 Return events
S2 Fail = The S2 Fail events are not logged in the module’s event log
= Logs the S2 Failure events
Electrical Trip = The Electrical Trip Alarms are not logged in the module’s event log
Alarms = Logs the Electrical Trip alarms
Latched Warnings = The Latched Warning Alarms are not logged in the module’s event log
= Logs the Latched Warning Alarms
Unlatched Warnings = The Unlatched Warning Alarms are not logged in the module’s event log
= Logs the Unlatched Warning Alarms
Breaker Auxiliary = The Breaker Auxiliary Failures are not logged in the module’s event log
Failures = Logs the Breaker Auxiliary Failures
Parameter Description
Breaker Type See overleaf for description of the Breaker Type.
Check Sync This option is only available when Scheme B is selected. See overleaf for
description of the Check Sync options
= None check sync operation
= During load transfer, the module only closes its breaker within the check
sync window. See overleaf for description of the Check Sync options.
Return to This option is only available when Check Sync is enabled. See overleaf for
programmed description of the Check Sync options
transition = Normal operation
= During load transfer if the check sync of the supplies does not occur within
two minutes, a ‘break’ or ‘open transition’ transfer occurs.
Elevator Post = Normal operation
Transfer = Any configurable output set to elevator control remains active for the
duration of the elevator delay after a load transfer has taken place.
Breaker Close This option is only available when Scheme C is selected. See overleaf for
Transition description of the Scheme C options
= Break before make operation
= During load transfer, the module only closes its breaker within the check
sync window. See overleaf for description of the Check Sync options.
Inhibit Retransfer to = When the S1 supply is reinstated after a failure, the re-transfer back to S1
S1 takes place.
= This prevents the load being transferred back to the S1 supply, even in
the event of the S2 supply failing.
Fail to Close This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
When the Close S1 or Close S2 output is activated, if the configured S1
Closed Auxiliary or S2 Closed Auxiliary digital input respectively do not
become active within the Fail To Close timer, the alarm is activated
Paralleling This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
This timer dictates how long the two supplies are closed in parallel for during
the Close Transition.
Fail to Open This option is only available when Scheme C and Breaker Close Transition are
selected. See overleaf for description of the Scheme C options
When the Close S1 or Close S2 output is de-activated, if the configured S1
Closed Auxiliary or S2 Closed Auxiliary digital input respectively do not de-
activate within the Fail To Open timer, the alarm is activated
S1 Identity Enter a text string to identify the module’s S1 source.
S1 Source Type Select the function of the module’s S1 sensing terminals:
Mains
Generator
S1 Source Priority Select the S1 priority
Available options to choose from:
Priority
Standby
S1 Phase Display Choose which phase voltage to show on the module display
S2 Identity Enter a text string to identify the module’s S2 source.
S2 Source Type Select the function of the module’s S2 sensing terminals:
Mains
Generator
S2 Source Priority Select the S2 priority
Available options to choose from:
Priority
Standby
S2 Phase Display Choose which phase voltage to show on the module display
NOTE: S1 Closed Auxiliary and S2 Closed Auxiliary inputs do not affect the operation of
the load switching in Breaker Scheme A
Activation of an input configured to S1 Load Inhibit or S2 Load Inhibit inputs cause the corresponding
breaker to be opened immediately. No other change in function occurs.
When the input is deactivated the breaker is closed again if appropriate.
If an input configured to S1 and S2 Load Inhibit is activated, outputs set to Open S1 and Open S2
energise, and inputs configured to Close S1 and Close S2 de-energise. Open S1 Pulse and Open S2
Pulse outputs only energise if the corresponding supply was on load before application of the S1 and
S2 Load Inhibit input.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.
Open S1
Close S2
Open S2
Close S1
Open S1 Pulse
Close S2 Pulse
Open S2 Pulse
Close S1 Pulse
Breaker Scheme B is intended only for use with certain designs of transfer switch. For example, rotary
transfer switches with very short changeover time.
This scheme is only suitable for breakers which require pulse signals for opening and closing.
TRANSFERRING TO S1
To open the S1 breaker the Open S1 output energises, it then de-energises when the S1 Closed
Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the ‘S1 Closed Auxiliary’ indicates the S1 breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the S2 breaker by energising the Open
S1 and Close S2 outputs simultaneously, it then de-energises these outputs when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
TRANSFERRING TO S2
To open the S2 breaker the Open S2 output energises, it then de-energises when the S2 Closed
Auxiliary indicates it has successfully opened, or after 1s whichever occurs first.
When the ‘S2 Closed Auxiliary’ indicates the S2 breaker has opened, the transfer timer begins.
