Fire Alarm System CS3000 Installation E6 08 2 E
Fire Alarm System CS3000 Installation E6 08 2 E
Salwico CS3000
Installation manual
çConsilium
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: [email protected]
Internet: www.consilium.se
Installation Manual Contents i
Salwico CS3000
Contents
About this manual ......................................................................... ii
Chapter 1: Installation
Chapter 2: Verification
Loops .................................................................................................... 2-1
Polarity fault ......................................................................................... 2-3
Wrong number of section units............................................................ 2-4
Information about analogue values ..................................................... 2-5
Control unit ....................................................................................... 2-7
Cable break ......................................................................................... 2-7
Earth fault ............................................................................................ 2-7
Short circuit.......................................................................................... 2-7
Mute faults ........................................................................................... 2-8
Reset faults.......................................................................................... 2-8
In chapter three you will find a brief description of loops and sections.
Installation Manual Chapter 1: Mechanical installation 1-1
Salwico CS3000
Chapter 1: Installation
The different parts of the CS3000 fire alarm system, the central unit, the
control units, repeaters and the section units, should first be
mechanically installed. The different section units are thereafter
electrically installed and set up according to the definition of the loops.
The cable must be tested before the loops can be connected to the
central unit, to eliminate any problem with the cable and the electrical
installation of the section units. The installation is completed with the
electrical installation of the central unit and the control unit(s).
Mechanical installation
Install the central unit, the control units, repeaters and the section units
according to the drawings. The control unit can be delivered installed in
the central unit or as a separate. Separate drawings are delivered with
the system.
Central unit
The central unit can be delivered in one of three standard cabinets, 10,
14 or 20U. Separate drawings are delivered with the system.
Section units
A section unit is a unit that can be connected to a loop, i.e. detector,
manual call point, address unit, timer, sprinkler, etc.
Electrical installation
A loop may consist of different types and different numbers of section
units, the connection to the loop depends on the type of section unit and
the configuration of your system. Some of the section units are
connected directly to the loop and some via an address unit. The figure
on the next page is an example of a loop which only includes one
section unit of each type..
Important!
• Set the address switch on each section unit when connecting them
to the loop. If an address unit is used, set the ID switch, too. See
Setting the address of the section units and Setting the ID later in
this chapter.
• All short circuit isolators must be bypassed before the loop is
tested. We recommend, connect the cores for terminal 2 and 4 and
the cores for terminal 1 and 3 are joined with a connector block,
inside the short circuit isolators.
Installation Manual Chapter 1: Mechanical installation 1-3
Salwico CS3000
57°C
SWM-1KL 80°C UVFD-2 SW-1EX
IN FIRE CENTRAL
1- 100°C 1- 1-
2- 150°C 2- 1-
LOOP X
3+ 3+ 2+
+ 4+ 4+ 2+
PRIMARY -
+ SLZ-2 SLZ-2
SECONDARY
-
KS-2(K)
1+
2-
3+
4-
Figure 1 - 1. One section unit of each type is connected to the loop in this example.
Installation Manual Chapter 1: Mechanical installation 1-4
Salwico CS3000
The measured value should be less then 100 ohm for a cable
with a maximum length of 2 km.
The base plate on the detector must also be marked with the section
number and the address.
• Print the section number at the correct address on the enclosed label
sheet.
• Stick the label to the outside of the base plate in full view.
Timer
An address interval must be set for each connected timer. The address
interval is set on two DIP-switches and the address interval indicates the
range of detectors to be disconnected. For more information, see Set
address interval on timer later on in this chapter.
Installation Manual Chapter 1: Mechanical installation 1-7
Salwico CS3000
103 1,2,3,6,7 104 4,6,7 105 1,4,6,7 106 2,4,6,7 107 1,2,4,6,7 108 3,4,6,7
109 1,3,4,6,7 110 2,3,4,6,7 111 1,2,3,4,6,7 112 5,6,7 113 1,5,6,7 114 2,5,6,7
115 1,2,5,6,7 116 3,5,6,7 117 1,3,5,6,7 118 2,3,5,6,7 119 1,2,3,5,6,7 120 4,5,6,7
121 1,4,5,6,7 122 2,4,5,6,7 123 1,2,4,5,6,7 124 3,4,5,6,7 125 1,3,4,5,6,7 126 2,3,4,5,6,7
127 1,2,3,4,5,6,7 128 8 129 1,8 130 2,8 131 1,2,8 132 3,8
133 1,3,8 134 2,3,8 135 1,2,3,8 136 4,8 137 1,4,8 138 2,4,8
139 1,2,4,8 140 3,4,8 141 1,3,4,8 142 2,3,4,8 143 1,2,3,4,8 144 5,8
145 1,5,8 146 2,5,8 147 1,2,5,8 148 3,5,8 149 1,3,5,8 150 2,3,5,8
Table 2 -1. Address switch settings for address 1-150. The digits in the table below indicates
which pins that should be set to the ON position.
