Whitepaper On Testing Certification Procedure by Nived BS
Whitepaper On Testing Certification Procedure by Nived BS
Executive
summary
This paper presents a testing and certification procedure for the evaluation of grid compliance of
power generating units (mainly wind and inverter-based solar stations), according to the amended
regulation released by the Central Electricity Authority of India (CEA) in February 2019.
2
WHITE PAPER
Introduction
Recently, a substantial upgrade of the grid connection a particular engineering recommendation (EREC G99)
requirements for power generating units (PGUs) has to provide requirements for the connection of PGUs to
been taking place worldwide. New requirements for the distribution networks in the U.K., where particular
PGUs are introduced in most countries to ensure advice for the compliance testing is also included13. A test
robustness and frequency/voltage support on the grid, procedure according to the European Network Code1 is
such as overvoltage ride through capability (OVRT) and currently under development by CENELEC Working Group
the frequency - active power response characteristics TC8X WG03, while similar updates are taking place also
1-7. The main drivers for these changes are the evolution in other countries such as in Spain, where the special
in the control capabilities of the units using power procedure for wind and photovoltaic farms used up to
electronic inverters as well as the expansion of the now14 is expected to be replaced.
distributed generation. In addition, the establishment
of harmonized rules for grid connection of all PGUs is In India, five years after the previous amended regulations
important for regulatory authorities and grid operators for grid connectivity requirements in which requirements
to provide a clear regulatory framework, ensure power for wind turbines and generating stations using inverters
system security, facilitate the integration of renewable were included for the first time16-17, the Central Electricity
energy sources (RES) and allow a more efficient use of Authority (CEA) came up with an amended regulation in
the network and resources for the benefit of consumers1. February 2019 with modifications and new connection
Therefore, most new grid code requirements apply rules18. The experience from testing and certification
to all types of PGUs, including synchronous and according to the previous requirements has shown that
asynchronous generators, inverter based technologies, the existence of a dedicated testing and certification
e.g., wind turbines (WTs) and solar inverters (PVs), and procedure for the verification of grid compliance, as
offshore installations. In addition, the recent grid code described in19, is important for all involved parties (public
requirements cover a wider range of nominal powers of authorities, manufacturers, testing and certification
the PGUs, starting from powers even below 1 kW. bodies, etc.) to work more efficiently and speed up the
installations of distributed power generating stations in
On the other hand, with the establishment of new grid India. Apparently, an updated procedure based on the
connection requirements, new challenges appear in latest CEA amendment has to be followed from now on.
the area of grid compliance testing and certification. The aim of this paper is to propose an updated testing
Obviously, the testing procedures followed up to now procedure for assessing compliance with the new CEA
need to be reviewed and updated accordingly. As an regulations (2019)18 using the deep experience of UL in
example, the IEC 61400-21, Ed.2 standard8, which was testing and certification according to the former CEA
widely used for WT testing for more than 10 years, regulations (2013)17.
was recently withdrawn and replaced with the new
IEC 61400-21-1, Ed.19. Similarly, several countries have Regarding the structure of the paper, in Section II, the
already adapted their particular testing procedures for amended requirements of the CEA standard for grid
grid compliance certification to the latest changes in connectivity are presented. Section III includes proposals
their grid codes, or they are currently in the adaptation for the necessary tests for each particular electrical
phase. In Germany, FGW has issued a new revision of the characteristic (fault ride through capability, flicker,
Technical Guideline 3 (FGW-TR3, 10), which incorporates harmonics, grid protection and control requirements).
the requirements of the new German grid codes for In Section IV, a brief discussion on the certification
connection to medium voltage (MV), high voltage (HV) procedure for the assessment of grid compliance is
and extra high voltage (EHV)2-4. The relevant German included, while the conclusions of the present work are
guidelines for the modeling and the certification of PGUs, summarized in Section V.
systems and components have been also updated11-12.
