Please follow the diagram below for wiring. And pay attention to the following issues:
Please follow the diagram below for wiring. And pay attention to the following issues:
+ PB - R S T U V W
DC-LINK POWER MOTOR
1
5 Figure 1-5 110kw-250kw Main Circuit Terminal Blocks
5 Table 1-6 Function description of the main circuit terminal of the inverter
Safety capacitor and varistor grounding selection screw (SIZE A~SIZE C EMC
EMC、VDR
screw on the left side of the fuselage)
The power output of the PV panel is connected to the “+” and “-” terminals. Please note that the
polarity is not reversed.
Make sure that the inverter input AC voltage level is consistent with AC grid voltage before
connecting with Input “R”, “S” and “T” terminals
If Grid is single-phase power supply, you can connect to R T or any two terminals of “R”, “S” and “T”.
If customer use PV solar only ,it is recommended to connect PV cable to any of RT
terminal,no polarity request
2
2、 VFD500M-PV Electrical cable Connection
Please follow the diagram below for wiring. And pay attention to the following issues:
Please follow the diagram below for wiring. And pay attention to the following issues:
5 Table 1-7 Function description of the main circuit terminal of the inverter
Safety capacitor and varistor grounding selection screw (SIZE A~SIZE C EMC
EMC、VDR
screw on the left side of the fuselage)
The power output of the PV panel is connected to the any two terminal of L1 L2 L3 on priority
Or if L1 L2 L3 are connected for AC grid ,+ terminal is for solar positive and PB for solar negative.
Make sure that the inverter input AC voltage level is consistent with AC grid voltage before
connecting with Input “L1”, “L2” and “L3” terminals
If Grid is single-phase power supply, you can connect to L1 L2 or any two terminals of “L1”, “L2”
and “L3”。
If customer use PV solar only ,it is recommended to connect PV cable to any of RT
terminal,no polarity request
220V 380V
Recommended DC input
250V-400V 450V-600V
voltage range (Vmpp)
3
Recommended Input Operation
305V(Vmpp) 530V(Vmpp)
Voltage
Ambient temperature range -10 °C~50 °C, derating if the temperature is above 40 °C
Standard CE/ROHS
Noted: We suggest solar panel power should be 1.4-1.5 times higher than solar pump power ,and solar pump
inverter power should be higher level than solar pump. When solar pump distance to inverter higher than
100m,it should be equipped with Output reactor or higher level power inverter .for Solar panel,l total VOC
less than Maximum DC voltage of inverter and Solar panel vmp is recommend 530V for 380V pump and 305V
for 220V pump
Power size of VFD500-PV refers to the standard 4 poles induction motor at rated voltage.
Overload: 150% rated output current, 1 minute
4
Drive model Max DC input current (A) Rated output current (A) Applicable water pump (kW)
VFD500M-40T00220-PV 12 5 2.2
VFD50040T01100-PV 39.2 25 11
VFD500-40T01500-PV 49.0 32 15
VFD500-40T01850-PV 50 37 18.5
VFD500-40T02200-PV 60 45 22
VFD500-40T03000-PV 81 60 30
VFD500-40T03700-PV 90 75 37
VFD500-40T04500-PV 130 90 45
VFD500-20T00400-PV 22.6 17 4
VFD500-20T00550-PV 30 25 5.5
5
VFD500-20T00750-PV 40 32 7.5
VFD500-20T01100-PV 60 45 11
VFD500-20T01500-PV 81 60 15
VFD500-20T01850-PV 90 75 18.5
VFD500-20T02200-PV 130 90 22
Noted 1: when the output voltage is 380V, the output current will be rated value; when the output
voltage is 400V、415 V or 440V,the output current will be calculated according to power.
