5100333-00 - Salwico Cruise - Installation Manual - M - EN - 2018 - X
5100333-00 - Salwico Cruise - Installation Manual - M - EN - 2018 - X
1 Introduction....................................................................................... 1
1.1 About this Manual ............................................................................ 1
1.2 Symbols used in the manual ............................................................. 2
1.3 Approvals........................................................................................... 3
3 Installation ........................................................................................ 9
3.1 Prerequisites for Installation ............................................................ 9
3.2 Mechanical Installation.................................................................... 9
3.2.1 Recommended installation order .................................................... 9
3.2.2 Control Panels................................................................................. 9
3.2.3 Loop Units ...................................................................................... 10
3.2.4 Mounting of Modules on a DIN rail ............................................... 10
4 Verification ........................................................................................ 21
4.1 Prerequisites for Verification............................................................ 21
4.2 Loops.................................................................................................. 21
4.2.1 Verification of Loops ...................................................................... 21
4.2.2 Testing of System Parts................................................................... 23
5 Commissioning Requirements.......................................................... 33
5.1 Prerequisite........................................................................................ 33
5.2 Loop Requirements ........................................................................... 33
5.3 Part A: Loop Configuration ............................................................. 33
5.4 Part B: Loop Status........................................................................... 33
5.5 Part C: Central Status....................................................................... 34
7 System Upgrade................................................................................. 49
7.1 Upgrade BIOS ................................................................................... 49
7.1.1 Upgrade BIOS for a CCP System from USB Stick ........................ 49
7.1.2 Upgrade BIOS in a Control Module via Ethernet (Control M X
without USB port)........................................................................... 50
10 Appendix - ID List............................................................................. 69
10.1 ID List................................................................................................ 69
10.1.1 Prerequisite ..................................................................................... 69
10.1.2 Setting the ID .................................................................................. 69
10.1.3 ID for NS-AIN type Address Units ................................................ 69
10.1.4 ID for AE/IC type Address Units.................................................... 70
1 Introduction
NOTE!
This manual has been revised based on system version 1.10.10.
Chapter Verification describes how to test the installed system. After the
installation is completed, the system is verified, which must be performed by a
person with good knowledge of the various functions. This chapter also includes
verification and troubleshooting.
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint!
Hint symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
1.3 Approvals
2 General Description
The Fire detection system is built on a scalable platform. A Single Central System
contains up to 126 Modules and a Multi Central System up to 30 Centrals.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
NOTE!
A warning will be displayed on the menu screen as long as the system is not running
Cause/Effect, which is the two first minutes after the system has been powered up
Hint!
For detailed requirements regarding system modules and loop units, refer to the data
sheets.
3 Installation
CAUTION!
It is highly important to eliminate or reduce any high external electromagnetic
interference which can have a negative effect on the loop communication.
Make sure that cabling is carried out according to local rules and regulations.
CAUTION!
All cables used during installation of the fire detection system shall be fire resistant.
CAUTION!
Always use use halogen free cables for loop lines and connections to external
systems.
The different parts of the system, the control and system modules, should first be
mechanically installed. The different loop units are thereafter electrically installed
and set up according to the definition of the loops and drawings.
The cables must be tested separately before the loops are connected to the loop
module. This eliminates any problem with the cable and electrical installation of
the loop units.
CAUTION!
Do not remove the protective cover from the detector until all paint work and
polluting (dusty) activities are finished and the area has been cleaned.
After installation: Be sure to remove all covers before the fire detection system is put
into operation.
The external control panels are delivered in cabinets for wall or console mounting.
Separate drawings are delivered with the system. Install the panels indoors in areas
The mechanical installation of the different types of loop and zone units are
described in their respective data sheets.
Channel 1 & 2
• Min 2 x 2 x 0.3 mm2, twisted pair shielded
(RS-485 + backup signal, one conductor)
NOTE!
The backup signal is only needed for one channel.
NOTE!
Channel 1 and Channel 2 should be routed separately for improved safety.
Detector loops
CAUTION!
It is strongly recommended to use halogen free cables for loop lines and connections
to external systems.
This is the minimum cable diameter that the fire detection system can handle.
International rules and regulations must be followed with regard to cable diameter.
• cable type
• shielded or unshielded cable
• power consumption
A cable is considered shielded if the shielded part is more than 10% of the cable's
total length.
CAUTION!
Never exceed the recommended cable lengths as listed in table Table 2 Loop cable
lengths.
Loop units are divided into three types. These types (1, 2 and 3) are based on the
individual load on the loop.
• FP10
• IC21
• IC44 with external 24 VDC
• MCP-A
• SCI-A
* For older products please see revision 2013_J (or earlier versions) of this manual.
** Using min. a 0.75 mm2 cable, otherwise max. 2000 m.
*** Using min. a 0.75 mm2 cable, otherwise max. 1000 m.
NOTE!
When calculating the number of loop units, consider the future expansion of new
loop units. Make sure there are at least 10% in spare addresses evenly distributed
between zones.
For example, if using type 1A loop units:
254 addresses x 0.9 = Max. 228 loop units/loops.
NOTE!
Concerning the number of loop units in Ex areas, follow the guidelines in the control
drawing for the unit, or use the "Ex-Calculator" (Excel spreadsheet) to verify the
intrinsic safety.
CAUTION!
When using older versions of MCP-A, SCI-A, all versions of EV-SPB-BI and
EV-BI, the total number of these units, including SCI (Short Circuit Isolator) units,
are limited to 40 pcs on each loop.
CAUTION!
For loop configuration it is extremely important to follow the compatibility list. Do
not mix different types of SCI units.
For more details about their connection, see Connections for Loop Units, page
71.
The information about the electrical installation of each type of loop unit is
provided in its respective data sheet.
NOTE!
• Set the address switch on each loop unit before connecting them to the loop. If
an address unit is used, set its ID switch. See Setting the Address on Loop
Units, page 15 later in this chapter and also Address List and Test Report,
page 66 and ID List, page 69.
CAUTION!
Do not remove dust protection covers from the smoke detectors until all polluting
activities (such as construction work) are finished and the area has been cleaned.
Hint!
Further information about loop units and cabling can be found in chapter Fire
Detection Installation Guidelines, page 35.
Figure 4. Typical connection diagram for SCI functionality in all loop units
NOTE!
The illustrated SCI units above are polarity dependent.
Figure 5. Typical connection diagram for SCI functionality in selected loop units
NOTE!
* Maximum 32 bases without SCI in-between two SCI bases.
The illustrated SCI units above are polarity dependent.
In order to become operational, all addressable loop units such as detectors, manual
call points, etc. that are connected to the Loop M loop module must be given an
address between 1-254.
NOTE!
Loop units located on a single physical loop must be given unique addresses.
The value of the address is set according to the switches set to ON position as
shown in the following figure:
By setting the switches numbered 1,2,3,4 and 6 to the ON position, the address is
configured as 1+2+4+8+32 = 47.
NOTE!
After setting the address, remove the label attached to the detector and use it to seal
the address switch.
Address units
In addition to the loop address, address units and I/O units are equipped with an ID
DIP switch. This ID DIP switch determines the unit’s functionality.
Addressable timers
The addressable timers are located on the detector loop in the same way as any
loop unit.
NOTE!
Timers do not affect the function of the manual call points or heat detectors.
1 For detailed information, refer to the data sheet for corresponding unit.
Follow this instruction to set the address and the functions of the Repeater M 4.3.
Example:
When activation of buzzers in a Zone is initialized for a first time, Loop will
measure current consumption of the groups and based on it decided if all groups of
the zone can be activated simultaneously or pulsed signal shall be used.
Loop x Group 1 (Zone 1, Addresses 1-60) are activated if current consumption is <
190 mA
NOTE!
Groups are not active simultaneously.
If more than four detectors on the loop detects fire, only the first four detectors will
indicate fire with steady light LEDs and the rest will indicate fire with blinking
LEDs.
The Loop M X module remembers in which order the detectors detected fire, so if
a fire alarm in a detector is reset the next detector that detected fire will switch
from blinking light to steady light.
Summary
• The Broadcast Buzzers functionality is limited to CN- and EV-Series (not
EV-PP/XXX) of detectors, since it is the only detector type that supports
broadcasts on the loop line.
• Max 8 Groups per loop.
• Max 65 detectors per group.
• If not all groups can be activated at the same time without violating maximum
current consumption of 190 mA, as many groups as possible is turned on for 1
second, then turned off and other groups are turned on, and so on.
