EN 50341-3-17e1 (Aspectos Normativospara Portugal - Linhas Aéreas de AT)
EN 50341-3-17e1 (Aspectos Normativospara Portugal - Linhas Aéreas de AT)
for
PORTUGAL
based on EN 50341-1:2001
EN 50341-3-17:2001 - 2/35 - Portugal
Contents
Foreword................................................................................................................................. 4
1 Scope ............................................................................................................................... 5
7 Supports ........................................................................................................................ 32
7.6 Concrete poles .......................................................................................................... 32
7.6.2 Basis of design .......................................................................................................... 32
7.6.2.3 Lateral reinforcement ................................................................................................. 33
7.6.3 Materials ................................................................................................................... 33
7.6.4 Serviceability limit states ............................................................................................ 33
7.6.5 Ultimate limit states.................................................................................................... 33
7.6.6 Design assisted by testing.......................................................................................... 33
7.10 Maintenance facilities ................................................................................................. 34
8 Foundations................................................................................................................... 34
8.5.2 Geotechnical design by calculation ............................................................................. 34
8.5.3 Geotechnical design by prescriptive measures ............................................................ 34
9 Conductors and overhead earthwires (ground wires) with or without telecommunication
circuits.................................................................................................................................. 34
9.2.2 Electrical requirements............................................................................................... 34
9.2.4 Mechanical requirements ........................................................................................... 34
10 Insulators.................................................................................................................... 35
10.7 Mechanical requirements ........................................................................................... 35
10.16 Selection, delivery and installation of insulators ........................................................... 35
11 Live equipments – overhead line fittings .................................................................... 35
11.2 Electrical requirements............................................................................................... 35
11.6 Mechanical requirements ........................................................................................... 35
12 Quality assurance, checks and taking ........................................................................ 35
EN 50341-3-17:2001 - 4/35 - Portugal
Foreword
2 The Portuguese NC has prepared this Part 3-17 of EN 50341, listing the portuguese
national normative aspects, under its sole responsibility, and duly passed it through the
CENELEC and CLC/TC 11 procedures.
NOTE The Portuguese NC also takes sole responsibility for the technically correct coordination of
this EN 50341-3-17 with EN 50341-1. It has performed the necessary checks in the frame of quality
assurance/control.
It is noted however that this quality assurance/control has been made in the framework of the
general responsibility of a standards committee under the national laws/regulations.
When no reference is made in Part 3-17 to a specific subclause, then Part 1 applies.
5 In the case of “boxed values” defined in Part 1, amended values (if any) which are defined
in Part 3-17 shall be taken into account in Portugal.
However any boxed value, wether in Part 1 or Part 3-17, shall not be amended in the
direction of greater risk in a Project Specification.
6 The Portuguese NC declares in accordance with subclause 3.1 of Part 1 that this Part 3-
17 follows the “General Approach” (clause 4.2), and that consequently subclause 4.3
“Empirical Approach” is not applicable for Portugal.
NOTE All national standards referred to in this Part 3-17 will be replaced by relevant European
Standards as soon as they become available and are declared by the Portuguese NC to be
applicable and thus reported to the secretary of CLC/TC 11.
Portugal - 5/35 - EN 50341-3-17:2001
1 Scope
NOTE When globally upgrading a line, the option of making the upgrading compatible with this Part 3-17 shall be
approved by the Portuguese Authorities responsible for the approval of the project in a case by case basis.
NOTE 1 The above code has specifications for both under and above 45 kV overhead lines as well as for
underground lines.
Decretos-Lei nºs: 182/95, 184/95 e 185/95, modificados pelos Decretos-Lei nºs: 56/97 e
198/2000:
Legislação do Sector Eléctrico, Transporte e Distribuição de Energia Elétrica
Legislation of the Electrical Sector, Transmission and Distribution of Electrical Energy
Decreto-Lei nº 251/87:
REGULAMENTO GERAL SOBRE O RUIDO
General Regulation on Acoustic Noise.
Decreto-Lei nº 69/2000:
REGIME DE AVALIAÇÃO DE IMPACTE AMBIENTAL
Environmental Impact Assessment
NOTE 2 This law states which overhead lines shall be subjected to a formal Environmental Impact Assessment
Process, and be subject to the approval of the Environment Ministry.
EUROPEAN COMISSION
Dirtectorate-General V – Employment, Industrial Relations and Social Affairs
“Public health and safety at work
Non-ionizing radiation
Sources, exposure and health effects” (1996).
IRPA/INIRC, 1990
Interim guidelines on limits of exposure to 50/60 Hz electric and magnetic fields. Health
Physics,58.