Installation manual Chapter 1: Setting the ID 1-8
CS3000
Set the ID
The ID must be set for the address units, AE-2, AE-2K and AE-2K/I,
since the function of the unit depends on this setting. Each device
connected to the system has an internal ID which is read and handle by
the control unit.
Address units
The ID is set with the 5-pole DIP-switch located on the same side as the
address DIP-switch. The ID is binary coded, the least significant bit is
indicated with "1" and the most significant bit is indicated with "5". The
settings of the DIP switch for the address units are listed below. The
digits in the table below indicates which pins that should be set to the
ON position.
The ID interval is 96 - 127. If all the five bits are set to ON the ID is
equal to 127-31= 96, and if all the five bits are set to OFF the ID is
equal to 127-0=127.
ON
OFF
5 4 3 2 1
Note. A connected timer does not affect the function of the manual call
points.
Installation manual Chapter 1: Cable requirements 1 - 10
Salwico CS3000
Cable requirements
The cable must fulfil the following requirements. We refer to current
regulation for the rest of the specification.
Loop lengths
The length of a loop or a sub-loop depends on the following three
parameters, type of cable, shielded cable or unshielded cable. A cable is
considered to be shielded if the shielded part of the cable is more than
10% of the total length. Never exceed the recommended cable lengths.
The section units are divided into three types, depending on their
individual load on the loop.
• SID-38T
• RDJ-2T
• TDT-2 and TDT-2K, rate-of-rise 57°C and rate-of-rise 86°C
• CSS3300 rectifier
• AE-2 and AE-2K, configured as a sprinkler (ID 107, 120, 121, 125
and 126), heat detector (127), door indication (117), manual call
point (116) and sub central (114)
• AE-2E with separate power supply
• NS-AUV, NS-AOS-IS, NS-AOHS-IS, NS-AOS-IS-NA and
NS-AIN1 ID2
Installation manual Chapter 1: Cable requirements 1 - 11
Salwico CS3000
You do not need to keep track of primary and secondary side when
connecting section units to the loop, for instance start counting from the
primary side.
Installation Manual Chapter 1: Connection to central unit 1 - 13
Salwico CS3000
Terminal description
The specification may be subject to changes without notice.
Terminal P1
ARK-2
(Programmable) C P1:12
NO P1:13
(Programmable) C P1:15
NO P1:16
(Programmable) C P1:18
NO P1:19
GA input P1:20
P1:21
Installation Manual Chapter 1: Connection to central unit 1 - 15
Salwico CS3000
C P1:23
NO P1:24
Installation Manual Chapter 1: Connection to central unit 1 - 16
Salwico CS3000
Terminal P2
Ark-2 and LPK-2
Fire P2:9
In + P2:15
In - P2:16
In + P2:19
In - P2:20
Installation Manual Chapter 1: Connection to central unit 1 - 17
Salwico CS3000
Terminal P3
RS232K-2 and KPK-2
Rx D P3:2
RTS P3:3
CTS P3:4
Gnd P3:5
Channel 1 P3:7
+
Channel 1 - P3:8
Channel 2 P3:9
+
Channel 2 - P3:10
RxD P3:12
RTS P3:13
CTS P3:14
Gnd P3:15
Channel 1 P3:17
+
Channel 1 - P3:18
Channel 2 P3:19
+
Channel 2 - P3:20
Installation Manual Chapter 1: Connection to central unit 1 - 18
Salwico CS3000
Terminal P4
INK-2 and UTK-2
5 + P4:5
6 + P4:6
7 + P4:7
8 + P4:8
(opto-isolated) 2 + P4:12
3 + P4:13
4 + P4:14
5 + P4:15
6 + P4:16
7 + P4:17
8 + P4:18
Terminal P5
INK-2
13 + P5:5
14 + P5:6
15 + P5:7
16 + P5:8
21 + P5:15
22 + P5:16
23 + P5:17
24 + P5:18
Terminal P6
UTK-2
(opto-isolated) 10 + P6:2
11 + P6:3
12 + P6:4
13 + P6:5
14 + P6:6
15 + P6:7
16 + P6:8
(opto-isolated) 18 + P6:12
19 + P6:13
20 + P6:14
21 + P6:15
22 + P6:16
23 + P6:17
24 + P6:18
Terminal S1
SPK-2
In + S1:3
In - S1:4
Out - S1:6
In + S1:7
In - S1:8
S1:9
S1:10
S1:11
S1:12
S1:13
S1:14
S1:15
S1:16
S1:17
S1:18
S1:19
S1:20
Installation Manual Chapter 1: Connection to control unit 1 - 22
Salwico CS3000
- 2
RS485 Option A+ 20
B- 21
Inputs Common 1, 2 - 3
1 + 4
2 + 5
Inputs Common 3, 4 - 22
3 + 23
4 + 24
- 7
- 26
1 + 9
2 + 10
3 + 28
4 + 29
Installation Manual Chapter 1: Connection to control unit 1 - 25
Salwico CS3000
RxD 12
RTS 13
CTS 14
Gnd 15
RTS 32
CTS 33
Gnd 34
- 17
+ 18
. 19
- 36
+ 37
. 38
Installation Manual Chapter 2: Loops 2-1
Salwico CS3000
Chapter 2: Verification
The definition of the loop must be performed by a person with a good
knowledge of the CS3000 fire system. The operator must have the authority to
work on access level 4. The system is delivered with a complete system
definition or a test definition.