Noted 2: when the output voltage is 220V, the output current will be rated value
6
For 380V OR 220V or 110V Three phase motor Pump connection
Q2
Solar panels
Q1 + PB -
R U
3 phase power input
S V M
T W
Main circuit
Control circult
PLC
Connector slip
+24V
Start/stop terminal 485+
DI1 RS485 port
Forced switch to 485-
mains
DI2
AO1
COM COM
DO1
+10V
AI1
AI1、AI2 input:
0~10V/0~20mA AI2 COM
GND T1A
Relay 1 output,
T1B Default is fault
signal output
T1C
OFF OFF
T2A
485 AI1 AI2 AO1 AO2 Relay 2 output,
ON V V V V T2B Default is auto main
ON ON & PV switching
Water T2C
Well Grounding (Optional)
tower OFF I I I I
1.3 VFD500-PV Wire Diagram of solar pump inverter (three phase pump)
7
Q2
Solar panels
Q1 + PB
R/L1 U
3 phase power input S/L2 V M
T/L3 W
Main circuit
Control circuit
+24V
Start/stop terminal
DI1 485+
Forced switch to RS485 port
mains 485-
DI2
HDI AO
AO output:
COM 0~10V/0~20mA
GND
High water level switch
DI3
Low water level switch
DI4
HDO
COM
COM
+10V
TA
AI input: AI1 Relay
0~10V/0~20mA TB output,Default is
AI2 fault signal output
TC
GND
OFF ON PE
I V AO
I V AI1
OFF ON 485
Water
Well
tower
1.4 VFD500M-PV Wire Diagram of solar pump inverter (three phase pump)
NOTE:
1:VFD500-PV Solar array output should be connected to the terminal ( +DC、-DC) of the
drive, please pay attention to the polarity of the solar array or you can connect solar array to R
and T but VFD500M-PV Solar array output should be connected to L1 L3 OR L1 L2 OR L2 L3
2: For control wire, recommend using shielded cable or shielded twisted pair.
3: Do not suggest using the power contactor to control the RUN/STOP of the drive.
4:In default carrier frequency, the maximum motor cable length is 100 meters. When the
motor cable is longer than 100m, it is recommended to use output reactor or DVDT filter or Sine
wave filter .
8
For 220V single phase motor connection
1: Single phase asynchronous motor wiring method (without
starting capacitor):
Notice: U is connected to the common end of the starting winding and the working
winding, V is connected to the starting winding, and W is connected to the working
winding;
Single-phase asynchronous motor if the rotary steering is not correct, you can
change the V and W wiring or set P22.13=1。
First solution: Set parameter P11.01=1 (Single phase motor type without capacitor) or
second solution: set P00.11=00031 if your motor frequency is 50 hz or set P00.11=32 if
your motor frequency is 60HZ
Q2
Solar panels
Q1 + PB -
Public terminal
Single phase AC R U
power input Start winding M
S V
Working winding
T W
Main circuit
VFD500-PV Wire Diagram of solar pump inverter (single phase pump without capacitor)
Q2
Solar Panels
Q1 + PB -
Single phase AC R U
power input S V M
Public terminal
T W
Main circuit
VFD500M-PV Wire Diagram of solar pump inverter (single phase pump without capacitor)
9
For 220V single phase motor connection
2:Single-phase asynchronous motor wiring method (with capacitor)
Notice1:First solution: Connect motor cable to power terminal U and V and enter BSC
mode to Set parameter P23.15=0(output phase loss shielding protection) or second
solution: set macro P00.11=00021 if your motor frequency is 50HZ or set P00.11=22 if
your motor frequency is 60HZ
Q2
Solar Panels
Q1 + PB -
Single phase AC R U
power input S V M
Public terminal
T W
Main circuit
VFD500-PV Wire Diagram of solar pump inverter (single phase pump with capacitor)
Notes: Single phase motor has three lines, first use the universal meter to check the
three lines resistor, the biggest value two lines parallel the start capacitor (recommend
the capacitor volume is 150UF/250V), the other line(common-coil) connect the power
terminal. Then use the universal meter to check the common coil with the other two
lines resistor, the lower one connects another power terminal
10
Wiring method for Compensation of Grid and Solar DC supply
The back of the photovoltaic panel must be connected with anti-reverse diodes, and
the photovoltaic panel will be damaged after the current is recharged
Q2
-
+
Solar panels
Q1 AC Contactor(KM1) + PB -
R/L1 U
AC M
S/L2 V
Input~
T/L3 W
KM1
T2A
220V~ T2B
T2C
Wiring diagram of main circuit for simultaneous photovoltaic and power supply
11
1.4 Control Circuit Terminal
OFF
Jumper switch
ON
K2
I
485 AI1 AI2 AO1AO2
K1
OFF
ON
PE1 PE2
+10V AI1 AO1 485+ GND DI1 DI2 DI3 DI4 HDI T1/A T1/B T1/C
GND AI2 AO2 485- COM DO1 HDO COM PLC +24V T2/A T2/B T2/C
13
2、Trial run(How to start solar pump inverter)
Make sure all cables connections of solar panel and pump motor correct and no
need to set any parameter, if you want to set parameter, you can do as follows.