AfK RECOMMENDATION N. 3
“Measures for the installation and operation of pipelines in the vicinity of three-phase high
voltage systems and single-line traction systems”.
“Mutual design considerations for overhead AC transmission lines and gas transmission
pipelines – Vol 2 : Prediction and mitigation procedures”, September 1978.
NOTE 3 The above directive specifies for overhead lines of 220 kV and above, whose length is above 15 km;
however, it can be regulated in the near future within Portugal otherwise (for instance, demanding environmental
evaluation for all lines above 100 kV).
3 Basis of design
3.1 General
(ncpt) PT.1
The design of the Portuguese overhead lines shall be based on 4.2 Actions, General
Approach. Some of the design parameters hereby indicated are based on statistical records
(i.e. wind loads) and some have been calibrated from empirical values (i.e. ice loads).
Subclause 4.3 Actions, Empirical Approach and parts related to it are not applicable.
Portugal - 7/35 - EN 50341-3-17:2001
NOTE 1 In the case of temporary lines Portuguese Authorities may allow a reliability level lower than 3.
NOTE 2 A temporary line shall not have a life span greater than 3 years. The duration of a temporary line shall be
restricted to the absolute necessary. Portuguese Authorities may enforce the dismounting, removal or substitution of
a temporary line.
NOTE 3 The reliability level of temporary lines may be specified in Project Specifications.
4 Actions on lines
4.2 Actions, General Approach
(ncpt) PT.1 Forces from conductors
Conductor forces are calculated without any partial factors. When designing supports the
conductor forces are assumed as a variable action.
For overhead line elements extending higher than 20 m above the ground the following
exponential law may be used for all terrain types
Vh = VR . (h/10)0,2
up to heights, h, of 100 m above the ground. For heights exceeding 100 m, or in special
cases in mountainous terrain where the wind shall be locally strengthened or weakened, a
separate evaluation is required.
2 0,4 2
Zone B : qh = 0,5 . ρ . 33 . (h/10) N/m
3
where ρ is the air density, equal to 1,225 kg/m at 15ºC and atmospheric pressure of
2
1013 hPa (qh = 0,613 Vh )
Table 4.2.2.2 / PT.1 - Basic dynamic wind pressure as function of the height h
and the wind zone
h [m] qh [Pa]
Zone A Zone B
0 727 880
10 727 880
20 727 880
30 855 1035
40 960 1161
50 1049 1270
60 1129 1366
70 1201 1453
80 1266 1532
90 1328 1606
(ncpt) PT.2
For conductors and earthwires the height to be considered in calculations is the height of
their attachment points above the ground level.
The drag factor CC for ordinary stranded conductors shall be according to its diameter, as
indicated in table 4.2.2.2.4.1/PT.3.
d [mm] CC
d ≤ 12,5 1,2
At angle supports the wind direction shall be along the bisector of the line deviation, unless
otherwise specified in Project Specifications. The horizontal transverse component of the
conductor tension shall be added to the resulting wind force.
For the purpose of calculating the horizontal components of the conductor tension the wind
direction may be taken as acting perpendicular to the conductors.
NOTE In this last case, in any one span L, the wind force will be simply given by:
Qwc = qh . Gc . Cc . d . L
When calculating wind loads in ice zones (see 4.2.3/PT.1 and PT.2) the load shall be calculated taking d as the
equivalent diameter D defined under subclause 4.2.4.4 of Part 1.
Qwt = qh . At . Ct
qh is the dynamic pressure (see 4.2.2.2/PT.1) at the height of the panel gravity center to the
ground.
• Towers with rectangular cross section with identical opposite faces made of flat sided
members
Ct = 3,2 - 2,8 . χ
EN 50341-3-17:2001 - 10/35 - Portugal
• Towers with rectangular cross section with identical opposite faces made of circular
section members (steel tubes instead of steel shaped profiles)
Ct = 2,24 - 1,96 . χ
χ = 2 . At / (h . (b1 + b2))
as indicated on fig. 4.2.2 of Part 1; these expressions for Ct are valid for values of χ in
the interval [0,1 - 0,6]. Furthermore they take into consideration the action of the wind
over all the faces of the tower.
(ncpt) PT.2
When considering wind forces over crossarms made of single metallic profiles the following
drag factors shall be used
U-shaped profiles
Ct = 0,60
Ice loads should be considered in zones located at altitudes above 600 m at the following
Portuguese Districts:
• Viana do Castelo
• Braga
• Vila Real
• Bragança
• Porto
• Viseu
• Guarda
• Castelo Branco
• Coimbra
• Portalegre
These zones where defined after taking in consideration that the ice formations over
conductors are related not only with minimum temperatures and high humidity of the air
verified in each zone, but also with the altitude. Experience has shown that for altitudes
under 600 m ice formation is not likely to occur.
lk = 11 . (10+d)/40 [N/m]
NOTE 1 A minimum ice load may also be modelled as an uniform ice sleeve with a thickness of 10 mm and
density of 900 kg/m 3 .
