6 FMX 100B
6 FMX 100B
286
UPS
Benefits
Front terminal design, easy access for faster installation and
maintainence 395
Optimal energy density, save floor space
110
54
No leakage and no acid smog spray during the operation
50˚C(-40˚F
Discharge: -40˚C ~ 50˚C (-40˚F ~ 122˚F)
122˚F)
Operating Temperature Range Charge: -20˚C ~ 45˚C(-4˚F
45˚C(-4˚F ~ 113˚F)
113˚F)
Storage:-20˚C ~ 40˚C(-4˚F
40˚C(-4˚F ~ 104˚F)
104˚F)
Recommended Operating Temperature 15˚C ~ 25˚C
25˚C (59˚F
(59˚F ~ 77˚F)
77˚F)
Recommended Charging Current 20 A
Float: 2.23 V/cell
Technical Features
Charging Voltage @25˚C(77˚F)
Equalize: 2.35 V/cell
Excellent capacity retention rate
Terminal M6
Long life float service design
Container Materials ABS/ABS V0 (Optional)
Excellent over discharge recovery
103% @ 40˚C(104˚F)
10) 85% @ 0˚C(32˚F) capability
60% @ -20˚C(-4˚F)
Design Life @25°C(77˚F) 12 years
6-FMX Series
Front Terminal Battery
6-FMX-100B
Performance Curve
Current Voltage Capacity
Discharge Performance at Different Discharge Rate ( I10A ) ( V/cell)
Constant Voltage Charge Characteristics@25˚C (%)
12.0
Voltage(V)
1.80 2.40
Charge voltage
12.5
1.50 2.30 100
Capacity
12.0
1.20 2.20 75
11.5
0.90 2.10 50
50% Discharge
11.0 100% Discharge
0.60 2.00 25
4HR 8HR 10HR
10.5 0.30 1.90 0
2HR
10.0 0 1.80
0.01 0.05 0.1 0.2 0.5 1 2 5 10 20 0 4 8 12 16 24 32 40 48
Discharge time (h) Charge time (h)
Capacity(%)
100
120 10°C
10HR
8HR 80
100 20°C
80 4HR
60
2HR 30°C
40°C
60
40
40
20
20
Code:3010400115/3010400116(V0)
0
-20 -10 0 10 20 30 40 50 0 3 6 9 12 15 18 21 24
Temperature(°C) Storage time (months)
*Declaration:
V3.0 20210118 EN
This information is generally descriptive only and is not intended to make or imply any representation,
guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications
are subject to modification without notice. Contact CHINASHOTO for the latest information. Welcome to Visit : www.chinashoto.com