Modified - Post Tensioned
Modified - Post Tensioned
Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct
a r t i c l e i n f o a b s t r a c t
Article history: This paper describes an analytical investigation into the design of unbonded post-tensioned (PT) precast
Received 26 May 2016 concrete beam-column connections that employ a friction device. Design formulas related to the moment
Revised 9 December 2016 capacities, hysteretic energy dissipation capacities, and self-centering capabilities of the PT connections
Accepted 3 February 2017
are developed in normalized form. The validation of the design formulas and the effect of normalized
Available online 16 February 2017
parameters such as friction force, initial post-tensioning force and the location of the friction device on
the moment and energy dissipation capacities are investigated. A design procedure to achieve desired
Keywords:
design moment and energy dissipation capacities for the PT connections is also developed using the
Design
Unbonded post-tensioning
design formulas. Contour plots for the linear limit moment and hysteretic energy dissipation ratio are
Energy dissipation provided for determining the required values of the normalized parameters. The investigation is based
Self-centering on the analytical responses from a nonlinear section analysis method for a number of PT connections
Precast concrete with various sets of normalized parameters. The results confirm the adequacy of the design formulas
Section analysis and design procedure.
Ó 2017 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.engstruct.2017.02.012
0141-0296/Ó 2017 Elsevier Ltd. All rights reserved.
T. Koshikawa / Engineering Structures 138 (2017) 170–180 171
tests on the PT connection specimens shown in Fig. 1 demonstrate 2. Design formulas for unbonded PT connections with a friction
that the BFD can provide satisfactory energy dissipation to PT con- device
nections. Song et al. [8] developed an armored precast concrete
beam-column connection with a friction device located at the The PT connections that employ either a WFD or a BFD studied
web of the beam, called a beam web friction device (WFD). They in this paper are shown schematically in Fig. 2. The precast beam is
conducted experimental and numerical studies on its hysteretic joined to the column by an axial post-tensioning force provided by
behavior, and found the connection to have good seismic perfor- a group of unbonded post-tensioning tendons that run straight at
mance with respect to energy dissipation, self-centering, and pre- the beam centroid and through the beam-column connection.
venting local damage. Further studies on the same connection The friction device, placed on the outside of the beam web (Fig. 2
were conducted by Song et al. [9], where the performance of PT (a)) or on the bottom surface of the beam (Fig. 2(b)), is connected
connections with WFDs was investigated experimentally through to the beam end and the column face. When relative displacement
a series of cyclic tests on a 0.5-scale, one-bay, one-story frame sub- occurs between the beam end and the column face, a friction force
assembly. Research and development of similar connections for develops in the friction device and provides moment resistance
steel frames has also been conducted by several other researchers together with the post-tensioning force.
(Tsai et al. [11], Iyama et al. [12], Wolski et al. [13], Guo et al. [14], In a properly designed PT connection, the behavior is primarily
and Lin et al. [15]). dominated by the opening and closing of a gap that occurs at the
Unlike PT connections with friction devices on both the top and beam-column interface. Fig. 3 shows the idealized moment-
bottom of the beam, the moment resistances due to the post- rotation behavior for PT connections with WFDs and BFDs. The
tensioning force and the friction force correlate to each other in term M represents the moment in the beam at the beam-column
these PT connections because they are in equilibrium with the interface and h represents the chord rotation of the beam. A posi-
compression force. In addition, the location of the friction device tive rotation corresponds to the gap opening at the bottom of the
may have a significant effect on the moment and energy dissipa- beam-column interface. As shown in Fig. 3, properly designed PT
tion capacities of PT connections. This paper presents an analytical connections have flag-shaped hysteresis curves under both posi-
investigation focusing on this issue in the design of PT connections tive and negative rotations, where the unloading curve goes back
having a friction device. Design formulas related to the moment to the origin as the energy corresponding to the area enclosed by
capacities, hysteretic energy dissipation capacities, and self- the loading and unloading curves is dissipated. The moments M llþ
centering capabilities are developed using normalized parameters and Mll that occur during the loading curves are the linear limit
suitable for such PT connections. Results obtained using the design moments [16,17] that are taken as the nominal moment capacities
formulas for the capacities are compared with results from nonlin- under positive and negative rotations. The moments when the
ear analyses using a section analysis method that can predict the unloading curves rejoin the loading curves are denoted as Mlrþ
relationship between the moment and relative rotation at the and M lr . Since the positive and negative moment resistances
beam-column interface under cyclic loading. The effect that using may be different depending on the location of the friction device,
normalized parameters has on the capacities of the PT connections the symbols for these moments are given separately for positive
is also examined. Based on the design formulas, a design procedure and negative rotations using + and indices. The design formulas
to determine the parameter values necessary to satisfy the for the PT connections are based on idealized moment-rotation
required moment and energy dissipation capacities is presented behavior. PT connections with friction devices on both the top
and analytically validated. and bottom of the beam are not covered by the design formulas.