Step 1: (Keypad control):Set motor parameter P11.02- P11.06 as per motor pump name
plate If dry run protection is required, measure the unload protection current(see details in
user manual chapter for dry run function) If dry run protection not required then miss this step
and go to step 2.
Step 2: Set other related special solar pump parameters for optimization if needed.
Step 3: After trial run finishing, if motor pump still not output water when inverter is running
more than 40 Hz. Please disconnect the power supply and replace any two-phase wiring of
the motor.
PMSM pump
Synchronous motor must be self-learning of motor parameters, otherwise there will be a risk
of flying,
P11.00=1 set to synchronous motor(special software)
P11.02=motor nameplate power
P11.03=Motor nameplate voltage
P11.04=Motor nameplate current
P11.05=motor nameplate frequency
P11.06=Motor nameplate speed
P11.22=Back EMF on the motor nameplate
If there is no such parameter on the nameplate, you can try to set 300V 350V for self-
learning (try self-learning for 380v level)
The difference between the back-EMF setting value and the actual value should be less
than 20%, otherwise the self-learning will be abnormal
After the parameter setting is completed, set P11.10=2, press RUN then the keyboard
appears Tune for self-learning.
2. How to use a float in the water tank to stop the pump if the tank is full?
If your float signal is digital signal Use float switch to short DI 3 and com ,see diagram 1.3
14
3.Use level probe in the well for protection against dry running
1st solution: See self learning of dry run(For LED display)
2nd solution: do it manually Set P24.13=30%-60%(as per real empty load current percentage based on
rated current) and P24.14 P24.16 and P23.21
3rd solution: If your sensor is digital switch ,just short D4 and com
4th solution:If your float signal is Analog signal, Connect Ai2 and 10V and GND and set P41.00=23 and
P41.03-P41.06
4.How to set minimum frequency ( for example) 30hz and maximum 50HZ
Set P47.05=30HZ and 47.06 to some time and 47.07 to some time. Please refer to details of P47.05-47.07
10. How to check and solve basic problem of inverter trips and error
a:Check the total vmp and voc of solar panels ,solar panel technical data
b:Check motor pump power and rated current
c: Check the distance between motor and inverter
d: Check trip record r25.00 r25.01 25.02 25.03 r26.00 r26.01 r26.02 r26.03 r26.08 r26.09 r26.10 r26.11
e: Check troubleshooting fault and find relevant solutions
f : Check if motor insulation has been damaged or motor is blocked
15
3、Keypad display
3.1 LED Instruction of operation and display
LED keyboard consists of 5 digital tubes, 7 lights, 8 keys and a potentiometer; can be used to set the
parameters, status monitoring and operation control, LED keyboard shape as shown in Figure 4-1:
Table 3-2 The name and function of each part of the keyboard
No. Part Name Function
1 Exit • exit menu level
16
8 Stop/Reset • During operation, press to stop the operation (restricted by
parameter 21.03).
• In fault status, press this key to reset the fault.
9 Indicator light:Hz ·Indicate the digital display unit, all three lights off menas other
units
10 Indicator light:A
11 Indicator light:V
12 Indicator When Hz" and "A" are lit at the same time, the unit of the currently
light:HZ+A(rpm/min displayed parameter is "RPM PER MINUTE
ute)
13 Indicator light: When "A" and "V" are lit at the same time, the unit of the currently
A+V(%) displayed parameter is "percent".
14 Running lights • Off: indicates a stop condition.
• On: indicates inverter is running.·
Blinking: Deceleration stopped.
15 Direction indicator • Used to indicate the sign of the variable when the LED is
displaying one of the variables listed in 27.02;
• In other cases the sign of the output frequency is indicated.
16 Command source • Off: The command source is the keyboard.
indicator • On: The command source is terminal.
• Blinking: The command source is communication.