Refer to Central Unit Terminal & Cabling Layout, page 75 for more information.
For other electrical installations, such as Printer and Basic Backup Signal (BBU),
refer to the specific project drawings.
Control Panel
If the Control Panel is placed outside of the central unit, connection is made via the
external Backbone Bus channel (BBE). Each cable should be routed seperately for
maximum safety.
4 Verification
Hint!
To verify cable status and loop unit addresses, it is possible to confirm the
addressable detector loops with a SE3000 test device before making connections to
the central unit.
4.2 Loops
4.2.1 Verification of Loops
CAUTION!
Be sure to remove protective covers from all installed detectors before the fire
detection system is put into operation.
CAUTION!
If a loop unit is removed it has to be replaced as soon as possible in order to secure
the functionality of the fire detection system.
NOTE!
Once the loop cable has been tested and is free from faults, the next step is to
connect it to the central.
4 Measure the voltage on the A-side in the If this is not the case, refer to
central unit. If all loop units are connected Polarity Fault, page 26.
correctly (no polarity fault), the voltage
range loop should be 30-37 VDC.
5 Verify that the correct number and type of If the list reports OK (?/?) the
loop units are installed in the correct place.answering side status will be
The system will provide you with the updated by pressing “1.
requested information if you use the Menu Update list”. The system will
» 6 Service Menu » 5 Loops, choose the scan the loop to determine
relevant loop, and then press “2=Loop answering side. The loop is
Units”. disabled during the scan and
Each loop unit will report on which side A the procedure may take
(primary) or B (secondary) it answers: several minutes (access code
OK (A/B) = Answer on both sides. 3 is required).
OK (A/-) = Answer only on A side.
If a loop unit is missing, see
OK (-/B) = Answer only on B side.
Wrong Number of Loop Units
OK (?/?) = The loop unit answers but the (only for Addressable Loops
loop module doesn’t know on on Loop M), page 27.
which side until an update is
made.
Press “1. Update list” to If the list reports No answer
perform an update. (-/-) but no corresponding
fault is active in the list by
No answer The loop unit does not answer
(-/-) = on either side.
pressing "1. Update list".
6 One loop is now verified and tested. Repeat steps 3-5 for all other
Continue with the next loop. loops.
7 Make a fire detector test of the complete Refer to the chapter about
Fire detection system. Testing of system parts.
Use appropriate test equipment (smoke
detector test gas, heat detector tester) to test
each detector and loop unit.
See section Recommended Test Equipment,
page 25.
Print out the “Fire alarm history list” found
under Menu » 7 History » 1 Fire History
List. This list contains the 1000 latest fire
alarms, and is cleared each time the system
is restarted.
8 Use a top to bottom procedure if you have
any problem with the verification of the
loop function.
Start by solving the problems that affect the
whole loop and then continue with the
problems with each address.
CAUTION!
Communication problems on a loop due to high external electromagnetic
interference have to be addressed as soon as possible in order to secure the
functionality of the complete fire detection system.
It is highly important to eliminate or reduce any external interference to restore
communication on the loop.
After installation of the Fire detection system, test the different parts of the system
to assure that they function properly.
CAUTION!
Check for contaminated detectors. Use the Control panel menu system to display a
list showing in which condition the detectors are.
For additional information about testing, please refer to the Service and
Maintenance Manual.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
NOTE!
A warning will be displayed on the menu screen as long as the system is not running
Cause/Effect, which is the two first minutes after the system has been powered up
• External alarm devices and controls are by default not activated in case of a
fire.
Hint!
This functionality can be turned off if controls are to be tested
while the tested zone is in test mode.
(Menu » 3 Disablements » 1 New Disablement » 3 External
Controls)
• The alarm level is lowered to give a quick response to detector test equipment.
• LED indicators on loop units are blinking.
• Each tested loop unit will indicate activation with a steady LED indicator.
• Key events (as well as information of system components and system
software) will be stored in the system log which can be saved on a USB
memory stick. If a printer is connected to the system, alarms will automatically
be printed as a result of the tested units.
• The units in alarm are automatically reset when the heat or smoke
concentration is under the alarm level, or when the test key is removed from
the manual call point.
NOTE!
Fire alarm from zones not in test mode will be handled normally by the fire detection
system.
The zone in test mode will automatically return to normal operation after two hours.
CAUTION!
During system start-up the smoke detectors perform a 15 minutes calibration
according to the level of particles in the air. No tests should be done during this
period.
1 Put the zone into test mode under: Menu » Access level 2B is required.
3 Disablements » 1 New disablement » 5
Test Mode .
2 Select a zone and confirm by pressing the The Disablements, Test, and
key. Zone/Unit indicators light to
confirm that they are in test
mode.
Each detector, manual call point and input in this fire zone can be tested during the
next two hours. Refer to Test Mode Overview, page 23 for further information
about a zone in test mode.
All alarms are listed under: Menu » 7 History » 1 Fire History List .
To return the tested zone to its normal condition, refer to Reset Test Mode, page
26.
CAUTION!
If the system previously had been put into regular fire detection service, a zone in
test mode should be manually monitored, e.g. by a fire watch in order to maintain a
tolerable risk level.
NOTE!
Use appropriate test equipment.
See section Recommended Test Equipment, page 25.
For detailed information, please refer to the data sheets for the products.
1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 List disablements.
2 Choose the zone in the disablement list and then press .
• The display
• All indications on the control panel
NOTE!
The user has to verify that the display and all indications are working properly. This
function will not generate a fault alarm in case something is faulty.
1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
2 Verify that the display momentarily shows a test image.
3 Verify that all system indicators and operational keys momentarily lights
up.
4.3 Troubleshooting
4.3.1 Polarity Fault
One or more loop units are not correctly installed if the measured voltage is much
less than 30 VDC. Proceed as follows to locate the loop units with polarity fault:
If a limited number of loop units do not answer, the problem may depend on one of
the causes listed below.
Hint!
* The system is equipped with a Hot Plug&Play function enabling the user to add or
delete detectors during normal operation without needing to change the
configuration file with a PC and restarting the system.
The configuration file may be updated during normal operation from Service Menu
(Menu » 6 Service Menu » 5 Loops) or directly from the Fault List (Menu » 1 Fault
Alarms » 1 Fault List). For additional information, please refer to the Service and
Maintenance Manual.
Address error
Use Menu » 6 Service Menu » 5 Loops, choose the relevant loop, and then press
“2=Loops Units” to list all found units on the loop. Compare the found loop units
with the ones configured.
There is a possibility that two or more loop units with the same address will
answer. Possible reports include “double address”, “no answer”, “bad
communication” or “abnormal condition”.
CAUTION!
A sub-loop cable break has to be located and corrected as soon as possible in order
to secure the functionality of the complete fire detection system.
The loop units which can have a sub-loop are some types of detectors and I/O units.
NOTE!
A cable break fault cannot be reset in case a fire alarm is present on the loop.
1 No answer is received on a single fed loop? The cable is broken before the
first loop unit.
2 The loop is a double fed loop? The cable is broken before the
first loop unit and after the
last loop unit.
1 The cable break is located between the “last” unit on the A side and the
“first” unit on the B side.
1 Measure the resistance between the + and - The measured value should be
poles. less then 185 Ohm for a cable
with a maximum length of 3
• Connect an ohmmeter between the km.
+ poles.
• Measure and repeat the procedure for
the - poles.
The control panel displays which loop or central has the earth fault.
1 Examine the faulty loop to locate the earth Follow the instructions below
fault. to measure the resistance with
an ohmmeter.
1 Measure between the + and - pole and earth The measured value should be
to detect an earth fault. more than 50 kOhm for a
cable with a maximum length
• Connect the ohmmeter between the of 3 km. Values below 8
+ pole and earth. kOhm (±2 kOhm) will be
• Measure and repeat the procedure for indicated as earth fault.
the - pole.
If the earth fault still remains after this step, examine the cables to all other devices
connected to the Fire detection system.
1 Search for the short circuits between the Follow the instructions below
central unit and the first short circuit to measure the resistance with
isolator. an ohmmeter.
1 The control unit displays which short Follow the instructions below
circuit isolators have been activated. Search to measure the resistance with
for the short circuit between the fault an ohmmeter.
reported short circuit isolators to find the
exact location of the fault.
1 Measure the resistance between the + pole The measured value should be
and the - pole. Connect an ohmmeter more than 100 kOhm for a
between the two poles. cable with a maximum length
of 3 km.
The faults are reset from the Fault list under Menu » 1 Fault Alarms » 1 Fault List.