2.1. Moment capacity formulas positive and negative linear limit moments M llþ and M ll for each
PT connection can be expressed as follows:
The moment capacity of a PT connection can be obtained by
D ap af D ap af
summing the contributions from the unbonded post-tensioning Mllþ ¼ T po þ F fs þ df ð1Þ
2 2
tendon and the friction device. Fig. 4 shows beam-column interface
equilibria for PT connections at the positive and negative linear
D ap af
limit moments. The compression force in the concrete Cc is Mll ¼ T po
assumed to act at mid-depth of the equivalent compression stress
2
block, and to be in equilibrium with the initial post-tensioning D ap af
F fs df PT connection with a WFD
force in the unbonded post-tensioning tendon Tpo and the friction 2
force in the friction device Ffs. The main difference between the ð2aÞ
forces in a PT connection with a WFD (Fig. 4(a)) and a BFD (Fig. 4
(b)) is the direction of the friction force under negative rotation, D ap þ af
which causes differences in the magnitude and location of the Mll ¼ T po
2
compression force in the concrete Cc, and hence the length of the
D ap þ af
moment arm. Assuming, for simplicity, that the friction force acts þ F fs df PT connection with a BFD ð2bÞ
2
parallel to the beam at the location of the friction device, the
where D is the beam depth and df is the distance between the mid- 1 1
mlr ¼ qp 1 þ pf qp ð1 þ pf Þ2 pf r f
depth of the beam and the location of the friction device. Expres- 2 0:85
sions in parentheses account for the lengths of the moment arms PT connection with a BFD ð8bÞ
of the initial post-tensioning force Tpo and the friction force Ffs. ap
and af are the components of the depth of the equivalent compres- where mlrþ and mlr are the moments Mlrþ and Mlr normalized by
0
sion stress block contributed by Tpo and Ffs, given by BD2 f c , respectively.
T po F fs
ap ¼ 0 ; af ¼ 0 ð3Þ 2.2. Formulas for energy dissipation capacities
0:85Bf c 0:85Bf c
0
where B is the beam width and f c is the compressive strength of the The energy dissipation capacities of PT connections with flag-
beam concrete. Note that although the first and second terms on the shaped hysteresis can be quantified using the hysteretic energy
right side of Eqs. (1), (2a) and (2b) can be considered to be the dissipation ratio bE, which is defined as the ratio of the hysteresis
moment contributions from Tpo and Ffs, respectively, both Tpo and loop area for the PT connection to the area of a bilinear elastic-
Ffs are related to the lengths of the moment arms, indicating that plastic connection with the same capacity [18]. According to Seo
the relation between Tpo and Ffs should be considered during design. and Sause [18], bE, which is one of the design parameters that con-
The linear limit moments given by Eqs. (1), (2a) and (2b) can be trols the ductility demands on unbonded PT systems, can range
put into normalized form by introducing the following normalized from 0 to 0.5 for a PT connection that self-centers.