NOTE 2 When data is available, greater ice loads may be considered not as a general designing criteria but as
special cases confined to the line section at the geographic location where data was gathered. Project
Specifications shall define the reference ice load to be taken into consideration.
(snc) PT.2
In Portugal only the combination of extreme ice load with a moderate wind load is
mandatory (see subclause 4.2.11 and 4.2.11/PT.1 for partial factors). Project Specifications
may call for the combination of high wind with moderate ice as well.
EN 50341-3-17:2001 - 12/35 - Portugal
- Conductors : 75 ºC
- Earthwires : 50 °C
(ncpt) PT.5 Temperature to be used for the combination of wind and ice
The temperature to be assumed when combining wind and ice shall be -10 ºC. In the
combination, the reduced values for wind load condition (ψI .QI ) shall be taken.
The maximum horizontal tension of a conductor or earthwire will be calculated in the most
unfavourable of the following assumptions:
The torsional loads may be reduced at supports with suspension strings to take into account
the relaxation of the load resulting from any swing of the string and elastic deflection or
rotation of the support. The characteristic residual tension will be given by
Pk = β * T0
where
Values given for β are default values. Project Specifications may allow for other reduction
factors based on accurate computer simulation or experimental values.
(ncpt) PT.2
The longitudinal loading (see 4.2.7 b)) is a static longitudinal one-sided load. Values and
combinations are defined under 4.2.10.2/PT.1 through PT.8 related to each type (intended
purpose) of support.
The intended purpose of one support does not prevent from using it in another way provided
its mechanical sufficiency is proven in acceptable economic conditions. In some cases this
may require an adaptation or small changes in its characteristics. The recommendation is,
however, that each support type shall be used according with its intended purpose.
Ice loads usually mean heavier and costly supports. As ice loads are in Portugal more the
exception than the rule, supports for ice zones will be specially designed for that purpose
and ice loads are not a general requirement. Project Specifications shall define for any
particular line which and where ice loads are to be considered, if any.
Lines using basic supports (T, A, B, DE) designed under 4.2.10.2/PT.2 through PT.5 assure
adequate strength to contain failure (cascading prevention). However, it is allowed the use of
basic type supports without this strength provided reinforcement supports of any basic type
as described under 4.2.10.2/PT.6 through PT.8 (RT, RA, RB) are used at least every ten
spans.
EN 50341-3-17:2001 - 14/35 - Portugal
Assumption 1
(load cases 1a and 1b, table 4.2.7)
( 1)
Wind acting perpendicular to the line on support, crossarms , insulators, conductors and
earthwires.
(2)
The horizontal components of conductors and earthwires tensions , at their attachment
points.
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 2
(Security loads - longitudinal load - load case 5b, table 4.2.7)
30% of the horizontal forces resulting from wind acting perpendicular to the line over
conductors and earthwires acting through the support axis, in the line direction, at the height
of the resulting force.
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 3
(Security loads - torsional load - load case 5a, table 4.2.7)
Static horizontal force equal to the release of tension of any one sub-conductor or earthwire,
all other conductors, sub-conductors and earthwires keeping a tension equal to the
( 3)
maximum residual horizontal conductor tension , without any wind or ice load on the
supports, in the direction parallel to the longitudinal axis of the support.
Selfweight of support, crossarms, insulators, conductors and earthwires.
NOTE Security Loads for tangent supports under Assumption 3 are dispensed for type Tangent Supports (T) if the
line design makes use of reinforcement tangent supports (RT) specified under 4.2.10.1/PT.1.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.2.7 apply in addition to
assumptions 1, 2 and 3.
Unbalance coefficients α, α1, α2, α3 and α4 shall be taken as
α = 0,5; α1 = 0,3; α2 = 0,7; α3 = 0,3; α4 = 0,7.
NOTE Load cases 2c and 2d given in table 4.2.7 are dispensed for type Tangent Supports (T) if the line design
makes use of reinforcement supports specified under 4.2.10.1/PT.1.
1)
Separate reference to crossarms is intended to embrace those cases where crossarms are not an integral part of the support.
2)
As the result of the topographic conditions of the line, the support is expected to sustain unbalanced longitudinal forces
(inclined strings with temperature change).
3)
See definition under clause 4.2.7/PT.1
Portugal - 15/35 - EN 50341-3-17:2001
Assumption 1
(load case 1a, table 4.2.7)
Wind acting in the direction of the bisector of the line angle over support, crossarms,
insulators, conductors and earthwires.