In the U.K., the Energy Networks Association (ENA) issued
3
WHITE PAPER
A. Electrical characteristics in normal iii. Active power set-point control: PGUs shall have the
capability of set-point control of the active power
operation (PQ) following the orders given the relevant load dispatch
The power quality parameters of interest are the center.
harmonics, DC current injection and flicker. The CEA iv. Active power ramp rate limitation: PGUs shall be
regulation does not refer explicitly to any measurement equipped with the facility for controlling the rate of
guideline but incorporates the following provisions: change of power output at a rate not more than ±
• With regard to harmonic current emissions, they 10% per minute.
should not violate the limits specified in the standard v. Frequency sensitive mode: PGUs shall have the
519 of the Institute of Electrical and Electronics capability to control active power in case of over- and
Engineers (IEEE)19. under-frequency at a droop between 3 to 6% and a
• The DC current injection of the PGUs at the point of dead band ≤ 0.03 Hz.
connection should not be greater than 0.5% of the vi. Synthetic inertia: For frequency deviations < 0.3 Hz,
rated current In. the station shall have the facility to provide within 1
• The flicker emissions should be kept within the limits second power frequency response of at least 10% of
specified in IEC 61000, which can be related to IEC the maximum active power capacity.
Technical Report 61000-3-721
It should be noted that, according to CEA, requirements
The above requirements have remained unchanged in the from (iii) to (vi) apply for generating stations with
new CEA amendment18. installed capacity of more than 10 MW connected at
voltage level of ≥33 kV.
B. Control capability
Control capability requirements apply to voltage-reactive C. Fault-ride-though-capability
power (Q-U) and frequency-active power (P-F) control. Fault-ride-through (FRT) capability in the amended CEA
More specifically, the following requirements apply: regulation18 also includes the requirement for OVRT
i. Reactive power capability: PGUs shall be capable of Capability of PGUs. The required voltage profile is shown
supplying the necessary reactive power in order to in Table 1 and Fig. 1. The requirements for grid support
ensure that power factor is kept within the limits of during the voltage dips are the following:
0.95 lagging and 0.95 leading. • During the voltage dip, the supply of reactive power
ii. Frequency range test: PGUs shall be capable of has first priority, while the supply of active power has
remaining connected to the network and operate second priority.
within the frequency range of 47.5 Hz to 52 Hz. In • Active power after voltage dips clearance shall be
addition, they should be able to deliver rated power restored to at least 90% of the pre-fault level within 1
in the frequency range of 49.5 to 50.5 Hz, subject to sec of restoration of voltage.
availability of the primary energy source, i.e., wind • For overvoltage events, the only requirement is that
speed or solar radiation. This performance shall be the PGUs shall remain connected to the grid
also achieved with a voltage variation of up to ± 5 %.
4
WHITE PAPER
0.15 300
0.85 3000
0.90 10000
0 (Instantaneous
> 1.30
trip)
a. V T/Vn is the ratio of the actual voltage to the nominal Fig. 1. Lower and upper limit of the voltage-against-time profile
system voltage. of any or all phases at the interconnection point according to the
amended CEA Grid Connectivity Standard19.
Table 1. Minimum requirements of LVRT/HVRT capability of
PGUs according to CEA requirements
5
WHITE PAPER
B. Harmonic measurements
The CEA requires that harmonic current injection of PGUs shall not exceed the limits specified in IEEE standard 51920.
This requirement also remained unchanged after the release of the new CEA regulation, but the harmonics measurement
procedure that must be followed from now on is compatible with the new IEC 61400-21-1 standard9. A basic difference
between this new IEC standard, compared to the old IEC 61400-218, is the harmonic aggregation method, which is now
common with the IEEE 519 method. However, there are still differences between the two guidelines, which have to be
taken into account when assessing the relevant grid compatibility presented in Table 2 In this table, the contents of the old
IEC 61400-21 are also included to highlight the changes in the procedure followed up to now.