The system log files can be downloaded using an approved USB memory stick
(available from an authorised dealer).
CAUTION!
Do not remove the USB memory stick until the download is finished.
1 Connect the USB memory stick to the USB port on the Control M 4.3
panel.
2 Choose Menu » 6 Service Menu » 8 System Log » 1 Save syslog.
3 Press OK to save the systems log files to the USB memory stick.
4 The system will now download the system log files. Wait until this process
is complete!
5 Disconnect the USB memory stick and copy the system log files to a PC.
File name example: sysLog_no_YYYY-MM-DD-xxxxxx
5 Commissioning Requirements
5.1 Prerequisite
The procedure described below in Loop Requirements is to be followed by the
installation team.
If nothing else is agreed, no commissioning engineer will be sent before the steps
below are confirmed and the appropriate papers are signed and sent to your local
Consilium office or authorized representative.
The list in Part A: Loop Configuration includes all data you need when configuring
the loops. Part B: Loop Status is more like a checklist - follow it point by point.
When you have completed this part you should have filled in, signed and faxed the
special document Address List and Test Report, page 66, one for each loop in the
system. Part C: Central Status is also a checklist, but it deals with the status of the
central unit.
NOTE!
During commissioning:
Test that all loop unit functions are correct.
1 All units shall be located at the proper place according to the drawings.
2 Fit detector heads, manual call points, address units, and control modules
into their bases.
3 Each loop unit shall be given a unique address. For analogue addressable
units, refer to Address List and Test Report, page 66.
4 Connect cables to loop unit terminals according to the data sheet for that
loop unit.
NOTE!
Deviations from the above criteria may cause time delays. These time delays will be
invoiced.
CAUTION!
Always refer to and act according to current local rules and regulations.
CAUTION!
Ensure that the fire detection system enclosure is installed in a location that satisfies
the environmental requirements.
NOTE!
Do not start an installation unless all conceivable considerations regarding detector
location have been taken into account.
For detailed connection and installation information, refer to the data sheet for each
unit.
• Set the address on every loop unit. Also set the ID on loop units which are
equipped with an ID DIP switch.
• After the loop unit address is set, place the adhesive label over the address DIP
switch to seal it. (Only applicable for detectors equipped with DIP switch.)
• An end of line resistor shall be installed in the end of each sub-loop (if used).
The type of resistors to be used and how to install them can be found in the
project documentation or in the data sheets.
• Make sure that smoke detectors maintain their protective dust covers until
polluting activities such as construction have been completed and the area have
been cleaned.
• Mark each loop unit with zone and address number. For detectors, the
markings shall be placed on the base, not on the detector head since it might be
replaced in the future. Also keep this in mind when marking other types of
loop units. Special adhesive labels for marking are available from Consilium or
one of Consilium's representatives.
• Make sure that the IP class for each unit meets the environmental
requirements.
• Plug unused cable glands.
• The maximum distance for a smoke detector from a wall or a bulkhead is 5.5
m. The maximum distance between two detectors is 11 m.
• Each smoke detector installed in engine room areas shall have two (2) meters
extra cables, this to make it possible to relocate the detector position when
performing “real” smoke tests with fans etc. running.
• In cabins and in lockers, mount the detector with its LEDs facing toward the
door. (Not applicable for detectors with OmniView LED.)
• Mount the detector giving it wide access to the whole area where the flames
are expected. The detector should be aimed toward the center of the detection
zone and have a completely unobstructed view of the protected area.
• Mount the detector in such a way that vibrations are avoided as much as
possible.
• Avoid shadow areas from objects in the room, by placing a second flame
detector facing the opposite side of the object, see Figure 13. An example of
flame detector mounting.
• Mount the flame detector to give it clear access to the location of the
anticipated fire. See data sheet of flame detector for more information about
cone of vision. Place the detector beside, but not directly above, the protected
object to prevent the risk that black smoke may block the flames. Place the
detector at an angle of 45° downwards. This way the detector will project both
downward and forward and catch the least amount of dirt. For more
information about its angle of projection, refer to the flame detector’s data
sheet.
• A general rule is to install the detector on a height that is twice the height of
the highest object in the supervised area, if possible.
• Avoid sources for false alarm (e.g. flares) from entering the detector’s cone of
vision.
CAUTION!
Depending on the number of IS isolators and Ex loop detectors that are to be
installed, the number and placement of short circuit isolators (SCIs) could be of
great importance.
Short Circuit Isolator, page 40.
Information on how the circuit installation shall be made in order to comply with
the ATEX directive is found in the control drawing for the detector type. Available
is also the "Ex-Calculator" (Excel spreadsheet) which can be used to verify the
intrinsic safety of a circuit with regard to the number and type of units, cable
length, and gas group. Contact your local supplier.
• Connect the detector to an address unit located outside the hot area and in an
environment suitable for it's IP class, and where it can easily be accessed for
service and maintenance. The maximum cable length between the detector and
the address unit is 25 m.
• The address should be set on the address unit and the function ID switch
should be set.
• An end-of-line resistor (SLZ-2) shall be fitted inside the detector base if the
detector is the last unit on the sub-loop.
• Installation shall preferably be hidden from the public but easily accessible for
service.
• The short circuit isolators must be connected with correct polarity.
• When there are more than five detectors on the Ex-loop, two parallel SCIs
must be installed before and after each IS isolator.
Figure 17. Example of a parallel SCI installation in a system with two IS isolators.
NOTE!
The SCI function between the IS isolators can also be
achieved by installing a detector or other loop unit equipped
with SCI.
6.1.11 Timers
• The timer unit is used for the temporary disablement of detectors in areas
where smoke or heat can occur under normal circumstances.
• The timer should be mounted for easy access and operation and well marked
with its function.
6.1.12 Bells
• Installation height is normally 0.2 m below the ceiling and max 2.2 m from the
deck or floor level.
• After installation, make sure that the gong is free from the cables, otherwise
the sound output may be reduced.
• Should be mounted with cable entrance facing downwards.
Cable categories
The cables are divided into the following categories with regard to their
electromagnetic compatibility (EMC):
NOTE!
Cables used in the Consilium fire detection systems generally belong to EMC
category C, the exception being control cables with voltage above 50 V (usually 230
V), that are rated category B.
Cable separation
To fulfill EMC requirements, cables of different categories must be separated from
each other in order to avoid capacitive or inductive interference. As an example,
loop cables installed too close and in parallel with cables connected to a switching
motor controller may affect the communication in the loop cable.
The table below shows the minimum cable separation between the different cable
categories.
NOTE!
When different types of cables cross each other at right angle (90°), other limitations
apply.
If the minimum cable distance cannot be met, each category of cables must be
provided with metallic tubes, trays, screens, or similar in order to physically
separate them from other cable categories.
The preferred location of a loop cable is in the bundles for low voltage cables (such
as for alarm, communication, measuring and navigation equipment).
Shielding of cables
Although not a requirement, shielding of the detector loop cables is recommended
in order to protect them from electromagnetic emissions. Other cables of category
C should always be shielded, whereas category A cables could optionally be
protected. However in environments with exceptionally high electromagnetic
disturbance levels we strongly suggest that shielding is done for all cable
categories.
Earthing of cables
The earthing of the loop cables must be adapted depending on the design of fire
detection system (see examples below). This is to ensure that no currents run
through the screen due to voltage differences between the earth points (so called
stray voltage).
Figure 21. Earth points in a stretched central system (marine SRtP applications only).
When installing metal cable tubes – following must be taken into account:
• If there is more than one cable in the same tube, the cross section (counted of
mutual external diameters) may be max 40% of the inner cross section of the
tube.
• If the tube is more than 10 m long, drafting holes has to be drilled.
• Tubes must be installed on support so that the background may be painted.
• Tube installation must be done by welding or by tube joints. Fastening
distances are located 100 mm from the tube end and afterwards every 1.5 m.
• Bending radius must be at least 6 times the external diameter of the tube.
• The upper tube end in open decks must be sealed up, this to prevent water from
coming in.
When installing plastic cable tubes – following must be taken into account:
6.2.5 Cabling
When installing the cables – take into account the minimum internal bending
radius, that has nominal value of six times the external diameter of the cable.
• If two separate routes for the cables are required – all supplies and involved
control cables must be passed by separate routes according to the drawings and
cable passing list.
• Do not bundle low voltage cables together with power cables, they have to be
separated from each other.
• When cable bundles are mounted on trays this can be done as follows:
• On the trays along the ship – the power cables on the left side (Port-side)
and the low voltage cables on the right side (Starboard-side) of the tray.