parameters related to the friction force, the initial post-tensioning For the idealized moment-rotation behavior of each PT connec-
force and the location of the friction device: tion in Fig. 3, bE can be given by
F fs T po 2df M llþ Mlrþ ðMll M lr Þ
pf ¼ ; qp ¼ 0 ; rf ¼ ð4Þ bE ¼ ð9Þ
T po BDf c D 2ðM llþ M ll Þ
where pf is the ratio of the friction force to the initial post- Substituting Eqs. (5), (6a) and (6b), (7), (8a) and (8b) into Eq. (9), the
tensioning force. qp is the initial post-tensioning force normalized hysteretic energy dissipation ratio bE for each PT connection can be
0
by BDf c , and also represents the initial stress induced in the beam also written using the normalized parameters as follows:
concrete normalized by the concrete compressive strength. rf is
pf ð1 0:85
2
qp Þ
the distance from the friction device to the mid-depth of the beam bE ¼
normalized by one-half the beam depth. Note that the values of pf 1 1
q ð1
0:85 p
þ pf 2 Þ þ pf ð1 0:85
2
qp Þ
and qp are greater than 0 for PT connections. The value of rf is equal PT connection with a WFD ð10aÞ
to 0 for a PT connection with a WFD located at the beam mid-depth,
while it is greater than 1 for a PT connection with a BFD. By dividing pf r f
0 bE ¼ PT connection with a BFD
both sides of Eqs. (1), (2a) and (2b) by BD2 f c , substituting Eq. (4) 1 0:85
1
qp ð1 þ pf 2 Þ þ pf r f
into them and rearranging, the positive and negative normalized ð10bÞ
linear limit moments mllþ and mll can be derived as functions of
the normalized parameters as follows: As can be seen from Eqs. (10a) and (10b), the only difference
between bE for the PT connections in the two cases is that
1 1
mllþ ¼ q 1 þ pf q ð1 þ pf Þ2 þ pf r f ð5Þ 1 0:85
2
qp in Eq. (10a) is replaced by rf in Eq. (10b). The value of
2 p 0:85 p
rf in Eq. (10b) is larger than 1 0:85
2
qp in Eq. (10a) because rf is
1 1 greater than 1 for PT connections with BFDs and 1 0:85 2
qp is less
mll ¼ qp 1 þ pf qp ð1 þ pf Þ2 pf r f than 1, so bE for PT connections with BFDs is larger than for PT con-
2 0:85
nections with WFDs with the same pf and qp values.
PT connection with a WFD ð6aÞ
2.3. Formulas for self-centering capability
1 1
mll ¼ qp 1 pf q ð1 pf Þ2 þ pf r f
2 0:85 p
To ensure the self-centering capability of PT connections, M lrþ in
PT connection with a BFD ð6bÞ Fig. 3 must be greater than or equal to 0. This requirement can be
where mllþ and mll are the positive and negative linear limit expressed in terms of the normalized moment mlrþ as
0
moments, respectively, normalized by BD2 f c . mlrþ P 0 ð11Þ
The moments M lrþ and M lr in Fig. 3, where the unloading
curves rejoin the loading curves, can also be expressed in a form Substituting Eq. (7) into Eq. (11) and solving for pf leads to the
similar to Eqs. (1), (2a) and (2b) by changing the signs of Ffs and following condition, where pf is greater than 0 for the PT connections:
af in these equations because the friction force changes direction, rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi!
0:85 1 4
reversing between loading and unloading. It should be noted that pf 6 1 1 þ rf ð1 þ r f Þ2 q rf ð12Þ
2 qp 0:85 p
the reversal of the friction force also affects the lengths of the
moment arms of the initial post-tensioning force Tpo and the fric- Eq. (12) expresses the upper bound of pf for PT connection design.
tion force Ffs. The normalized form of these moments thus can be Fig. 5 shows the calculated upper bound of pf from Eq. (12)
written using the normalized parameters as follows: against rf values ranging from 0 to 2 and qp values of 0.05, 0.10,
1 1 0.15, and 0.20. In every case, the upper bound of pf is 1 when rf
mlrþ ¼ qp 1 pf qp ð1 pf Þ2 pf r f ð7Þ is 0, and decreases as rf increases. For a given value of rf greater
2 0:85
than 0, increasing qp decreases the upper bound of pf, but the upper
1 1 bound of pf varies only slightly for different values of qp. These
mlr ¼ qp 1 pf qp ð1 pf Þ2 þ pf rf results suggest that the upper bound of pf is determined roughly
2 0:85
by rf. In design, this can be used to estimate an upper bound for
PT connection with a WFD ð8aÞ
the friction force Ffs in a PT connection for a known initial post-
174 T. Koshikawa / Engineering Structures 138 (2017) 170–180
(a) Geometry of PT connection (b) Cross section and displacement at beam-column interface
(a) Specimen with a friction device (b) Specimen without a friction device
Fig. 7. Comparison of hysteretic behavior from analytical responses and experimental results.