The horizontal components of the conductors and earthwires tension, at their attachment
points, shall be taken for the wind load at reference temperature (wind always acting along
the bisector of the angle).
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 2
(Security loads - longitudinal load - load case 5b, table 4.2.7)
30% of the horizontal tension resulting from wind acting along the bisector of the angle on
conductors and earthwires, acting through the support axis, in the direction perpendicular to
the angle bisector, at the height of the resulting force.
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 3
(Security loads - torsional load - load case 5a, table 4.2.7)
Static horizontal force equal to the release of tension of any one sub-conductor or earthwire,
all other conductors, sub-conductors and earthwires keeping a tension equal to the
maximum residual horizontal conductor tension, without any wind or ice load on the
supports, in the direction parallel to the longitudinal axis of the support.
Selfweight of support, crossarms, insulators, conductors and earthwires.
NOTE 1 When calculating the horizontal tension of conductors and earthwires for assumptions 2 and 3 above, it is
acceptable to consider the wind acting perpendicular to the conductors and earthwires.
NOTE 2 Security Loads for angle supports under Assumption 3 are dispensed for type Angle Supports (A) if the
line design makes use of reinforcement angle supports (RA) as specified under 4.2.10.1/PT.1.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.2.7 apply in addition to
assumptions 1, 2 and 3.
Unbalance coefficients α, α1, α2, α3 and α4 shall be taken as
α = 0,5; α1 = 0,3; α2 = 0,7; α3 = 0,3; α4 = 0,7.
NOTE Load cases 2c and 2d given in table 4.2.7 are dispensed for type Angle Supports (A) if the line design
makes use of reinforcement supports specified under 4.2.10.1/PT.1.
Assumption 1
(load case 1a, table 4.2.7)
Wind acting perpendicular to the main line, if the support is a tangent one, or along the
bisector of the angle of the main line if the support is an angle support, over support,
crossarms, insulators, conductors and earthwires of the main line.
Wind acting along the same direction as considered above on conductors and earthwires of
the contiguous half-span of the branched line.
The horizontal components of the main line and branched line conductors and earthwires
tensions, at their attachment points, shall be taken for the wind load at reference
temperature (wind acting in the same direction as considered above).
Selfweight of support, crossarms, insulators, conductors and earthwires.
The same as assumption 1 except for the wind direction which should be along the main line
in the case of a tangent support or perpendicular to the bisector of the angle of the main line
in the case of an angle support.
Security loads
Torsional and longitudinal loads as stated for T or A supports must be considered. The most
unfavourable unbalanced combination must be sought considering also the branched line.
NOTE Torsional loads for branch supports are dispensed for type Branch Supports (B) if the line design makes
use of reinforcement branch supports (RB) as specified under 4.2.10.1/PT.1.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.1.10.1 apply with unbalanced
coefficients as given in the main text. The most unfavourable unbalanced combination must
be sought considering also the branched line.
NOTE 1 For lines outside ice zones, assumption 2 may be dispensed if for the branched line the support next to
branched support is a dead-end support and the mechanical tension of conductors and earthwires on the span in
between is neglectable.
NOTE 2 Load cases 2c and 2d given in table 4.2.7 are dispensed for type Branch Supports (B) if the line design
makes use of reinforcement supports specified under 4.2.10.1/PT.1.
Assumption 1
(load case 1a, table 4.2.7)
Assumption 2
(Security loads - torsional load – load case 5a, table 4.2.7)
Static horizontal force equal to the release of tension of any one sub-conductor or earthwire,
all other conductors, sub-conductors and earthwires keeping a tension equal to the
maximum residual horizontal conductor tension, without any wind or ice load on the
supports, in the direction parallel to the longitudinal axis of the support.
Selfweight of support, crossarms, insulators, conductors and earthwires.
Ice Zones
At ice zones, load cases 2a, 2b and 3 given in table 4.2.7 apply in addition to assumptions 1
and 2.
Unbalance coefficients α, α1, α2, α3 and α4 shall be taken as
α = 0,5; α1 = 0,3; α2 = 0,7; α3 = 0,3; α4 = 0,7.
Assumption 1
(load case 1a and 1b, table 4.2.7)
Wind acting perpendicular to the line on support, crossarms, insulators, conductors and
earthwires.
The horizontal components of conductors and earthwires tension, at their attachment points.