Loops
We assume that there are no communication problems in the system since the
cable has already been tested but each loop have to be verified. The
verification procedure is described below, step by step.
1. Connect the primary side of one of the loops to the central unit.
2. Power on the system. The POWER LED is lit and the text CS3000
CONTROL UNIT is shown in the display. The system is up and running.
If the system detects a fault in the system at start-up, the fault code is
displayed. For more information about the fault codes, see Appendix C:
Fault codes.
3. Set the address on each control unit by using the service mode.
• Press F1 (SERVICE).
• Press (ADDRESS).
• Enter the address for a control unit. The address interval is 217 to 232,
address 217 is equal to control unit 1, address 218 is equal to control
unit 2, etc. You need to know how the control units are defined in the
Definition program to be able to set the correct address.
4. Deactivate the built-in short circuits isolators by using the service mode.
• Press F1 (SERVICE).
7. Verify that the correct number of section units and the correct type of
section units are installed in the correct place. The system will provided
you with the requested information if you use the Section unit status list. If
a section unit is missing, see Wrong number of section units later on in
this chapter.
Note! All the short circuits isolators are by-passed and should therefore be
present in the Section unit status list.
STATUS SECTION:8
UNITS EXPECTED: 7 FOUND: 7
DISCONNECTED: 7
SPK STATUS BYTE: 4 CURR.(M AMP): 0
The section number is displayed on line one. The second line displays the
expected numbers of section units in the selected section, including built-in
short circuit isolators, and how many units the system found. The third line
displays how many units that are disconnected in the selected section. The
fourth line displays the status of the SPK in decimal value and the estimated
current consumption for the section.
The different statuses of the SPK is listed with its binary value below. You
have to convert the decimal value to a binary value, where bit 0 is the least
significant bit (LSB) and thereafter use the list below to defined the SPK
status.
SPK status:
Bit
0: 0 Double-fed loop
1 Single-fed loop (side 1)
1: 0 No time delay for smoke detectors
1 Time delay for smoke detectors
2: 0 Differential detectors are not allowed
1 Differential detectors allowed
3: 0 Normal sensitivity for smoke detectors
1 High sensitivity for smoke detectors
4: 0 Marine application
1 Industrial application
5: 0 Prim alarm allowed
1 Prim alarm not allowed
6: 0 Abnormal condition caused by dirty detector
1 Fault caused by dirty detector
7: 0 No pre-alarm
1 Pre-alarm
9. Restart the system and wait for about five minutes before data is relevant
in the system.
10. Verify the section addresses again, repeat point 7.
11. One loop is now verified and tested. Continue with the next loop. Repeat
this procedure for all loops.
12. Make a fire detector test of the complete fire alarm system, use test gas to
test each detector. The test is documented on the printer connected to a
central unit or print out the Fire alarm history list. This list is cleared
every time the system is restarted.
• Press F4 (MORE).
The latest reset fire alarm is displayed first. All the information about the
fire is displayed on line one and additional text is displayed on line two.
The total number of alarms and the fire alarm in order is displayed on line
three.
To make a printout
• Press F1 (PRINTOUT).
13. We recommend you to use a top to bottom procedure if you have any
problem with the verification of the loop function. Start to solve the
problems that affect the whole loop and thereafter continue with the
problems with each address.
Polarity fault
One or more section units are not correctly installed if the measured voltage is
much less then 30 VDC. Proceed as follows to locate the section units with
polarity fault : Divide the cable in two halves, locate the polarity fault on one
of the halves. Divide this half of the cable again into two halves. Continue to
divide the cable into halves until you have found the polarity fault.
All the section units are correctly installed when the measured voltage is
around 30 VDC.
If a limited number of section units do not answer, the problem may depend on
one of the causes listed below. When the correct number of section units is
installed, return to Loops, point 7.
Cause Remedy
To few section units installed. Install the missing section units.
Wrong address for the section Set the correct address.
unit
Two or more section units with See Address error paragraph on the
the same address. next page.
Section unit is broken. Replace the section unit.
Note! Restart the system after each time you have changed an address. You
have to wait for about five minutes after restart before data is relevant in the
system.
