SM8420 00 - en Us

This document provides specifications for the SM8420 magnetic-inductive flow meter. It measures flow rates from 0.2 to 150 l/min with an accuracy of ±(0.8% of measured value + 0.2% of full scale). It has 2 digital outputs, 1 analog output, and can measure temperatures from -20 to 90°C. The flow meter connects via an IO-Link interface and supports various output configurations and parameter settings.

Uploaded by

Angga Suryadarma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views6 pages

SM8420 00 - en Us

This document provides specifications for the SM8420 magnetic-inductive flow meter. It measures flow rates from 0.2 to 150 l/min with an accuracy of ±(0.8% of measured value + 0.2% of full scale). It has 2 digital outputs, 1 analog output, and can measure temperatures from -20 to 90°C. The flow meter connects via an IO-Link interface and supports various output configurations and parameter settings.

Uploaded by

Angga Suryadarma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

SM8420

Magnetic-inductive flow meter


SMK11XGXFRKG/US-100

Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Measuring range 0.2...150 l/min 0.012...9 m³/h 3.6...2378 gph 0.06...39.6 gpm
Process connection Rc 1 DN25
Application
System gold-plated contacts
Media Conductive liquids; water; water-based media
conductivity: ≥ 20 µS/cm
Note on media
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C] -20...90
Pressure rating [bar] 16
Pressure rating [Mpa] 1.6

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — SM8420-00 — 10.08.2021 —
SM8420
Magnetic-inductive flow meter
SMK11XGXFRKG/US-100

Electrical data
Operating voltage [V] 18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 80
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 5
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Inputs
Inputs counter reset
Outputs
Total number of outputs 2
Output signal switching signal; analog signal; pulse signal; IO-Link; frequency signal; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Max. voltage drop switching
[V] 2
output DC
Permanent current rating of
[mA] 100
switching output DC
Number of analog outputs 1
Analog current output [mA] 4...20; (scalable)
Max. load [Ω] 500
Pulse output flow rate meter
Short-circuit protection yes
Type of short-circuit
yes (non-latching)
protection
Overload protection yes
Measuring/setting range
Measuring range 0.2...150 l/min 0.012...9 m³/h 3.6...2378 gph 0.06...39.6 gpm
Display range -180...180 l/min -10.8...10.8 m³/h -2853.6...2853.6 gph -47.56...47.56 gpm
Resolution 0.1 l/min 0.006 m³/h 0.6 gph 0.01 gpm
Set point SP 1...150 l/min 0.06...9 m³/h 16.2...2376 gph 0.27...39.6 gpm
Reset point rP 0.2...149.2 l/min 0.012...8.95 m³/h 3.6...1903 gph 0.06...39.42 gpm
Analog start point ASP 0...120 l/min 0...7.2 m³/h 0...1903 gph 0...31.71 gpm
Analog end point AEP 30...150 l/min 1.8...9 m³/h 475...2376 gph 7.92...39.6 gpm
Low flow cut-off LFC 0.2...7.5 l/min 0.012...0.45 m³/h 3...118.4 gph 0.05...1.98 gpm
Frequency end point, FEP 30.2...150 l/min 1.8...9 m³/h 480...2376 gph 8...39.6 gpm
Frequency at the end point
[Hz] 1...10000
FRP
Volumetric flow quantity monitoring
Pulse length [s] 0.002...2
Pulse value 0.01...99990000 I

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — SM8420-00 — 10.08.2021 —
SM8420
Magnetic-inductive flow meter
SMK11XGXFRKG/US-100

Temperature monitoring
Measuring range [°C] -20...90
Display range [°C] -42...112
Resolution [°C] 0.1
Set point SP [°C] -19.6...90
Reset point rP [°C] -20...89.6
Analog start point [°C] -20...68
Analog end point [°C] 2...90
In steps of [°C] 0.1
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring
± (0,8 % MW + 0,2 % MEW)
range)
Repeatability ± 0,2 % MEW
Temperature monitoring
Accuracy [K] ± 2,5 (Q > 5 % MEW)
Reaction times
Flow monitoring
Start-up delay [s] 0...50
Response time [s] < 0.25; (dAP = 0, T09)
Damping for the switching
[s] 0...5
output dAP
Temperature monitoring
Response time [s] 15; (Q > 10 % MEW, T09)
Software / programming
hysteresis / window; normally open / closed; switching logic; Frequency output;
Parameter setting options
current/pulse output; Start-up delay; display can be deactivated; Display unit
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port class A
Process data analog 3
Process data binary 2
Min. process cycle time [ms] 6
Type of operation DeviceID
Supported DeviceIDs
default 966
Operating conditions
Ambient temperature [°C] -20...60
Storage temperature [°C] -25...80
Protection IP 65; IP 67

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — SM8420-00 — 10.08.2021 —
SM8420
Magnetic-inductive flow meter
SMK11XGXFRKG/US-100

Tests / approvals
EMC DIN EN 60947-5-9
model number 006MI
accuracy class -
maximum allowable error ± 1,0 % FS
CPA approval
Q (min) 0,01 m³/h
Q (t) -
Q (max) 9 m³/h
Shock resistance DIN IEC 68-2-27 20 g (11 ms)
Vibration resistance DIN IEC 68-2-6: 5 g (10...2000 Hz)
MTTF [years] 114
UL approval number I014
UL approval
File number UL E174189
Pressure equipment directive sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 775.3
Material stainless steel (1.4408/316); stainless steel (1.4404 / 316L); PC; PBT+PC-GF30
Materials (wetted parts) stainless steel (1.4404 / 316L); PEEK; carbon fiber PEEK; FKM
Process connection Rc 1 DN25
Displays / operating elements
Color display 1,44", 128 x 128 pixels
Display
2 x LED, yellow
Remarks
MW = Measured value
Remarks
MEW = Final value of the measuring range
Pack quantity 1 pcs.
Electrical connection
Connector: 1 x M12; Contacts: gold-plated

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — SM8420-00 — 10.08.2021 —
SM8420
Magnetic-inductive flow meter
SMK11XGXFRKG/US-100

Connection

Colors to DIN EN 60947-5-2


OUT1: Switching output Volumetric flow quantity monitoring
Switching output Temperature monitoring
Pulse output quantity meter
Frequency output volumetric flow monitoring
Frequency output Temperature monitoring
signal output Preset counter
IO-Link
OUT2: Switching output Volumetric flow quantity monitoring
Switching output Temperature monitoring
analog output flow
analog output temperature
Input counter reset
Core colors :
BK = black
BN = brown
BU = blue
WH = white

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — SM8420-00 — 10.08.2021 —
SM8420
Magnetic-inductive flow meter
SMK11XGXFRKG/US-100

Diagrams and graphs

Pressure loss / volumetric flow quantity