• On the trays across the ship – the power cables to the fore side and the
low voltage cables in the stern side of the tray.
• On the fore or aft stem bulkhead trays in vertical shaft – the power cables
to the Port-side or the Starboard-side bulkhead trays, the power cables to
the fore side and the low voltage cables to the stern side of the tray.
• In cable junctions and when exiting the cable trays bridges fastening bolts have
to be used – low voltage cables for alarm, communication, navigational and
measuring equipment have to be installed in their own bundles.
• Each fire detector installed in engine room areas shall have two (2) meters
extra cables, this to make it possible to relocate the detector position when
performing “real” smoke tests with fans etc. running.
• Wet spaces:
• Cables are penetrated from the below or from the side.
• Let the cables enter the sealing at a right top angle (or as near a right
angle as possible).
• Dry spaces:
• The cable can enter from any direction.
No cables are to be installed below 50 mm distance from bottom or fuel oil tank,
except cables ending in these spaces.
6.2.8 Markings
• Cables entering terminal boxes and equals shall be marked with identification
markings.
• The cable identification is to be done with a metal dymo-tape – on open decks
the dymo-tape must be of stainless steel.
• Cable markings are the same as the identification marks in the drawings.
• The cable is passed in switchboards, decks and terminals unpeeled as near the
connection place as possible.
• Mark extra wires (not used) and do not cut them.
• Earthing wire is marked following national rules and regulations.
• Cable wire ends of 0.5–2.5 mm2 shall be equipped with compression-type
collar, if the contact screw presses direct wires.
• A cable eye shall be installed at the end of a conductor, connected by means of
a screw or a bolt.
• No more than two conductors shall be connected onto one side of the same
terminal.
CAUTION!
It is highly important to eliminate or reduce any high external electromagnetic
interference which can have a negative effect on the loop communication.
Make sure that cabling is carried out according to international rules and regulations.
The mounting heights are according to the table below, unless otherwise specified
in the installation drawings.
7 System Upgrade
Prerequisites
• Computer running Windows 7, 8, or 10.
• Empty USB memory stick (bootable)
• BIOS release
1 Copy the file cm_bios_v_xx to the root catalogue of the USB memory stick
(where xx is the version number).
NOTE!
The above file naming convention is only applicable from
BIOS version 2e onward. For BIOS versions earlier than
2e the file shall be named cm_bios.
2 Reboot the control module.
1 Repeat step B.1-B.4 for all the Control M 4.3, Repeater M 4.3 and Control
M 2.2 in the system.
2 Remove the BIOS file from the USB stick.
NOTE!
Primarily, use a USB memory stick to upgrade BIOS in a Control M 4.3, Repeater M
4.3, Control M 2.2 or Control M X with USB port.
To Control M X without USB port you have to use the Ethernet connection.
Prerequisites
• Computer running Windows 7/8/10 and an Ethernet cable.
• BIOS release
1 Go to Tools » Options.
2 Select manual configuration.
3 In the drop down list. Select the network adapter that you connect your
cable to.
4 Select OK to confirm your selection.
1 The tool should now automatically attempt to establish connection with the
target and print out detected Central and Card address together with current
flashed firmware version.
2 The tool should now be ready to download new firmware.
1 Press the Program Firmware button and This may take some time to
wait. complete.
2 Target will reboot. If the target hardware has a
version before 1.2.0 you may
still be able to program it by
manually rebooting the target
when requested by the tool.
(If the bootloader supports
booting over Ethernet.)
3 Target will then re-establish connection
with the tool and start downloading the new
firmware.
4 Target will be reflashed.
5 Target will reboot and start the new
firmware.
Hint!
Recommendations for centrals containing many control modules/repeaters and/or
distributed centrals can be found in section Upgrading Large Systems, page 59.
Hint!
Files can also be transferred from a PC running System Software Updater to the
CCP System using SSH and SCP protocols. Please refer to the System Software
Updater instructions which can be found in the Appendix section of the Service &
Maintenance Manual.
Hint!
Go to the Service Menu, in order to check if the firmware or BIOS upgrade has been
successful.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
NOTE!
It is essential to use the same version of the configuration software as the firmware
in the system. Otherwise there might be a conflict and major functions be set out of
order.
Prerequisites
• Empty USB memory stick (bootable)
• CCP software release
• Computer running Windows 7/8/10 and an Ethernet cable (necessary for
Control M X without USB-port)
• BIOS version R2n or later already installed for a Control M X with USB port
1 Make sure the configuration software installed on the computer matches the
new firmware version.
2 Download valid configuration from Control M 4.3 (or Control M 2.2) to
USB memory stick.
3 Resave the configuration file (.ccp) using the CCP configuration sw version
that match the firmware version.
1 Copy the file cm_firmware to the root catalogue of the USB memory stick.
1 Insert the prepared USB memory stick into File name: cm_firmware
the control module.
Hint!
Recommendations for centrals containing many control modules/repeaters and/or
distributed centrals can be found in section Upgrading Large Systems, page 59.
Hint!
Files can also be transferred from a PC running System Software Updater to the
CCP System using SSH and SCP protocols. Please refer to the instructions for the
System Software Updater program.
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
NOTE!
It is essential to use the same version of the configuration software as the firmware
in the system. Otherwise there might be a conflict and major functions be set out of
order.
Prerequisites
• USB memory stick
• MicroSD memory card
• CCP software release
• Computer running Windows 7/8/10
• BIOS version R2h or later already installed for the Control M 4.3, Control
M 2.2 and Repeater M 4.3 modules
• BIOS version R2n or later already installed for a Control M X with USB port
1 Make sure the configuration software installed on the computer matches the
new firmware version.
2 Download valid configuration from Control M 4.3 (or Control M 2.2) to
USB memory stick.
3 Resave the configuration file (.ccp) using the CCP configuration sw version
that matches the firmware version.
NOTE!
If the firmware version is 1.8.0 or later, and the control module has an SD card, the
CCP Firmware Update Tool can not be used. In this case the control module must be
upgraded via System Software Updater instead. Instructions can be found in the
Appendix section of the Service & Maintenance Manual.
NOTE!
Primarily, use a USB memory stick to upgrade firmware in in a Control M 4.3,
Repeater M 4.3, Control M 2.2 or Control M X with USB port.
To Control M X without USB port you have to use the Ethernet connection.
Prerequisites
• Computer running Windows 7/8/10 and an Ethernet Cable.
• CCP software release image file (i.e. cm_firmware).
• The Control Module must have at least Firmware 1.2.0 in order to support
update via Ethernet.
1 Go to Tools » Options.
2 Select manual configuration.
3 In the drop down list. Select the network adapter that you connect your
cable to.
4 Select OK to confirm your selection.
1 The tool should now automatically attempt to establish connection with the
target and print out detected Central and Card address together with current
flashed firmware version.
2 The tool should now be ready to download new firmware.
1 Press the Program Firmware button and This may take some time to
wait. complete.
Hint!
Before following the instructions below it might be a good idea to understand the
basics of what the instructions are trying to achieve in order to avoid excessive
master/slave switches and to minimize the traffic that occurs when the system is
trying to synchronize its state between all control modules.
In order to reduce the number of master/slave switches the ordering of the upgrade
is to start with the control modules on the primary system bus and then proceed
with the control modules on the secondary system bus.
To further reduce traffic on extension buses. Upgrade and restart the control
modules owning an extension bus before the repeaters on the extension bus.
Finally, for really large systems (more than 5000 loop units) it will further reduce
the traffic to disconnect the system buses completely at 1.1 and 1.2 during the
upgrade.
Upgrade for control panel modules (Control M 4.3 and Control M 2.2)
Hint!
Further information can be found in section C. Upgrade the firmware in a Control M
4.3, Repeater M 4.3, Control M 2.2 or Control M X with USB port, page 52.
8 Appendix - EN 54 Functions
8.1 EN 54 Functions
Optional functions with requirements
The following optional functions with requirements are available in the Fire
detection system:
10 Appendix - ID List
10.1 ID List
10.1.1 Prerequisite
The ID switch must be set on the address unit type AE and NS-AIN. The ID
defines the function and the type of the unit connected to the address unit.
The value of the ID is according to the switches set to the “ON” position as shown
in the following figure:
The switches numbered 1 and 3 are set to the ON position. The values for these
switches are 1+4=5.
(NS-AIN1 has constant sub-loop voltage, while NS-AIN2 has pulse voltage).