When the transfer timer expires, the module attempts to close the S1 breaker by energising the Open
S2 and Close S1 outputs simultaneously, it then de-energises these outputs when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first
When the S1 and S2 Load Inhibit input is activated while S2 is closed the Open S2 output energises,
it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully opened, or
after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while S1 is closed the Open S1 output energises,
it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully opened, or
after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.
TIMING DIAGRAM
S1 has
opened S2 has closed
Open S1
Close S2
Open S2
Close S1
S1 has opened
Non-Sync Non-Sync
S2 has
Transfer Time Transfer Time closed
NOTE : The module waits indefinitely for synchronisation unless the ‘Return to
programmed transition’ function is active in which case after 2 minutes it performs a non-sync
transfer as described in the previous section.
NOTE: The transfer time is ignored during a check-sync but is used if the transfer fails
and it performs a non-sync transfer.
TRANSFER TO S2
When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S1 and Close S2 outputs simultaneously. These outputs are de-energised when the S2 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
TRANSFER TO S1
When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S2 and Close S1 outputs simultaneously. These outputs are de-energised when the S1 Closed
Auxiliary input indicates it has successfully closed, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.
TIMING DIAGRAM
In Sync
S2 has closed
Open S1
Close S2
Open S2
Close S1
In Sync
S1 has
closed
Breaker scheme C supports open transition, open transition with check-sync and closed transition
with check-sync.
S1 / S2 LOAD INHIBIT
Activation of an input configured to S1 Load Inhibit or S2 Load Inhibit inputs cause the corresponding
breaker to be opened immediately. No other change in function occurs.
When the input is deactivated the breaker is closed again if appropriate.
If an input configured to S1 and S2 Load Inhibit is activated, outputs set to Open S1 and Open S2
energise, and inputs configured to Close S1 and Close S2 de-energise. Open S1 Pulse and Open S2
Pulse outputs only energise if the corresponding supply was on load before application of the S1 and
S2 Load Inhibit input.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.
TIMING DIAGRAM
Open S1
Close S2
Open S2
Close S1
Open S1 Pulse
Close S2 Pulse
Open S2 Pulse
Close S1 Pulse
NOTE : The module waits indefinitely for synchronisation unless the ‘Return to
programmed transition’ function is active in which case after 2 minutes it performs a non-sync
transfer as described in the previous section.
NOTE: The transfer time is ignored during a check-sync but is used if the transfer fails
and it performs a non-sync transfer.
TRANSFER TO S2
When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S1 and Close S2 outputs simultaneously. The Close S2 Output Pulse is de-energised when the
S2 Closed Auxiliary input indicates the source has successfully closed, or after 1s whichever occurs
first.
TRANSFER TO S1
When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window the module energises the
Open S2 and Close S1 outputs simultaneously. The Close S1 Output Pulse is de-energised when the
S1 Closed Auxiliary input indicates the source has successfully closed, or after 1s whichever occurs
first.
When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is deactivated the load is returned to the supply that was
disconnected, providing that supply is healthy.
TIMING DIAGRAM
Open S1
Close S2
Open S2
Close S1
Open S1 Pulse
Close S2 Pulse
Open S2 Pulse
Close S1 Pulse
NOTE: When Breaker Close Transition is enabled, the module performs a sync transfer
without the need for enabling the Check Sync feature.
TRANSFER TO S2
When the module is about to transfer from S1 to S2 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window, the module energises the
Close S2 output and checks for the S2 Closed Auxiliary input activating. If the S2 Closed Auxiliary
activates within the Fail to Close time, the Paralleling timer begins. If the S2 Closed Auxiliary does not
activate within the Fail to Close time, the Open S2 output is activated and the S2 Fail to Close alarm
activates.
At the end of the Paralleling timer, the module de-energises the Close S1 output and checks for the
S1 Closed Auxiliary input de-activating. If the S1 Closed Auxiliary does not de-activate within the Fail
to Open time, the Open S1 and Open S2 outputs are activated and the S1 Fail to Open alarm
activates.
TRANSFER TO S1
When the module is about to transfer from S2 to S1 it activates the check sync function.
When the S1 and S2 supplies are within the phase and frequency window, the module energises the
Close S1 output and checks for the S1 Closed Auxiliary input activating. If the S1 Closed Auxiliary
activates within the Fail to Close time, the Paralleling timer begins. If the S1 Closed Auxiliary does not
activate within the Fail to Close time, the Open S1 output is activated and the S1 Fail to Close alarm
activates.
At the end of the Paralleling timer, the module de-energises the Close S2 output and checks for the
S2 Closed Auxiliary input de-activating. If the S2 Closed Auxiliary does not de-activate within the Fail
to Open time, the Open S1 and Open S2 outputs are activated and the S2 Fail to Open alarm
activates.
When the S1 and S2 Load Inhibit input is activated while the S2 is closed the Open S2 output
energises, it then de-energises when the S2 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is activated while the S1 is closed the Open S1 output
energises, it then de-energises when the S1 Closed Auxiliary input indicates that it has successfully
opened, or after 1s whichever occurs first.