17 Fault indicator • When it is on, the drive is faulty.
VFD500-PV digital keyboard display is divided into four layers, from top to bottom are: monitoring status, menu mode
selection status, function code selection status, parameter editing / viewing status, as shown in Figure 4-2. In the menu mode
selection status, press 【UP】 or 【DOWN】 key to select menu mode, press 【ENTER】 to enter the selected menu
17
SHIF SHIF SHIF SHIF
MONITO
R T T T T Monitoring
volume1
STATUS
Monitoring volume1 Monitoring volume2 Monitoring volume3 Monitoring volume4
ESC
MENU UP UP UP UP
CHOOSE “-bSC-
ESC
STATE ”
Standard mode DOWN User-difined mode DOWN DOWN DOWN
Check mode Wizard mode
ESC ENTER ESC ENTER ESC ENTER ESC ENTER
COMMAND
CODE
【UP、DOWN、SHIFT】 【UP、DOWN】 【UP、DOWN】 【UP、DOWN】
PARAMETER
EDIT/VIEW
STATUS
【UP、DOWN、SHIFT】 【UP、DOWN、SHIFT】 【UP、DOWN、SHIFT】 【UP、DOWN、SHIFT】
When the inverter is in the stop state, the digital tube is cyclically scrolling to
display:
“00000”DC bus voltage(r27.03)given frequency(r27.01)“00000”
When the inverter is in running state, the digital tube is cyclically scrolling to
display.:
“00000”DC bus voltage(r27.03)output frequency(r27.00)output current
(r27.06)output ac output voltage(r27.05)“00000”
After the solar pump inverter is power on, the keyboard menu mode is user-
defined mode. Most of users only need to pay attention to the parameters displayed
in this mode. To check the complete inverter parameters, press the and
18
3.5 Error code:For other alarm codes, please refer to Chapter 5 of the manual.
alarm code meaning
Light weak fault, please refer to function
Sleep
code P47.05~P47.07
A.FULL Full water protection P47.18-47.21
After the above warning occurs, the solar pump inverter will decelerate to stop and
cannot be started again until the warning condition is not released. When the warning
is released, the system will start automatically.
During the warning, the digital tube will flash the alarm code, and after 2s, it will display
the other interface for 2s.
20
Function Name Description Default Property
code
motor name plate and motor model
parameter be careful to use
P11.03 Motor rated voltage 10V~2000V Depend ★
P11.02<30kW:0.01A
P11.04 Motor rated current Depend ★
P11.02>=30kW:0.1A
P11.05 Motor rated frequency 1.00Hz~600.00Hz 50.00Hz ★
P11.06 Motor rated RPM 1~60000rpm Depend ★
R16.02
0:Standard mode (display frequency only)
P21.00 Monitoring display 1:Automatic scrolling display(Check 3.1 in 0 ★
detail )it show hz,current,power and voltage
220V level: 160V~300V
P23.02 Undervoltage threshold 220/380 ★
380V level: 350V~520V
Undervoltage trip 220V Level:160V~300V
P23.05 200/300 ★
threshold 380V Level:350V~520V
Output phase loss 0.0-25%, 0% means output phase detections
P23.15 25% ☆
function shielded
Unit:hour
Accumulative running
r27.15 ●
time
0: invalid
The parameters behind the 47 group
cannot be changed!
Solar pump Mppt 1: Enable, to enable the special mppt
P47.00 1 ★
function enable function of the PV pump inverter
22
Function Name Description Default Property
code
0.001~1.00 tracking response.it is not
P47.10 Regulator integral gain 0.05 ☆
recommended to change
P47.28 Starting coefficient 0.000~1.000 0.850 ☆
Unit digit:fast starting
0:Disable 1:Enable
P47.30 Fast speed function 11 ☆
Ten digit:Fast mppt tracking
0:Disable 1:Enable
47.03 is waiting time to start solar pump inverter without press start button, Our solar pump inverter Is purely
automatic start ,no setting software and simple and smart
Make sure solar panels cables and motor cables are well connected ,it will automatically start after 600S,10
Minutes is a threshold ,if you want to test this function ,you can set P47.03=10s,so power off and power on ,it will
start after 10s
Set the starting voltage of the MPPT
algorithm.
P47.04 MPPT starting voltage 305V(530V) ★
When the MPPT function is disabled, this
value is the reference voltage.
