0% found this document useful (0 votes)
261 views

Technical Specification For 33KV VCB Board

This document provides the technical specifications for a 33KV VCB board for use outdoors inside a structural shed. It includes specifications for the rated voltage, current, frequency variation tolerance, system details, earthing system, interrupter type, degree of protection, breaker ratings, breaking and making capacities, auxiliary contacts, busbar sizes and materials, insulation, color coding, wiring, surge protection, enclosure material, and other component details. The board will include 4 incomers rated 1250A each, 1 incoming rated 2000A, and 1 outgoing rated 2000A.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
261 views

Technical Specification For 33KV VCB Board

This document provides the technical specifications for a 33KV VCB board for use outdoors inside a structural shed. It includes specifications for the rated voltage, current, frequency variation tolerance, system details, earthing system, interrupter type, degree of protection, breaker ratings, breaking and making capacities, auxiliary contacts, busbar sizes and materials, insulation, color coding, wiring, surge protection, enclosure material, and other component details. The board will include 4 incomers rated 1250A each, 1 incoming rated 2000A, and 1 outgoing rated 2000A.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Technical specification for 33KV VCB Board – OUTDOOR KIOSK inside structural Shed.

33 KV Outdoor Make HT Board (4incomer+1Outgoing) for Solar Plant Power Evacuation


Sr. SCL Requirement incomer-1250A -3nos + Incoming -
Particular
NO. 1nos+ Outgoing -1 nos
1 RATED VOLTAGE 33KV (+/- 10%)
2 RATED SYSTEM CURRENT 1250Amp
3 Maximum Voltage 36KV
4 Allowable Voltage Variation +/- 10%
5 Allowable frequency Variation +/- 5%
Combined voltage & frequency
6 +/- 10%
Variation
7 SYSTEM DETAILS 3PH, 3 WIRE, 50Hz (+/- 5%),
8 SYSTEM EARTHING SOLID EARTHED SYSTEM

9 Type of interrupter VCB INDOOR (Vacuum) with inbuilt earth switch

DEGREE OF PROTECTION AS PER


10 IP54
IEC 62271-200
1250 AMP (3nos Incomer)+ 2000A 1 nos Incomer+
11 BREAKER RATING
Outgoing 1nos - 2000A
12 BREAKER MAKE Model ABB, Siemens
BREAKING CAPACITY OF
13 31.5kA/3 SEC
BREAKER
14 MAKING CAPACITY 100 KAp
Breaker In panel current rating
15 at 50Deg C ambient as per IEC VTS
62271-1,2017

One minute power frequency


16 withstand voltage to earth (wet 70kVRMS
and dry) rms

Impluse withstand voltage to


17 earth with 1.2/50µs, wave of +ve 170kVp
and -ve polarity (Peak)
18 First -pole-to clear factor 1.5
Rated operating sequence (for
19 O-0.3 sec-CO-3min-CO
auto reclosing)
20 CLOSING COIL CONTROL SUPPLY 110V DC

First TRIPPING COIL CONTROL


21 110V DC
SUPPLY
Second Trip Coil CONTROL
22 230V AC
SUPPLY
INDICATION CKT CONTROL
23 110V DC
SUPPLY
PANEL ILLUMINATION, SPACE
24 HEATER and UTILITY SOCKET 230V AC
SUPPLY
SPRING CHARGE MOTOR
25 90-260 AC/DC (Universal )
CONTROL SUPPLY
26 BREAKER AUXILIARY CONTACT 6NO+6NC Aux. Contact,
27 MAIN BUSBAR SIZE VTS as per design, type, and caluclations
28 MATERIAL OF BUSBARS COPPER

29 INSULATION OF BUSBARS HEAT SHRINKABLE SLEEVE - HBT (RATED FOR FULL IL)

30 BUS COLOR CODES R,Y,B COLOURED STICKER


31 EARTH BUS SIZE 50 x 6 mm/As Per Latest Standard
32 MATERIAL OF EARTH BUS COPPER
Internal Arc Testing for Breaker &
33 Internally Arc Tested at 40 KA
Panel as per IEC 62271
Light Sensors for Internal Arc
a shall be configured with relay
Protection 40kA
Cable Alley, Breaker Chamber, Bus bar chamber and
b No. of Light Sensors
Brekaer Jaw (4nos)
34 Insulation Class Class F (155)

35 LOTO system Lockout Tag out arrangement in Each panel

Breaker Operation (casstte


36 BREAKER RACK IN/RACK OUT FROM FRONT SIDE
mounted design)

PSU14_2X(Breaker Contact Multiplier)(52X) Projection


Mounted on Plug in Base
37 Breaker Multiplier Contacts:7NO+7NC,Aux Voltage:110VDC,
Electrically Reset Type Relay.
(52X)
ANNUNCIATION OC, EF, DIFFERENTIAL, OV, UV,86,TSS,AC
& DC SUPPLY FAIL
ANNUNCIATOR
38 AUX VOLT:90 -270 VAC/DC,FLUSH WITH PB FOR
(12 Windows)
ACCEPT/RESET/OP.TEST/SILENCE ALARM CONT.FOR
TRIP/NON-TRIP,OP:MANUAL RESET

3 PHASE, 4 WIRE,CT:1A, ANALOG OUTPUT:4-20mA, NO.OF


OUTPUT:FOUR
AUXILIARY SUPPLY:110VDC/AC, PT SEC.:110VAC, CT/PT
39 Multifunction Transducer PROGRAMMABLE,ACCURACY CLASS:0.2,
Supported communication protocol :RS
485/Modbus/TCP over IP, Accuracy class 0.2 Rishabh
M40

TRIP CIRCUIT SUPERVISION RELAY NON-DRAWOUT, FLUSH,


CASE SIZE:1/2 CONTACTS :1NO+1NC+2C/O SR AUXILIARY
41 TRIP CIRCUIT SUPERVISION RELAY VOLTAGE :110-125V AC/DC (95)
TRIP CKT SUPERVISIONOF BOTH DC AND AC TRIPPING
COILS TC-1 & TC-2 OF BREAKER

42 Master Tripping relay Tripping Relay,(86) With HR Flag Aux.Volt:110 V DC

With Base For Plug-in Relay, Aux.Voltage: 110V DC,


43 DC Failure Relay
Contacts:4C/O SR (80F)DC FAIL RELAY

With Base For Plug-in Relay, Aux.Voltage:110V DC,


44 Anti pumping Relay
Contacts: 4C/O SR (94)

Control wiring 1.5 Sq.MM, CT CKT: 2.5 Sq.mm, PT CKT: 2.5


45 CONTROL WIRING CABLES
Sq.mm, AC CKT: 1.5 Sq.mm FRLS WIRE,

46 CABLES MAKE Universal / Polycab / KEI / CCI / RPG / Finolex / Havells.

DC CKT: GREY, AC CKT: BLACK, EARTHING CKT: GREEN


47 COLOUR CODE
RED FERRULES PROVIDED FOR TRIP CKT

48 CT & PT CKT R-RED, Y-YELLOW, B-BLUE, N- Black, Earth- Green


COMMUNICATION/SIGNAL
49 SHIELDED PAIR CABLE 1.5 Sq.mm Copper
CABLE
50 PAINT SHADE As per existing HT Panel
PANEL MADE UP OF ALUZINC MATERIAL & DOOR WITH
51 Material
CRCA SHEET METAL
Surge protection (SPD) with
52 Type-1 ZNO METAL OXIDE(GAPELESS)SURGE ARRESTOR
surge counter
53 Panel enclosure Aluzinc Sheet/CRCA
54 Frame 2 mm ALZINC/CRCA
55 Side panel & Doors 2.0 mm thick CRCA Sheet
56 Gland Plate 3.0 mm thick CRCA Sheet
57 Operating Height Max. 2.2 mtr & minimum 0.4 mtr
58 Incoming Cable Entry Bottom

Both Incomer should be suitable for 3R*240sqmm


1. incomer 1- 2R/ Phase, Total 2 Run 3R*240 mm2 Cable
2. incomer 2- 3R/ Phase, Total 2 Run ,3R*240 mm2 Cable
Bus Bar Jointing /Cable
59 3. incomer 3- 2R/ Phase, Total 2 Run ,3R*240mm2 Cable
termination Arrangement
4. incomer 4- 2R/ Phase, Total 2 Run ,3R*240mm2 Cable
1. Outgoing with 5R/ Phase, Total 15 Run ,3Cx300 mm2
Cable

Bi directional measurement
(Accuracy: 0.2s) , Power , Energy, Harmonic distortions,
60 MULTIFNCTION ENERGY METER Analog Output : 4-20mA (2Nos),
communication : Modbus and Ethernet/Optical with
compatible software to communicate with SCADA

MULTIFNCTION ENERGY METER


61 Secure/ Enercon/L&T / Scheinder / Socome / SATEC/GE
MAKE
TERMINAL BLOCKS (CONTROL)-
62 ELMEX / PHOENIX / CONNECTWELL / WAGO.
Wags screwless
Line PT
Cast Rasin, Draw Out Type Potential Transformer with
01 No. PT is to be supplied loose
Fuse, PTR : 33KV/√3/110/√3/ 110/√3/ 110/3 Core 1: 30
as spare
63 VA, CL 0.2
BALAJI / ETE / KAPPA / VIDHYUT /
Core 2: 30 VA, CL 3P
PRAGATI/AE/AS PER UHBVN
Core 3: 30 VA , CL 3P(open delta with VDR)
Approved Vendors

64 PT VOLTAGE FACTOR 1.2 TIMES FOR CONT. & 1.9 TIMES FOR 8 HRS, 36/70/170KV

65 PT OPERATION Draw Out Type


50/1A 1%of EF min range for sensitive E/F 50/1 A CBCT
CBCT
should be capable

Incoming - CAST RESIN CT,CTR: 300/1A, 0.2s, 5P20, PS,


Current Transformer
10VA
3 Nos. 1 Phase CTs
STC: 40KA/1Sec
01 No. CT is to be supplied loose
Total 03 Nos. CTs are to be installed in Panel
66 as spare
Outgoing - CAST RESIN CT,CTR: 1250/1A, 0.2s (10VA),
BALAJI / ETE / KAPPA / VIDHYUT /
5P20, PS,PS (Transformer Diff. and REF)
PRAGATI/AE/AS PER UHBVN
STC: 40KA/1Sec
Approved Vendors
Total 03 Nos. CTs are to be installed in Panel

Numerical Protection Relay


(50+51+50N+51N+86+94+80+95+67+67N+27 +59+Sensitive
Protection
earth fault ) with Inrush Feature & Earth fault sensitive
Order code and relays in both
feature <0.2 %+ +Vector Surge relay/decoupling relay ) +
incomer panels (4 installed +
67 DF/DT & LOAD SHEDDING protection
2loose)
COMM PROTOCOL:WITH REAR RS485 FOR MODBUS, IEC
61850 BI:12 BO:10 AUX VOLTAGE:110V DC
Communication :Ethernet/Optical, AUX VOLTAGE:90 -
270Vac/dc, with compatible software

Cable/Line Differential 87C/87L


RED 615 - 1 Nos of Relay in each panel WITH FIBRE OPTIC
(4installed+ 2loose) for incomers
PORT (87C) COMM PROTOCOL:WITH REAR RS485 FOR
68 Order code and relays in both
MODBUS and IEC61850 BI:12 BO:10 AUX VOLTAGE:110V
incomer panels with LIU & patch
DC with Patch Cord and LIU
chord

69 RELAY MAKE ABB


All settings, scheme logic, event records etc. shall be
accessible through the HMI in Numerical Relay

70 Realys Common Features The numerical relays shall have continuous self-
monitoring and cyclical test facilities. The internal clock
of the system shall be synchronized through the GPS
Time Synchronizing System.

All Spare Contacts of Breaker, Relays and Energy Meter


71 Spare Contacts are required to be wired upto terminalfor Remote
Monitoring use
72 Warranty 2 Years
Site Testing and Comissioning of HT Panel and Complete
74 Comissioning Services (3days)
Protection System
SCL Inspection / Waiv off will be required before
76 Inspection
dispatch
77 Spares As per annexure
Base frame of suitable size for all
78 panels shall be in scope of As per panel Design & GA
supplier.
For Outgoing 33 kV HT board metering arrangement (adapter board)

Metering Panel/ Adapter Panel


(suitable for 2 nos of energy
For ABT metering as per metering regulations and sealing
79 meter) and separate CT & PT
arranagments for both TTB's
and panel shall have necessary
sealing arrangements

TERMINAL BLOCKS (CONTROL)-


Wags screwless ELMEX / separate sealing for TTB provide for metering in Adapter
a
PHOENIX / CONNECTWELL / panel
WAGO.

Line PT
Cast Rasin, Draw Out Type Potential Transformer with
01 No. PT is to be supplied loose
Fuse, PTR : 33KV/√3/110/√3/ 110/√3
as spare
b CORE 1: 0.2, CORE 2: 0.2 (to be provided as per CSPTCL
BALAJI / ETE / KAPPA / VIDHYUT /
approved make and specifications ) with proper sealing
PRAGATI/AE/AS PER UHBVN
arrangement of PT sec. Terminal
Approved Vendors

c PT VOLTAGE FACTOR 1.2 TIMES FOR CONT. & 1.9 TIMES FOR 8 HRS, 7.2/20/60KV
d PT OPERATION Draw Out Type

Current Transformer CAST RESIN CT,CTR: 1250/1A, 0.2s, 0.2s


BALAJI / ETE / KAPPA / VIDHYUT / Total 03 Nos. CTs are to be installed in Panel to be
e PRAGATI/AE/AS PER UHBVN provided as per CSPTCL approved make and
Approved Vendors 01 No. CT is specifications) with proper sealing arrangement of CT
to be supplied loose as spare sec. terminal

ABT Meter, Make : SECURE METER Model : ProQ Standard


Class 0.2S, with RS 485 Port, sealing arrangement at Main
Cover ,terminal cover ,15 Minute block average for Freq.
ABT Meter , Energy, Bidirectional feature.
(Availability Based Tariff Meter as
per latest Standard) with DLMS and TOD Features Required. 15 Min. Blocks Energy,
f Terminal sealing ,TTB sealing and Load Survey Log of 30 Days
Meter sealing arrangement is Including SANDS MRI tool and Licenced BCS Software
required for Metering cum (for Data aquiring to PC) ABT Meters Pl. consider ABT
adaptor panel meter with CMRI tool + Licensed software for
communication with installation , cable for
communication to meter and CMRI tool to Computer
and all other accessories