When the S1 and S2 Load Inhibit input is de-energised the load is returned to the supply that was
disconnected, providing that supply is healthy.
TIMING DIAGRAM
Close S1
Close S1 Pulse
Open S1
Open S1 Pulse
S1 Closed
Auxiliary
Close S2
Close S2 Pulse
Open S2
Open S2 Pulse
S2 Closed
Auxiliary
S2 Fail to S2 Fail to
Close Timer Open Timer
NOTE: The module’s digital inputs are configured as either negative or positive switching
in groups of three, this is determined in the modules configuration.
Close or Open To
Activate
Under the scope of IEEE 37.2, function numbers are also used to represent functions in
microprocessor devices and software programs. Where the DSE input functions are represented by
IEEE 37.2, the function number is listed below.
Function Description
Not used The input is disabled
Alarm Mute This input is used to silence the audible alarm from an external source,
such as a remote mute switch.
Alarm Reset This input is used to reset any latched alarms from a remote location. It is
also used to clear any latched warnings which may have occurred (if
configured) without having to stop/unload S2.
Auto Restore Inhibit In the event of a remote start/S1 failure, S2 is instructed to start and take
IEEE 37.2 - 3 Checking Or load. On removal of the remote start signal/S1 return the module continues
Interlocking Relay to run S2 on load until the Auto Restore Inhibit input is removed. This input
allows the controller to be fitted as part of a system where the restoration
to S1 is controlled remotely or by an automated system.
Auto start Inhibit This input is used to provide an over-ride function to prevent the controller
IEEE 37.2 - 3 Checking Or from starting S2 in the event of a remote start/S1 out of limits condition
Interlocking Relay occurring. If this input is active and a remote start signal/S1 failure occurs
the module does not give a start command to the S2. If this input signal is
then removed, the controller operates as if a remote start/S1 failure has
occurred, starting and loading S2. This function is used to give an ‘AND’
function so that S2 is only called to start if S1 fails and another condition
exists which requires S2 to run. If the ‘Auto start Inhibit’ signal becomes
active once more it is ignored until the module has returned the S1 supply
on load and shutdown.
This input does not prevent starting of the engine in MANUAL or TEST
modes.
Auxiliary S1 Fail The module monitors the incoming single or three phase supply for Over
voltage, Under Voltage, Over Frequency or Under frequency. It may be
required to monitor a different S1 supply or some aspect of the incoming
S1 not monitored by the controller. If the devices providing this additional
monitoring are connected to operate this input, the controller operates as if
the incoming S1 supply has fallen outside of limits, S2 is instructed to start
and take the load. Removal of the input signal causes the module to act if
S1 has returned to within limits providing that the S1 sensing also indicates
that the S1 is within limits.
Auxiliary S1 Ready Allows an external device (such as the engine control module) to instruct
the controller that S1 is healthy and available to take load. The controller
then monitors the voltage and frequency to check they are within
acceptable limits before performing the load transfer function.
Auxiliary S2 Fail The module monitors the incoming single or three phase supply for Over
voltage, Under Voltage, Over Frequency or Under frequency. It may be
required to monitor a different S2 supply or some aspect of the incoming
S2 not monitored by the controller. If the devices providing this additional
monitoring are connected to operate this input, the controller operates as if
the incoming S2 supply has fallen outside of limits, S1 is instructed to start
and take the load. Removal of the input signal causes the module to act if
S2 has returned to within limits providing that the S2 sensing also indicates
that the S2 is within limits.
Parameter descriptions are continued overleaf…
Function Description
Auxiliary S2 Ready Allows an external device (such as the engine control module) to instruct
the controller that S1 is healthy and available to take load. The controller
then monitors the voltage and frequency to check they are within
acceptable limits before performing the load transfer function.
External Panel Lock This input is used to provide security to the installation. If the External
Panel lock input is active, the module does not respond to operation of the
Mode select or start buttons. This allows the module to be placed into a
specific mode (such as Auto) and then secured. The operation of the
module is not affected and the operator is still able to view the various
instrumentation pages etc. (Front panel configuration access is still
possible while the system lock is active).
Force Transfer To S1 Activating this input causes the module to open S2 and transfer the load to
S1 disregarding the status of S1.
When S1 is not available, the load remains off until the supply is back
within limits.
Force Transfer To S2 Activating this input causes the module to open S1 and transfer the load to
S2 disregarding the status of S2.
When S2 is not available, the load remains off until the supply is back
within limits.
Inhibit Scheduled Run This input is used to provide a means of disabling a scheduled run.
IEEE 37.2 - 3 Checking Or
Interlocking Relay
Lamp Test This input is used to provide a test facility for the front panel indicators
fitted to the module. When the input is activated all LED’s illuminate.