transverse reinforcements that could substantially confine the con- The dimensions and material properties used in the analysis are
crete at the beam end, the compressive strength of each concrete identical for all cases: beam width B = 0.6 m, beam depth D = 1.0 m,
fiber was set to the same value in the analysis. Fig. 7 compares beam length l = 4.0 m, the unbonded length of the post-tensioning
the analytical responses with the experimental results for the tendon lp = 5.0 m, the compressive strength of the beam concrete
0
load-beam chord rotation response of specimens with and without f c ¼ 50 N=mm2 , and the yield strength of the tendon
a friction device. In the analyses, the load is calculated as the f py ¼ 1500 N=mm2 . For all PT connections, the initial stress of the
moment at the beam-stub interface divided by the measured dis- unbonded post-tensioning tendon is set to 40% of the yield
tance from the applied load to the interface. Also, in calculating strength of the tendon fpy so that there is no tendon yielding. Thus,
the beam chord rotation, the contribution of the beam’s elastic the tendon area is adjusted depending on the initial post-
flexural deformation to the deflection is considered together with tensioning force Tpo in each PT connection.
the relative rotation at the beam-stub interface. The analytical Monotonic and cyclic load analyses of the PT connections under
responses agree reasonably well with the experimental results, vertical loads V applied at the tip of the beam were conducted
including the differences between the responses of specimens with using the section analysis method shown in Fig. 6. The monotonic
and without a friction device. The slight discrepancies in the max- load analyses for upward and downward loading were done sepa-
imum load and the unloading behavior when a friction device is rately for each PT connection. The displacement history of the cyc-
present may be related to the difference between the analytical lic load analyses consists of two cycles of sets of six beam chord
and actual force-deformation relationship of the friction device. rotations h: 0.005, 0.01, 0.015, 0.02, 0.025, and 0.03 rad. The analyt-
According to Song et al. [8] and Kim and Christopoulos [22], the ical results and validation of the design formulas for PT connec-
actual relationship is influenced by the flexibility of the connection tions are presented below.
elements (i.e. the steel members and connection bolts of the fric- As examples of the analytical results, Figs. 8(a) and (b) show the
tion device in the specimen) and the positions of the clamping ele- analytical moment-rotation responses corresponding to rf = 0.0
ments (i.e. the prestressing bars of the friction device in the and 1.5, respectively for a PT connection with pf = 0.20 and
specimen) that can cause reduction and gradual changes in the qp = 0.10. The normalized beam end moment m is the moment in
stiffness during unloading. The discrepancies may be improved 0
the beam at the beam-column interface normalized by BD2 f c . The
by considering the above influence in the analysis method if test
beam chord rotation h is calculated as the vertical displacement
data are available or an evaluation method has been established.
at the tip of the beam due to the opening and closing of the gap
at the beam-column interface combined with elastic beam deflec-
4. Analytical validation of design formulas tion divided by the beam length l. The thick curves represent the
response under monotonic loading, while the thin curves represent
The design formulas described in Section 2 were validated using the response under cyclic loading.
analytical responses of a number of PT connections with various The analytical results show essentially bilinear behavior with a
sets of normalized parameters. Table 1 lists the complete set of gradual transition from the initial to the second stiffness under
normalized parameters pf, qp, and rf considered in this analytical monotonic loading. Upon unloading, the moment decreases due
validation. The range of pf values is determined based on Eq. (12) to the reversal of the direction of the friction force in the friction
and Fig. 5 for PT connections with BFDs, and the same values are device. The differences in moment between the loading curve
used for PT connections with WFDs for comparison. The upper and the unloading curve are roughly constant in each cycle of pos-
bound of qp is set at 0.2 to comply with the recommendation in itive and negative loadings.