Address error
Use the Section unit status list, Data, see Loops point 7 this chapter, to find the
missing units. However, there is a possibility that one or more section units
with the same address will answer, which is reported as bad communication,
an abnormal condition.
Installation Manual Chapter 2: Loops 2-5
Salwico CS3000
If you want to connect a unit that you can not find in this table, please contact
our service department.
NB! The value within brackets indicates the maximum alarm level for rate of
rise detectors. The detector may generate a fire alarm before it reaches the
maximum alarm level if the temperature rise is to fast. The fire alarm
condition is generated by signal processed data.
*
The normal value depends on the environment. The system indicates on the
display when there is a fault on a detector.
Installation Manual Chapter 2: Loops 2-6
Salwico CS3000
If you want to connect a unit that you can not find in this table, please contact
our service department.
Installation Manual Chapter 2: Loops 2-7
Salwico CS3000
Control unit
At power-up the text CS3000 CONTROL UNIT, the date and the time are
displayed on the display if all the units have been installed correctly. A fault
code is otherwise displayed on the operating panel, the fault indication is
flashing and the internal buzzer is sounding. A fault must be muted and reset.
All the fault codes, their cause and how an operator with some knowledge of
the system can solve the problem, are listed in Appendix A: Fault codes.
When a fault occurs, localise the problem and deal with it.
Cable break
No section units are answering.
- The cable is broken before the first section unit if no answer is received on a
single fed loop.
- The cable is broken before the first section unit and after the last section unit
the if the loop is a double fed loop.
Section units are answering.
Look for the last section units answering on each side of the loop. The cable
break is situated after or between the answering units.
Earth fault
Check the loops one by one.
Short circuit
No section units answers
Search for the short-circuits between the central unit and the first short circuit
isolator.
The easiest way to find a short circuit is to divide the cable in two halves,
locate the short circuit on one of the halves. Divide this half of the cable again
into two halves. Continue to divide the cable into halves until you have found
the short circuit.
Installation Manual Chapter 2: Loops 2-8
Salwico CS3000
Mute faults
The internal buzzer is temporarily silenced when the door is opened.
The fault indication stops flashing and turn over to steady yellow. The fault is
put on a fault list and the next fault is displayed, if there are more faults in the
system, otherwise the system returns to its previous state. The latest fault is
always displayed first. How many faults there is in the system and which fault
in order that is displayed are presented on line three. You can scroll the faults
up and down by using the ↑ and ↓ keys.
Reset faults
The cause of the problem must have disappeared before a fault can be reset.
The faults are reset from the Fault list.
The text on line three disappears after about 5 seconds. Check the problem and
deal with it. Thereafter try to reset the fault again.
Installation Manual Chapter 3: Section description 3 - 2
Salwico CS3000
The two-core cable is used both for power supply to the section units and as a
communication link between the loop processor and the section units.
The loop is mastered by a processor in the central unit and every detector is
polled in address sequence, reporting alarm conditions and fault conditions.
All fire detecting units can interrupt this polling sequence if they have detected
a fire condition. The potential fire condition is immediately processed by the
central unit.
The loop processor activities are divided into two phases. After power up all
the section units on the loop are identified and every address is polled, this is
the booting sequence. The polling sequence starts when the boot sequence is
finished.
Boot sequence
The section units are identified during the booting sequence. Every address is
polled and if the processor receives an answer to the poll, the type of the
detector or the section unit is registered and it is then set-up according to the
type. Each section unit must consequently have a unique address.
All section units are set-up to work properly. All fire detecting units are
programmed with their alarm levels, to make them able to interrupt the
sequential polling in case of a potential fire condition.
If the number of detected section units differs from the preset number of units,
this is reported as a fault condition.
Polling sequence
When the system has completed the booting sequence the polling sequence is
automatically started. The processor keeps on polling the section units in
address sequence. Each time a section unit is polled the processor asks the unit
about its analogue value.
If the value belongs to a fire detecting unit it will be processed and in case of a
potential fire or fault condition it will be verified according to a verification
algorithm before it is reported to the user/operator. If the polled section unit is
not a fire detection unit the value read is reported as a status. The status can
either be normal or indicate an event. The status will be verified if it is not
normal, and the resulting action depends on the type of section unit. The
reported action may be a fault condition, turning off detectors, etc.
Cable breaks and short circuits are detected during the polling sequence.
Communication errors are also reported.
When a fire detecting section unit discovers that its analogue value has passed
the pre-programmed alarm level a message is sent after which the polling
Installation Manual Chapter 3: Section description 3 - 3
Salwico CS3000
Functions
The functions of the system are grouped into different levels and each level is
opened with an access code. You can use some of these functions to get
information about the status of the system, to change some values or to test
some functions, if you have the authority to enter access level three. All
functions are described in CS3000 User's Guide. The most useful functions
during the installation procedure are listed below.