This is Manual mppt threshold voltage ,when you want to use manual mppt mode ,first you need to set mppt
function disable P47.01=00 (Unit digit 0 is means manual control ,ten’digit 0 is means CVT enables also manual
mppt function ,you can check solar panel configuration and calculate VOC and VMP and set P47.04=VMP
24
Function Name Description Default Property
code
to Sleep and stop
If automatic switching is enabled, it will
switch to ac grid operation, and the MPPT
function will be disabled
This is light detection threshold to measure solar radiation and solar power in a setting time (P47.06 Detection
time),if customer do not want to keep pump running below this frequency so it can make pump sleep below this
frequency ,for example ,if pump can not run to 20hz in a setting time ,inverter will sleep and stop. if solar power
is enough in detection time ,then it will not report sleep alarming and return to normal
0.0~3000.0s
1. When DI-60 is valid
2. The analog detection channel is greater
than P47.19 (positive logic) or the analog
Full water level
P47.20 detection channel is less than P47.19 10.0s ☆
detection time
(inverse logic)
When 1 or 2 conditions are met and P47.20
is maintained, the system reports A.Full and
shuts down
Full water recovery 0.0~3000.0s
P47.21 10.0s ☆
time When the condition described in P47.20
26
Function Name Description Default Property
code
does not meet full water level detection
requirement ,it will be returned to normal
state after delay
Conditions for full water detection to take effect:
1. The DI terminal arbitrarily set to function No. 60 receives the input switch close signal. For example, when
P06.03 is set to 60, DI3 is closed.
2. When the ten’s digit of P47.18 is 0 and the analog input is greater than the detection value, for example:
set P47.18=01, P47.19=50%, at this time AI1 input is greater than 5V or 10mA
3. When the tens place of P47.18 is 1 and the analog input is less than the detection value, for example: set
P47.18=11, P47.19=50%, at this time AI1 input is less than 5V or 10mA
4. After 1, 2 or 3 conditions are met, the system will report A.FULL for the set time on P47.20
Full water recovery conditions:
5. The system enters the full water detection stage and displays A.FULL
When conditions 1, 2 and 3 are not met, and the maintenance time is greater than the time set in P47.21,
the system recovers.
Low power detection 0.0~6000.0kW
P47.22 0.0kW ☆
value 0.0-ineffective
0~1000s
During operation, when the actual output
Low power detection
P47.23 power (r16.02) is less than P47.22 and the 10.0s ☆
time
time of P47.23 is maintained, the system
reports A.Pol and stops.
0~1000s
When the condition described in P47.23
Low power recovery
P47.24 does not meet Low power protection 10.0s ☆
time
requirement ,it will be returned to normal
state after delay
Overcurrent detection
P47.25 0.0~999.9A 0.0A ☆
value
0.0~3000.0s
During operation, when the actual output
Overcurrent detection
P47.26 current (r27.06) is more than P47.25 and the 10.0s ☆
time
P47.26 time is maintained, the system
reports A.Pol and stops.
0.0~3000.0s When condition described in
Overcurrent recovery P47.26 does not meet Over current
P47.27 10.0s ☆
time protection requirement ,it will be returned to
normal state after delay
P47.28 Starting coefficient 0.000~1.000 0.850 ☆
Photovoltaic panel working coefficient = rated mppt voltage / open circuit voltage
Characteristics of photovoltaic panels for example 30.7/37.9 = 0.81
P47.29 Starting adjustment 10~100V 40V ☆
27
Function Name Description Default Property
code
29
Function Name Description Default Property
code
1. Set P47.00=0, P00.07=20.00-30.00, P00.06=0, and then press to run the drive
2. Check the function code P27.00, wait until its value becomes 20.00, and then enter the
function code P24.13,
3. press the keyboard and simultaneously for more than 2 seconds,, and if
the value changes, the load-off self-learning is completed(LCD display not support)
4. Press to stop running, set P47.00=1, P00.06=1, In this process, the pump no need to
take out from water
Saying P24.12 = 1, P24.13 = 40.0%, P24.14 = 3.0s, then the diagram is shown below.
12 1.2
10 1
8 0.8
OutPutCurrent(1.0A)
6 0.6
Load loss dection
4 0.4
2 0.2
0 0
0 5 10 15
Seen from the diagram shown above, if the output current is fall down to 40.0% of
the max output current and the status last for P24.14 then the drive will set the alarm
dry. If with P23.21 is not set, then the drive will coast stop while if P23.21 is set to
value 3000, then the drive will keep on running with dry alarm.