Open / Close S1 Allows connection of an external signal to control open and closing of the
IEEE 37.2 - 52 AC Circuit S1 load switch device.
Breaker
Open / Close S2 Allows connection of an external signal to control open and closing of the
IEEE 37.2 - 52 AC S2 load switch device.
Circuit Breaker
Remote Start off load If this input is active, operation is similar to the ‘Remote Start on load’
function except that S2 is not instructed to take the load. This function is
used where an engine only run is required e.g. for exercise.
Remote Start on load When in auto mode, the module performs the start sequence and transfers
load to S2.
In Manual mode, the load is transferred to S2 if the supply is already
healthy, however in manual mode, this input does not generate start/stop
requests of S2.
Reset Breaker Alarms This input is used to reset any of the Fail to Open or Fail to Close alarms
when using Breaker Scheme C without pressing the Stop Button.
S1 and S2 Load Inhibit This input is used to prevent the module from loading the S1 and S2
IEEE 37.2 - 3 Checking Or supplies. If the S1 or S2 supply is already on load activating this input
Interlocking Relay causes the module to unload that supply. Removing the input allows the
supply to be loaded again.
Function Description
S1 Closed Auxiliary This input is used to provide feedback to allow the controller to give true
IEEE 37.2 - 3 Checking Or indication of the contactor or circuit breaker switching status. It must be
Interlocking Relay connected to the S1 load switching device auxiliary contact.
(Breaker Scheme B)
In ‘Breaker Scheme A’, Incorrect application of this signal does not trigger
an alarm condition, it is used solely for indication of the breaker status.
2.5 OUTPUTS
The Outputs section is subdivided into smaller sections.
Select the required section with the mouse
Select what
the output is
to be used to
control
The list of output sources available for configuration of the module outputs is listed in the section
entitled Output Sources.
The list of output sources available for configuration of the module outputs is listed in the section
entitled Output Sources.
The list of output sources available for configuration of the module relay outputs also applies to the
LED configuration and expansion relay outputs.
Under the scope of IEEE 37.2, function numbers are also used to represent functions in microprocessor devices
and software programs. Where the DSE output functions are represented by IEEE 37.2, the function number is
listed below.
2.6 S1
The S1 section is subdivided into smaller sections. Select the required section with the mouse.
2.6.1 S1 OPTIONS
Parameter Description
Open When
S2 Available NOTE: Active when S1 source is set to Standby. For further details see
section entitled Application Options elsewhere in this document
Parameter Description
VT Fitted = The voltage sensing to the controller is direct from the alternator
= The voltage sensing to the controller is via Voltage Transformers (VTs or PTs)
This is used to step down the generated voltage to be within the controller voltage
specification.
By entering the Primary and Secondary voltages of the transformer, the controller
displays the Primary voltage rather than the actual measured voltage.
This is typically used to interface the DSE module to high voltage systems (ie 11kV)
but also used on systems such as 600V ph-ph.
2.6.2 S1 TIMERS
Timer Description
Start Delay Used to give a delay before starting in AUTO mode. This timer is activated
upon the respective start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start
signals or short term S2 failures.
Return Delay A delay, used in auto mode only, that allows for short term removal of the
request to unload the supply before action is taken. This is usually used to
ensure the supply remains on load before accepting that the start request has
been removed.
Transient Delay Used to delay the detection of S1 failure. This is normally used to prevent
short term transients or brownout conditions from being classified as a S1
Failure and opening the breaker.
2.6.3 S1 ALARMS
Alarm Description
Under Voltage = S1 Under Voltage detection is disabled
IEEE 37.2 – 27 AC = S1 Under Voltage gives an alarm in the event of the mains voltage
Undervoltage Relay falling below the configured Under Voltage Trip value. The Under Voltage
Trip value is adjustable to suit the application. The alarm is reset and the
S1 is considered within limits when the S1 voltage rises above the
configured Under Voltage Return level.
Over Voltage = S1 Over Voltage detection is disabled
IEEE 37.2 – 59 AC = S1 Over Voltage gives an alarm in the event of the S1 voltage rising
Overvoltage Relay above the configured Over Voltage Trip value. The Over Voltage Trip
value is adjustable to suit the application. The alarm is reset and the S1 is
considered within limits when the S1 voltage falls below the configured
Over Voltage Return level.
Under Frequency = S1 Under Frequency detection is disabled
IEEE 37.2 – 81 Frequency = S1 Under Frequency gives an alarm in the event of the S1 frequency
Relay falling below the configured Under Frequency Trip value. The Under
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S1 is considered within limits when the S1 frequency rises
above the configured Under Frequency Return level.