Section description
Each loop is equal to 1 section. There may be a total of 64 loops in the system.
A section can only be part of one loop. The address interval, the section
number and the number of units are specified for each section. The section
number may be in the range 1 - 64. The definition of the sections is made in
the system definition.
Different types of section units may be connected to the section. The system
allows the connection of maximum 150 addresses per section. If more than 32
detectors/manualcall points are connected to the section they must be
physically delimited by short-circuit isolators.
Installation Manual Chapter 4: Commissioning requirements 4 - 1
Salwico CS3000
Loop Requirements
The list in part A (Loop configuration) includes all data you need when
configuring the loops. Part B (Loop status) is more like a check list, use it and
follow it point by point. When you have completed this part you should have
filled in, signed and faxed the special document ”Address list/test report for
Consilium Loop Units” one for each loop in the system. Part C (Central status)
is also a check list but it deals with the status of the central unit.
Summary
The following documents must be filled in and faxed to Consilium
+46 - 31 58 57 40 and your local Consilium representative in your
country before commissioning of the system starts.
1. ”Address list/test report for Consilium Loop Units”, appendix A, one for
each loop.
Installation Manual Appendix A
Salwico CS3000
Appendix A
The Address List/Test Reports
Address List / Test Report Loop no...............(1/2)
for Consilium Marine CS4000 Fire Alarm Loop Units
1 2 3 4 5 6 7 8
Example 8 o o o
o
o o o o OK o ON
o o o o o o o
o o
9 o o o o o o Not OK
OFF
OK OK OK OK OK
o o o o o o o o o o o o o o o o o o o o o
1 o o o o o o o 31 o o o 61 o o o 91 o o o 121 o o o
o o o o o o o o o o o o o o o o
2 o o o o o o o 32 o o o o o o o 62 o o o 92 o o o o 122 o o o
o o o o o o o o o o o o o o o o o o o o o
3 o o o o o o 33 o o o o o o 63 o o 93 o o o 123 o o
o o o o o o o o o o o o o o
4 o o o o o o o 34 o o o o o o 64 o o o o o o o 94 o o o 124 o o o
o o o o o o o o o o o o o o o o o o o
5 o o o o o o 35 o o o o o 65 o o o o o o 95 o o 125 o o
o o o o o o o o o o o o o o
6 o o o o o o 36 o o o o o o 66 o o o o o o 96 o o o o o o 126 o o
o o o o o o o o o o o o o o o o o o o
7 o o o o o 37 o o o o o 67 o o o o o 97 o o o o o 127 o
o o o o o o o o o o
8 o o o o o o o 38 o o o o o 68 o o o o o o 98 o o o o o 128 o o o o o o o
o o o o o o o o o o o o o o o
9 o o o o o o 39 o o o o 69 o o o o o 99 o o o o 129 o o o o o o
o o o o o o o o o o o o
10 o o o o o o 40 o o o o o o 70 o o o o o 100 o o o o o 130 o o o o o o
o o o o o o o o o o o o o o o o o
11 o o o o o 41 o o o o o 71 o o o o 101 o o o o 131 o o o o o
o o o o o o o o o o o o o
12 o o o o o o 42 o o o o o 72 o o o o o o 102 o o o o 132 o o o o o o
o o o o o o o o o o o o o o o o o o
13 o o o o o 43 o o o o 73 o o o o o 103 o o o 133 o o o o o
o o o o o o o o o o o o
14 o o o o o 44 o o o o o 74 o o o o o 104 o o o
o
o
o o
o 134 o o o o o
o o o o o o o o o o o o o o o o
15 o o o o 45 o o o o 75 o o o o 105 o
o o
o
o
o o
o 135 o o o o
o o o o o o o o o o
16 o o o o o o o 46 o o o o 76 o o o o o 106 o
o
o
o
o
o o
o 136 o o o o o o
o o o o o o o o o o o
17 o o o o o o 47 o o o 77 o o o o 107 o o
o
o
o
o o
o 137 o
o o
o
o o o
o
o o o o o o o o
18 o o o o o o 48 o o o o o o 78 o o o o 108 o o
o o
o
o o
o 138 o
o
o
o
o o o
o
o o o o o o o o
19 o o
o o
o
o o o 49 o o o o o 79 o o o 109 o
o
o o
o
o o
o 139 o o
o
o
o o o
o
o o o o o
20 o o
o
o
o
o o o 50 o o o o o 80 o o o o o o 110 o
o o o
o
o o
o 140 o o