the Japanese guidelines [23]. The two rf values are for a PT connec- Fig. 9 shows the effect of the normalized parameters on the nor-
tion with a WFD (rf = 0.0) and with a BFD (rf = 1.5). Combinations of malized linear limit moments of the PT connections in Fig. 8. In
these parameter values result in 32 different PT connections. Figs. 9(a) and (b), the pf values vary, and in Figs. 9(c) and (d), the
qp values vary. The results in Fig. 9 show that the normalized linear
Table 1
limit moments are mainly affected by the qp values, and are not so
Normalized parameter values used in analytical validation. dependent on the pf values. An increased pf value results in a slight
0
increase in the normalized linear limit moment. Part of the differ-
pf(=Ffs/Tpo) qp ð¼ T po =ðBDf c ÞÞ rf(=2df/D)
ence between the normalized linear limit moments for PT connec-
0.00 0.05 0.0 tions with rf = 0.0 and PT connections with rf = 1.5 can be observed
0.10 0.10 1.5 most clearly under positive loading. For PT connections with the
0.20 0.15
same pf and qp values, the normalized linear limit moments for
0.30 0.20
PT connections with rf = 0.0 are smaller than for those with rf = 1.5.
176 T. Koshikawa / Engineering Structures 138 (2017) 170–180
(a) for PT connection with =0.0 (b) for PT connection with =1.5
(c) for PT connection with =0.0 (d) for PT connection with =1.5
The dashed lines in Figs. 8 and 9 show the estimated values of As in Fig. 9, the bE values for PT connections with varying pf
the normalized moments mllþ ; mll ; mlrþ ; and mlr from Eqs. (5), values are shown in Figs. 10(a) and (b), and the bE values for
(6a) and (6b), (7), (8a) and (8b). The estimated normalized linear PT connections with varying qp values are shown in Figs. 10
limit moments mllþ and mll , the differences in positive moment (c) and (d). In calculations based on the analytical response,
between mllþ and mlrþ , and the differences in negative moment the bE value for a given cycle is assumed to be the area of that
between mll and mlr can all be seen to agree reasonably well with cycle’s analytical hysteresis loop divided by the area of the cor-
the analytical results. responding bilinear elastic-plastic loop, which is defined by the
Fig. 10 plots the hysteretic energy dissipation ratios bE for PT linear limit moments from Eqs. (1), (2a) and (2b) and the elastic
connections with rf = 0.0 and 1.5 for each beam chord rotation rotational stiffness of the beam.
cycle. These are calculated from the second cycle of each ana- The bE values from the analytical response for each PT connec-
lytical response under cyclic loading (indicated by markers) as tion are nearly identical regardless of the amplitude of the beam
well as from Eqs. (10a) and (10b) (indicated by dotted lines). chord rotation cycles, except for those with rf = 0.0 and larger qp
T. Koshikawa / Engineering Structures 138 (2017) 170–180 177
(a) for PT connection with = 0.0 (b) for PT connection with = 1.5
values. The exceptions shown in Fig. 10(c) may be due to progres- Similar agreement was observed between the estimated values
sive damage in the beam concrete during the larger rotation cycles and the analytical results for moment and energy dissipation
that led to a shortening of the moment arm of the friction force capacities for the other PT connections used in the analytical vali-
under both positive and negative loadings. Figs. 10(a) and (b) show dation. The results of the analytical validation indicate that both PT
that the bE increases significantly as the pf value increases. Also, connection capacities can be estimated using the normalized
Figs. 10(c) and (d) show that changes in qp have a smaller effect parameters introduced in the design formulas. It is also worth not-
on the bE values, and the effect is different for PT connections with ing that the normalized moment-rotation responses are not seri-
rf = 0.0 and rf = 1.5. An increased qp value leads to a slight decrease ously affected by the dimensions and material properties if the
in bE for PT connections with rf = 0.0, but a slight increase when PT connections have the same set of normalized parameters (see
rf = 1.5. In addition, for PT connections with the same pf and qp val- Fig. 11, where the normalized parameters are the same as those
ues, bE for connections with rf = 0.0 is smaller than for those with of the PT connections in Fig. 8). Thus, the estimates based on the
rf = 1.5. design formulas in normalized form can be applied to PT connec-
As can be seen in Fig. 10, the bE values estimated by Eqs. (10a) tions with different dimensions and material properties.