Over Frequency = S1 Over Frequency detection is disabled
IEEE 37.2 – 81 Frequency = S1 Over Frequency gives an alarm in the event of the S1 frequency
Relay rising above the configured Over Frequency Trip value. The Over
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S1 is considered within limits when the S1 frequency falls
below the configured Over Frequency Return level.
Alarm Description
Phase Rotation = The phase rotation is not checked
Detection = An Electrical Trip alarm is generated when the phase rotation of S1
IEEE 37.2 – 47 Phase supply is not matching the configurerd Phase Rotation setting.
Sequence Relay
2.7 LOAD
The Load section is subdivided into smaller sections. Select the required section with the mouse.
Timer Description
CT Primary Primary rating of the Current Transformers
CT Secondary Secondary rating of the Current Transformers
Full Load Rating Full load rating (100% rating) of the load current
Max kW Rating Full load rating (100% rating) of the load kW
Click to enable or
disable the option.
The relevant values
below appears
greyed out if the
alarm is disabled.
Setting Description
Enable Provides control of configurable outputs set to Load Shedding Control.
= Load Shedding Control is disabled.
= The module monitors the load and control any outputs configured to
Load Shedding Control (1-5)
Outputs in Scheme The number of outputs (max 5) that is included in the function.
Outputs at Start The number of outputs configured to Load Shedding Control 1-5 that is
energised when the set is required to take load. The Transfer Delay / Load
Delay timer begins. At the end of this timer, the load switch is closed – S2 is
placed on load.
Trip / Trip Delay When the load level is above the Trip setting for the duration of the Trip
Delay, then the ‘next’ output configured to Load Shedding Control is activated
(max 5)
Return / Return Delay When the load level is below the Return setting for the duration of the Return
Delay, then the ‘highest numbered’ output configured to Load Shedding
Control is de-activated and the timer is reset.
Transfer Time / Load The time between closing the Load Shedding Control outputs (Outputs at
Delay Start) and closing the load switching device.
Timer Description
Non-sync Transfer The time between one supply’s load switch being opened and the other
Time supply’s load switch being closed. Used to give time for the load switches to
move to their correct positions and to prevent the mechanical interlock from
“jamming”.
This timer is also used to give a ‘dead time’ to ensure that any machinery
stops fully after removal of the supply, before applying the new supply to the
equipment (for instance directly driven AC motors).
Check-Sync Transfer The time allowed for the Sync Transfer to be completed. If the two supplies
Time do not come in sync during this time, the module reverts to perform a Non-
Sync Transfer.
Breaker close pulse The amount of time that Breaker Close Pulse signals are present when the
request to close a breaker is given.
Breaker Trip pulse The amount of time that Breaker Open Pulse signals are present when the
request to open a breaker is given.
Elevator Delay Use to delay the Elevator Control output before and after load transfer takes
place. See section entitled Application for details of Elevator Control.
2.8 S2
The S2 section is subdivided into smaller sections. Select the required section with the mouse.
2.8.1 S2 OPTIONS
Parameter Description
Open When
S1 Available NOTE: Tick box shown for read only purpose. To configure the tick box
see section entitled S1 Options elsewhere in this document.
NOTE: Active when S2 source is set to Standby. For further details see
section entitled Application Options elsewhere in this document
= The S2 breaker can be requested to open regardless if S1 is available. This is
useful when using DC controlled opening signals.
= The S2 breaker is only requested to open when S1 is available. This is required
when S2’s breaker’s opening signals are supplied by S1’s supply.
Immediate S2
Dropout NOTE: This feature is not enabled when Open When S1 Available is
enabled or when S2 is set to Standby. For further details see
section entitled Application Options elsewhere in this document.
= Upon S2 failure, the S2 Breaker remains closed until a transfer to S1 is
initiated.
= Upon S2 failure, the S2 Breaker opens immediately.
AC System This defines the topology of the alternator/source and the connections to the DSE
module sensing terminals.
Parameter Description
VT Fitted = The voltage sensing to the controller is direct from the alternator
= The voltage sensing to the controller is via Voltage Transformers (VTs or PTs)
This is used to step down the generated voltage to be within the controller voltage
specification.
By entering the Primary and Secondary voltages of the transformer, the controller
displays the Primary voltage rather than the actual measured voltage.
This is typically used to interface the DSE module to high voltage systems (ie 11kV)
but also used on systems such as 600V ph-ph.
2.8.2 S2 TIMERS
Timer Description
Start Delay Used to give a delay before starting in AUTO mode. This timer is activated
upon the respective start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start
signals or short term S2 failures.
Return Delay A delay, used in auto mode only, that allows for short term removal of the
request to unload the supply before action is taken. This is usually used to
ensure the supply remains on load before accepting that the start request has
been removed.
Transient Delay Used to delay the detection of S1 failure. This is normally used to prevent
short term transients or brownout conditions from being classified as a S1
Failure and opening the breaker.