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 2
(Security loads - longitudinal load - load case 5b, table 4.2.7)
Assumption 3
(Security loads - torsional load - load case 5a, table 4.2.7)
Static horizontal force equal to the release of tension of any one sub-conductor or earthwire,
all other conductors, sub-conductors and earthwires keeping a tension equal to the
maximum residual horizontal conductor tension, without any wind or ice load on the
supports, in the direction parallel to the longitudinal axis of the support.
Selfweight of support, crossarms, insulators, conductors and earthwires.
NOTE Assumption 3 is dispensed in the case of supports having articulated cros sarms, given sufficient proof that
the support is not subjected to torsional loads.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.2.7 apply in addition to
assumptions 1, 2 and 3.
Unbalance coefficients α, α1, α2, α3 and α4 shall be taken as
α = 0,5; α1 = 0,3; α2 = 0,7; α3 = 0,3; α4 = 0,7.
EN 50341-3-17:2001 - 18/35 - Portugal
(ncpt) PT.7 Reinforcement Angle Supports (RA) (also tension or strain supports)
The support is nominally supposed to have its transverse axis along the bisector of the line
angle. Reinforcement angle supports shall be designed for the following assumptions:
Assumption 1
(load case 1a, table 4.2.7)
Wind acting in the direction of the bisector of the line angle over support, crossarms,
insulators, conductors and earthwires.
The horizontal components of the conductors and earthwires tension, at their attachment
points, shall be taken for the wind load at reference temperature (wind always acting along
the bisector of the angle).
Selfweight of support, crossarms, insulators, conductors and earthwires.
Assumption 2
(Security loads - longitudinal load - load case 5b, table 4.2.7)
Assumption 3
(Security loads - torsional load - load case 5a, table 4.2.7)
Static horizontal force equal to the release of tension of any one sub-conductor or earthwire,
all other conductors, sub-conductors and earthwires keeping a tension equal to the
maximum residual horizontal conductor tension, without any wind or ice load on the
supports, in the direction parallel to the longitudinal axis of the support.
Selfweight of support, crossarms, insulators, conductors and earthwires.
NOTE 1 When calculating the horizontal tension of conductors and earthwires for assumptions 2 and 3 above, it is
acceptable to consider the wind acting perpendicular to the conductors and earthwires.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.2.7 apply in addition to
assumptions 1, 2 and 3.
Unbalance coefficients α, α1, α2, α3 and α4 shall be taken as
α = 0,5; α1 = 0,3; α2 = 0,7; α3 = 0,3; α4 = 0,7.
Assumption 1
(load case 1a, table 4.2.7)
Wind acting perpendicular to the main line, if the support is a tangent one, or along the
bisector of the angle of the main line if the support is an angle support, over support,
crossarms, insulators, conductors and earthwires of the main line.
Wind acting along the same direction as considered above on conductors and earthwires of
the contiguous half-span of the branched line.
The horizontal components of the main line and branched line conductors and earthwires
tensions, at their attachment points, shall be taken for the wind load at reference
temperature (wind acting in the same direction as considered above).
Selfweight of support, crossarms, insulators, conductors and earthwires.
Security loads
Torsional and longitudinal loads as stated for RT or RA supports must be considered. The
most unfavourable unbalanced combination must be sought considering also the branched
line.
Ice Zones
At ice zones, load cases 2a, 2b, 2c, 2d and 3 given in table 4.1.10.1 apply with unbalanced
coefficients as given in the main text. The most unfavourable unbalanced combination must
be sought considering also the branched line.
5 Electrical requirements
5.2.1 Normal current
(ncpt) PT.1 Design maximum temperatures for normal current
Unless otherwise specified in Project Specifications, the design temperature to be used in
maximum sag calculations or line templating shall be not lower than:
- Conductors : 75 ºC
- Earthwires : 50 °C
EN 50341-3-17:2001 - 20/35 - Portugal
NOTE 1 In order to not introduce limitations on the use of low sag or extremely low sag cables, the maximum
temperature will be used for all steel, aluminium, aluminium steel reinforced, aluminium alloy, aluminium alloy steel
reinforced and alumoweld cables. The arising of new materials which can economically work at higher temperatures
will be subject to special considerations, always assuring that clearances stated under clause 5 are met.
NOTE 2 Even when the expected maximum operating temperature ( temperature corresponding to the steady
state) is lower than the specified maximum temperature, the specified design maximum temperature shall be used
in sag calculations and tower spotting when verifying clearances and safety distances.