o o
o o o
o
o o o o o o o
21 o
o
o
o
o
o o o 51 o o o o 81 o o o o o 111 o o o o
o
o o
o 141 o
o
o o
o o o
o
o o o
22 o
o o
o
o
o o o 52 o o
o
o
o o
o o 82 o o o o o 112 o o o o
o o o
o 142 o
o o o
o o o
o
o o o o
23 o o o
o
o
o o o 53 o
o
o
o
o o
o o 83 o o o o 113 o
o o o
o o o
o 143 o o o o
o o o
o
24 o o o
o o
o o o 54 o
o o
o
o o
o o 84 o o
o
o
o
o
o
o 114 o
o
o o
o o o
o 144 o o o o
o
o o
o
25 o
o o
o o
o o o 55 o o o
o
o o
o o 85 o
o
o
o
o
o
o
o 115 o o
o o
o o o
o 145 o
o o o
o
o o
o
26 o
o
o
o o
o o o 56 o o o
o o o
o o 86 o
o o
o
o
o
o
o 116 o o
o
o
o o o
o 146 o
o
o o
o
o o
o
27 o o
o
o o
o o o 57 o
o o
o o o
o o 87 o o o
o
o
o
o
o 117 o
o
o
o
o o o
o 147 o o
o o
o
o o
o
28 o o
o o o
o o o 58 o
o
o
o o o
o o 88 o o o
o o
o
o
o 118 o
o o
o
o o o
o 148 o o
o
o
o
o o
o
29 o
o
o o o
o o o 59 o o
o
o o o
o o 89 o
o o
o o
o
o
o 119 o o o
o
o o o
o 149 o
o
o
o
o
o o
o
30 o
o o o o
o o o 60 o o
o o o o
o o 90 o
o
o
o o
o
o
o 120 o o o
o o o o
o 150 o
o o
o
o
o o
o
o o o o o o o
o o
9 o o o o o o Not OK
OFF
OK OK OK OK
o o o o o o o o o o o o o o o o o o o o
151 o o o 181 o o o 211 o o o 241 o o o
o o o o o o o o o o o o o o o o o
152 o o o o o 182 o o o 212 o o o o 242 o o o
o o o o o o o o o o o o o o o o o o o o o
153 o o o o 183 o o 213 o o o 243 o o
o o o o o o o o o o o o o o o o o o
154 o o o o 184 o o o o 214 o o o 244 o o o
o o o o o o o o o o o o o o o o o o o o o o
155 o o o 185 o o o 215 o o 245 o o
o o o o o o o o o o o o o o o o o o o
156 o o o o 186 o o o 216 o o o o 246 o o
o o o o o o o o o o o o o o o o o o o o o o o
157 o o o 187 o o 217 o o o 247 o
o o o o o o o o o o o o o o o o o o o o
158 o o o 188 o o o 218 o o o 248 o o o
o o o o o o o o o o o o o o o o o o o o o o o o
159 o o 189 o o 219 o o 249 o o
o o o o o o o o o o o o o o o o o o o
160 o o o o o o 190 o o 220 o o o 250 o o
o o o o o o o o o o o o o o o o o o o o o o o
161 o o o o o 191 o 221 o o 251 o
o o o o o o o o o o o o o o o o o
162 o o o o o 192 o o o o o o 222 o o 252 o o
o o o o o o o o o o o o o o o o o o o o o
163 o o o o 193 o o o o o 223 o 253 o
o o o o o o o o o o o o o o o o
164 o o o o o 194 o o o o o 224 o o o o o 254 o
o o o o o o o o o o o o
165 o o o o 195 o o o o 225 o o o o 255 o o o o o o o o
o o o o o o o o o o o
166 o o o o 196 o o o o o 226 o o o o 0 o o o o o o o o
o o o o o o o o o o o o o o
167 o o o 197 o o o o 227 o o o
o o o o o o o o o o o
168 o o o o o 198 o o o o 228 o o o o
o o o o o o o o o o
169 o
o o
o
o
o
o
o
199 o o o 229 o o o
o o o o o o o o
170 o
o
o
o
o
o
o
o
200 o o o o o 230 o o o
o o o o o o o o o o
171 o o
o
o
o
o
o
o
201 o o o o 231 o o
o o o o
172 o o
o o
o
o
o
o
202 o
o
o
o
o o
o o
232 o o o o
o o o o o
173 o
o
o o
o
o
o
o
203 o o
o
o
o o
o o
233 o o o
174 o
o o o
o
o
o
o
204 o o
o o
o o
o o
234 o
o
o
o
o
o o o
175 o o o o
o
o
o
o
205 o
o
o o
o o
o o
235
o o
o
o
o
o o o
176 o o o o
o o
o
o
206 o
o o o
o o
o o
236 o o
o o
o
o o o
177 o
o o o
o o
o
o
207 o o o o
o o
o o
237
o
o
o o
o
o o o
178 o
o
o o
o o
o
o
208 o o o o
o
o
o o
238 o
o o o
o
o o o
179 o o
o o
o o
o
o
209 o
o o o
o
o
o o
239
o o o o
o
o o o
180 o o
o
o
o o
o
o
210 o
o
o o
o
o
o o
240 o o o o
o o o o
Appendix B
Connections for Consilium Marine loop units
ÇConsilium Marine
Loop IN +1
-2
+3 Loop OUT
-4
Address units
NS-AIN1/ID2 NS-AIN1/ID3
Conventional detectors
1 (+) Safe area Hazardous area, IS units Loop IN 1 (+)
Loop IN
2 (-) 2 (-)
Loop OUT 3 (+) Loop OUT 3 (+) Detector Last detector
4 (-) IS unit Last IS unit 4 (-)
NS-ISOLATOR
5 (+) 5 (+) 1 1 + + 1 1 + +
ELR-33
6 (-) 1 11 (+) 1 (+) 1 1 + + 1 1 + + 6 (-) 2 2 2 2
ELR-33
7 (+) 1 2 12 (-) 2 (-) 2 2 2 2 7 (+)
8 (-) 2 8 (-)
NS-AIN2/ID7 NS-AIN2/ID8