Warming Up Time The amount of time that the set runs BEFORE being allowed to take load.
This is used to warm the engine to prevent excessive wear.
Fail Delay The module instructs that S2 is to start and waits for the period of this timer
for S2 to become available. If it is not available when the timer expires, the
S2 failure alarm is triggered.
Cooling time The amount of time that the set runs OFF LOAD before being stopped. This
is to allow the set to cool down and is particularly important for engines with
turbo chargers.
Fail to Stop Delay = Alarm is disabled
= If the supply is called to stop and is still running after the configurable
Fail to Stop delay time expires, a Fail to Stop alarm is generated.
2.8.3 S2 ALARMS
Alarm Description
Under Voltage = S2 Under Voltage detection is disabled
IEEE 37.2 – 27 AC = S2 Under Voltage gives an alarm in the event of the mains voltage
Undervoltage Relay falling below the configured Under Voltage Trip value. The Under Voltage
Trip value is adjustable to suit the application. The alarm is reset and the
S2 is considered within limits when the S2 voltage rises above the
configured Under Voltage Return level.
Over Voltage = S2 Over Voltage detection is disabled
IEEE 37.2 – 59 AC = S2 Over Voltage gives an alarm in the event of the S2 voltage rising
Overvoltage Relay above the configured Over Voltage Trip value. The Over Voltage Trip
value is adjustable to suit the application. The alarm is reset and the S2 is
considered within limits when the S2 voltage falls below the configured
Over Voltage Return level.
Under Frequency = S2 Under Frequency detection is disabled
IEEE 37.2 – 81 Frequency = S2 Under Frequency gives an alarm in the event of the S2 frequency
Relay falling below the configured Under Frequency Trip value. The Under
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S2 is considered within limits when the S2 frequency rises
above the configured Under Frequency Return level.
Over Frequency = S2 Over Frequency detection is disabled
IEEE 37.2 – 81 Frequency = S2 Over Frequency gives an alarm in the event of the S2 frequency
Relay rising above the configured Over Frequency Trip value. The Over
Frequency Trip value is adjustable to suit the application. The alarm is
reset and the S2 is considered within limits when the S2 frequency falls
below the configured Over Frequency Return level.
Phase Rotation = The phase rotation is not checked
Detection = An Electrical Trip alarm is generated when the phase rotation of S2
IEEE 37.2 – 47 Phase supply is not matching the configured Phase Rotation setting.
Sequence Relay
Parameter Description
Plant Battery Undervolts The alarm activates when the battery voltage drops below the configured Pre-
IEEE 37.2 -27 DC Alarm level for the configured Delay time. When the battery voltage rises above the
Undervoltage Relay configured Return level, the alarm is de-activated.
Plant Battery Overvolts The alarm activates when the battery voltage rises above the configured Pre-
IEEE 37.2 -59 DC Alarm level for the configured Delay time. When the battery voltage drops below
Overvoltage Relay the configured Return level, the alarm is de-activated.
2.10 COMMUNICATIONS
The module includes an RS232 port for connection to a modem and an RS485 ports for connection to
another device. The protocol used is Modbus RTU.
2.10.1 BASIC
Modbus Slave
ID
Baud rate adjustable
from 1200-115200
Timer Description
Port usage Only one of the two serial ports is used at any one time (RS232 or RS485)
The options are :
No Modem – RS232 ports is used for direct RS232 connection to PLC, BMS
etc
Incoming modem calls – RS232 port connected to modem, used to accept
incoming calls only.
Incoming and outgoing modem (Sequence) – RS232 port connected to
modem used to accept incoming calls and also make calls upon shutdown
alarms.
Outgoing modem alarms (Sequence) - RS232 port connected to modem,
used to make calls upon shutdown alarms.
Incoming and outgoing modem (Cyclic) – RS232 port connected to
modem used to accept incoming calls and also make calls upon shutdown
alarms.
Outgoing modem alarms (Cyclic) - RS232 port connected to modem, used
to make calls upon shutdown alarms.
RS485 – The RS485 port is active. This is often used to connect to PLC’s,
building management systems and other third party equipment.
Timer Description
Alarm Number The phone number that the module dials upon an alarm condition. This
number must be connected to a PC modem on a PC running the
Configuration Suite Software.
GSM Modem = The connected modem is a fixed line telephone modem
= The connected modem is a GSM (cellular) modem. The GSM signal
strength meter and GSM operator are shown on the module display.
SMS Message The Message centre used to send SMS messages. This number is usually
Centre Modem stored on the SIM card and need not be entered here.
A number is only needed here if it is not stored on the SIM card.
SMS Recipient Numbers of the cell phones to send SMS messages to.
Numbers Leave blank if SMS function is not required.
GSM MODEM
DSE do not stock or supply SIM cards for the modem, these must be obtained from your local GSM
provider.