41 Group Pump sleep and wake-up parameters:
30
Function Name Description Default Property
code
Sleep source (AI1 ~ AI2)<P41.03, inverter
sleeps
Wake-up source (AI1 ~ AI2)>P41.04, the
inverter wakes up
0 ~ 65535
No user password status (P00.01 = 1 after
power-on):
Entering the same non-zero value twice in
succession sets a user password and enters
lockout.
P00.00 User password password lock state: 0 ☆
Enter the password to enter the unlock state.
unlocked state:
Enter the original password to enter the lock
state; enter the same value twice in a row to
change the password (clear the password if you
enter 0 twice in a row).
0:NO ACTION
11:Restore default parameter except for motor
parameter and auto-tune related parameter and
P00.03 RESET 0 ★
factory parameter
12:Restore default to factory parameter
13:Clear tripping record
31
Function Name Description Default Property
code
0:keypad
1:terminal
Source of the
P00.06 2:communication 0 ★
Operation Command
Command source: run、stop、forward、
reverse、jog、fast brake stop.etc
Numeric frequency
P00.07 00.00Hz~maximum frequency 50.00Hz ☆
setting
0:Digital setting
1:AI1
2:AI2
3:AI3(reserved)
4:AI4(reserved)
Main frequency source 5:HDI
P01.00 0 ★
selection (A) 6:multi-step speed
7:communication
8:PID
9:Internal PLC
Notice:DI terminal function code 26-32 superior
than this function code
0:No function
1:READY
2:RUN
P07.01 DO1 function 3:Error1(stop fault) 0 ☆
4:Error2(same as Error1 except
undervoltage)
5:Warning output(fault but in running)
0:No function
1:READY
2:RUN
3:Error1(stop fault)
P07.02 DO2 function 0 ☆
4:Error2(same as Error1 except
undervoltage)
5:Warning output(fault but in running)
0:No function
1:READY
Relay 1 Output terminal 2:RUN
P07.03 function group(T1A T1B 3:Error1(stop fault) 3 ☆
T1C) 4:Error2(same as Error1 except
undervoltage)
5:Warning output(fault but in running)
0:No function
1:READY
2:RUN
Relay 2 Output terminal
3:Error1(stop fault)
P07.04 function group(T2A T2B 47 ☆
4:Error2(same as Error1 except
T2C) optional
undervoltage)
47:Warning output(fault but in running)
auto main & PV switching
P07.17 Relay 1 invalid delay The delay time from the deactivation of the relay 0.000s
☆
to the actual action
33
Function Name Description Default Property
code
0~200%
It is used to compensate the speed drop of the
asynchronous motor VF control with load, and
improve the speed control accuracy. Please
P12.11 Slip compensation gain adjust according to the following principles: 0% ☆
Increase the setting when the motor speed
is lower than the target value with loading.
Reduce this setting when the motor speed
is higher than the target value with loading,
0:Standard mode (display frequency only)
P21.00 Monitoring display 1:Automatic scrolling display(Check 3.1 in 0 ★
detail )it show hz,current,power and voltage
Depend on drives power
≤7.5kW: 1kHz~12.0kHz
11kW~45kW: 1kHz~8kHz
≥55kw: 1kHz~4kHz
The carrier frequency can be reduced when it
came like following phenomenon:
1 The leakage current generated by the inverter
Carrier/swithcing is large
P22.00 Depend ☆
frequency 2 The interference generated by the inverter has
an impact on peripheral devices
3 Long wiring distance between inverter and
motor
The carrier frequency can be increased when it
came like following phenomenon:
1 The electromagnetic noise generated by the
motor is large
0:effective when running
Cooling method (fan 1:Forced control( effective when power on)
P22.14 2 ☆
control) 2:adjustable as per drive temperature
34
Function Name Description Default Property
code
(equal to change Phase between V and W and
UV and UW
Unit’digit :Overvoltage stall control
0:overvoltage stall disabled
1:overvoltage stall enabled
2:overvoltage stall enabled self-adjustable
The over-voltage stall function limits the amount of
over-voltage faults
as much as possible.
36
Function Name Description Default Property
code
0:no auto tuning
1:Stationary auto tuning of Asynchronous
motor
It is suitable in the cases when the motor can
not de-couple form the load. The auto tuning for
the motor parameter will impact the control
P11.10 Auto-tune/self-learning 0 ★
accuracy.
2:dynamic or Rotational auto tuning of
Asynchronous motor
Comprehensive motor parameter auto tune
It is recommended to use rotation auto tuning
when high control accuracy is needed.