Loop IN 1 (+) Sprinkler station Loop IN 1 (+)
2 (-) 2 (-)
Loop OUT 3 (+) ELR-4.7 Flow switch (no flow position)
Loop OUT 3 (+) ELR-4.7 Input
4 (-)
5 (+) 4 (-)
6 (-) 5 (+)
7 (+) 6 (-)
ELR-4.7 Sprinkler valve (open position)
8 (-) 7 (+)
8 (-)
Addressable IS units
NS-AOS-IS
NS-AOHS-IS Safe area Hazardous area
ACP-IS
NS-ISOLATOR-A NS-AOS-IS ACP-IS
NS-AOHS-IS
Loop in 21(+)
22(-) 1(+) 1(+)
Loop out 23(+) To next IS unit
2(-) 2(-)
24(-) (max 20)
Black (-) Red (+)
Call point circuits
ÇConsilium Marine
ID Switch
Detectors
Evolution type detectors
RDJ-2
RDJ-2T
RDO-2
TDT-2
HA100-HA110 Loop in 1(+) Loop out
OA100-140 6(-)
IA100-140
3(-)
WITH BASES:
UB-1, UB-2
SPB-ADAPT
EV-P 3 mA remote
EV-PH
EV-DP output
EV-DPH
EV-H 54
EV-H 84
EV-H A1R
Major computer failure Program execution has stopped. Contact our service department.
8 Additional section unit(s) * Wrong definition of number of Compare the installation with
section units. the drawings. Contact our
service department.
Section unit connections faulty. Connect the unit correctly.
21 Bad answer (Abnormal Bad communication with one or Exchange the section unit if the
condition) several section units, could be condition remains or returns. If
temporary. this fault is not temporary
contact our service department.
22 No answer Wrong type of section unit. Exchange to the correct section
unit.
The section unit has two Check the units.
addresses.
Hardware fault. Exchange the unit.
A fuse is blown. A secondary Exchange the fuse.
fault appears, code (83).
Cable break in loop or system Mend the cable. See Cable at
loop. A secondary fault appears, the end of this appendix.
code (121).
23 Wrong loop unit mark Section unit faulty. Exchange the section unit.
24 Wrong unit status Section unit faulty. Exchange the section unit.
Wrong software in CS3000. Change the software.
Wrong type of detector Install correct type of detector.
installed. Restart the system.
25 Unknown ID Communication error Reboot and retry. If this does
not solve the problem, contact
our service dept.
Software too old Update software
26 Bad loop comm. * The loop communication is bad. Test the loop. Measure the cable
(Abnormal condition) resistance. See Cable at the end
of this appendix.
27 Loop comm. stopped The loop communication is Contact our service department.
stopped by a section unit.
28 Loop trans. stopped Communication error on central Contact our service department.
unit level.
29 Communication error
Two section units with the same Check the section units.
address.
Faulty section unit. Exchange the section unit.
41 Booted The system is booting. Contact our service department.
42 Boot disabled Section unit is faulty. Exchange the section unit.
Address unit on a sub-loop is Test the sub-loop.
faulty.
Installation Manual 3
Fault codes
43 Wrong address interval Overlapping address intervals. Set a valid address interval.
End-address of the interval is Set a valid address interval.
lower then the start-address.
44 Illegal address
Faulty section unit. Exchange the section unit.
Replace unit
89 No autoalarm Unable to use autoalarm
Optical smoke detector: Clean
90 Polluted detector Detector head is polluted.
the detector head according to
(Abnormal condition)
recommendations.
126 Short circuit on prim. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the primary side.
127 Short circuit on sec. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the secondary side.
141 Earth fault + Earth fault between the positive See Earth fault at the end of this
connector and earth. appendix.
142 Earth fault - Earth fault between the negative See Earth fault at the end of this
connector and earth. appendix.