DSE Part
Description
Number
0830-001-01
NOTE: This modem is supplied ready configured to operate with the
DSE module. When purchasing from a third party, the modem is not
configured to communicate with the module.
Sierra Fastrack Xtend GSM Modem supplied with power supply cable, RS232
connection cable and GSM antenna. Suitable for GSM operating on 900/1800
MHz bands.
2.10.2 ADVANCED
Modem initialisation
strings. These set up the
modem to perform the
functions required.
The initialisation strings are commands that are sent to the modem upon powering up the DSE
module and additionally at regular intervals subsequently, whenever the module initialises (resets) the
modem.
Setting Description
E0 Echo off
S7=60 Wait for carrier time 60s
S0=0 (not auto answer) Do not answer
S0=2 (auto answer) Answer after two rings
&S0 DSR always on
&C1 DCD is active if modem is online
&D3 Reset (ATZ) on DTR-drop
H0 Hang up (disconnect)
SILENT OPERATION
The modem connected to the module usually makes dialling noises and ‘squeal’ in the initial stages of
making a data call. To control this noise, add the following command to the end of the initialisation
string :
Setting Description
M0 Silent operation
M1 Sounds during the initial stages of making a data call
M2 Sounds always when connected (not recommended for normal use but is also of use for
troubleshooting)
The factory settings for the initialisation strings are suited to the Multitech ZBA Global Modem :
When connected to the Sierra Fastrack Xtend GSM modem, the initialisation strings must be altered
by changing the factory set &D3 to &D2.
Setting Description
&D2
Hang up on DTR-drop
(required for Sierra Fastrack Xtend)
&D3
Reset on DTR-drop
( factory settings)
OTHER MODEMS
When using modems not recommended by DSE first try either of the options shown above. If
problems are still encountered, you must contact your modem supplier for further advice.
Timer Description
Master inactivity The module looks by default at the USB port for communications.
timeout When activity is detected on the RS232 or RS485 port, the module switches
to look at the relevant port for further data. If no data activity is detected on
the port for the duration of the master inactivity timer, it reverts to looking at
the USB port.
This must be set longer than the time between modbus polls from the
master.
Connect delay The amount of time that is allowed to elapse between the alarm being
registered and the controller dialling out with the fault.
Retries The number of times the module attempts to contact the remote PC by
modem.
Retry delay The amount of time between retries.
Repeat cycle delay The amount of time between cycles.
2.10.2.3 MODBUS
Parameter Description
Inter-frame Delay Set the time delay between the DSE module receiving a MODBUS RTU
request and the DSE module’s response.
Parity Checking Set the Modbus string Parity
First ensure the modem is set to communication with the DSE module at 9600 baud – Modems
supplied by DSE are factory adjusted to operate with the module. Only modems purchased from a
third party may require adjustment.
To change the modems RS232 baud rate you need a command line terminal program (Hyperterminal
by Microsoft is a good solution). Operation of this terminal program is not supported by DSE, you
must contact your terminal program supplier.
Connect the modem RS232 port to your PCs RS232 port. You may need an additional card in your
PC to provide this facility.
Use Hyperterminal (or similar) to connect to the modem at its current baud rate. You may need to
contact your modem supplier to obtain this detail. If this is not possible, use ‘trial and error’ methods.
Select a baud rate, attempt connection, press <ENTER> a few times. If the modem responds with OK>
then you are connected at the correct baud rate. Any other response (including nothing) means you
are not connected so select another baud rate.
Close the Hyperterminal connection (do not remove power from the modem) then open a new
connection to the modem at 9600 baud.
This saves the new setting in the modem. Power is now safe to be removed. The next time power is
applied, the modem starts with the new settings (Baud rate = 9600), suitable to communicate with the
module.
Most GSM modems have a Status LED. The Sierra Fastrack Xtend modem as recommended and
supplied by DSE has a RED Status LED, operating as follows.
The following section is an excerpt from the operator manual (DSE Publication 057-158) and details
the Serial Port instrument, used for monitoring operation of the module serial port.
NOTE: Factory Default settings are for the RS232 port to be enabled (no modem
connected), operating at 19200 baud, modbus slave address 10.
1)
2)
In case of communication failure between the modem and module, the modem is automatically reset
and initialisation is attempted once more :
3)
In the case of a module that is unable to communicate with the modem, the display continuously
cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and
attempts to communicate with it again. This continues until correct communication is established with
the modem.
In this instance, you must check connections and verify the modem operation.
2.11 SCHEDULER
The scheduler is used to automatically start S2 on a configured day and time and run for the set
duration.
The S2 supply made to run on load or off load depending upon the configuration:
The scheduler allows for the configuration of two different banks, this offers the possibility of having
monthly scheduled events or weekly events. See overleaf for more information on Monthly and
Weekly events.
