Ignition Server Sizing and Architecture Guide
Ignition Server Sizing and Architecture Guide
inductiveautomation.com 1-800-266-7798
Ignition Server Sizing and Architecture Guide
Table of Contents
Table of Contents 2
Introduction 4
SQL Database 5
Small Historian 5
2 Cores (2 GHz+), 2GB memory, SSD 5
2 Cores (2 GHz+), 4GB memory, SSD 5
Medium Historian 6
4 Cores (4 GHz+), 8GB memory, SSD 6
4 Cores (4 GHz+), 16GB memory, SSD 6
Large Historian 6
8 Cores (4 GHz+), 16GB memory, SSD 6
Ignition Memory 6
Standard Architecture (Single Server) 7
Small Ignition Project 7
ARM, 1GB memory, SSD 7
2 Cores (2 GHz+), 2GB memory, SSD 8
2 Cores (3 GHz+), 4GB memory, SSD 8
Medium Ignition Project 8
4 Cores (3 GHz+), 4GB memory, SSD 8
4 Cores (4 GHz+), 8GB memory, SSD 8
4 Cores (4 GHz+), 16GB memory, SSD 8
Large Ignition Project 8
8 Cores (4 GHz+), 8GB memory, SSD 8
8 Cores (4 GHz+), 16GB memory, SSD 9
16 Cores (4 GHz+), 32GB memory, SSD 9
Scale-Out Architecture 9
Gateway Network 9
Gateway Network Features 10
Enterprise Administration 10
Distributed Services 10
Security Zones and Service Security 10
One I/O / One Frontend 11
One OPC-UA Server / One I/O / One Frontend 12
Two I/O / One Frontend 13
Tag Provider Best Practice 13
Page 2
Ignition Server Sizing and Architecture Guide
Tag Paths 13
Full Scale-Out With Load Balancer 14
Examples of Load Balancers 15
Value Changes Are Key 15
Optimizations 16
Polling rates 16
Deadbands 16
Leased and Driven Tag Groups 16
Event-Driven 17
Scripts 17
Avoid Polling Queries and Use Caching 17
Tag Historian Stale Data Detection 18
Vision Client Tag Poll Rate 18
Gateway Network Optimizations 19
Remote Tag Provider Alarm Subscription 19
Remote Tag Provider History Mode 19
Running Ignition on Virtual Machines 19
Summary 19
Software 20
Resource Allocation 20
Dedicated Resources 20
VMWare Specific Settings 20
Common Questions 21
Q: My CPU utilization isn’t too high. Do I still need Dedicated Resources? 21
Q: How do I know if I need dedicated resources? 21
Q: I already have dedicated resources, and I’ve allocated a large number
of vCPUs, but my Ignition system is still overloaded. What do I do? 21
References 22
VMWare 5.5 Latency Sensitivity 22
VMWare 6.7 Latency Sensitivity 22
Page 3
Ignition Server Sizing and Architecture Guide
Introduction
Ignition is a development toolkit, with unlimited licensing and different modules, that give you the
tools to build solutions. An Ignition project can be as small as a data collector for a few tags or as large
as an enterprise solution with hundreds of devices, hundreds of thousands of tags, and hundreds of
visualization clients. It is extremely important to find the right architecture and sizes of servers for your
Ignition project so that the project will work as intended and have room for growth in the future.
This guide is intended to provide some tips to help you determine the correct architecture depending
on your requirements. It is important to note that any architecture that you come up with needs to be
fully tested and verified. Throughout that process you can observe the performance characteristics of
the server in order to make any necessary adjustments to the architecture. There is no guarantee on
performance since it is based on your design choices.
The features you use in Ignition also play a large role in performance. Features, such as the following,
require processing time and memory:
• Device communication
• OPC-UA (client and server)
• Tags (OPC, Expression, SQL query, etc.)
• Historian (storage and retrieval)
• Alarming (status, journal, notification pipelines)
• Transaction groups (especially large numbers)
• Scheduled PDF reports
• Sequential Function Charts
• Scripting
- Tag change scripts
- Scripts running on the server (timer, message handlers, etc.)