143 High current Normal current exceeded Check power consumers
144 Earth fault Earth fault (either positive or Locate and fix the cause
negative)
145 Low voltage Too low system voltage from Test the rectifier and measure
the power unit the voltage. Contact our service
department.
147 Fire Prewarning The system has detected a Check the unit.
smoke value approaching the
alarm level.
148 Fault alarm transmitted Obsolete Obsolete
149 Fire brigade disconnection Industrial application only. Reconnect the connection.
Transfer to fire brigade
disconnected.
150 Timer Stuck The timer does not work Check the unit.
properly.
153 Emergency power failure The emergency power is Check the emergency power
missing
154 Secondary power failure All 115/230VAC power supplies Check the power supplies
are faulty
161 Door Open A door is still open one minute Check the door.
after the instruction to close it
was sent.
162 Door closed A door intended to be open is Open the door
closed
163 Open Door Subloop Cable break between module Mend the cable.
Break and open door sensor.
164 Door Closed Subloop Cable break between module Mend the cable.
Break and closed door sensor.
Installation Manual 6
Fault codes
166 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been opened
167 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been closed
170 Sensor Fault The detector has a faulty sensor Replace the detector.
element.
NB This fault could be the result Check the location of the
of air blowing at the unit. detector and if need be, move it
to a less windy location.
171 Cable break from input 1 There is a cable break on input Check the cable.
1.
172 Cable break from input 1 There is a cable break on input Check the cable.
2.
173 Door Feedback There is no response from the Check the door-holder relay and
door-holding relay. its cable.
174 No power supply for loop No power feed from the pcb. DC/DC converter faulty.
175 Door in wrong position Door in wrong position. Check for obstruction.
176 Cable break positive side Check for a cable break on Mend the cable break.
positive lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
177 Cable break negative side Check for a cable break on Mend the cable break.
negative lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
178 Wrong type of loop unit Check the ID setting of the Set a correct value on the DIP-
found faulty unit. switch of the unit.
179 Unable to detect short Unable to detect short circuit. Exchange loop-PCB.
circuit
180 Valve Closed Valve closed. Check why it is closed.
181 Loop cable short circuit Short circuit on subloop. Check cable.
182 Cable break A cable break has been detected. Check corresponding cables.
183 Cable overload, current There is an overload in the Check if too many units are
limit reached cable. connected to the cable. Compare
with cable data.
184 Power fault The power supply is lost. Check power generation.
Installation Manual 7
Fault codes
185 Loss of capacity to charge The battery charger is unable to Check the battery charger and
battery charge the battery. the battery.
186 External Fault Fault from input. Check cable and/or external
unit.
187 Double address on loop Check the offending units Set correct addresses for the
against drawings. units, with the DIP-switches.
Cable break
No section units are answering.
- The cable is broken before the first section unit if no answer is received on a
single fed loop.
- The cable is broken before the first section unit and after the last section unit
the if the loop is a double fed loop.
The easiest way to find a short circuit is to divide the cable in two halves,
locate the short-circuit on one of the halves. Divide this half of the cable again
into two halves. Continue to divide the cable into halves until you have found
the short-circuit.
Fuses
Check the fuses on the boards included in the system. The fuses are mounted
on the front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4,
LPK-2, RS232K-2, SPK-2 and UTK-2. The fuses to the IKK-4 are mounted on
the board itself.
* The central unit is not working properly. Indicator No. 1 (green) is not lit.
Installation Manual USCG Appendix D D-1
CS3000
Appendix D:
Installation and operation addendum
The fire detection system must be installed and configured in accordance with Subpart 161.002 and
Subchapter J of Title 46 of the U.S. Code of Federal Regulations, and with the 1993 or later version of
NFPA 72. This is in addition to any other requirements specific to the vessel and its route. Only those
components listed on the approved component list may be used.
The approved component list identifies those components that may be used in locations requiring an
exceptional degree of protection. Location requiring an exceptional degree of protection means a
location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.
These locations include--
(1) On deck;
(2) A machinery space;
(3) A cargo space;
(4) A location within a galley or pantry area, laundry, or water closet which contains a shower or
bath; and
(5) Other spaces with similar environmental conditions.
The fire detection system shall be installed as a fully addressable system. Any non-addressable
initiating device must be used with an addressing unit to provide an address for that device. Each
addressing unit shall be used to support only one device. Examples of non-addressable initiating
devices are the manual call point NS-CPWP and the UV-flame detector NS-DUV.
A trouble signal must be annunciated by the activation of the Models UR-2K and UR-2KN timers.
Timer UR-2K must be installed in a locker.
The fire control panels (CS3000 and CS3004) must be installed with two sources of external power.
The internal battery cannot be used to satisfy the requirement for a secondary source of power.
Installation manual USCG Appendix E E-1
CS3000
Appendix E:
Component list for USCG approved systems
Approved Component List for Salwico CS3000 or CS3004 systems as an U.S. Coast Guard approved system.