Cavity Walls
Cavity Walls
A solid parapet wall should not be less than the thickness of the wall on
which it is carried and its height should not exceed four times its thickness.
Page7
Bye-law requirements
The building regulation requires that a building shall be so constructed that
the combined dead, imposed and wind loads are sustained and transmitted
to the ground safely and without causing any movement which will impair
the stability of any part of another building.
i. Bricks or blocks shall be of the required strength and properly bonded and
solidly put together with mortar.
ii. Cavities should not be less than 50mm nor more than 100mm in width at
any level.
iii. All cavity walls should have leaves at least 90mm thick.
iv. The leaves should be securely tied together with ties.
v. The leaves shall each be less than 100mmin thickness at any level.
vi. The combined thickness of the two leaves of a cavity wall plus 10mm
should not be less than the thickness required for a solid wall of the same
length and light.
vii. Mortar should be of the required strength .
A gauged mortar of 1:1:6 by volume is more suitable , the gauged mortar
should not be weaker than 1:2:9.
viii. Cavity walls of any length need to be provided with roof lateral support and
those over 3.000 in length will also require floor lateral support at every
floor forming a junction with the supported wall.
ii. Give good thermal insulation, keeping the building warm in winter and cool
in summer.
iii. No need for external rendering.
iv. Enables the use of cheaper and alternative materials for the inner
construction.
v. A nominal 225mm cavity wall has a higher sound insulation value than a
standard one brick thick wall.
Disadvantages of cavity wall construction
i. Requires a high standard of design and workmanship to produce a soundly
constructed wall, this will require good supervision during construction.
ii. Slightly dearer in cost than a standard one brick thick wall.
Prevention of damp in cavity wall
from rust.
Either copper or bonze or similar durable or non-corrodible metal ties are
selected for important buildings.
They must be so shaped that water from the outer leaf will not pass along
them to the inner leaf.
These ties are distributed at a maximum horizontal distance apart of
900mm and 450mm vertically, they are staggered.
At door and window jambs and at angles they should be placed at 300mm
vertical intervals to increase stability.
Page7