• Visualization clients
Page 4
Product Data Sheet | Perspective® Module
Ignition is heavily multithreaded and can handle configurations with all of the features above at
reasonable limits. Some of the features above, such as device communication and tags, have
predictable performance. Other features, such as visualization clients, have less predictable
performance since they are based on how the user interacts with the system and how the project is
configured. For example, we can allow a user to pull back a year of historical data on a trend and poll
it at a one-second rate. We can go hours or days without anyone using that screen but then we could
have a situation where 10 people are using it at the same time causing an increased load on the server.
In most cases, a single server is sufficient to handle everything. However, when projects get large or
when we push the limits of Ignition, we need to utilize multiple servers. Luckily, Ignition is modular and
has the ability to scale-out by separating different modules and features onto dedicated servers. At the
end of the day, those separate servers work as one Ignition unit and are completely transparent to the
user, thanks to Ignition’s Gateway Network and standards like OPC-UA, SQL, MQTT, and more.
The purpose of this guide is to walk you through projects of different sizes to understand their hardware
requirements and architecture. Since Ignition has a lot of different features, this guide is going to focus
on the number of devices, tags, and clients.
SQL Database
The SQL database (MySQL, Microsoft SQL Server, etc.) in all of these scenarios below should be on its
own dedicated server. If you want to put it on the same server as Ignition, you will need more processing
power and memory. Here are some basic database sizing tips:
Small Historian
Requires approximately 300GB disk space/year if 100% of the values are changing every second
sustained (approximately 6GB with 2% change, smaller with slower rates)
Page 5
Ignition Server Sizing and Architecture Guide
Requires approximately 3TB disk space/year if 100% of the values are changing every second sustained
(approximately 60GB with 2% change, smaller with slower rates)
Medium Historian
4 Cores (4 GHz+), 8GB memory, SSD
500 - 2,500 value changes per second
Requires approximately 7TB disk space/year if 100% of the values are changing every second sustained
(approximately 150GB with 2% change, smaller with slower rates)
Requires approximately 15TB disk space/year if 100% of the values are changing every second sustained
(approximately 300GB with 2% change, smaller with slower rates)
Large Historian
8 Cores (4 GHz+), 16GB memory, SSD
5,000 - 10,000 value changes per second
Requires approximately 30TB/year if 100% of the values are changing every second sustained
(approximately 60GB with 2% change, smaller with slower rates)
Note: Some databases on a properly tuned server can max out at 10,000 value changes per second.
For example, MySQL will max out server performance at 10,000 value changes per second, so it is
advisable to stay within 5,000. Microsoft SQL Server can handle up to 20,000-30,000 value changes
per second with the latest version. However, throughput and query speed is dependent on hardware
and database setup. Speed of retrieving data in Ignition can also be impacted with higher storage
throughput. You can achieve higher throughput by installing another Ignition instance on the same
server as the database and use Ignition’s remote tag history feature through the Gateway Network. This
will avoid sending a large amount of raw data (SQL inserts) through the network and will, instead, send
compressed data over the network, ultimately resulting in the same inserts but executed locally.
Ignition Memory
The amount of memory Ignition has allocated in Ignition’s ignition.conf configuration file can be adjusted.
You need to set the proper amount of memory for each of the scenarios below. Typically, you can leave
1-2GB of memory to the Operating System (OS) and use the rest for Ignition. See our documentation for
more details on setting Ignition’s memory:
Page 6
Ignition Server Sizing and Architecture Guide
https://docs.inductiveautomation.com/display/DOC81/Gateway+Configuration+File+Reference#Gateway
ConfigurationFileReference-GatewayMemoryAllocation
PLCs
Ignition
Server
Touch
Panels
Database
Web-Launched
Clients
Web-Based
Designers
Mobile
Devices
Ignition’s most common architecture consists of a single on-premise Ignition server connected to a
SQL database, PLCs, and clients. In this case, all functionality is configured on the same Ignition server.