Control M 4.3
A Control panel with a 4.3” display that manages and supervises a system and
can act as bus master or slave.
Repeater M 4.3
A Repeater panel with 4.3” display that can act as bus slave.
Control M 2.2
A Control panel with a 2.2” display that manages and supervises a system and
can act as bus master or slave.
Control M X
A Control module without display that can act as bus master or slave. It is used
for providing additional communication channels in the system.
Loop M X
A module that supplies one addressable Loop.
I/O M 70
A module that provides 8 I/Os of type I/O 70. Each I/O can be programmed for
use as: an input (max 70 mA), an output for buzzers, relays etc (max 70 mA) or
a conventional detector zone.
I/O M 700
A module that provides 8 I/Os of type I/O 700. Each I/O can be programmed for
use as: an input or an output for magnets, power supply etc (max 700 mA).
Relay M 8
A module that provides 8 potential free contacts.
Surge Prot M
A module that provides surge protected power inputs for the BBI, terminal
board for BBE and electronic short circuit protected outputs for Control or
Repeater panels.
Charger M
A module that supervises and controls the power and battery functions.
Bus Isolator M
This module is used for dividing the system backbone bus into segments. It can
provide power to Control Panel M 4.3 and Control M 2.2.
PSU M AC/DC 5A
A 5 ampere 115/230 VAC/VDC Power Supply.
PSU units can be used in pairs to supply 5+5 A.
For complete information, see the data sheet for each module.
Figure 24. An example of a central unit terminal layout with cabling for a marine installation.
13 Appendix - Termination
The outputs supporting the Basic Backup Signal have an X-Fire property that can
be set in the Configuration Program.
Modules not having full contact with the controller act upon the Basic Backup
Signal.
NOTE!
The pre-alarm level does not affect the Basic Backup Signal.
• Modules that can act as a Controller are able to generate a 2.0 V Surveillance
Voltage on the Basic Backup Signal. At present only the Control Modules can
act as a Master.
• Only one module within each Central may generate the 2.0 V Surveillance
Voltage on the Basic Backup Signal.
• All modules that can generate alarms are able to generate the 6.0-28 V Fire
Voltage signal on the Basic Backup Signal. At present Modules with an
addressable detector loop (Loop M X) and conventional Zone ( I/O 70 M) can
generate alarms.
• If an I/O module is operating in normal or quarantine mode and the master
does not poll the module for 75 seconds, the module shall enter isolated mode
where it monitors fire inputs and issues fire alarms on its own I/O and using
the Basic Backup Signal according to their pre-stored configuration.
• Modules that can be configured to handle X-Fire Alarm shall supervise the
Basic Backup Signal for faults. At present this only excludes the Bus Isolator
Module.
13.2.2.1 Connections
Figure 26. Two Bus Isolator M Figure 27. Terminal drawing of two
Bus Isolator M
CAUTION!
A 2 kΩ resistor is pre-fitted between terminals 31 and 32.
• Remove the resistor if the Basic Backup (BBU) output is being
used.
• Ensure the resistor remains fitted if the terminals are not in use.
If the resistor is missing when the BBU signal is activated (fire
alarm), it will not be possible to reset the alarm.
Figure 28. Example of BBE connection between two (or more) backbone segments in one spur
NOTE!
Only one of the Basic Backup (BBU) channels shall be connected.
Figure 29. Example of BBE connection between three (or more) backbone segments (1, 2, 3, n) in
several spurs
BBE = Backbone External, BBI = Backbone Internal, = 120 ohm resistor. Use twisted
pair cables for the BBE connections. See Figure 28. regarding the BBE, BBU and resistor
specific connections.
WARNING!
In case of remedy “replace the unit” or “replace the module” – this has to be carried
out as soon as possible in order to secure the functionality of the fire detection
system.
Listed in the table below are all fault codes generated by system modules2 and loop units3 ,
their causes, and how an operator with knowledge of the system can classify and solve the
problem.
A fault generated by a system module is often identified as:
“CENTRAL nn Unit type nn Fault description , FAULT nnn”
A loop unit fault is often identified as:
“ZONE nn Unit type nn Fault description , FAULT nnn”
Hint!
Instructions for troubleshooting and replacement can be found in the Installation
manual or the Service & Maintenance manual.
Unit or
Fault Code Cause Remedy Failure classification
Module
One module has
been replaced by
Switch to the correct module. • Minor fault if
another type of
module. redundant system
and only one module
One module address
in the redundant
has been changed to
function.
the same address as
another module on Check address of the modules. • Major fault if
System the same backbone redundant system
modules (a secondary fault and one or more
appears). modules in the
redundant function.
Defect module. Replace the module.
Cable break, short • Major fault if one or
circuit or wrong more modules in a
Locate the cable break, short non-redundant
electrical connection
circuit or check the electrical system.
of the internal
connections.
communication bus
NO ANSWER (BBI to BBE).
Explanation: Lost
The loop unit has
communication.
electrically been
128 The system has Connect the loop unit.
disconnected from
recognized a
the loop.
unit/module but
lost contact. The loop unit has Check that the correct loop unit
been replaced by is installed.
another type of loop
unit, or the loop unit Check that the ID switch for an • Minor fault if only
ID has been I/O ICxx unit is set correct. one detector within
changed. an area covered by
other detectors.
One loop unit 1. Check address of the units.
Loop units
address has been set • Major fault if two or
2. Rescan or restart the loop.
to the same address more detectors
as another loop unit within the same
on the same loop (a area.
secondary fault
appears).
Defect unit. Replace the unit.
Cable break or short
circuit in a loop (a Locate the cable break or short
secondary fault circuit.
appears).
Unit or
Fault Code Cause Remedy Failure classification
Module
The detector has a
faulty sensor Replace the unit.
element.
The smoke detector Protect the detector from the
is exposed to strong airflow or consider repositioning
airflow. the detector.
• Check the device on the
129 SENSOR FAULT Loop units Input on a sub-loop sub-loop. Major fault
has a removed or
faulty device, an • Check the end of line
open circuit, or a component.
cable break. • Locate the cable break.
Loop I/O Check that the cable between Major or Minor fault
IN1 CABLE There is a cable
133 units with input and end of line resistor is depending on project
BREAK break on input 1.
inputs complete. specific function.
Loop I/O Check that the cable between Major or Minor fault
IN2 CABLE There is a cable
134 units with input and end of line resistor is depending on project
BREAK break on input 2.
inputs complete. specific function.
Unit or
Fault Code Cause Remedy Failure classification
Module
Charger M 1. Measure the voltage from the
power source.
• If voltage OK, change
External 24V power
loop unit.
Loop units source missing or
135 EXT 24V FAIL with the local power • If voltage NOT OK, Major fault.
external supply unit is change the DC/DC.
power defective.
2. If problem not solved contact
an authorized service office.
There is a fault in
the feedback
Check the cable for the feedback
between the loop
from the connected device to the
Loop I/O unit and the Major or Minor fault
FEEDBACK loop unit, for instance the
136 units with externally connected depending on project
FAULT door/damper.
inputs device (for example, specific function.
a door or a damper).
External load is Check the cable and the external
missing. load.
Loop I/O A supervised unit
Major or Minor fault
POSITION units with (for example, a door
137 Check for abnormal conditions. depending on project
FAULT specific or damper) is in the
specific function.
IDs wrong position.
• Major fault if no
short circuit isolators
A short circuit in the on the loop.
CM 4.3
detector loop cable
CM 2.2 Locate the short circuit. • Major fault if loop
or conventional
I/O M 70 with short circuit but
LOOP SHORT zone.
138 not for non-affected
CIRCUIT areas.
Loop unit
with short A short circuit in the
Locate the short circuit. Major fault.
circuit detector loop cable.
isolator
• Major fault if no
short circuit isolators
on the loop.
Short circuit on the
LOOP A SHORT
139 Loop M X A-side of a detector Locate the short circuit. • Major fault if loop
CIRCUIT
loop. with short circuit but
not for non-affected
areas.
• Major fault if no
short circuit isolators
on the loop.
Short circuit on the
LOOP B SHORT
140 Loop M X B-side of a detector Locate the short circuit. • Major fault if loop
CIRCUIT
loop. with short circuit but
not for non-affected
areas.
Unit or
Fault Code Cause Remedy Failure classification
Module
• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK positive conductor
141 Loop M X Locate the cable break.
POSITIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.
• Minor fault if in no
combination with
A cable break on the
other faults.
CABLE BREAK negative conductor
142 Loop M X Locate the cable break.
NEGATIVE on the Loop M X • Major fault if in
has been detected. combination with
other faults.
Unit or
Fault Code Cause Remedy Failure classification
Module
CM 4.3 Short circuit has
CM 2.2 1. Locate the short circuit.
been detected on an
I/O M 70 output to the 2. Reset the fault.
SHORT I/O M 700 affected module.
149 Major fault.
CIRCUIT Short circuit has
been detected on Locate the short circuit on the
Loop units
external cabling to external cabling to the loop unit.
the loop unit.
Loop I/O 1. Open the valve.
External equipment Major or Minor fault
units with
150 VALVE CLOSED indicates that the 2. Contact an authorized depending on project
specific
valve is closed. service office. specific function.
IDs
1. Check the address of the
system module.
The affected system
System module is not in the 2. Check the system
modules system configuration file.
configuration file. 3. Contact an authorized
service office.
PRESENT NOT
152 Minor fault.
CONFIGURED 1. Check the address of the
loop unit.
The affected loop
unit is not in the 2. Check the system
Loop units configuration file.
system
configuration file. 3. Contact an authorized
service office.
There is an earth
Charger M
fault on the positive Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
155 Minor fault.
POSITIVE has detected an earth Locate the earth fault on the
Loop units fault on the positive external power supply to the
conductor from the loop unit.
power supply.
There is an earth
Charger M
fault on the negative Locate the earth fault.
Loop M X
conductor.
EARTH FAULT A power loop unit
156 Minor fault.
NEGATIVE has detected an earth Locate the earth fault on the
Loop units fault on the negative external power supply to the
conductor from the loop unit.
power supply.
ChangeOv A fuse has been
Replace the fuse.
er M Ext blown.
157 FUSE FAULT Minor fault.
A fuse in a power Contact an authorized service
Loop unit
loop unit has blown. office.
Unit or
Fault Code Cause Remedy Failure classification
Module
A battery fuse has
been blown, or a
Charger M Replace fuse or restore the cable.
cable to the battery
BATTERY is broken. Major or Minor fault
158 CABLE/FUSE 1. Check the connection to the depending on project
FAULT There is a problem specific function.
battery.
with the battery
Loop units
connected to the 2. Consider replacing the
power loop unit. battery.
CM 4.3
CM 2.2
RM 4.3 A cable break or
Charger M short circuit has Restore the cable.
CABLE I/O M 70 been detected.
159 BREAK/SHORT I/O M 700 Major fault.
CIRCUIT Loop M X
• Check the end of line
Loop I/O Input on a loop unit
component.
units with has an cable break
inputs or short circuit. • Locate the cable break.
Charger M
ChangeOv Emergency power Major or Minor fault
EMERGENCY Check the emergency power
162 depending on project
POWER FAULT er M Ext has been lost. supply.
specific function.
Loop units
The battery charger
BATTERY (Charger M) is The battery charger (Charger M)
164 Charger M Minor fault.
CHARGER unable to charge the is unable to charge the battery.
battery.
EXTERNAL
CM 4.3
FAULT
CM 2.2
Can be generated Major or minor fault.
RM 4.3 External equipment
165 by customized Check the external equipment. See project specific
Charger M is indicating a fault.
defined fault. See system description.
I/O M 70
Custom text for the
I/O M 700
particular fault.
Unit or
Fault Code Cause Remedy Failure classification
Module
CHECKSUM
EEP
The booting
Only applicable
sequence was not
167 for a redundant Loop M X Rescan or restart the loop. Minor fault.
completed in a
controlled loop
correct way.
with two Loop M X
modules
If restarts happen repeatedly
System The module has
168 RESTARTED without known reason, contact Minor fault.
modules restarted.
an authorized service office.
The module has
1. Restart the module.
been in the
TOO LONG System
169 validating or 2. Contact an authorized Minor fault.
BOOT TIME modules
configuring states service office.
for too long.
CM 4.3 There is too high
EXTERNAL Check the load and reduce if
170 CM 2.2 external load on a Major fault.
LOAD possible.
I/O M 70 conventional zone.
EXTERNAL CM 4.3 Unexpected voltage
171 POWER CM 2.2 detected in a Located and remove the source. Major fault.
SOURCE I/O M 70 conventional zone.
1. Measure the voltage from the
power source.
• If voltage OK, change
Low voltage on the module.
primary 28VDC
LOW POWER • If voltage NOT OK,
172 Charger M power supply to the Major fault.
SUPPLY PSU 1 change or adjust the
internal system
DC/DC.
modules.
2. Contact an authorized
service office.
Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source.
• If voltage OK, change
module.
The incoming 24
LOW POWER
VDC supply to the • If voltage NOT OK,
175 SUPPLY Loop M X Major fault.
internal circuit change or adjust the
OPERATING
boards is too low. DC/DC.
2. Contact an authorized
service office.
The configuration
file is corrupt. 1. Download the configuration
file again.
An error has
occurred during 2. Contact an authorized
downloading of the service office.
CM 4.3
SYSTEM configuration file.
CM 2.2
176 CONFIGURATI Open configuration file in the Major fault.
CM X
ON FAULT The configuration correct version of CCPConf and
RM 4.3
file is saved in an resave the configuration file.
incompatible Which version of CCPConf used
version of the depends on the version of the
CCPConf. firmwares installed in the CCP
modules.
Loop I/O
External equipment Major or Minor fault
LOW units with Check the pressure on the
177 indicates low depending on project
PRESSURE specific supervised unit.
pressure. specific function.
IDs
Charger M
The main power
180 MAINS POWER ChangeOv Check the main power supply. Major fault.
supply is lost.
er M Ext
The connection
between the main
processor and the
CM 4.3
processor handling
the keyboard input
has been lost.
The module is
leaking power. The
INTERNAL Charger M supply and Contact an authorized service
181 Major fault.
FAULT consumption differ office.
greatly.
The Loop M X has
failed to schedule a
loop unit it
Loop M X considers to be in
working condition
for more than 30
minutes.
Unit or
Fault Code Cause Remedy Failure classification
Module
• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
183 CH 1
modules on channel 1 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.
• Minor fault if in no
combination with
The module has
NO ANSWER other faults.
System stopped answering Contact an authorized service
184 CH 2
modules on channel 2 on the office. • Major fault if in
BACKBONE
backbone bus. combination with
other faults.
Unit or
Fault Code Cause Remedy Failure classification
Module
The configuration
file in the system is Synchronise the configuration
not the same in all file between all panel.
CM 4.3 modules.
CM 2.2 Central X Module Y
CM X settings in
CONFIG NOT RM 4.3 configuration file Check configuration and
213 SYNCHRONIZE Major fault.
compared to DIP-settings.
D
DIP-settings are not
OK.
The DIP-settings of
the Charger M are Check configuration and
Charger M
incorrect compared DIP-settings.
to configuration file.
The Charger M is
delivering a higher
current than the
maximum allowed
current limit to the
CURRENT affected Bus/Output. 1. Check the number of
modules configured.
214 LIMIT Charger M The Charger M is Major fault.
EXCEEDED consuming a higher 2. Check the external load.
current than the
maximum allowed
current limit from
the affected
PSU/Battery.
The battery
connected to the
CHARGING
affected Charger M Charge the battery with an
215 CURRENT Charger M Major fault.
is charged with a external charger.
EXCEEDED
higher current than
allowed.
The firmware in a 1. Try to reset the fault.
Charger M
module does not 2. If not possible to reset try to
ChangeOv
comply with the update firmware again.
er M Ext
INCOMPATIBL modules hardware (Might demand for system
216 I/O M 70 Major fault.
E FIRMWARE version. reboot.)
I/O M 700
The fault might
Mux M 16 3. Contact an authorized
occur during
Relay M 8 service office.
firmware update.
1. Measure the voltage from the
power source.
• If voltage OK, change
The voltage module.
delivered from PSU
HIGH • If voltage NOT OK,
217 Charger M 1 to the affected Major fault.
VOLTAGE PSU 1 change or adjust the
Charger M module
DC/DC.
is too high.
2. Contact an authorized
service office.
Unit or
Fault Code Cause Remedy Failure classification
Module
1. Measure the voltage from the
power source. • Minor fault if power
• If voltage OK, change sources are
The voltage module. redundant and not
delivered from PSU from the same
HIGH • If voltage NOT OK,
218 Charger M 2 to the affected source.
VOLTAGE PSU 2 change or adjust the
Charger M module
DC/DC. • Major fault if power
is too high.
from the same
2. Contact an authorized power source.
service office.