and (10b) have trends similar to those from the analytical response
described above, but there are some differences that depend on the
various normalized parameters. In the analytical response, the PT 5. Design procedure
connections dissipate energy through not only the friction device
but also by the beam concrete’s compression, which is not consid- This section describes a design procedure to achieve desired
ered in Eqs. (10a) and (10b). Thus, for PT connections with pf = 0.0 design moment and energy dissipation capacities for PT connec-
(i.e., with no friction device), the bE values from the analytical tions. The procedure is developed using the design formulas vali-
response are positive whereas the estimated values are zero, as dated above to determine the values of the normalized
shown in Figs. 10(a) and (b). This also affects the differences parameters necessary to achieve design targets for the positive
between the analytical and estimated bE values for PT connections normalized linear limit moment mllþ and hysteretic energy dissipa-
with larger pf values. The differences decrease as the pf values tion ratio bE. In this procedure, the negative or average normalized
increase when rf = 0.0 (Fig. 10(a)), and are roughly constant when linear limit moment can also be taken as the target design value in
rf = 1.5 (Fig. 10(b)), indicating that desirable, stable energy dissipa- the same manner if necessary.
tion can be better achieved when the friction device is located on Fig. 12 shows contour plots for mllþ and bE used in the design
the bottom surface of the beam than when it is on the beam’s procedure. Both mllþ and bE are described as functions of the nor-
web. Moreover, Figs. 10(c) and (d) show that the differences malized parameters pf and qp for PT connections with rf = 0.0 in
increase as qp values increase because increasing the initial post- Fig. 12(a) and rf = 1.5 in Fig. 12(b). Solid lines in the figures show
tensioning force leads to the beam concrete dissipating more the contour lines for three mllþ values (0.04, 0.06 and 0.08) calcu-
energy. lated from Eq. (5). Dashed lines show the contours of three bE val-
178 T. Koshikawa / Engineering Structures 138 (2017) 170–180
Fig. 11. Analytical responses of PT connections with different dimensions and material properties.
Fig. 12. Contour plots for normalized linear limit moment and hysteretic energy dissipation ratio.
ues (0.125, 0.250 and 0.375) calculated from Eqs. (10a) and (10b). PT connections with rf = 1.5 (Fig. 14). However, they are smaller
Note that the contour line for bE = 0.375 does not appear in the than the design targets for bE = 0.250 for PT connections with
range of Fig. 12(a). The shaded area in Fig. 12(b) represents the rf = 0.0 (Figs. 13(b) and (d)), indicating that the energy dissipation
area beyond the upper bound of pf from Eq. (12). As mentioned provided by a friction device located on the beam web is lower
previously, the upper bound of pf is 1 for PT connections with than expected in the design formulas when the friction force is
rf = 0.0, so the shaded area does not appear in Fig. 12(a). large relative to the initial post-tensioning force. This can also be
In Fig. 12, it can be seen that the contour plots for certain values seen in Fig. 10(a) and may be due to the reversal of the friction
of mllþ and bE intersect. The normalized parameter values pf and qp force at the beginning of each half-rotation cycle. The analytical
at the intersection can be assumed to be the required values for the response of the friction force variation during a single rotation
design targets for mllþ and bE. As examples, Figs. 13 and 14 show cycle is shown in Fig. 15(a) for the PT connection in Fig. 13(b). In
the analytical cyclic responses of PT connections for target design the half-rotation cycles, the friction force acts in the negative direc-
values of mllþ ¼ 0:4 and 0:8 and bE ¼ 0:125 and 0:250. In this anal- tion at the start of the rotation and then transitions gradually to
ysis, the pf and qp values at the intersections indicated by dots in the positive direction. The gradual transition delays the develop-
Fig. 12 are set for PT connections that have the same dimensions ment of the full friction force in the positive direction, so this
and material properties used in Section 4. The responses for PT may lead to a loss of energy dissipation. This is not observed in
connections with rf = 0.0 and the pf and qp values from Fig. 12(a) PT connections with rf = 1.5 (see Fig. 15(b)), and is not considered
are shown in Figs. 13(a)–(d). Similarly, the responses for PT con- in the design formulas. Thus, for PT connections with rf = 0.0, it
nections with rf = 1.5 and the pf and qp values from Fig. 12(b) are may be desirable for pf values to be set slightly larger than the val-
shown in Figs. 14(a)–(d). Along with the analytical moment- ues at the intersections in Fig. 12(a) to achieve the design energy
rotation response, the average value of the hysteretic energy dissi- dissipation capacity while achieving the design target mllþ values.
pation ratio bEave, calculated from all of the second beam chord From Figs. 12–14, it can be seen that PT connections with rf = 0.0
rotation cycles of the analytical response, is also shown in each and rf = 1.5 require different combinations of pf and qp values for
figure. the same design target mllþ and bE values. A comparison of these
Figs. 13 and 14 show that these PT connections have moment PT connections, targeting the same mllþ and bE values, shows that
capacities that satisfy the design targets for mllþ . The calculated the pf and qp values for PT connections with rf = 1.5 are smaller
bEave values satisfy the design targets for bE = 0.125 for PT connec- than those for PT connections with rf = 0.0, and the differences
tions with rf = 0.0 (Figs. 13(a) and (c)), and are more satisfactory for are amplified as the target mllþ and bE values grow.
T. Koshikawa / Engineering Structures 138 (2017) 170–180 179
(a) Targeting = 0.04 and = 0.125 (b) Targeting =0.04 and = 0.250
(a) Targeting = 0.04 and = 0.125 (b) Targeting = 0.04 and = 0.250
Fig. 15. Analytical friction force variation during second cycle of 0.01 rad beam chord rotation.
6. Conclusions [3] Bradley BA, Dhakal RP, Mander JB, Li L. Experimental multi-level seismic
performance assessment of 3D RC frame designed for damage avoidance.
Earthquake Eng Struct Dyn 2008;37(1):1–20.
The following conclusions can be drawn from this study: [4] Rodgers GW, Solberg KM, Chase JG, Mander JB, Bradley BA, Dhakal RP, et al.
Performance of a damage-protected beam-column subassembly utilizing
external HF2V energy dissipation devices. Earthquake Eng Struct Dyn
1. The moment capacities, hysteretic energy dissipation capaci-
2008;37(13):1549–64.
ties, and self-centering capabilities of PT connections with [5] Rodgers GW, Solberg KM, Mander JB, Chase JG, Bradley BA, Dhakal RP. High-
WFDs or BFDs can be expressed as functions of normalized force-to-volume seismic dissipators embedded in a jointed precast concrete
frame. J Struct Eng 2012;138(3):375–86.
parameters pf, qp, and rf, which are related to the friction force,
[6] Morgen BG, Kurama YC. A friction damper for post-tensioned precast concrete
initial post-tensioning force, and location of the friction device, moment frames. PCI J 2004;49(4):112–33.
respectively. The design formulas suggested that the upper [7] Sugiura H, Sashima Y, Sanada Y. Performance evaluation tests of unbonded
bound of pf for ensuring self-centering capability in PT connec- prestressed concrete beams with/without a friction damper. In: 20th
Symposium on Developments in Prestressed Concrete, Hakodate, Japan;
tions can be determined roughly using rf values. 2011 [in Japanese].
2. The proposed nonlinear section analysis method is able to pre- [8] Song LL, Guo T, Chen C. Experimental and numerical study of a self-centering
dict the behavior of PT connections under cyclic loading. The prestressed concrete moment resisting frame connection with bolted web
friction devices. Earthquake Eng Struct Dyn 2014;43(4):529–45.
analytical results of a number of PT connections with various [9] Song LL, Guo T, Gu Y, Cao ZL. Experimental study of a self-centering prestressed
sets of normalized parameters showed that their moment concrete frame subassembly. Eng Struct 2015;88:176–88.
capacities were mainly affected by qp values and the hysteretic [10] Morgen B, Kurama Y. Seismic design of friction-damped precast concrete
frame structures. J Struct Eng 2007;133(11):1501–11.
energy dissipation capacities were mainly affected by pf values. [11] Tsai KC, Chou CC, Lin CL, Chen PC, Jhang SJ. Seismic self-centering steel beam-
For PT connections with the same pf and qp values, both capac- to-column moment connections using bolted friction devices. Earthquake Eng
ities for PT connections with WFDs (rf = 0.0) were smaller than Struct Dyn 2008;37(4):627–45.
[12] Iyama J, Seo CY, Ricles JM, Sause R. Self-centering MRFs with bottom flange
those of PT connections with BFDs (rf = 1.5). Comparisons
friction devices under earthquake loading. J Constr Steel Res 2009;65
between the estimated values from design formulas and the (2):314–25.
analytical results showed generally reasonable agreement for [13] Wolski M, Ricles JM, Sause R. Experimental study of a self-centering beam–
column connection with bottom flange friction device. J Struct Eng 2009;135
moment and energy dissipation capacities.
(5):479–88.
3. The analytical results also confirmed the adequacy of the design [14] Guo T, Song L, Zhang G. Numerical simulation of the seismic behavior of self-
procedure, but for PT connections with rf = 0.0, slightly larger pf centering steel beam-column connections with bottom flange friction devices.
values than those that arise from the design procedure might be Earthquake Eng Eng Vibr 2011;10(2):229–38.
[15] Lin Y, Sause R, Ricles J. Seismic Performance of a large-scale steel self-centering
needed to achieve design energy dissipation capacity. For PT moment resisting frame: MCE hybrid simulations and quasi-static pushover
connections aiming to provide the same moment and energy tests. J Struct Eng 2013;139(7):1227–36.
dissipation capacities, the pf and qp values for PT connections [16] El-Sheikh M, Pessiki S, Sause R, Lu LW. Moment rotation behavior of unbonded
post-tensioned precast concrete beam-column connections. ACI Struct J
with BFDs (rf = 1.5) were smaller than for connections with 2000;97(1):122–32.
WFDs (rf = 0.0), and the differences were amplified as the target [17] Perez FJ, Sause R, Pessiki S. Analytical and experimental lateral load behavior
capacities grew. of unbonded post tensioned precast concrete walls. J Struct Eng 2007;133
(11):1531–40.
[18] Seo CY, Sause R. Ductility demands on self-centering systems under
earthquake loading. ACI Struct J 2005;102(2):275–85.
Acknowledgments [19] Koshikawa T, Kadowaki H, Matsumora M. Energy dissipation efficiency of
unbonded post-tensioned precast concrete beam-column connections with
beam-end dampers. In: 15th World Conference on Earthquake Engineering,
Support for this research from JSPS KAKENHI Grant Number Lisbon, Portugal; 2012.
15K06282 is gratefully acknowledged. [20] Koshikawa T. Energy dissipation in post-tensioned self-centering precast
concrete connections with a friction device. In: 8th International Structural
Engineering and Construction Conference, Sydney, Australia; 2015.
References [21] Matsumora M, Koshikawa T, Kikuchi M. Evaluation of ultimate strength and
rotation angle for unbonded post-tensioned precast concrete beams by using
[1] Stone WC, Cheok GS, Stanton JF. Performance of hybrid moment-resisting section analysis. J Struct Constr Eng 2014;79(701):1005–13 [in Japanese].
precast beam-column concrete connections subjected to cyclic loading. ACI [22] Kim H-J, Christopoulos C. Friction damped post tensioned self-centering steel
Struct J 1995;92(2):229–49. moment-resisting frames. J Struct Eng 2008;134(11):1768–79.
[2] Priestley MJN, Sritharan S, Conley JR, Pampanin S. Preliminary results and [23] Architecture Institute of Japan, Guidelines for structural design and
conclusions from the PRESSS five-story precast concrete test building. PCI J construction of prestressed concrete buildings based on performance
1999;44(6):42–67. evaluation concept (draft), Tokyo, Japan; 2015 [in Japanese].