Ignition’s licensing is unlimited. However, Ignition is limited by the size of the hardware. With larger
hardware, Ignition can handle more device connections, tags, and clients.
Page 7
Ignition Server Sizing and Architecture Guide
Page 8
Ignition Server Sizing and Architecture Guide
†R
esults can vary based on design choices. The examples are based on typical usage. Faster polling
rates, increased value changes, and utilization of other Ignition features, such as scripts, Transaction
Groups, SFCs, and more, can significantly impact the overall performance.
Scale-Out Architecture
In larger systems, it is often easier to have multiple Ignition installations to help split the load between
the frontend tasks and the backend tasks. This is perfect for single large systems that aren't split up into
different sites. In cases where systems are split into different sites, the Hub and Spoke Architecture is
usually a better fit.
In the Scale-Out architecture, you have at least one Gateway that handles backend communications.
The backend Gateway deals with all PLC and device communications. The frontend Gateway handles all
of the Clients, serving up the data pulled from the backend Gateway. This is made possible through the
Gateway Network, connecting Gateways to each other, and allowing tags to be shared through remote
tag providers.
Gateway Network
The Gateway Network allows you to connect multiple Gateways together over a wide area network and
opens up many distributed features between Gateways.
• A dedicated HTTP data channel that can handle multiple streams of message data.
• Security settings that restrict incoming connections based on a whitelist or on manual approval
of the connection. Incoming connections can also be disabled entirely.
• An available SSL mode. When enabled, connections must send SSL certificates to prove their
identity. A connection will not be accepted until its SSL certificate is approved. Optionally,
client certificates can be configured to be required as well as server certificates.
Page 9
Ignition Server Sizing and Architecture Guide
Enterprise Administration
The Enterprise Administration Module (EAM) uses the Gateway Network for message and file transfer
and can monitor network connections for availability. The EAM reports whenever communications are
lost via alarm events and system tags.
Distributed Services
Distributed services included the following:
• Remote Realtime Tag Providers: Provides the ability to read/write tags from a remote Ignition
server. Perfect for frontend servers that need to see the tags on the backend. This includes
reading and writing to tags, seeing alarms, and even querying historical data.
• Remote Historical Tag Providers: Provides the ability to send historical data to another Ignition
server for storage to a SQL database. Also provides the ability to remotely query historical data
when a connection to the SQL database is not available.
• Remote Alarming: Provides the ability to send alarm notifications to another Ignition server.
Perfect when email, voice, or SMS is only available on a central Ignition server.
• Remote Alarm Journal: Provides the ability to send alarm history to another Ignition server for
storage to a SQL database.
• Remote Audit Logs: Provides the ability to send audit logs to another Ignition server for storage
to a SQL database.
Page 10
Ignition Server Sizing and Architecture Guide
PLCs
SQL
Database
I/O
Clients
Frontend Anywhere
With this architecture, you have one Ignition server communicating to the PLCs and performing backend
tasks such as polling live values, historian, and alarming. The backend server is responsible for logging
data to the SQL database. The frontend server handles all of the visualization clients (Vision and
Perspective) and should also communicate to the SQL database for querying historical data.
With this architecture, you can handle more device connections, tags, and clients since you have two
servers. You can easily expand to multiple I/O servers and frontend servers as the size of the project
increases, allowing for easy scalability.
Page 11
Ignition Server Sizing and Architecture Guide
PLCs
SQL
Database
I/O
Frontend
OPC-UA
Clients
Anywhere
With this architecture, a dedicated OPC-UA server that handles all of the PLC communication was
introduced. Essentially, you are breaking apart OPC-UA from a single server. This architecture lets one
handle a larger set of devices. The I/O server simply handles the tag value changes. You can easily
handle a larger set of tags, in regards to history and alarming, with additional OPC-UA servers for
different sets of PLCs.
Page 12
Ignition Server Sizing and Architecture Guide
Cs
PL
p2
ou
Gr
Cs
PL
p1
ou I/O
Gr
SQL
Database
I/O
Clients
Frontend Anywhere
With this architecture, you have two Ignition servers communicating to different sets of PLCs, allowing for
communication to a larger set of devices and tags. For example, it is possible to handle approximately
250,000 tags from 200 devices. You can easily add additional I/O servers as necessary.
Tag Paths
It is recommended to use fully-qualified tag paths in your projects, especially with visualization templates
and screens. A fully-qualified path allows Ignition to know exactly where the tag is, including the tag
provider name.
Page 13
Ignition Server Sizing and Architecture Guide
With that path, you don’t know which tag provider it comes from. An Ignition project will use the project’s
default tag provider, which is only one provider.
Notice the path includes the tag provider. You can easily provide a parameter in a visualization template
that can change the tag provider and the tag path, allowing us to point to any tag from any provider.
C s
PL Local
p2
ou Client
Gr
Ignition
s Edge
LC
p 1P Local
ou Client
Gr
I/O
SQL
Ignition Database
Edge
I/O
Load
Frontend
Balancer Clients
Anywhere
The best thing about the Scale-Out architecture is that it is easy to scale up Ignition as your system
grows. In the image above, more frontend Gateways were added to help handle an increase in clients,
and a Load Balancer to automatically distribute the clients between them. When using a load balancer,
it is important to turn on “sticky” sessions to ensure the connection stays consistent for at least one
hour. The frontend server has to be completely stateless. It gets its data from the I/O servers and the
SQL database. Using this architecture with an appropriate number of frontend servers, you can handle
thousands of concurrent clients along with a high number of devices and tags.
Page 14
Ignition Server Sizing and Architecture Guide
The reason value changes are key, is due to the fact that we have to process the value change, for
alarms, the historian, and more. That processing requires memory and compute time. The more tags
we have changing per second, the more processing. An Ignition server at the high end can handle
approximately 50,000 value changes per second processing through the tag system, alarming, historian,
and clients. However, as mentioned above, some SQL databases have a limit of 10,000 value changes
per second on a dedicated instance. So, your job is to try to reduce the number of value changes per
second. Ignition can handle more devices, tags, and clients through optimization and reducing value
changes.
Let’s look at some different scenarios that help to understand what a server can handle. Each scenario
represents a number of tags that max out performance on a server.
As you can see, more tags can be handled by optimizing poll rates & deadbands. It is possible to have a
high number of device connections and tags through optimization.
Page 15
Ignition Server Sizing and Architecture Guide
Optimizations
You can really optimize your system by paying close attention to the number of value changes
happening every second. The more you tune the system, the more you can handle, and the better
performance you will get. Here are some things to consider:
Polling rates
Tag groups (or scan classes) dictate how often Ignition polls data from PLCs. Make sure you are using
proper polling rates. Not everything has to be at a 1 second rate. Some values can be polled slower than
others since they don’t change very often. Try to determine all of the possible polling rates you require.
For example, you might need a set of tags at a 1 second rate for alarming or history while the rest of the
tags can be polled at 5 second or minute intervals.
Deadbands
Deadbands log fewer data points, particularly when value changes are too small to be significant. They
are especially useful in a process that inspects with a high frequency, but is most interested in capturing
value changes exceeding a defined magnitude or percentage. Deadbands can be either absolute
or percentage-based. Absolute is based on an absolute change in the value whereas percentage
deadbands mean the value has to change by a particular percentage. There are also two deadband
modes: digital and analog. Digital deadband is stored when a new value is +/- the deadband value away
from the previously stored value. Analog mode’s values are evaluated with a modified ‘Sliding Window’
algorithm that tries to log the least amount of points necessary to draw the graph correctly.
There are deadbands on tags for both realtime and historical. Realtime deadbands means Ignition will
not process the new value at all unless it changes according to the configuration. Historical deadbands
apply after and dictate when a value will get logged to the historian. That allows one to see more
granular data on realtime screens but log fewer points.