2. Contact an authorized
service office.
Unit or
Fault Code Cause Remedy Failure classification
Module
The voltage level
internally in the
Charger M is at least
1 volt below the
voltage delivered
from the PSUs.
INTERNAL Contact an authorized service
223 Charger M Without battery Major fault.
VOLTAGE LOW office.
charge, the system
shuts down at 18.5
VDC. With battery
charge, the system
shuts down at 21
VDC.
The voltage level
internally in the
Charger M is at least
1 volt above the
voltage delivered
INTERNAL from the PSU:s.
Contact an authorized service
224 VOLTAGE Charger M Without battery Major fault.
office.
HIGH charge, the system
starts up at 20.0
VDC. With battery
charge, the system
starts up at 25.5
VDC.
CM 4.3
CM 2.2
When the affected
CM X
module measures 1. Check backbone signals for
Charger M
the X-Fire signal in cable breaks.
ChangeOv
225 XFIRE SIGNAL the backbone, the Major fault.
er M Ext 2. Contact an authorized
voltage level of the
I/O M 70 service office.
signal is below 4
I/O M 700
volts.
Loop M X
Relay M 8
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
primary system bus connections according to the
CM 4.3 redundant.
PRIMARY within 30 seconds drawings.
226 CM 2.2
SYSTEM BUS by the master • Major fault if
CM X 2. Contact an authorized
(module with communication is
service office.
address 1) in the not redundant.
affected central.
No activity has been
• Minor fault if
registered on the 1. Check the electrical
communication is
secondary system connections according to the
CM 4.3 redundant.
SECONDARY bus within 30 drawings.
227 CM 2.2
SYSTEM BUS seconds by the slave • Major fault if
CM X 2. Contact an authorized
(module with communication is
service office.
address 2) in the not redundant.
affected central.
Unit or
Fault Code Cause Remedy Failure classification
Module
1. Check the electrical
The affected module connections according to the
has not responded drawings.
CM 4.3
NO ANSWER within 30 seconds
228 CM 2.2 2. Replace the module. Major fault.
SYSTEM BUS on
CM X
primary/secondary 3. Contact an authorized
system bus. service office.
Unit or
Fault Code Cause Remedy Failure classification
Module
A relay is broken or
in a state that
damages the relay.
233 RELAY Relay M 8 Replace the module. Major fault.
(The voltage over
the relay coil is too
high.)
The affected module 1. Check for cable breaks on
NO ANSWER is not answering on the extension bus. Major or Minor fault
RM 4.3
234 EXTENSION the extension bus depending on project
MN400 2. Contact an authorized
BUS where it is specific function.
service office.
connected.
1. Check the address of the
The type of module module according to
WRONG TYPE
System found is different electrical drawings.
236 OF MODULE Major fault.
modules from the type
FOUND 2. Contact an authorized
configured.
service office.
Unit or
Fault Code Cause Remedy Failure classification
Module
A write operation
Major or Minor fault
DEVICE WRITE into the loop unit’s
241 Loop units Replace the loop unit. depending on project
FAULT internal EEPROM
specific function.
memory failed.
CM 4.3 The system has not
Contact an authorized service
242 SERVICE TIME CM 2.2 been serviced for a Major fault.
office.
CM X period of time.
System
modules Internal system Contact an authorized service
255 ILLEGAL Major fault.
error. office.
Loop units
Active high By active high it means that the output is normally not energized in normal condition
and when system is not energized. By active high on input it means that the input is
normally not energized. This is the NO contact on a relay.
Active low By active low it means that the output is normally energized in normal condition and
system running. By active low on input it means that the input is normally energized.
This is the NC contact on a relay.
Alarm condition The state of the system when a fire or gas has been detected.
Alarm delay When activated the activation of alarm devices will be delayed for a preset time
(normally 2 minutes).
Alarm device Device that is activated in case of fire, for example audible and optical alarms like
bells, sirens and flashlights.
Alarm Transfer Output A supervised output for signalling that a fire has occurred. The Alarm Transfer Output
is usually used in onshore systems for alerting the fire brigade.
APF Application Program File.
Application program file A file holding the application parameters for the FDS.
ASP detector Aspiration detector.
Backbone Bus External The main bus outside a central cabinet used for communication between modules and
(BBE) stretched central parts. It consists of two redundant RS485 channels, two 24 VDC
power lines and the Basic Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone Bus Internal (BBI) The main bus inside a central cabinet used for communication between modules. It
consists of two redundant RS-485 channels, two 24 VDC power lines and the Basic
Backup (BBU) signal and Synchronisation Signal (SYNC).
Backbone segment A Backbone bus may be split in several segments. Power feeding can be separate for
each segment by using one Charger M per segment. Communication can be isolated
between segments by using Isolator modules.
Basic Backup Signal (BBU) A signal in the Backbone bus that is used for transmitting the central's alarm status.
The signal is only used when a module in managed mode loses communication with its
controller module.
BER Bit Error Rate
BusCon M 20 A Bus Connector with 20 connectors in the flat-cable. This unit is used to connect the
Control M 4.3 to the backbone bus and also has the common fire and fault outputs.
Cause/Effect The Cause/Effect program defines how the inputs and outputs of the system should act.
CCP Consilium Common Platform. General modules which create a system for Consilium
products.
CCP platform An umbrella name for all the modules and devices that can be connected together, e.g.
“the Control M 4.3 module is a member of the CCP platform”.
Central A Central is a complete system that can operate autonomously; monitor its detectors
and inputs, activate its outputs and display its faults and alarms. If connected to other
centrals, it exchanges information with the other centrals via the System bus, thus
allowing all centrals to act as one system.
Each central can only have one Backbone bus.
Central cabinet Enclosure to contain a complete or part of a central.
Charger M The Charger Module. Can connect two PSU’s and a battery and feeds the power
channels on the backbone bus.
Compact central Central cabinet including basic functionality of Fire Detection System such as: Control
panel, Power supply, Battery backup, basic I/Os and at least one analogue addressable
loop. The cabinet supplies limited expansion possibilities.
Configuration File A file holding the configurable parameters for the FDS.
Control module The Control M 4.3, the Control M 2.2 and the Control M X can all act as Controller
modules, i.e. be in controller mode.
Control panel The Control M 4.3 and Control M 2.2 can act as a Control panel, i.e. they have an HMI
and the rights to manipulate and supervise the system.
Controller mode Control modules can run in Controller mode, i.e. being Master or Hot Standby Master
within a central. Control modules can also be in managed mode, that is being a module
that is managed by the master. All other modules are always running in managed
mode.
Controller module A Control module that is in Controller mode (master or hot standby) in a central or
system.
Control M 2.2 A Control Panel with a 2.2” graphical colour display used to manage and supervise a
system.
Control M 4.3 Control Module with a 4.3” display, a keyboard and all the mandatory indications
required to comply with EN 54.
Control M X Control Module, a control module without a display, keyboard or mandatory
indications.
CR It is a heat detector class. The C means fixed alarm temperature at 84ºC. The R means
it also gives alarm for RoR.
CS Heat detector classification in EN 54-7; ‘C’ class indicates a static response
temperature of 84°C and ‘S’ that the detector will not respond below 80°C.
DCS Distributed Central System (see also Stretched central).
Detector A device capable of detecting smoke, heat, flames or gas.
DIP switch Dual in-line package switch. Used to set address etc. on loop units and modules.
Disablement Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
will be inhibited.
EMC Electromagnetic Compatibility.
EMI Electromagnetic Interference.
EN 54 The European product standard for fire detection and fire alarm systems.
ESD System Emergency Shut Down System, embedded system taking care of safety procedures in
case of emergency, for example shut down of fire doors, ventilation etc.
Ex Ex can mean different things depending on when it is mentioned. Examples: ‘Ex
proof’ means ‘Explosion Proof’, ‘Ex area’ means ‘Hazardous Area’ which is an area
where the atmosphere might be explosive. ‘Ex certified’ means both ATEX and IECEx
certification.
Ex-classification The protection type used in a hazardous area; e.g. Ex d.
Extension bus An additional (RS485) bus used inside a central for intra-central communication. The
Extension bus is typically used for connecting Repeater modules (that does not require
redundant communication and power) and should not be confused with the Backbone
bus.
External communication Communication to external entities is called external communication, using for
example MODBUS, NMEA or TCMS protocols.
External control Outputs used to control external equipment, for example fire doors.
Fault condition The state of the system when a fault is detected.