2.11.2 BANK 1
Function Description
Schedule Period Determines the repeat interval for the scheduler bank.
Weekly: Provides the ability to select certain days of the week when the
scheduler is needed
Monthly: Provides the ability to select the weeks of the month when the
scheduler is needed
In case both Monthly and Weekly scheduled run intervals are required,
two Banks are provided.
Week The option is available when the Schedule Period is configured as
Monthly.
Select the number of the week the schedule is required in each month.
Day Specify the day of week the scheduled run takes place
Transfer Mode Determines the transfer action when the scheduled event occurs.
Do Not Transfer: the existing supply remains on load and the transfer is
inhibited even when this supply fails
Off Load: the Target supply is taken forced off load. If the other supply is
available this then supplies the load
Transfer: the load is transferred to the Target supply. If the Target does
not become available, the load remains on the existing supply.
Target Choose the Target supply for the Transfer Mode action.
Start Time Determines at what time of day the scheduled run starts
Duration Determines the duration of time for the scheduled run
Clear Resets the values for the Week, Day, Start Time and Duration to defaults
2.12 EXPANSION
The Expansion page is subdivided into smaller sections.
Select the required section with the mouse.
Select the DSENet ID of the input expansion you wish to configure. The ID of the expansion input
module is set by rotary decimal switch accessible under the removable cover of the device.
Select the DSENet ID of the relay expansion you wish to configure. The ID of the relay board is set by
rotary decimal switch accessible under the removable cover of the device.
Select the DSENet ID of the LED expansion you wish to configure. The ID of the Annunciator is set by
rotary decimal switch accessible on the back of the device.
2.13 ADVANCED
The Advanced page is subdivided into smaller sections.
Select the required section with the mouse.
2.13.1 PLC
The PLC Logic adds comprehensive PLC functionality to the DSE controller.
This is an advanced section, used entirely at your own risk.
NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com
The PLC Logic adds comprehensive PLC functionality to the DSE controller.
This is an advanced section, used entirely at your own risk.
PLC Logic Conditions
PLC Logic
Actions
PLC Logic Counters and Timers configuration
Add Label, Import Rung, Search counter /
timer
For instance if the conditions in the rung are met, the action takes place.
NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com
PLC Functions allow the PLC logic to create alarm conditions or drive ‘virtual inputs’ on the controller.
A PLC function is configured in the same way as a module digital input.
For advanced Modbus users of the controller, configurable Gencomm pages are available.
The intention is to allow the user to create personal collections of data in subsequent registers to
minimise the number of modbus reads required by the master, and hence speed up data collection.
3 SCADA
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool
and also as a means of monitoring and control.
As a service tool, the SCADA pages is to check the operation of the controller’s inputs and outputs as
well as checking the system parameters.
Click to connect
to the module
Module’s firmware
revision number
3.2 MIMIC
This screen provides a mimic of the control module and allows the operator to change the control
mode of the module.
Only the mode control and load switch buttons are operational in the mimic display. The menu
navigation buttons are inoperable.
3.3 LANGUAGES
Current language
in the module
Select new
language
Click to send
the new
language to the
module
Shows if the output channel is active or not. This State of the output
output is Close but is active. The output is (open or closed)
configured to be Close S1 Output de-energise.
As relay is normally closed (N/C) and the Close
S1 source is present, the output is activated to
close the N/C relay.
Shows if the
Virtual LED is
active or not
3.7 S1 & S2
The S1 and S2 pages are subdivided into smaller sections.
Select the required section with the mouse.
3.7.2 POWER
3.8 LOAD
Shows the measurement of the load current.
3.10 ALARMS
Shows any present alarm conditions.
3.11 STATUS
Shows the module’s current status.
3.13 MAINTENANCE
The Maintenance page is subdivided into smaller sections.
Select the required section with the mouse.
3.13.1 TIME
Display of the
module’s
current date
and time
3.13.2.1 S1 & S2
Display of the
module’s
current value
for the Type the new value or
parameter click the up and down
arrows to change the
settings
Click Set to
adjust the
module to the
selected value
NOTE: If the PIN is lost of forgotten, it is not possible to access the module!
Allows a PIN (Personal Identification Number) to be set in the controller. This PIN must be entered to
either access the front panel configuration editor or before a configuration file is sent to the controller
from the PC software.
NOTE: Data logging is a ‘live’ function – Maximum 8hrs duration is shown so long as the
PC is left connected to the controller.
Navigation
sliders
Zoom
slider
3.15 PLC
NOTE: For further details and instructions on PLC Logic and PLC Functions, refer to DSE
Publication: 057-175 PLC Programming Guide which is found on our website:
www.deepseaplc.com
Flag State –
Clear means
the flag is not
set.
3.16 EXPANSION
The Expansion page is subdivided into smaller sections.
Select the required section with the mouse.