Without proper deadbands, systems will log ‘noise’ on analog signals. It never makes sense to have
more sensitivity for logging than a sensor’s rated precision.
The better you tune your deadbands, the fewer value changes you will have in the system. You can
avoid fluttering on analog values and costly historian storage.
Page 16
Ignition Server Sizing and Architecture Guide
Driven tag groups are a great option for history where faster logging is conditionally required. Tag
groups do not set your historical logging rate, but influence the frequency at which Ignition will see the
data change.
Leased tag groups are a great option when you only want to poll tags when it is needed on a screen.
There are a lot of values in PLCs that aren’t used for history or alarming, only for viewing on a screen. We
don’t need to poll those values all of the time.
It is important to note that leased and driven tag groups have an impact when using Ignition’s
OPC-UA server and drivers as subscriptions change quite often. A change in subscription requires
Ignition’s device driver to reoptimize per device connection, which re-reads every tag configured on
that connection at the moment any leased or driven tag changes between the fast and slow rates.
Because of this, when using Ignition’s OPC-UA server and drivers with leased or driven tag groups it is
recommended to create two device connections to the PLC if allowed. One connection for the direct
tag groups and one connection for leased and driven tag groups. That way leased and driven tag group
subscription changes don’t have an effect on the direct tag groups and avoid costly re-optimizations and
stale overlays.
Event-Driven
It is extremely important to only execute logic on change, especially with expressions and SQL queries.
This will avoid additional computation when values haven’t changed. Ignition 8.0+ introduced new
execution modes on tags, of which “Event-Driven” is notable. Event-driven only fires the expression
or SQL query when a dependency changes (i.e., tag value event or alarm event) versus running at a
specific rate all the time. Imagine having an expression tag in a UDT that performs a switch statement on
an integer value to provide a human-readable state. The state doesn’t change very often. Let’s say you
have 2,000 UDT instances resulting in 2,000 expressions. Event-driven will only ever fire the expression
when the state changes, which is very infrequent. Alternatively, fixed rates could fire 2,000 expressions
every second, which could be a lot of unnecessary computations.
It is recommended to use event-driven on expressions, derived tags, and SQL query tags. It is also
recommended to set a tag’s history mode to “On Change” as well.
Scripts
You can write scripts in several places within Ignition. It is very important to understand where and
when those scripts are running. Avoid runScript expressions unless absolutely necessary. Avoid lots of
timer scripts on the Gateway or in the client. Avoid lots of tag change scripts. Ultimately, try to reduce
the number of scripts you have on both the server and clients. You can view Ignition’s Gateway status
page for more information on running scripts and execution engines. Expressions run much faster than
scripts, so use expressions instead of scripts wherever possible. Use scripting where it makes sense,
as scripting is very powerful and useful, but be mindful of the processing power the scripts you write
require.
Page 17
Ignition Server Sizing and Architecture Guide
Named queries can opt-in to caching the results on the Gateway. This means if another request to the
same Named Query comes in, the Gateway can return the cached result instead of having the database
executing the query again. This will use more memory on the Gateway (to maintain the results) but could
result in fewer queries running against the database. When polling is necessary or if you have a lot of
clients open, use named queries with caching to provide better performance.
Unless absolutely necessary, we recommend turning this feature off and simply letting the system track
values as they change. If there are clock drift or system issues, those should be dealt with as well, and
treated as separate issues to resolve. To turn off the feature, first, disable the stale data detection setting
for your history providers in the Ignition Gateway configuration page under Tags → History. Edit your
provider and under Advanced Settings disable “Enable Stale Data Detection”. Next, set the history mode
on all of your historical tags to “On Change”. Lastly, check your SQL database to see if you have a high
number of rows in the sqlth_sce table with the following query:
If you have hundreds of rows, or more, consider consolidating the rows into one row per scan class and
rate. You can use this query to find the ideal minimum number of rows:
SELECT scid, MIN(start_time) start_time, MAX(end_time) end_time, rate FROM sqlth_sce GROUP BY
scid, rate
Page 18
Ignition Server Sizing and Architecture Guide
Vision clients and the Ignition designer have to communicate to the Ignition Gateway in order to get tag
values. Of course, you only need to get the data you are interested in seeing on screen. In that case,
Vision clients and the designer create a subscription on the tags that they need. However, the Gateway
cannot notify the client/designer when a tag changes so the client/designer must poll the Gateway. The
Client poll rate (in milliseconds) is the rate at which a Vision client or Ignition designer polls the Gateway
for updates to its subscribed tags. By default, the setting is set to 250ms. That means every Vision
client and designer will poll the Gateway every 250ms to see if any of the tags they are subscribed to
has changed. If nothing has changed, we get an empty result. The rate is quite fast but typically not a
problem. However, if you have a high number of Vision clients it can cause additional load on the server.