It should be stressed at this point that the harmonic measurement method proposed by the IEEE 519 standard is mainly
oriented to loads operating at constant power. From that perspective, measurement on a daily and weekly basis may not
cover all power levels in case of WTs and may not be sufficient. Therefore, it is recommended that the power-bin-wise
measurement procedure is adopted, according to IEC 61400-21-1. The averaging time and the aggregation method of IEEE
519 can be applied afterwards for the evaluation of the harmonic results.
Integer harmonics up
Harmonic frequencies up to 9 kHz Up to 9 kHz
to 50th order
Table 2. Comparison between IEC and IEEE standards with regard to the harmonic evaluation procedure
6
WHITE PAPER
7
WHITE PAPER
X SR X SC
Regarding the necessary measuring points, measuring Z2
LVRT Container
S1
Transformer
8
WHITE PAPER
9
WHITE PAPER
10
WHITE PAPER
11
WHITE PAPER
At partial load:
10 Active power before fault entry 0,1 Pn - 0,5 Pn Y N
At full load: ≥ 0,9 Pn
13 Voltage drop level defined by the testa within voltage ranges of Table 3. Y N
Fault ride through
Active power response time after Restored to at least 90% of the pre-fault level
16 Y N
voltage dip clearance within 1 s of restoration of voltage
a) To be confirmed based on the no load test because of the voltage change under load conditions
12
WHITE PAPER
Summary and
conclusion
In this paper, a testing procedure to determine the electrical characteristics of all types of power generating units
(including wind turbines and solar inverters) in accordance to the latest CEA requirements (2019) is proposed. As far
as possible, this testing procedure follows the latest international standards and guidelines, and mainly IEC 61400-
21-1. However, some additional specifications are imposed by CEA that need to be sufficiently addressed through
dedicated tests.
This paper also specifies the type and number of field tests and measurements to be performed, the measurement
and evaluation specifications (duration of measurements, statistical evaluation process, etc.) as well as reporting
requirements. In some cases, further discussion on the interpretation of certain CEA requirements is included. In
addition, this paper contains proposals for the efficient assessment and interpretation of the results to ensure that the
final decision is according to CEA requirements.
The proposed procedure should replace the one used up to now for more than 5 years that was based on the previous
CEA regulation (2013) and is expected to contribute to the fast adoption of the new CEA requirements by all involved
parties, speeding up the grid compliance evaluation process followed by the public authorities in India.
Contact us:
13
WHITE PAPER
Endnotes
1. Commission Regulation (EU) 2016/631 of April 14, 11. FGW e.V., Technical Guidelines - Part 4, “Demands
2016, “Establishing a network code on requirements on modelling and validating simulation models of
for grid connection of generators.” the electrical characteristics of power generating
units and systems, storage systems as well as their
2. VDE-AR-N 4110, “Technische Regeln für den Anschluss components,” Revision 9, 01.02.2019.
von Kundenanlagen an das Mittelspannungsnetz und
deren Betrieb (TAR Mittelspannung),” VDE Verband 12. FGW e.V., Technical Guidelines - Part 8, “Certification
der Elektrotechnik Elektronik Informationstechnik e. V of the electrical characteristics of power generating
(Association of German Electrical Engineers). units, systems and storage systems as well as their
components on the grid,” Revision 9, 01.02.2019.
3. VDE-AR-N 4120, “Technische Regeln für den Anschluss
von Kundenanlagen an das Hochspannungsnetz und 13. Engineering Recommendation G99, “Requirements for
deren Betrieb (TAR Hochspannung).” the connection of generation equipment in parallel
with public distribution networks on or after 27 April
4. VDE-AR-N 4130, “Technische Regeln für den Anschluss 2019,” Issue 1 – Amendment 3, 16 May 2018.
von Kundenanlagen an das Höchstspannungsnetz und
deren Betrieb (TAR Höchstspannung).“ 14. AEE, “Procedure for verification validation and
certification of the requirements of the P.O. 12.3 on
5. NGET, “The Grid Code,” Issue 5, Revision 33, April 2019. the response of wind farms and photovoltaic farms in
the event of voltage dips,” Version 9, 2011.