NOTE 3 Usually it is not economical to have cables working at temperatures of 75 °C or above at steady state
regimes. Therefore the conductor is usually chosen to fit to an expected load flow in steady state to temperatures
around 60 °C. However, temporary steady state overloads must be allowed and verified as not leading to a final
temperature above 75 °C.
dT
C ⋅ St ⋅ = I 2 ⋅ RT + α ⋅ R ⋅ d − 8 .55 ⋅ ( T − T A ) ⋅ ( v ⋅ d ) 0.448 − E ⋅ σ ⋅ π ⋅ d ⋅ (T 4 − T A4 )
dt
where
α Absorptivity coefficient
RT Electrical resistance at temperature T of conductors
R Solar radiation
v Wind speed
E Effective emissivity of the conductor
σ Stefan-Boltzmann constant
60 kV : 25,0 kA
150 kV : 31,5 kA
220 kV : 31,5 kA
400 kV : 40,0 kA
NOTE Irrespective of shielding considerations (subclause 5.3.3.5), some of the above currents invariably require
two earthwires (groundwires), most particulary if one of them is an OPGW. Project Specifications shall specify in this
respect.
Portugal - 21/35 - EN 50341-3-17:2001
NOTE It is recommended that the maximum temperature of ACSR or AAAC conductors shall not be greater than
125 ºC. Besides thermal fatigue one of the reasons is that above 125 ºC sag calculations lead to significant errors
due to fact that compression forces arise on aluminium wires in ACSR conductors. When considering the maximum
conductor temperature it shall be taken into consideration the drop point of the grease.
70 / t [A/mm2]
(ncpt) PT.6
Values indicated under 5.2.2/PT.1 through PT.5 are reference values and provide a safe
margin to account for growth. Project Specifications may indicate different values, higher or
lower.
NOTE Geometry of the shield wire(s) shall be such to assure that a flashover due to a direct lightning stroke into
the phase conductors is reduced to one per 100 km line per year. Considering stroke peak currents at around 40-
50 kA (mountainous regions) leads to the approximate conclusion that the external protection angle shall not be
greater than about 20º for lines up to 150 kV and 30º for lines up to 400 kV.
For different values of U90%_ff_is from the indicated due calculations shall be made using
formulae given under Annex E of Part 1.
Portugal - 23/35 - EN 50341-3-17:2001
NOTE The range of switching overvoltages shall take into account the following reference factors for phase-earth
switching overvoltage function of the highest system voltage:
(ncpt) PT.5
For each highest system voltage the greater values from tables 5.3.5/PT.3-1 through PT.3-3
and 5.3.5/PT.4 shall be taken into account.
- Conductors : 75 ºC
- Earthwires : 50 °C
Table 5.4.3/PT.2
Type of conductors k
ACSR, AACSR, steel, copper, bronze 0,6
AAC, AAAC 0,7
f = sag in meters of the conductor at maximum design temperature (+75 ºC) and no wind.
SL = length in meters of the swinging section of the insulator string, in a direction
perpendicular to the line
Outside ice zones, clearance between conductors may be reduced to (2/3).D provided the
horizontal distance between the vertical planes passing through the points of attachment is
in excess of (2/3).D.
NOTE When earthwire sag is smaller than phase conductor sag, clearance between them may be reduced at the
vicinity of the support, provided that the clearance at midspan between them at the minimum sag temperature is not
smaller than D given under 5.4.3/PT.2; minimum sag is conventionally taken as the sag at –5ºC/no wind outside ice
zones and –10ºC/no wind at ice zones.
5.4.4 Clearances to ground in areas remote from buildings, roads, railways and
navigable waterways
(ncpt) PT.1 Table 5.4.4 - Clearances to trees
Clearance to trees shall be 2 m + Del , but greater than 2,5 m.
A protection strip is defined centered along the line axis which is 25 m wide for lines of
voltage up to 100 kV and 45 m wide for lines of voltage above 100 kV. Within this strip, taken
into account all environmental aspects as well, trees may be taken down or lopped in order
to assure at all times the minimum clearance given above. This includes also trees which by
falling do not maintain a minimum clearance to conductors under maximum sag conditions
(75 ºC, no wind) of 1,5 m.
NOTE 1 Exceptionally, trees outside the protection strip may be taken down or lopped, those which by its size
and/or particular conditions of instability may pose an unacceptable risk to the line, namely by not maintaining a
minimum clearance of 1,5 m if they fall.
NOTE 2 The above specified does not apply to species protected under Portuguese law, which in general can not
be taken down and have strict lopping limitations.
EN 50341-3-17:2001 - 26/35 - Portugal
NOTE 3 It is strongly recommended that whenever possible the lopping of fruit trees and of slow growth species
shall be avoided or at least limited to the strictly necessary.
NOTE 4 Under Portuguese law owners may plant trees or other cultures within the protection strip, provided it does
not pose any violation of the clearance conditions stated above.
NOTE It is recommended to reduce to the possible minimum the establishment of overhead lines within villages or
above buildings in general which are not part of electrical installations.