You can easily reduce this load by changing the setting to 1 second. So, if you have 100 clients open, you
will get 400 requests per second for tag changes by default. If you change the setting to 1 second, you
will get only 100 per second. The setting for this is in the designer under Project → Properties on the
Project → General tab.
Page 19
Ignition Server Sizing and Architecture Guide
Summary
One of the main deployment environments today for Ignition is on Virtual Machines (VMs). A large
percentage of enterprise customers use Ignition on VMs rather than bare-metal physical servers.
Although VMs by design are slower than running on bare metal, as long as the correct VM configuration
is properly applied, Ignition should run well in these environments.
Software
Ignition will run on any hypervisor that properly emulates hardware and an Operating System. When
Ignition is running on a VM, it is most commonly used on VMWare, mainly because of VMWare’s ubiquity.
Inductive Automation does not recommend VMWare above other hypervisors, and as long as resource
allocation is appropriate, has not seen hypervisor-specific issues in any recent virtualization software
Resource Allocation
CPU and memory allocation should be determined by the engineers creating the Ignition projects. Small
systems may be 4 vCPUs with 8GB of RAM. Very large systems could be 32 vCPUs or more with 64+GB
RAM.
When Ignition is running small systems with only a handful of clients and tags, normal resource
allocation is often acceptable. When it is running critical applications or running any kind of significant
load, dedicated resources are required for the system to stay performant.
Dedicated Resources
When first specing an Ignition Gateway’s needs, always mention the need for dedicated vCPUs and
memory. If an Ignition Gateway starts small, it might not be initially needed, but as it grows dedicated
resources will be required to avoid issues. If dedicated resources aren’t initially configured, there may
later be significant pushback from IT departments who weren’t anticipating this need.
After configuring this, check to make sure the vCPU allocation is 100% dedicated to the Ignition VM. If it’s
not, it means the whole VM Host is over-provisioned, and this will need to be fixed.
Page 20
Ignition Server Sizing and Architecture Guide
Common Questions
If you’ve already started with shared resources, there is one main sign that dedicated resources are
becoming necessary.
Clock Drift. This is an Ignition metric on the status pages and is a measure of when the
Operating System runs a task that’s scheduled. Ignition schedules a task to run in 1s. Under
most circumstances, that task will run in 1000ms exactly. If it doesn’t, there is a problem with the
Operating System getting the CPU cycles it needs to run that task. It’s either a CPU allocation
problem, a very heavily loaded system, other software affecting the Operating System, or the
hypervisor not providing resources or enough resources quickly enough. Dedicated resources
almost always clear up Clock Drift. Note that having too few vCPUs allocated can also contribute
to Clock Drift.
Delays in common tasks, slow processing, historian issues if the database and devices aren’t
overloaded, and other sluggish behavior can all be signs that dedicated resources are needed as well.
Page 21
Ignition Server Sizing and Architecture Guide
Q: I already have dedicated resources, and I’ve allocated a large number of vCPUs, but
my Ignition system is still overloaded. What do I do?
A: At some point, a single Ignition server will reach its limit, regardless of CPU and memory allocations.
Inductive Automation’s scale-out architecture is the general recommendation for moving beyond the
limits of a single system.
References