6. IEEE Standard 1547-2018, “IEEE Standard for
Interconnection and Interoperability of Distributed 15. CENELEC, CLC/TS 50549-10 - “Requirements for
Energy Resources with Associated Electric Power generating plants to be connected in parallel with
Systems Interfaces.” distribution networks - Part 10: Tests demonstrating
compliance of units.”
7. P.O. 12.2, “Instalaciones de Generacion y de demande:
Requisitos minimos de diseno, equipamiento, 16. Central Electricity Authority (CEA), “Technical
funcionamiento, puest en servicio y securidad,” Standards for Connectivity to the Grid – Regulations
Proposal for public consultation from the Spanish 2007,” New Delhi, Feb. 21, 2007.
Ministry of Energy, May 2019
17. CEA, “Technical Standards for Connectivity to the Grid
8. IEC 61400-21 Wind turbine generator systems, Part – Amendment Regulations, 2013,” New Delhi, Oct. 15,
21, “Measurement and assessment of power quality 2013.
characteristics of grid connected wind turbines,” Ed.
2.0, 2008-08. 18. CEA, “Technical Standards for Connectivity to the Grid
– Amendment Regulations, 2019,” New Delhi, Feb, 6,
9. IEC 61400-21-1 Wind energy generation systems – 2019.
Part 21-1: “Measurement and assessment of electrical
characteristics – Wind turbines,” Ed.1, May 2019. 19. Nivedh BS, Sokratis Tentzerakis, Jens Dirksen, Fritz
Santjer, “Testing procedure for the evaluation of grid
10. FGW e.V., Technical Guidelines for Power Generating compliance of power generating units according
Units and Systems - Part 3 (TG3), “Determination of to the requirements of the Indian Grid Code,”
the electrical characteristics of power generating 1st International Conference on Large-Scale Grid
units and systems, storage systems as well for their Intergation of Renewable Energy in India, New Delhi,
components in medium-, high- and extra-high voltage India, Sept. 6-8, 2017.
grids,” Revision 25, 01.09.2018.
14
WHITE PAPER
20. IEEE Standard 519-2014, “IEEE Recommended Practice 24. Technical Report IEC/TR 61000-3-6, “Electromagnetic
and Requirements for Harmonic Control in Electric compatibility (EMC) – Part 3-6: Limits – Assessment
Power Systems.” of emission limits for the connection of distorting
installations to MV, HV and EHV power systems,”
21. Technical Report IEC/TR 61000-3-7, “Electromagnetic Edition 2.0, 02-2008.
compatibility (EMC) – Part 3-7: Limits – Assessment
of emission limits for the connection of fluctuating 25. IEC TS 62910 Technical Specification Edition 1.0, 2015-
installations to MV, HV and EHV power systems,” 10: “Utility-Interconnected photovoltaic inverters
Edition 2.0, 02-2008. - Testing procedure for low voltage ride-through
measurements.”
22. IEC 61000-4-7 Electromagnetic compatibility (EMC)
– Part 4-7, “Testing and measurement techniques 26. IEEE Standard 1547.1-2005, “IEEE Standard
– General guide on harmonics and interharmonics Conformance Test Procedures for Equipment
measurements and instrumentation, for power supply Interconnecting Distributed Resources with Electric
systems and equipment connected thereto,” Ed. 2.1, Power Systems.”
2009-10.
27. ISO/IEC 17025, “General requirements for the
23. IEC 61000-4-30 Electromagnetic compatibility (EMC) competence of testing and calibration laboratories.”
– Part 4-30, “Testing and measurement techniques
– Power quality measurement methods,” Ed. 3.0,
2015-02.
15
UL.com
UL and the UL logo are trademarks of UL LLC © 2021.
02/21