I/O 700 An Input/Output type providing a different function depending on the configuration of
the system. The programmable functions are:
• General Input
• Fault Input
• Output (24 VDC/700 mA)
I/O Module A module with inputs and/or outputs. I/O modules always run in Managed mode, that
is they must be managed by a Controller module.
I/O pin or I/O signal An I/O pin or an I/O signal is a logical signal, compare to terminal.
IDA The IDA communication protocol.
Inter-central communication Communication between centrals is called inter-central communication.
Interface channel A communication channel used to interface the systems with external devices.
Interface channels can be configured to communicate on different protocols.
Internal power supply Output power from PSU.
Intra-central communication Communication within a central is called intra-central communication. This
communication is between modules.
IP Ingress Protection - rating used to specify the environmental protection (enclosure) of
electrical equipment.
IS Intrinsically Safe.
Isolator M Isolator Module; used to distribute a part of a FDS.
ISS Integrated Safety System.
Loop The same as a loop-line.
Loop cable A cable which the FDS uses to power and communicate with the loop units. The loop
begins and ends in the loop module in the FDS.
Loop module The piece of hardware within the FDS which powers and communicates with the loop
units connected to its loop-line.
Loop unit Fire detectors, gas detectors, manual call points and other devices that can be
connected to the Loop.
Loop-line A common name for the cable, loop devices and other equipment connected to a loop
module.
Loop-line IS A part of the loop-line protected by a galvanic isolator.
LRU A Line-Replaceable Unit (LRU) is a modular component that is designed to be
replaced quickly at an operating location.
Managed mode The opposite of Controller mode. All modules that are managed by a Controller
module are in Managed mode.
MCP Manual Call Point.
MCS Multi Central System. A system consisting of more than one central.
MFZ Main Fire Zone.
Mode of operation Modules in the system can take on different roles. Connected to the Backbone bus they
can be in:
• Central Controller Mode (Master or Hot Standby)
• Central Managed Mode
Modules connected to the System bus can be in:
• System Controller Mode (Master or Hot Standby)
• System Managed Mode
Module A module that is a part of the platform, where it can be used to build centrals. Modules
within the platform generally supply a Backbone bus interface. Controller modules
also have a System bus Interface.
Module address Module addresses are set via DIP switches on the modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
N/A Not Applicable.
OEM Original Equipment Manufacturer.
PA Public Addressing.
Power output Output providing power supply, normally used to power external devices.
Pre-Alarm condition A condition preceding the Alarm condition to give early warning for potentially
dangerous situations like a smouldering fire.
Programmable output Output which signal behaviour is configurable via the Configuration program.
PSU Power Supply Unit.
Rate of Rise Rate of Rise functionality by using C/E commands for setting of a different alarm
threshold and temperature rise threshold for heat detectors.
Redundancy Refers to the quality or state of being redundant, that is exceeding what is necessary or
normal. In the system the term is used to describe backup functionality like in Hot
Standby Controller modules.
Redundant loop Redundant loop means loop module redundancy on one single loop-line between two
loop modules.
Relay Electrically operated switch output, normally providing C/NO/NC contacts for
connection of signal receiver.
Repeater panel The main attribute for Repeater panels is that they can show information but not affect
the central (or system) they belong to. The Repeater M 4.3 is a Repeater panel.
RS-485 Serial communication interface used for external communication and BackBone bus.
Is a standard defining the electrical characteristics of drivers and receivers for use in
balanced digital multipoint systems.
Safe State Modules enter 'safe state' when they detect system faults. Modules in Safe State put
their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
Salwico Language A text based interpreting language for making logical cause effect expressions
developed by Consilium.
SCI Short Circuit Isolator.
SCM Software Configuration Management.
SCS Single Central System.
SMig system Salwico Safety Management interactive graphics, a PC-based software package
providing graphical presentation and control of the system.
Spur Branch from a loop-line without return.
Stretched central (DCS) A central that is physically distributed to two or more physical locations. One location
may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
Sub-loop It is possible to connect sub-loop units to some loop units using a sub-loop cable. The
cable is however not a loop. One end is connected to the loop unit and the other end is
connected to the sub-loop unit.
Sub-loop unit A device which cannot be connected directly to the loop. A sub-loop unit can be a
switch or a relay contact will be used to send a fire or fault alarm to the FDS.
Synchronization signal A signal in the Backbone bus that is used for transmitting synchronization signal used
by system modules to synchronize there behaviour.
System A system consists of a number of loop units and one or more centrals.
System bus The communication bus used for connecting multi-central systems. The System bus is
used for inter-central communication but can also be used for external communication.
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System bus.
TBD To Be Done, To Be Decided/Determined.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Test condition Detectors put in the Test condition (or test mode) are inhibited from generating the
Alarm condition but the alarms are displayed on the Control panels to prove that the
tested detectors are operational.
USB Universal Serial Bus, a communications bus that may be used to connect flash
memories, keyboards, mice or other devices.
Warning Condition The state of the system when a warning is detected. Warnings are not as serious as
faults and only of informative nature, for example in case of a lightly contaminated
detector.
Zone A group of detectors located in a geographical area.
Index
A E
About testing.......................................................... 23 Earth fault, Troubleshooting .................................. 29
Address programming tool, Instructions for.......... 17 Electrical siren, Installation guidelines .................. 42
Address units, Setting the address ......................... 16 Electrical equipment, Location of.......................... 48
Address units, ID for AE/IC type .......................... 70
Address units, ID for NS-AIN type ....................... 69 F
Address units, Installation guidelines .................... 39
Fault list ................................................................. 27
Addressable indication units, Setting the address.. 16
Fault list ................................................................. 31
Addressable timers, Setting the address................. 16
Fault report............................................................. 32
Fault list ................................................................. 31
B Fire detection system, System description............. 5
Backbone Bus External (BBE), Electrical Fire history list ....................................................... 24
installation.............................................................. 10 Fire detection system, System data........................ 6
Basic Backup Signal .............................................. 83 Fire history list ....................................................... 22
BBU ....................................................................... 83 Firmware Update Tool, Troubleshooting............... 58
Bells, Installation guidelines.................................. 41 Firmware, Upgrade from microSD card ................ 54
BIOS, Upgrade for a CCP System......................... 49 Firmware, Upgrade from USB stick ...................... 51
BIOS, Upgrade in a control module via Ethernet .. 50 Firmware, Upgrade in a control module via
Broadcast buzzers ................................................. 18 Ethernet .................................................................. 56
Bus Isolator M........................................................ 75 Flame detectors, Installation guidelines................. 36
Buzzers, Group activation...................................... 18
G
C Guidelines, Loop units installation ........................ 35
Cable break, Troubleshooting ................................ 28
Cable requirements, Electrical installation ............ 10 H
Cabling, Installation guidelines ............................. 44
Heat detector, Installation guidelines..................... 36
Central unit terminal layout with cabling .............. 76
Change Over M Ext ............................................... 75
Charger M .............................................................. 75 I
Cold room Heat detectors, Installation guidelines. 39 I/O M 70................................................................. 75
Commissioning requirements ................................ 33 I/O M 700............................................................... 75
Control M 2.2......................................................... 75 Installation guidelines, Cabling and electrical
Control M 4.3......................................................... 75 installation.............................................................. 44
Control M X........................................................... 75 Installation order, Mechanical installation............. 9
Control Panel M 4.3, Installation order ................. 9 Intrinsically safe isolator........................................ 40
Control panel display, Testing................................ 26 IS Smoke detector for EX areas, Installation
Control panels, Mechanical installation................. 9 guidelines ............................................................... 37
Control panels, Electrical installation .................... 20
Conventional high temperature Heat detectors, L
Installation guidelines ............................................ 38
Loop lengths, Electrical installation ...................... 11
Loop M X............................................................... 75
D Loop units without address switches, Setting the
Detector loops, Electrical installation .................... 13 address.................................................................... 15
Detector loops, Cable requirements....................... 11 Loop units, Setting the address .............................. 15
DIP switch, Setting the ID ..................................... 69 Loop configuration................................................. 33
Disablement list ..................................................... 26 Loop status ............................................................. 33
Door holder magnet 130kp, Installation Loop units with address switches, Setting the
guidelines ............................................................... 42 address.................................................................... 15
Door holder magnet 65kp, Installation guidelines. 42 Loop units, Connections for................................... 71
Door release switch, Installation guidelines .......... 42 Loop units, Mechanical installation....................... 10
Download system log file ...................................... 32 Loops, Verification of ............................................ 21
www.consilium.se