Portuguese Authorities may exceptionally consider a line over a school building, if it is not
feasible or economically advisable to change the line corridor. Special environmental and
security measures shall in that case be considered and approved by the Portuguese
Authorities regarding electrical, mechanical and aesthetic aspects.
Portugal - 27/35 - EN 50341-3-17:2001
(ncpt) PT.4 Table 5.4.5.2 - Antenna, street lamps, flag poles, advertising signs and
similar structures
Formulas given apply, but clearance shall always be in excess of 3 m.
(ncpt) PT.5 Table 5.4.5.2 - Line in the vicinity of buildings where explosives are
manufactured or stored
In the vicinity of buildings where explosive substances are manufactured or stored, the
establishment of overhead lines is not allowed at horizontal clearances inferior to 190 m for
lines up to 100 kV and 210 m for lines above 100 kV.
For railways, tramways, etc., which have an overhead electrical traction system distance
given to electrical components shall be 2 m + Del, with a minimum of 3 m. Whenever this
distance is not known the minimum clearance to top of rail shall be:
NOTE A road zone is the ground occupied by the road itself and the surrounding acquired land, and other
installations as toll facilities and or parking facilities. When there are bridges these also included. Exceptionally the
road authority may allow a s upport at a smaller distance, defining any special conditions necessary.
NOTE A railway zone is the ground occupied by the railway itself and the surrounding ground to a distance not
smaller than 1,5 m from the outside of the rail to each side of the railway.
(ncpt) PT.4 Table 5.4.5.3.2 - Clearances to line near roads, railways and navigable
waterways
Clearance to loading gauge or the components of an electric traction system wire installation
of a railway or trolley bus line for maximum sag load case shall be 2 m + Del ; clearance to
outer edge of a carriageway (incl. Hard shoulder) of a motorway, highway, country road or of
a waterway shall be 2 m + Del .
EN 50341-3-17:2001 - 28/35 - Portugal
Portuguese Authorities may exceptionally consider a line over a sports area, if it is not
feasible or economically advisable to change the line corridor. Special environmental and
security measures shall in that case be considered and approved by the Portuguese
Authorities regarding electrical, mechanical and aesthetic aspects.
In the vicinity of housing buildings the difference between the “Equivalent Sound Level”
originated from the line (corrected from the acoustic noise originated from any other
surrounding industrial equipments) and the level of ambient noise, exceeded during 95 % of
a reference period of time of 24 hours, shall be less or equal to 10 dB (A) (Portuguese
General Regulation on Acoustic Noise, see subclause 2.3).
Portugal - 29/35 - EN 50341-3-17:2001
NOTE Limits above are also endorsed and recommended within the European Union (see subclause 2.3). The
basic criterion is to limit current densities induced in the head and trunk by continuous exposure to electric and
magnetic fields to an absolute limit of 10 mA.m-2. However, the recommendation of the Council of the European
Union to a basic limit of exposure compatible with a maximum current density in the body of 2 mA.m-2 for the
general public shall be met by the design of 50 Hz systems.
•AfK RECOMMENDATION N. 3
“Measures for the installation and operation of pipelines in the vicinity of three-phase high voltage systems and
single-line traction systems”
“Mutual design considerations for overhead AC transmission lines and gas transmission pipelines – Vol 2 :
Prediction and mitigation procedures”, September 1978
6 Earthing systems
6.2.2.2 Earthing and bonding conductors
2
The minimum cross-section for earthing and bonding copper conductors shall be 16 mm
2
above the soil or 35 mm underground. For earthing and bonding conductors of other
materials an electrically equivalent cross-section must be assured. In the case of reinforced
concrete poles the lengthwise reinforcement may, bearing in mind the necessary cross-
section, be used as part of the earth electrode.
• For category 3 fault elimination must be assured to be always less than 0,5 s; otherwise,
category 3 shall be dealt with in the same way as category 2.
• For category 4 fault elimination must be assured to be always less than 3 s; otherwise,
category 4 shall be dealt with in the same way as category 3.
NOTE 2 Category 1 locations (public zones) shall be dealt with in a case by case basis always performing
measurements in situ to assist or confirm calculation models.
NOTE 3 Measures to reduce the touch voltage through equalizing the potential rise are allowed; alternatively, the
use of an insulating top level of soil like gravel or asphalt is also allowed; when performing calculations or field
measurements the subject of a touch voltage shall be assumed at 1 m away from the tower or pole, in any direction,
whichever is the most unfavourable, either by the geometric characteristics of the earthing configuration or the soil
characteristics.