★
Synchronous motor
P11.12 back electromotive force 0.0V ~ 2000.0V Induced electromotive force at Depend
BEMF rated speed
P24.01
Motor output
frequency
0
Fn
37
Function Name Description Default Property
code
Overload
time
80min
Overload gain P24.00=1.20
64min
Overload gain P24.00=1.00
5min
160s
5
s
100% 120% 140% 160% 180% 200% 220%
* Overload protection starting current
First graph: Motor overload protection starting current Second graph: Motor Overload Protection Curve with
Different Overload Protection Gains
Motor overload only protects the motor from overload when P24.04 is enabled.P24.00 is used to adjust the
overload inverse time curve time, as shown in the right figure above, the minimum motor overload time is 5.0s.
Note: Users need to correctly set the three parameters of P24.00, P24.01 and P24.02 according to the actual overload
capacity of the motor. If set unreasonable, prone to motor overheating damage and the inverter is not timely warning of
the danger of protection
39
Function Name Description Default Property
code
r26.16 Last fault 3 trip type Same as last fault description - ●
r26.17 Output frequency at fault Unit:0.01Hz - ●
r26.18 Output current at faul Unit:0.1A - ●
r26.19 Bus voltage at fault Unit:V - ●
0.01s~20.00s
P40.18 Integral time TI1 1.00s ☆
40
Function Name Description Default Property
code
0.000s~0.100s
P40.19 Differential time TD1 0.000s ☆
41
Function Name Description Default Property
code
0.00V~
P04.25
Correspondin
g setting
P04.23 Curve A horizontal axis 1 0.00V ☆
P04.2
6
- P04.2
4 P04.2 AI
100.0% 3
P04.25
~
P04.24 Curve A vertical axis 1 Note: Input less than P04.23, 0.0% ☆
100.0%
output decided by curve ten’s
digit
Setting method mode for AI1 4~20mA
P04.23
form
P04.25 Curve A horizontal axis 2 ~ 10.00V ☆
1. Switch the corresponding AI1
10.00V
jumper on the IO board to current;
-
2. Set the function code: P04.07 Unit’s
100.0%
P04.26 Curve A vertical axis 2 place=0 (default), P04.23=2.00. 100.0% ☆
~
100.0%
Correspondi
ng setting
0.00V~ P04.30
P04.27 Curve B horizontal axis 1 0.00V ☆
P04.29
P04.28 AI
- P04.27 P04.29
100.0%
P04.28 Curve B vertical axis 1 0.0% ☆
~
100.0%
P04.27
Note: Input less than P04.27, output
P04.29 Curve B horizontal axis 2 ~ 10.00V ☆
decide by curve ten’s digit
10.00V
42
Function Name Description Default Property
code
43
Chapter 5 Fault Diagnosis and Solution
VFD500-PV inverter has 24 types of warning information and protection function. In case of abnormal
fault, the protection function will be invoked, the inverter will stop output, and the faulty relay contact of the
inverter will start, and the fault code will be displayed on the display panel of the inverter. Before
consulting the service department, the user can perform self-check according to the prompts of this
chapter, analyze the fault cause and find out solution. If the fault is caused by the reasons as
described in the dotted frame, please consult the agents of inverter or factory directly.
Fault
Fault Name Display Possible Causes Solutions
code
44
Fault
Fault Name Display Possible Causes Solutions
code
45
Fault
Fault Name Display Possible Causes Solutions
code
46
Fault
Fault Name Display Possible Causes Solutions
code
47
Fault
Fault Name Display Possible Causes Solutions
code
48
Fault
Fault Name Display Possible Causes Solutions
code
49
Fault
Fault Name Display Possible Causes Solutions
code
50
Chapter 6 Service Agreement
2. Service free for Failure or trouble caused by our product quality issue.
3. For the service that Exceeding Guarantee time or failure not caused by
drive quality issues is out of the free range:
From inappropriate, negligent or incorrect installation or adjustment
of the optional operating parameters of the equipment or from
mismatching the drive with the motor;
Not permitted by the factory supplier, modified the drive devices;
Out of the VFD500-PV product specification application;
Failure consequences by fire, flooding, earthquake etc., un-foresee
natural disasters;
Without drive’s serial number or the S.N. can not be identified clearly.
51
Solar pump inverter maintenance warranty card
User corporation:
Address:
Fault information:
52