Portugal - 31/35 - EN 50341-3-17:2001
Basic Design
(1) Support of NO
insulating
material
NO
YES
(3) Immediate (6) Determination of touch
automatic UT
disconnection
YES NO
(8) Measures
(7) UT < UTP required
Correct design
Figure 6.2.4.2/PT.1
(6) When performing calculations or field measurements the subject of a touch voltage shall
be assumed at 1 m away from the tower or pole, in any direction, whichever is the most
unfavourable, either by the geometric characteristics of the earthing configuration or the
soil characteristics; modelling of the earthing configuration resistance and potential
evolution along the soil shall be based as accurately as possible in the local soil
characteristics, specially in category 1 sites (public zones).
(7) For U TP see 6.2.4.1/PT.1; permissible touch voltages are defined for 4 different
categories.
(8) Measures to reduce the touch voltage through equalizing the potential rise, like for
instance the use of conductive ring(s) around the pole or tower are allowed;
alternatively, the use of an insulating top level of soil like gravel or asphalt is also
allowed. Project Specifications shall specify adequate measures for the basic design
which, however, may have modifications if so fi eld conditions do allow.
1. Public zones. Places of high population density even if only in special occasions like
supermarkets, fairs and open space markets, playgrounds, areas where people
gather, recreation or sports areas, swimming pools, camping areas and similar
locations where people may walk barefoot. In calculations body impedance shall be
considered 1000 Ω, and no additional resistance.
2. Frequented zones. Places where people may walk frequently and it can be
reasonably assumed that they are using shoes such as pavements of public roads,
parking places and locations within urban areas; also agricultural zones in countryside
where the work is done mainly by man (as opposed to mainly by machines); also
meant are objects like fences and other conductive structures. In calculations body
impedance shall be considered 1000 Ω, and additional resistance not greater than
1000 Ω.
3. Seldom frequented zones. Zones not included in the previous categories and where
the human presence is rare like agricultural zones in countryside where the work is
done mainly by machines, cattle ranches, etc.
4. Non frequented zones. Zones where the human presence is most rare, like zones
with no agricultural aptitude, steep slopes, rockfaces, etc.
7 Supports
7.6 Concrete poles
(ncpt) PT.1
Reinforced concrete poles and their crossarms shall be designed on the basis of the load
assumptions as given in 4.2.10.1/PT.1.
7.6.3 Materials
(ncpt) PT.1
The concrete strength shall be at least of class C30/37 for reinforced poles and C35/45 for
prestressed poles.
(ncpt) PT.2
For reinforced concrete poles with I-profiled cross-section, the design values for maximum
width of cracks are:
(ncpt) PT.2
The alternative method of subclause 7.6.6, Part 1, shall be used in the case b) of 7.6.5/PT.1.
(ncpt) PT.3
For concrete poles with I-profiled cross-section the maximum deflection after permanent
loading for 15 min at serviceability limit state (where H is the total pole length) shall be:
For concrete poles with I-profiled cross-section the maximum residual deflection (where H is
the total pole length) shall be:
NOTE 2 Warning and safety signs shall comply with Portuguese standards NP 522, NP 608 and NP 609 in what
regards colors and symbols..
8 Foundations
8.5.2 Geotechnical design by calculation
(ncpt) PT.1
The method to be used to determine the foundation design resistance Rd shall be given in
Project Specifications.
NOTE 1 Single footing foundations where the predominant load is the overturning moment shall be designed in
such a way that the overall tilt is not greater than 1%.
NOTE 2 Until there is enough experience of practical application of ENV 1997-1-1 (Eurocode 7) separate footings
foundations where the predominant loadings are vertical downward and uplift forces shall be designed to withstand
at least 1,5 times the design non-accidental loads resulting from the supports, exclusive of any partial factors, and
1,25 times the design accidental loads resulting from the supports (deterministic approach).
NOTE 3 Project Specifications (for line design, not for support design) shall indicate if soil characteristics are to be
determined by inspection and/or testing of soil characteristics or by defining/confirming geotechnical characteristics
of “standard” soils given in Annex M.
H [m] he [m]
H ≤ 15 0,1 . H + 0,5
15 < H ≤ 20 2,0
20 < H ≤ 27 2,5
27 < H ≤ 34 2,8
34 < H case by case
where H, is the total pole length. These values are not valid in rocky soils.
10 Insulators
10.7 Mechanical requirements
(ncpt) PT.1
Insulator strings shall have a mechanical or electromechanical specified minimum failing
load of at least RTS (rated tensile strength) of the conductors.
NOTE Project Specifications may specify additional requirements, namely regarding strength coordination.
The insulator shall also have a serial number which allow to identify the date of assembling
and the origin of the materials.
Palleting. Each pallet shall have a label with the indication of: