0% found this document useful (0 votes)
77 views56 pages

BA142FEN

This document provides operating instructions for the Prolevel FMC 661 level measurement transmitter. It can be used with various capacitance probes and hydrostatic sensors. The document covers safety notes, an introduction to the transmitter's application and measuring principles, installation instructions, operating instructions including calibration, and troubleshooting information. Certificates are listed that approve its use in hazardous areas when used with certain probes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views56 pages

BA142FEN

This document provides operating instructions for the Prolevel FMC 661 level measurement transmitter. It can be used with various capacitance probes and hydrostatic sensors. The document covers safety notes, an introduction to the transmitter's application and measuring principles, installation instructions, operating instructions including calibration, and troubleshooting information. Certificates are listed that approve its use in hazardous areas when used with certain probes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

BA 142F/00/en/07.

98a
016562-1000
valid for Software 1.x
prolevel
FMC 661
Level Measurement
Operating Instructions

Endress + Hauser
Nothing beats know-how
Short Instructions Prolevel FMC 661

Short Instructions

Operation
Selects vertical matrix position
4 yellow relay LEDs,
1 red alarm LED,
1 green operation LED LC display Selects horizontal matrix position

+ Select position V0H0

Selects next digit

+ Move decimal point

Increases value of digit

Decreases value of digit

Registers entry

..Quick configuration for level measurement


Function Matrix Action
1 Reset transmitter V9H5 ● Enter 671
Press »E« to register entry
- Omit if commissioned as in Section 4.1
2 »Empty« calibration* V0H1 ● Fill vessel 0…40% full (probe covered)
Enter level in %, m, ft, etc.
Press »E« to register entry
3 »Full« calibration* V0H2 ● Fill vessel 60…100% full
Enter level in %, m, ft, etc.
Press »E« to register entry
4 0/4 mA signal V0H3 ● Enter 0 for 0…20 mA signal, 1 for 4…20 mA signal
Press »E« to register entry
V0H5 ● Enter level for 0/4 mA signal (if not 0)
Press »E« to register entry
V0H6 ● Enter level for 20 mA signal (if not 100)
Press »E« to register entry
5 Relays 1a and 1b V1H0 ● Enter level for switching in calibration units
Press »E« to register entry
V1H1 ● Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register
6 Relays 2a and 2b V1H5 ● Enter level for switching in calibration units
Press »E« to register entry
V1H6 ● Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register
V1H9 ● Enter 1 = Relay 2 assigned to channel 1
Press »E« to register entry
* Can be performed in reverse order
Endress+Hauser
Prolevel FMC 661 Table of Contents

Table of Contents

Short Instructions . . . . . . . front cover

Notes on Safety . . . . . . . . . . . . . 3

1 Introduction . . . . . . . . . . . . . . 5
1.1 Application . . . . . . . . . . . . . . . 6
1.2 Measuring system . . . . . . . . . . . . 7
1.3 Measuring principle . . . . . . . . . . . . 8
1.4 Functional description . . . . . . . . . . . 9
1.5 Technical data . . . . . . . . . . . . . 10

2 Installation . . . . . . . . . . . . . . 12
2.1 Probes and sensors . . . . . . . . . . . 13
2.2 Prolevel FMC 661 installation . . . . . . . 14
2.3 Transmitter wiring . . . . . . . . . . . . 15
2.4 Sensor connection . . . . . . . . . . . 16
2.5 Rackbus RS-485 option . . . . . . . . . 18

3 Controls . . . . . . . . . . . . . . . 19
3.1 Operating matrix . . . . . . . . . . . . 19
3.2 Keyboard and display . . . . . . . . . . 20
3.3 Commulog VU 260 Z . . . . . . . . . . 21
3.4 Rackbus RS-485 (option) . . . . . . . . 22

4 Level Measurement . . . . . . . . . . 23
4.1 Commissioning . . . . . . . . . . . . 23
4.2 Calibration . . . . . . . . . . . . . . 24
4.3 Analogue Outputs . . . . . . . . . . . 30
4.4 Relays . . . . . . . . . . . . . . . . 32
4.5 Measured value display . . . . . . . . . 34
4.6 Parameter locking . . . . . . . . . . . 34

5 Level Measurement with Limit Switch . . 35


5.1 Level measurement with automatic calibration
correction . . . . . . . . . . . . . . . 36
5.2 External limit switch . . . . . . . . . . . 39

6 Trouble-Shooting . . . . . . . . . . . 40
6.1 Fault recognition . . . . . . . . . . . . 40
6.2 Incorrect measurements . . . . . . . . . 42
6.3 Simulated operating mode . . . . . . . . 43
6.4 Exchanging transmitters and sensors . . . . 44
6.5 Repairs . . . . . . . . . . . . . . . . 45

7 Appendix . . . . . . . . . . . . . . . 46
7.1 Calibration and linearisation in volume units . 46

Index . . . . . . . . . . . . . . . . 48

Operating matrix . . . . . . . back cover

Endress+Hauser 1
Table of Contents Prolevel FMC 661

2 Endress+Hauser
Prolevel FMC 661 Notes on Safety

Notes on Safety
The Prolevel FMC 661 is a field transmitter for level measurement which can be used Approved usage
with a variety of capacitance probes and hydrostatic sensors. It has been designed to
operate safely in accordance with current technical and safety standards, and must be
installed by qualified personnel according to the instructions in this manual.

The manufacturer accepts no responsibility for any damage arising from incorrect use,
installation or operation of the equipment. Changes or modifications to the equipment
not expressly approved in the operating manual or by the bodies reponsible for
compliance may void the user’s authority to operate the equipment.

The Prolevel FMC 661 transmitter is available with certificate of conformity for use with Certificates
probes and sensors operating in hazardous areas. The Table below indicates the
combinations available and conditions for installation. Full details can be taken from the
certificates. Please note that where quoted technical data differs from that listed in
Section 1.5, that in the certificate applies.

Certificate Instruments Notes


Certificate of Conformity Prolevel FMC 661 [EEx ia] IIC,
PTB No. Ex-96.D.2074 install outside Ex-area
CSA FMC 661 Class I, II, III
LR 53988-81 Div. I
Groups A-G
FM FMC 661 Class I, II, III
J.I. 0Z2A7.AX Div. I
Groups A-G
PTB Certificate of Capacitance probes EEx ia IIC T4…T6
Conformity Multicap DC 11, DC 16, suitable for installation on Channel 1
PTB Ex 93.C.2171 X DC 21, DC 26 of Prolevel FMC 661

ZE 104F/00/d
for Germany
ZE 103F/00/d, e, f
for foreign countries

PTB Nr. Ex-93.C.2062 X with electronic insert


ZE 097F/00/d EC 37 Z or EC 47 Z
Certificate of Conformity DB 50…53 EEx ia IIC
PTB Nr. Ex-96.D.2017 X with FEB 17 or FEB 17 P T4…T6
KEMA No. Ex-92.C.8494 Liquiphant EEx ib IIC T6
ZE 076F/00/d, e, f FDL 30, 31, 35, 36 suitable for installation on Channel 2
for foreign countries of Prolevel FMC 661
Type approval Capacitance probes Dust-Ex, Zone 10 (Germany)
BVS 93.4.8004 B 11 450 S; 21265 S with suitable for installation on Channel 2
electronic insert EC 17 Z of Prolevel FMC 661
German Lloyd Prolevel FMC 661 Level indication on channel 1
No. 97517 HH Capacitance probes (EC 37 Z or EC 47 Z)
Insert EC 37 Z or EC 47 Z Level limit detection on channel 2
Insert EC 17 Z (EC 17 Z)
Suitable for unlimited use within the
Rules
German Lloyd DB 50, 50 L, 52, 53
No. 99350-97HH with FEB 17 or FEB 17 B

Endress+Hauser 3
Notes on Safety Prolevel FMC 661

Safety conventions
In order to highlight safety-relevant or alternate operation procedures in the manual the
following conventions have been used, each indicated by a corresponding icon in the
margin.

Note!
• A note highlights actions or procedures which, if not performed correctly, may
indirectly affect operation or may lead to an instrument response which is not
Note!
planned.

Caution!
• Caution indicates actions or procedures which, if not performed correctly, may lead
Caution! to personal injury or incorrect functioning of the instrument

Warning!
• A warning indicates actions or procedures which, if not performed correctly, will lead
Warning!
to personal injury, a safety hazard or destruction of the instrument

4 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction

1 Introduction
The Prolevel FMC 661 field transmitter measures level with hydrostatic pressure sensors
or capacitance probes. It may be installed, commissioned and maintained by authorised
personnel only. The operating manual must have been read and understood before the
equipment is installed: instructions are to be followed exactly.

Since it is not possible to describe all applications in detail, the standard application, In this manual
continuous level measurement, has been used as the basis for the functional description.
Other applications as listed in Section 1.1 are described in Chapter 5. The operating
instructions are structured as follows:
• Chapter 1: Introduction;
contains general information including application, measurement
principle, functional description and technical data.
• Chapter 2: Installation;
contains hardware configuration, installation instructions and
connection diagrams.
• Chapter 3: Controls;
describes operation with the front panel keys, Commulog VU 260 Z,
and via the Rackbus RS-485 interface.
• Chapter 4: Calibration and Operation;
tells you how to commission the Prolevel for the standard
application including calibration, linearisation, analogue outputs,
relays and locking the parameter matrix.
• Chapter 5: Level Measurement with Limit Switch;
describes the automatic calibration correction and other operating
modes of the Prolevel FMC 661.
• Chapter 6: Trouble-Shooting;
contains a description of the self-checking system with error
messages, the simulation feature as well as instructions for
configuration on replacement of the transmitter, probe or
electronic insert.
• Appendix: Contains a flowchart for calibration and linearisation using
volume units.
• Index: lists key words to help you find information quickly.

Short instructions for the standard set-up, continuous level measurement, which is used Short instructions
in 80% of applications, are to be found in the front cover. We advise you to commission
as described in Section 4.1. before using this procedure as this ensures that probes can
be exchanged without the need for re-calibration.

In addition to this manual, the following publications provide information on configuration Further documentation
of the Prolevel FMC 661.
• BA 028F Commulog VU 260 Z handheld terminal
• BA 134F Rackbus RS-485
The installation of the probes, electronic inserts and accessories is described in the
documentation accompanying these articles - see text for references. When installing
probes in explosion hazardous areas the instructions included in the accompanying
probe certification must also be observed.

Endress+Hauser 5
Chapter 1: Introduction Prolevel FMC 661

1.1 Application

Fig. 1.1:
Standard application showing hazardous area safe area
Prolevel FMC 661 controlling alarm
level measurement relay
➀ Capacitance probe Channel 1 0/4...20 mA
limit relays
➁ Hydrostatic probe 1
Bulk solids

Endress+Hauser

1 or
PROLEVEL
FMC 661 123.4
1A
1B
2A
V H
2B
3
+
_ E

Liquids

Prolevel FMC 661


transmitter

Channel 1
2
or

BA142_01

The Prolevel FMC 661 is designed for level measurement with a capacitance probe or
hydrostatic pressure sensor. A second channel allows level limit detection with a vibration
sensor, i.e. Liquiphant or Soliphant, or capacitance probe. The applications described
in this manual are as follows:
• Level or volume measurement …Chapter 4
• Level limit detection …Chapter 5
• Level measurement with automatic calibration correction …Chapter 5.
Prolevel transmitters may also be used for applications in explosion hazardous areas
and possess intrinsically-safe sensor circuits conforming to EEx ia IIC. A list of certificated
combinations is to be found in »Notes on Safety« preceding this chapter.

Fig. 1.2:
Left: hazardous area safe area hazardous area safe area
Prolevel FMC 661 with
Liquiphant limit switch channel 1 level
FMC 661 FMC 661
➀ Maximum fail-safe mode 1 1
➁ Minumum fail-safe mode Endress+Hauser

PROLEVEL
FMC 661 123.4
Endress+Hauser

Max 1A
V H
PROLEVEL
123.4

3
1B FMC 661
2A
2B 1A
3
+ 1B V H
_ E
2A
2B
3
+
_
Right: E

Prolevel FMC 661 with


simultaneous level measurement
and limit switching or
➀ Capacitance level probe or
➁ Hydrostatic level sensor
channel 2 channel 2 limit
➂ Limit switch
switch
The same arrangement is used Min
2 2
for automatic calibration
correction

BA142_02 BA142_03

6 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction

1.2 Measuring system

Fig. 1.3:
The Prolevel FMC 661 can be
used as a stand-alone unit, see
Personal computer with Figs 1.1 and 1.2 or as part of
operating software, e.g. an operating system.
Commutool, Commuwin, A RS-485 adapter or PC card
Commugraph allows direct connection to a
personal computer, the FXA 675
and gateway ZA 67x connection
to a supervisory system using
the Modbus, Profibus or FIP
protocol
Prolevel transmitters (and other units with Rackbus RS-485)

supervisory network
RS-485 adapter or PC card
Endress+Hauser Endress+Hauser Endress+Hauser

ZA 673
FXA 675
PROLEVEL
FMC 671 123.4 PROLEVEL
FMC 671
PROLEVEL
FMC 671
ON
1A 1A 1A
1B
2A
V H 1B
2A
1B
2A
2B 2B 2B
3
+ 3 3

_ E

1 RB/485
RACKBUS
2 PROFIBUS

Rackbus RS-485 alternative


FXA 675 + ZA 67x
BA142_04

A working system for level measurement comprises:


• Prolevel FMC 661 transmitter,
• Capacitance probe or hydrostatic sensor for level measurement with
appropriate electronic insert, see Chapter 2
• If required, vibration sensor or capacitance probe for level limit detection or
automatic calibration correction.

The Prolevel may operate as a stand alone unit with standard 0/4…20 mA output; two
sets of two relays, freely assignable to channel 1 or 2, can be used to control pumps,
valves, annuciators etc.. Alternatively, the Prolevel may be operated remotely over the
optional Rackbus RS-485 interface, either direct from a personal computer or as part of
a process control system. Connection to Modbus, Profibus or FIP networks can be
realised through the gateways ZA 672, ZA 673 or ZA 674 respectively.

The Prolevel is available in two versions: Versions


• With display and front panel controls,
• Without display and front panel controls — in this case the transmitter must be
configured by the Commulog VU 260 Z handheld terminal or over the optional
Rackbus RS-485 interface.
In all other respects, the two versions are identical. More details on controls and operation
can be found in Chapter 3.

Endress+Hauser 7
Chapter 1: Introduction Prolevel FMC 661

1.3 Measuring principle


The Prolevel FMC 661 measures level on the basis of the capacitance and hydrostatic
measurement principles. In both cases the measured value is processed by the
electronic insert and passed on as a frequency signal.

Capacitance The probe and vessel form the two plates


D
measurement of a capacitor, the total capacitance of
which can then be calculated from the
formula: C1

2πε0εr x L pF (1)
Ctot = C1 + -------------
L d
ln (D/d)
whereby
Ctot = total capacitance
C1= capacitance of feed through
ε0= dielectric constant of air (8.85)
εr= rel. dielectric constant of product BA142_05

D= diameter of vessel Fig. 1.4:


d= diameter of probe Capacitance measurement principle
L= length of probe immersed in
product in meters

Measurement in If the product conducts, the capacitance is


conducting media now determined by the thickness and D
properties of the insulating material d Conducting
product
surrounding the probe. Equation (1)
applies, whereby the variable D is now the insulation
diameter of the probe with insulation. In this
case the capacitance varies by approx.
300 pF/m.
L
Measurement is independent of dielectric
constant and not affected by changes in
this variable.
BA142_06

Fig. 1.5:
Measurement in conducting media

Hydrostatic In an open vessel, the level is derived from


measurement the hydrostatic pressure exerted by a
column of liquid on a probe placed at its
foot. The pressure exerted is:
p1 = ρxgxh (2) atmospheric
pressure
whereby
p1 = hydrostatic pressure
ρ = density of the liquid p1 = ρ x g x h
g = acceleration due to gravity h
p1
h = height of the liquid column.

Assuming a constant density, the level of


BA142_07
the liquid can be calculated from the
pressure measured by the Deltapilot.
Fig. 1.6:
Hydrostatic measurement principle

8 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction

1.4 Functional description

Fig. 1.7:
Signal processing in the
frequency level volume
Prolevel FMC 661 for single
channel operation (level
zero point shift and/or limit switching)
Channel 1

cap./press. level volume analog


H2
V2 current
H1 V1
Hz cap./press. level digital

offset [Hz] range lower limit range upper limit


electronic V1 V2
insert
sensitivity [Hz/pF] offset [pF] sensitivity [pF/cm]

Channel 2

level relay 1a, 1b


frequency
limit
2
detection relay 2a, 2b

switch point
hysteresis
min. / max. fail-safe mode
switching delay
BA142_08

Fig. 1.7 is a block diagram of the Prolevel FMC 661. The transmitter supplies the power
to the sensor. The capacitance or pressure measured by the sensor is converted into a
frequency signal by the electronic insert located in its head and transmitted to the Prolevel
over a two-core cable. The signal is then processed to provide six operating modes.

Mode in V8H0 Function Table 1.1:


Prolevel FMC 661 operating
0 Simultaneous level measurement and limit detection on channels 1 and 2 modes

1 Level measurement on channel 1 only


2 Limit detection on channel 2 only
5 Corrected level measurement — the level measurement at channel 1 is
corrected when the product covers the limit switch at channel 2
6 Simulation of level, volume or current at channel 1
7 Simulation of limit detection at channel 2
By calibrating at two levels, »empty« and »full«, the frequency signal is converted to a Signal processing
level measurement in the units entered during calibration. In mode 5, the measured value
at channel 1 is then corrected. For non-linear volume/level relationships, volume can be
calculated from level via the vessel characteristic which describes the shape of the
vessel. The signal resulting from the calibration and linearisation provides a standard
0/4...20 mA output, proportional to level or volume. Any portion of the measuring range
can be taken to provide a scaled output. The two sets of two relays can be assigned to
either measuring channel to provide level control by switching pumps on and off.

All measured values and the complete configuration can be accessed via the optional
Rackbus RS-485 interface.

If a fault condition is detected, e.g. a break in sensor - transmitter cable, the analogue Fail-safe operation
signal switches to -10 % or +110 % level or holds the last measured value. The alarm
relay de-energises and the red LED on the front panel lights. In addition, each set of
relays can be set to switch on or off as required.

Endress+Hauser 9
Chapter 1: Introduction Prolevel FMC 661

1.5 Technical data

General specifications Manufacturer: Endress+Hauser GmbH+Co.


Designation: Prolevel FMC 661
Function: Transmitter for level measurement with capacitance and hydrostatic
probes as well as level limit detection with capacitance and vibration
probes
Input signal: Level proportional PFM signal
Interfaces: 0/4…20 mA, Rackbus RS 485 (option)
Reference conditions: to IEC 770 (TU = 25°C) or as specified
Miscellaneous: CE mark
Input characteristics

Signal input, channel 1


Signal: Pulse frequency modulated signal from connected probe or sensor
Explosion protection: PTB [EEx ia] IIC, FM, CSA, intrinsically safe signal circuits separated
from each other and rest of the electronics
Probe or sensor: Multicap or other capacitance probe with EC 37 Z or EC 47 Z
electronic insert
Deltapilot S hydrostatic sensor with FEB 17/FEB 17 P

Switch input, channel 2


Signal : Pulse frequency modulated signal from connected probe or sensor
Limit switch: Multicap probe with EC 16 Z or EC 17 Z electronic insert
other capacitance probe with EC 17 Z electronic insert
Liquiphant FDL 30 / FDL 31 / FDL 35 / FDL 36
Output characteristics Soliphant DM 90 Z / DM 91 Z / DM 92 Z

Analog output
Output: 0... 20 mA, switchable to 4... 20 mA
Signal underflow: -2 mA;
Signal overflow: + 22 ± 0.2 mA
Output on alarm: selectable +110%, -10% or hold
Current limitation: 23 mA
Temperature 0.3%/10 K of range end value
coefficient:
RFI (E = 10 V/m) 1%
Warm-up time: 1s
Output damping: 0 to 100 s, selectable
Max. load: 600 Ω
Load effect: negligible

Relays
Type: 5 relays with potential-free changeover contacts
Function: 2 pairs of two limit relays with freely selectable switch points and
hysteresis for operation in min. or max. fail-safe mode
1 alarm relay (de-energises on fault condition)
Switching capacity: 6 A, 250 VAC ; 750 VA at cos ϕ = 0.7, 1500 VA at cos ϕ = 1
6 A, 250 VDC; 200 W

10 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction

Display and keyboard Output characteristics


(continued)
Display (LCD): 4 digit measured value display with optional lighting, segmented
current display in 10% steps, various indicators (communication,
signal underflow, overflow)
Light emitting diodes: 1 yellow status LED for every limit relay (lit = relay energised)
1 red alarm LED, lit = alarm — relay de-energised;
flashing = warning — relay remains energised
1 green LED to indicate power on
Keyboard: 6 keys for parameter entry, option available without keys
Interfaces: 0/4…20 mA, Rackbus RS 485 (option)
Reference conditions: to IEC 770 (TU = 25°C) or as specified

Communication interface
Commulog VU 260 Z: 2 communication sockets in terminal compartment
Rackbus RS 485 optional interface for direct connection to a personal computer via
adapter or interface card, or to Rackbus via FXA 675 interface card
Rackbus address via 6-gang DIP-switch in terminal compartment
bus termination via 4-gang switch in terminal compartment
Power supply

Alternating voltage: 230 V / 115 V / 110 V (85...253 V), 50/60 Hz or


24 V / 48 V (20...55V), 50/60 Hz or
Direct voltage: 24 V (16...60V),
residual ripple max. 2 Vpp within tolerance
Power consumption: max. 7 W, switch-on current 880 mA
Safe isolation: between power supply and signal outputs, CPU, Rackbus RS-485,
switch-on current 880 mA and electronics Environment

Operating temperature: 0°C…60°C


Limiting temperature: -20°C…60°C
Storage temperature: -40°C…80°C
Climatic class: to Table 10, Class R, DIN 40 040, instrument outdoors,
average annual humidity 95%, dew permissible
Ingress protection: IP 66 with closed housing and corresponding cable glands
IP 40 with open housing, IP 20 with open terminal compartment
Electromagnetic Emission to EN 50 081-2, industrial use
compatibility: Immunity to EN 50 082-2
and NAMUR industrial standard, at 10 V/m
Vibration resistance: to Table 6, Class W, DIN 40 040
Mechanical
Explosion protection: [EEx ia] IIC, FM, CSA see also "Notes on Safety"
specifications

Housing: for wall- or post-mounting


Dimensions (l x b x h) 292 mm x 176 mm x 253 mm, see Fig. 2.3
Weight: 2.6 kg
Materials: body ABS (acrylnitrilbutadenestyrol)/PC (polycarbonate), RAL 5012 (blue)
transparent cover, polycarbonate
front panel, blue with white field for labelling

Electrical connection
Cable entries: 5 pre-stamped cable entries Pg 16 each in bottom and rear of terminal
compartment
4 pre-stamped cable entries Pg 13.5 in bottom

Endress+Hauser 11
Chapter 2: Installation Prolevel FMC 661

2 Installation
This Chapter describes:
• Probes and sensors for the Prolevel FMC 661
• Installation of the Prolevel FMC 661
• Transmitter wiring
• Sensor connection.
• Hardware configuration for Rackbus RS-485 option.
Fig 2.1 shows the structure of the chapter.

Technicians and fitters It is assumed that suitably qualified personnel are to be used for the installation and
electrical connection of the system components. This is particularly important when the
sensors are to be installed in hazardous areas. Please note the following:

Warning!
• The Prolevel FMC 661 transmitter must be installed outside explosion hazardous
areas.
Warning!
• Observe the specifications in the certificates as well as local regulations when
mounting the sensors in hazardous areas

Fig. 2.1:
Structure of Chapter 2,
Installation 2.1 2.2 2.3

Measuring Mounting the Wiring the


system Prolevel Prolevel
Probe constants transmitter transmitter

2.4 2.5

Wiring the Wiring and


sensors and configuration for
probes Rackbus RS-485

BA142_09

12 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation

2.1 Probes and sensors


Table 2.1 lists the sensors most frequently used with the Prolevel FMC 661 transmitter.
In addition to those listed, all probes which can be used with an EC 17 Z, EC 37 Z or
EC 47 Z electronic insert can be connected to the transmitter. Installation hints can be
taken from the appropriate Technical Information Sheet.

Channel 1 Channel 2 Table 2.1:


Selection of probes suitable for
Principle Probe TI sheet Insert Probe TI sheet Insert use with the Prolevel FMC 661
Capacitance DC 11 TI 169F EC 37 Z DC 11 TI 169F EC 17 Z
DC 16 TI 096F EC 47 Z DC 16 TI 096F EC 16 Z
DC 21 TI 208F DC 21 TI 208F FEC 22
DC 26 TI 209F DC 26 TI 209F
11 322 Z E 11.81.03 11 450 (Z/St) TI 197
11 500 Z TI 161F 11 961 (Z) E 04.77.04
21 211 E 10.73.18 21 262 (Z/St) TI 227
Multicap TE, TA, E, A 21 265 (Z/St) TI 195
TI 239, 240, 242, 243 Multicap TE, TA, E, A
Hydrostatic Deltapilot S TI 257 FEB17 Not suitable
pressure DB 50, 50 L, 51, 52, 53 FEB 17P
Vibration Not suitable Liquiphant EL 17 Z
DL 17 Z 013154-0008 EM 17 Z
FDL 30/31/35/36 TI 185F

Soliphant
DM 90 Z…92 Z TI 124F
BA042

Deltapilot S hydrostatic pressure sensors and EC 37 Z/47 Z inserts are supplied with the Sensor constants
sensor constants zero frequency »fo« and sensitivity »∆f« or »S«, see Fig. 2.2. For
Deltapilot S sensors the constants depend on the measuring range, see Table 2.2. Note
these constants and enter them into fields V3H5 and V3H6 during commissioning,
Section 4.1. This dispenses with the need for a recalibration of the transmitter on
replacement of the sensor or insert.

Fig. 2.2:
CA (pF) C(S)(pF) Location of sensor constants on
EC 37 Z/47 Z electronic insert
17 18 FMC 480 Z
and Deltapilot S DB 4x housing
d4 d2 FMC 470 Z
d4 / z4 d2 / z2 FMC 671 / 672 / 676 / 677 Z
7 8 HAA 420 Z
1 2 3 4 5 6
+ I
II

Ex I II
1 MHz
fo 475,3 57,2
sensor constants
S 6,805 0,652
EC10015EP 8
EC 47 Z
BA142_10

Cell Electronic insert FEB 17/FEB 17 P Table 2.2:


Measuring ranges and sensor
type Range f0 ∆f Range f0 ∆f constants of
Deltapilot S DB 5x
0.1 bar BA 0…100 mbar 200 10 DA -100…100 mbar 200 5
0.4 bar BB 0…400 mbar 200 2.5 DB -400…400 mbar 200 1.25
1.2 bar BC 0…1200 mbar 200 0.833 DC -900…1200 mbar 200 0.476
4.0 bar BD 0…4000 mbar 200 0.25 DD -900…4000 mbar 200 0.204

Endress+Hauser 13
Chapter 2: Installation Prolevel FMC 661

2.2 Prolevel FMC 661 installation

Fig. 2.3:
Dimensions in mm of Prolevel 292
106
FMC 661 housing
1" = 25.4 mm min. 52

ø 4.5

253

201
gap
min. 69

275.5

BA142_11

Location Where possible, find a shady, protected spot in which to mount the Prolevel transmitter:
• Nominal operating temperature: 0°C…+60°C
Use a protective hood or provide cooling if the ambient temperature exceeds +60°C. For
temperatures below -20°C insulate the instrument.

Mounting The Prolevel FMC 661, with IP 66 protective housing, can be mounted on a wall or post
outdoors or in the control room. Fig. 2.3 gives details for wall mounting.

Fig. 2.4 shows how the Prolevel can be


post-mounted with the all-weather cover.
The fastenings (nuts and bolts) for both
post mounting and all-weather cover are
supplied with the units.

• Post mounting:
Material: galvanised steel
(for 2" post Order No. 919 566-0000;
for 1" post: 919 566-1000);
stainless steel 1.4301 (≅ SS 304 H)
(for 2" post Order No. 919 566-0001;
for 1" post: 919 566-1001);
Weight: 1 kg

• Prolevel all-weather cover:


Material: Aluminium, blue paint-finish;
Order No. 919567-000
Material: Steel 1.4301 (≅SS 304 H),
blue paint-finish; Order No. 919567-001

BA142_12

Fig. 2.4:
Post-mounting with all-weather cover

14 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation

2.3 Transmitter wiring

Fig. 2.5:
L+ L-
Terminal assignments for
RS-485 [EEx ia] IIC
L1 N 1a 1b 2a 2b Prolevel FMC 661
B DGND A
-+ -+
ground externally
PE terminal strip

1 2 3 4 5 11 12 13 21 22 23 31 32 33 41 42 43 51 52 53 60 61 62 81 82 91 92

Commulog VU 260Z

bus switches
RxD/TxD-N

RxD/TxD-P
L+
L-

DGND
16...60 VDC

0/4...20 mA

Sensor 1

Sensor 2
RS-485
PE
L1

optional interface
N

relays channel 1

relays channel 2
85...253 VAC
20...55 VAC

level sensor
alarm relay

limit switch
current 1

BA142_13

Warning!
• Make electrical connections with the power supply switched off!
• The PE terminal strip must be grounded externally (contact protection)!
• When wiring up probes and sensors in explosion hazardous areas, observe the Warning!

instructions on the certificate and other local regulations.

The terminal strip for cable diameters up to 2.5 mm2 is located in a separate connection Terminal strip
compartment. Fig. 2.5 shows the wiring diagram for the Prolevel FMC 661 (Terminal 3 is
reserved for the internal protective ground):
• Remove the plastic cover from the front of the connection compartment
• Press out the pre-stamped cable entries as required
bottom: 5 x Pg 16, 4 x Pg 13.5; rear: 4 x Pg 16.

The power requirements are printed on the nameplate at the right-hand side of the Power
nameplate, see also Section 1.5, "Technical Data".
• If the specifications on the nameplate do not correspond to those of your
power supply, do not connect up - you may damage the instrument!
• Connect the protective ground to the metallic terminal strip provided at the left
— this ensures safe isolation and contact protection.
• Current output, relay outputs, power connection and sensor input are all
electrically isolated from one another.

Only one non-floating device can be connected to the current output. Analogue outputs
• There is no limit to the number of floating devices, other than that imposed by
considerations of the maximum load of 600 Ω.

For the switching capacity of the relays see the technical data in Section 1.5. Relays
• Relays 1a and 1b are normally assigned to channel 1
• Relays 2a and 2b are normally assigned to channel 2.
The assignment can be changed by software, see Section 4.4.

Endress+Hauser 15
Chapter 2: Installation Prolevel FMC 661

2.4 Sensor connection

Sensor cable Use commercial 2-core installation cable, max. line resistance 25 Ω/core, for the sensor/
transmitter cable — the Prolevel satisfies the quoted EMC standards with this cable.

Level probes and The Prolevel FMC 661 can be operated with a variety of sensor types, each requiring a
sensors, channel 1 different electronic insert. For Channel 1, continuous level measurement:
• EC 37 Z or EC 47 Z for capacitance and Multicap probes
EB 17 or EB 27 P for Deltapilots S

Level limit switch, The level limit switch may be a vibration probe — Liquiphant (liquids) or Soliphant (solids)
channel 2: — or a capacitance probe, with electronic insert
• EC 16 Z/EC 17 Z for Multicap probes
EC 17 Z for other capacitance probes
• EL 17 Z for Liquiphant probes
EM 17 Z for Soliphant probes

Fig. 2.6:
Connection diagram for Channel 1 Channel 2
81 82 91 92
electronic inserts Insert bridge if
Left: Capacitance/Multicap conductive
EC 37 Z/EC 47 Z build-up on probe
Insert bridge for
Right: Capacitance/Multicap
Range II (standard) Insert bridge
EC 17 Z
Remove for Range I (see instructions)
Ground Ground
connection connection

BA142_14 BA142_15

EC 37 Z and EC 47 Z The electronic inserts EC 37 Z and EC 47 Z have two measuring ranges which can be
selected by inserting a bridge between terminals 4 and 5 of the insert, see Fig 2.6. Full
instructions on selection of the insert are to be found in Publication E 07.80.06/1c.
• Note the zero frequency fo____ and sensitivity S_____on the insert for the
range you have selected.

EC 17 Z The EC 17 Z electronic insert can be used at Channel 2 with capacitance and Multicap
probes for limit level switching. The connection diagram is shown in Fig. 2.6. Technical
information is given in Publication E 11.84.04/1a.

EC 16 Z The EC 16 Z electronic insert is for use on channel 2 with the Multicap probes with active
build-up compensation. Wire it up as described in the Technical Information Sheet
TI 170F delivered with the insert.

16 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation

The FEB 17/FEB 17 P electronic insert can FEB 17 and FEB 17 P


81 82 Channel 1 be used at Channel 1 with Deltapilot S
DB 5x… sensors to measure level and
volume in open vessels. The sensor
constants are listed in Tabel 2.2.

1 2 3 4 • Note the zero frequency f o_____ and


FEB 17/FEB 17 P sensitivity ∆f _____ of the probe

BA142_56

Fig. 2.7:
Connection diagram for Deltapilot S with
FEB 17/FEB 17 P electronic insert

The EL 17 Z electronic inserts can be used EL 17 Z and EM 17 Z


91 92
at Channel 2 with Liquiphant sensors for
Channel 2
limit level switching. For Soliphant sensors
the EM 17 Z insert is used. Publications
013154-0008 and BA 042 (014897-0002)
contain full installation instructions.

BA142_16

Fig. 2.8:
Connection diagram for Liquiphant/Soliphant
electronic inserts EL 17 Z/EM 17 Z

Endress+Hauser 17
Chapter 2: Installation Prolevel FMC 661

2.5 Rackbus RS-485 option

Fig. 2.9:
Rackbus RS-485 topologies
showing setting of bus 150Ω

termination resistance A 1
OFF
ON 2
OFF
ON E OFF
ON
Rt

Inset: Rpull 60 61 62 60 61 62 60 61 62
Suggestion for wiring the bus
Master PE
60 61 62

Rt PE

Data A
Data B
B 1
OFF
ON

L1 60 61 62 PE
Rpull Screen

Master 150Ω
OFF Rt
2 ON E OFF
Rt ON
PE
60 61 62 60 61 62
L2 (> L1)

PE

BA142_19/20

Wiring the bus Up to 25 Prolevel FMC 661 transmitters can be connected to the Rackbus RS-485.
Instructions for wiring and grounding the bus are to be found in Operating Instructions
BA 134F which is delivered with Prolevel instruments having the Rackbus RS-485 option.
The Prolevel can be wired as indicated in the inset in Fig. 2.9.

Note!
• Terminal 61 is connected internally to the PE ground terminal strip
• The screening must be grounded and have electrical continuity throughout — read
Note!
BA 134F for grounding instructions

Bus address and Fig. 2.10 shows the configuration elements


termination for remote operation of the Prolevel 1 2 4 8 16 32 (=10)
address switch
FMC 661. Every transmitter must have a OFF
ON
unique bus address:
• Switch off power, loosen screws and SW1
open the terminal compartment L+ L-
L1 N 1a 1b 2a 2b
RS-485
B DGND A
[EEx ia] IIC

-+ -+
• Set the address at DIP-switch SW1
(Example: 2 + 8 = 10) terminal compartment SW2

For the last transmitter on the bus, i.e.


392Ω 150 Ω 392 Ω
furthest away from the computer:
+5V
• Switch in the terminal resistance at
bus termination
DIP-switch SW2: OFF; ON; ON; OFF OFF
switch
ON
• Close front panel, tighten screws. BA142_21

Fig. 2.10:
DIP-switches for bus address and termination

18 Endress+Hauser
Prolevel FMC 661 Chapter 3: Controls

3 Controls
This Chapter describes how the Prolevel FMC 661 transmitter is operated. It is divided
into the following sections:
• Operating matrix
• Keyboard and display
• Commulog VU 260 Z handheld terminal
• Rackbus RS-485.

3.1 Operating matrix


All functions, including the analogue outputs and relay switch points are configured via
the operating matrix, see Figs 3.1 and 3.2:
• Each field in the matrix is accessed by a vertical (V) and horizontal (H)
position which can be entered at the front panel of the Prolevel FMC 661, by
the Commulog VU 260 Z or for the Rackbus RS-485 from a personal computer.
A matrix card, reproduced at the back of this manual, is delivered with the Prolevel
FMC 661 transmitter.

Fig. 3.1:
Prolevel FMC 661 display Prolevel FMC 661
Parameter matrix operation with
Parameter at current matrix Current matrix position function of V and H keys.
position The complete matrix has 10 x 10
fields, although not all are used

Pressed together
Move to V0H0

Move V0… V9, V0 Move H0 … H9, H0


BA142_22

Fig. 3.2:
Commulog display Commulog VU 260 Z display and
key functions
Parameter
The Tag No. and measurement
Bar chart of Diagnostics key - press units are entered in the VA level
analogue signal to display error which can be accessed by the
message when icon Commulog or via the Rackbus
blinks RS-485 interface only

Escape key - press to


move to field 00

Entry key - press to call


Matrix selection keys - or quit parameter entry
press to move about matrix BA142_23

Endress+Hauser 19
Chapter 3: Controls Prolevel FMC 661

3.2 Keyboard and display

Fig. 3.3:
Matrix position indicator
Front panel of the
Prolevel FMC 661 transmitter Measured value display

The transmitter is also available


Communications indicator
without the keyboard VH
Current underflow/overflow
00
indicator

Endress+Hauser 10-step segmented display


showing percentage
0/4 … 20 mA signal
4 yellow limitPROLEVEL
relay
FMC 671 LEDs 123.4
•lit, relay energised 1A
1B
2A
V H
2B
3
+
_ E
Matrix selection keys

Red alarm relay LED Parameter entry keys


• Lights on fault condition,
relay de-energises
• Flashes on warning
relay remains energised Green operational LED
• Lights in normal operation
BA142_24

Fig. 3.1 shows the LC-display with matrix of the Prolevel FMC 661, Fig. 3.3 its front panel.
Table 3.1 below describes the function of the operating keys.
• Changes are not possible if the matrix has been locked (Section 4.6).
• Non-flashing parameters are either read-only indications or locked entry fields.

Table 3.1: Keys Function


Prolevel FMC 661
Parameter entry and display keys Matrix selection
• Press V to select the vertical position.

• Press H to select the horizontal position

+ • Press simultaneously to select the measured value field, V0H0

Parameter entry
• Select the digit to be changed.
The digit at the extreme left is selected and flashes.
• Move to the next digit by pressing »⇒« again. When the last digit
is reached »⇒« selects the leftmost digit again.
+ • To change the position of the decimal point, press down both
»⇒« and »+«. The decimal point moves 1 space to the right.
• Increases the value of the flashing digit

• Decreases the value of the flashing digit


• To enter a negative number decrease the leftmost digit until a
minus sign appears in front of it
• Press »E« to register entry.
• Unregistered entries remain ineffective and the instrument will
operate with the old value.

20 Endress+Hauser
Prolevel FMC 661 Chapter 3: Controls

3.3 Commulog VU 260 Z


Fig. 3.4:
Commulog sockets Measured value and Configuration with handheld
segmented current display terminal Commulog VU 260 Z

The Prolevel FMC 661 appears


as device FMC 671 Z

FMC 671 Z
L+ L- RS-485
L1 N 1a 1b 2a 2b B DGND A
-+ -+

Warning!
power and relay terminals
are live!
Warning! Warning!

Function keys

Matrix selection
terminal compartment keys

BA142_25

The Prolevel FMC 661 without keyboard can be configured with the Commulog VU 260 Z
handheld terminal, Figs 3.2 and 3.4. A full description of Commulog operation is to be
found in Operation Instructions BA 028. Table 3.2 summarizes the key functions.
Warning!
• The power and relay terminals in the terminal compartment are live!. Warning!

Keys Function Table 3.2:


Prolevel FMC 661
Matrix selection Parameter entry and display
keys for Commulog VU 260 Z
• Select matrix position

• »Escape key«, selects the position V0H0

• Displays error message if diagnostics icon flashes


• Press »Escape« to reset fault alarm and return to last position
Parameter entry
• Calls the parameter entry mode
• Quits parameter entry mode and registers the entered value
• Select the digit to be changed: the selected digit flashes.

• Enter the desired value: If the parameter is alphanumeric:


- The ⇑ key scans through all characters starting from
"-" through: 0,1,..,9,.,/,+, space, Z,Y,X,W,..
- The ⇓ key scans through all characters starting from
"-" through: A,B,..,Y,Z, space,+,/,.,9,8,...
+ • Move the decimal point:
- ⇐ and ⇑ together to move left or
+ - ⇒ and ⇑ together to move right.

• Restores original value and quits entry mode.


The Commulog stays at the selected matrix field.

Endress+Hauser 21
Chapter 3: Controls Prolevel FMC 661

3.4 Rackbus RS-485 (option)

Fig. 3.5:
Parameter entry in configuration
software V0H2
full calibration
4 x 5 field portion of
matrix scrolled on
7.00 m 7.00
monitor
parameter entry

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V0
V1
V2
V3
V4
V5
V6
V7
Selection of V8
vertical position
V9
V0… VA
VA

Selection of horizontal
position H0 … H9
BA142_26

Prolevel FMC 661 transmitters with Rackbus RS-485 interface can be configured from a
personal computer using one of the Endress+Hauser operating programs:
• Fieldmanager 485 Version 5.0 and Commugraph 485 if connected to the
computer via a RS-485/RS-232C converter or RS-485 card.
• Commuwin, Commutec operating program, Commutool if connected via the
FXA 675 and gateway ZA 67x.

The operation corresponds to that of the keyboard version. Full details of the programs
can be taken from, e.g. Operating Instructions BA 134F, which is delivered with all
Prolevel transmitters with Rackbus RS-485 interface.

Note!
Note! • The Prolevel appears in all programs with the designation "FMC 671 Z"

22 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

4 Level Measurement
This chapter is concerned with the level measurement functions (operating mode 1 in
V8H0, default) of the Prolevel FMC 661; the principle sections describe:
• Commissioning
• Calibration: — for upright cylindrical tanks
— for horizontal cylindrical tanks
— for tanks with conical outlet
— dry calibration for hydrostatic sensors
• Analogue outputs
• Relays
• Display of measured values
• Locking the parameter matrix.
With the exception of the dry calibration, the configuration procedure is independent of
whether a hydrostatic pressure sensor or capacitance probe is connected to the Prolevel.

4.1 Fig. 4.1:


Procedure: calibration and
fo, S/ f Sensor operation for level measurement
constants

4.2
Calibration Calibration
Standard horizontal "Dry"
calibration
conical ρgh calibration
cylinder tank

4.3
Analogue
output

4.4 4.5 4.6


V0H0
Measured Parameter
Relays lock
values

BA142_27

4.1 Commissioning
When programming the Prolevel for the first time, reset the module to the factory based
parameters, see Table in back cover. Then enter the probe constants fo and S (∆f) —
measured at 25°C. This ensures that the EC 37 Z/EC 47 Z electronic insert or Deltapilot
can be replaced without the need for recalibration, see Section 6.4.

Step Matrix Entry Significance


1 V9H5 e.g. 671 Enter any number 670…679 to reset transmitter
2 - »E« Register entry

3 V3H5 e.g. 475.3 Enter zero frequency fo (offset) of electronic insert or sensor
4 - »E« Register entry

5 V3H6 e.g. 6.805 Enter sensitivity, S or ∆f, of electronic insert or sensor


6 - »E« Register entry

Endress+Hauser 23
Chapter 4: Level Measurement Prolevel FMC 661

4.2 Calibration
This section describes three methods of calibration which require the tank or silo to be
filled and the entry of:
• an »empty« level at V0H1 and
• a »full« level at V0H2.
The fourth method can be used to make a »dry« calibration for hydrostatic sensors. For
horizontal cylinders and tanks with conical outlet, users requiring a volume or weight
measurement can activate the linearisation procedure.

Note!
• Prolevel is not bound to specific level units: during calibration it merely assigns the
Note!
numbers entered to the measured frequencies for »empty« and »full«.

1) Standard calibration
for upright cylinders # Matrix Entry Remarks V0H1
1 V0H1 E Tank empty, current capacitance probe
level in your units
2 - »E« Register entry

3 V0H2 F Tank full, current


level in your units
probe or sensor
4 - »E« Register entry covered

5 V0H0 Level Measured value in


the units selected.
»Empty« level E
(0… 40%)

Note!
Note! • The calibration can be performed in
Deltapilot
reverse order.
• For bulk solids (capacitance probes!),
the probe measures the depth of
emersion in the product only. Account
V0H2
for any filling mound or outflow
depression by the entered levels.
• Density correction, see p. 29. »Full« level F
(60… 100%)
After calibration If the product level is entered in %:
• % level is displayed at V0H0
• the 0/4…20 mA signal range
corresponds to 0…100% level
• relays 1a and 1b switch at 90% in
maximum fail-safe mode.

Next step… If the level is entered in length, volume or


weight units, the analogue output and
relays must be set, see p. 30…33.
BA142_28

Fig. 4.2:
Parameters for standard calibration

24 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

2) Calibration for
# Matrix Entry Remarks horizontal cylinders
V0H1 1 V0H1 E Tank empty, current
100% for entries in % level in %, m, ft
2 - »E« Register entry

3 V0H2 F Tank full, current


level in %, m, ft
probe or Level %: refer E% and F% to the
4 - »E« Register entry
sensor bottom (0%) and the top (100%)
covered of the tank! D is then 100%

»Empty« level E
(0… 40%) After calibration the level can be read off at
V0H0 in %, ft or m.
0% for entries in %
A volume measurement can be made by Linearisation, horizontal
calling the linearisation table for horizontal cylinder
V0H2 cylinders. Two parameters are entered:
100% »Full« level F • Tank diameter, D
(60… 100%)
• Tank volume, V.

# Matrix Entry Remarks


5 V2H7 D Tank diameter,
%, m or ft
6 - »E« Register entry

7 V2H8 V Tank volume*,


hl, gal…
0%
8 - »E« Register entry

9 V2H0 1 Activate linearisation


10 - »E« Register entry
100%
V (V2H8)
* If V =100 is entered, % volume is measured

D (V2H7)
The linearisation starts at the tank bottom. Offset
Empty If the zero point of the calibration does not
calibration E start at the same point you must now enter
E = 0? a negative offset in the units of calibration.
OFF (V3H4)
Zero point for linearisation
# Matrix Entry Remarks
BA142_29 1. V3H4 –OFF Offset, m or ft
2 - »E« Register entry
Fig. 4.3:
Parameters for calibration and linearisation in a
horizontal cylinder
• Volume is displayed at V0H0 After linearisation
• Level is displayed at V0H9
• Density correction, p. 29.

Set analogue output and relays in volume Next step…


units, see p. 30…33.

Note!
• For linearisation volume => level,
see Appendix, p 46.
Note!

Endress+Hauser 25
Chapter 4: Level Measurement Prolevel FMC 661

3) Calibration for tanks


with conical outlet # Matrix Entry Remarks
V0H1
1 V0H1 E Tank empty, current
level in %, m, ft
2 - »E« Register entry

3 V0H2 F Tank full, current


level in %, m, ft
4 - »E« Register entry
probe or sensor
covered

After calibration the level can be read off at »Empty« level E


V0H0 in %, m, or ft. Volume or weight can (0… 40%)

be measured after a) manual or b) semi-


0% = start of linearisation
automatic entry of a linearisation table.

a) Linearisation, manual You require a linearisation table, H/V or


H/G, max. 30 pairs in increasing order V0H2
»Full« level F
• Level H in %, m or ft (60… 100%)
• Volume V or weight G in customer units.

# Matrix Entry Remarks


5 V2H1 0 Manual
6 - »E« Register entry

7 V2H2 1 Table no.


8 - »E« Register entry

9 V2H3 V/G1… 30 Volume/weight*


10 - »E« Register entry

11 V2H4 H1… 30 Level m or ft*


12 - »E« Register entry
V2H0...V2H5
13 V2H5 »E« Next table no.* H
— springs to V2H3 8

*Repeat # 9… 13 until all values entered

13 V2H0 3 Activate "manual" 7


6
14 - »E« Register entry 5
4
3
2
1
V/G
Note!
• First pair ~ 0 % level, in %, m, ft.
Note! last pair ~ 100 % level, in %, m, ft. V2H4 V2H3
H1 V/G1
• On error E602 or E604, correct table.
H2… V/G2…
Re-activate linearisation in V2H0. H30 V/G30
• For linearisation volume => level,
see Appendix, p. 47. BA142_30

After linearisation • Volume/weight is displayed at V0H0 Fig. 4.4:


Parameters for calibration and linearisation in a tank
• Level is displayed at V0H9 with conical outlet
• Density correction, p. 29.

Next step… Set analogue output and relays in volume


or weight units, p. 30…33.

26 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

After calibration, p. 26, the semi-automatic b) Semi-automatic


V2H0...V2H5
linearisation can be made: linearisation
• Enter known volume V/weight G in V2H3
volume
measurement • Level is displayed in V2H4

»Full« level F No. Matrix Entry Remarks


5 V2H1 1 Semi-automatic
6 - »E« Register entry
probe or sensor
covered 7 V2H2 1 Table no.
8 - »E« Register entry

9 V2H3 V/G1… 30 Volume/weight*


10 - »E« Register entry

11 V2H4 »E« Register level H1… 30*


»Empty« level E

0% = start of linearisation
12 V2H5 »E« Next table no.*
— springs to V2H3

BA142_31 *Repeat # 9… 12 until all values entered


Fig. 4.5:
13 V2H0 3 Activate "manual"
Parameters for calibration and semi-automatic
linearisation in a tank with conical outlet 14 - »E« Register entry

Note!
• On error E602 or E604, correct table. Re-activate linearisation in V2H0.
Note!

• Volume/weight is displayed at V0H0 After linearisation


• Level is displayed at V0H9
• Density correction, p. 29.

Set analogue output and relays in volume or weight units, p. 30…33. Next step…

To delete a pair of values: Deletion of value pairs


V2H0 = 0
• Enter table number in V2H2
• Enter 9999 in V2H3 or V2H4
H1 V1
H2 V2
H3 V3
... ...
...
Hn
...
Vn
There are two possibilities for deleting a Deletion of linearisation
linearisation:

V2H0 = 1, 3
• Enter "0" in V2H0: The linearisation is
de-activated but the table remains
H1 V1
H2 V2 stored
H3 V3
... ... — Enter 1 (horizontal cylinder) or
...
Hn
...
Vn
3 (linearisation table) to re-activate.

• Enter "4" in V2H0: the manual or


V2H0 = 4 semi-automatic linearisation is deleted,
H1 V1 V2H0 = 0
H2 V2
H3 V3 — The linearisation for horizontal
... ...
... ... cylinders is deactivated but remains
Hn Vn
stored.
BA142_32

Fig. 4.6:
De-activating a linearisation

Endress+Hauser 27
Chapter 4: Level Measurement Prolevel FMC 661

4) » Dry calibration« A dry calibration for hydrostatic sensors requires:


• the »empty« level at which the measurement should start
ρgh • the maximum height of the liquid column at »full« level and
• the density of the liquid
• the calculated offset and sensitivity of the display.

Caution!
• The sensor constants must have been entered as per Section 4.1.
Caution! • Check the calibration during the first filling of the tank! If your calculations are
incorrect the levels measured will be incorrect also!

Example: display in % Calculate the pressure in mbar acting at


display for pzero = 0 the sensor for the desired »empty« level P mbar
and the span (»full« - »empty«): level sensor sensitivity ∆f, S
(V3H2)
pmbar = 10 x ρ (kg/dm3) x g (m/s2) x ∆h (m)

display sensitivity
mbar/digit, V3H2
For 0.45 m water, display = 0%,
For 10.45 m water, display = 100%
Span (0%…100%) = 10 m
• pzero = 10 x 1.0 x 9.807 x 0.45
= 44.13 mbar offset
V3H1
pspan = 10 x 1.0 x 9.807 x 10.00
sensor zero, f0 f (Hz)
= 980.7 mbar frequency (V3H5)
• Offset = pzero = 44.13 mbar BA142_33

Sensitivity = pspan/span = 980.7/100 Fig. 4.7:


9.807 mbar/% Offset and sensitivities for dry calibration

Sensor calibration
# Matrix Entry Remarks
1 V0H2 e.g. 100 Full level (100%) display
2 - »E« Register entry
»Full« e.g. 10.45 m
3 V3H1 e.g. 44.13 Offset in mbar 100 VH
00

4 - »E« Register entry span = 100%

5 V3H2 e.g. 9.807 Sensitivity mbar/%


= e.g. 10 m

6 - »E« Register entry


pempty = ρ x g x 0.45
e.g. = 44.13 mbar
7 V0H0 **.** Measured value %

The Prolevel now measures 0 at 44.13 mbar 0 VH


00 »Empty«, e.g. 0.45 m

Next step… Set analogue outputs and relays in %, see sensor


p. 30…33. sensor zero offset
point
BA142_34

Fig. 4.8:
Parameters for dry calibration, display in %

28 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

Calculate the pressure in mbar acting at the sensor for the desired »empty« level and Example: display in hl
the span (»full« - »empty«): display for pzero ≠ 0
pmbar = 10 x ρ (kg/dm3) x g (m/s2) x ∆h (m)
For 0.0 m water, display = 50 hl
For 10.0 m water, display = 2000 hl
Span (50…2000 = 1950) = 10 m
• pzero = 10 x 1.0 x 9.807 x 0.0 = 0.0 mbar
p1950 = pspan = 10 x 1.0 x 9.807 x 10.00 = 980.7 mbar
• Offset = pzero = = 0.0 mbar
Sensitivity = pspan/span = 980.7/1950 = 0.5029 mbar/hl

Sensor calibration
display # Matrix Entry Remarks
»Full« e.g. 10 m 1 V0H2 e.g. 2000 Full level (100%)
2000 VH
00 2 - »E« Register entry
span = 2000 - 50 = 1950

3 V3H1 0.0 Offset in mbar


4 - »E« Register entry
= e.g. 10 m

pempty = ρ x g x 0.0 5 V3H2 e.g. .5029 Sensitivity mbar/hl


e.g. = 0 mbar 6 - »E« Register entry

The Prolevel now measures 0 at 0 mbar — a


negative level offset must be entered, p. 25
»Empty« = 0.0 m
50 VH
00
7 V3H4 e.g. -50 Level offset
8 - »E« Register entry
sensor zero
point negative level offset
BA142_35

Fig. 4.9:
Parameters for dry calibration, display in hl

Set analogue outputs and relays in the units used for calibration, e.g. hl, see p. 30…33. Next step…

If the product changes after calibration, the measurement can be corrected by entering Density correction for
a density factor at V8H7: hydrostatic sensor
Factor = old factor x new density
old density
The measured value is divided by the factor before display.
Note!
Note!
• For an automatic density correction using an additional external limit switch see
»Calibration Correction« in Chapter 5

Endress+Hauser 29
Chapter 4: Level Measurement Prolevel FMC 661

4.3 Analogue Outputs


This section describes the setting of the analogue outputs. The following parameters can
be entered or changed:
• Analogue signal range
• Output damping
• Value for 0/4 mA and 20 mA
• Output at fault

Analogue signal range Two settings are possible:


analogue signal range
• 0 = 0...20 mA (default)
• 1 = 4...20 mA 20

Depending on the level values entered at


V0H5 and V0H6 for the start and end of the
range, it is possible that signals below
4 mA and above 20 mA can be generated V0H3 = 1

mA
in normal operation.

V0H3 Range Current limits


0 0...20 mA -2…22 mA
1 4...20 mA -2…22 mA 4
V0H3 = 0

Example: 0
0% (V0H5) level % 100% (V0H6)
4… 20 mA # Matrix Entry Remarks
BA142_36
1 V0H3 1 4… 20 mA
2 - »E« Register entry Fig. 4.10:
Selection of analogue signal range, V0H3

Output damping This parameter sets the degree of damping


of the analogue output: on a sudden
change in level, 63% of the new value is
attained in the set time (0...100 s).

Example:
Output damping # Matrix Entry Remarks
0 < t < 100
1 V0H4 20 Damping 20 s
2 - »E« Register entry

The digital values at V0H0, V0H8 and V0H9


BA142_37
are also influenced by the output damping.
Fig. 4.11:
Output damping, V0H4

30 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

The 4mA (V0H5) and 20 mA (V0H6) values, Value for 4 mA and


default values 0% and 100%, determine 20 mA
the levels at which the analogue signal
100% V0H6
range begins and ends.

level Example:
# Matrix Entry Remarks 4 mA = 20%,
V0H5 1 V0H5 20 4mA value, 20 % 20 mA = 80%
2 - »E« Register entry
0%
0/4 mA 20 mA 3 V0H6 80 20 mA value, 80%
4 - »E« Register entry

BA142_38

Fig. 4.12:
Value for 4 mA and 20 mA, V0H5 and V0H6 Note!
• Set in calibration/linearisation units
• When V0H3 = 0, V0H5 = 0 mA value Note!

The analogue output can be set such that Output on alarm


V0H7 it takes on distinctive values when a fault
1 = +110% with alarm is detected. Depending on the
22
20 setting in V1H3/V1H8, the relays may also
alarm follow the analogue output. The entry is
2 = hold value made in V0H7:
mA

• 0 = -10% of signal range


4 • 1 = +110% of signal range (default)
• 2 = last value is held
t
0
-2 Example:
0 = -10% # Matrix Entry Remarks Output -10 % on alarm
1 V0H7 0 -10% on alarm
BA142_39 2 - »E« Register entry
Fig. 4.13:
Output on alarm, V0H7

The current values set on an alarm are


shown in the table

Current on alarm when V0H7 =


V0H3 =
0: (-10%) 1: (+110%) 2: hold
0: 0…20 mA ≤ -2 mA ≥ 22.0 mA last value
1: 4…20 mA ≤ -2 mA ≥ 22.0 mA last value

Caution!
• If setting 2 is chosen, the fault recognition system on the 0/4…20 mA signal line is
Caution!
effectively deactivated. Although the transmitter recognises a fault, i.e. the alarm
relay de-energises and the associated LED lights, the signal output to any follow-up
instrumentation appears to indicate a correct measured value.

Endress+Hauser 31
Chapter 4: Level Measurement Prolevel FMC 661

4.4 Relays

Fig. 4.14:
Relay LEDs as a function of relay
status: Limit relays
limit relay: lit, energised 1a, 1b , 2a, 2b
out, de-energised yellow LEDs
alarm relay (default setting):
lit, de-energised
out, energised

r ua r ua r ua
1a 11 12 13 11 12 13 11 12 13
1b 21 22 23 21 22 23 21 22 23
2a 31 32 33 31 32 33 31 32 33
2b 41 42 43 41 42 43 41 42 43
normal operation power failure: de-energised

Alarm relay 3
red LED

r ua r ua r ua
3 51 52 53 51 52 53 51 52 53
normal operation fault power failure: de-energised
BA142_40

Operating modes The Prolevel FMC 661 has five independent relays with potential-free changeover
contacts. Relays 1a, 1b, 2a and 2b are limit relays, relay 3 is an alarm relay which always
de-energises on fault condition. Relays 1a and 1b are set together, as are 2a and 2b.
Five parameters set the limit relays, Table 4.1 summarises their function:

Table 4.1: Parameter Matrix position for Entry/Function


Parameters for setting limit relays
relays
1a, 1b 2a, 2b
Switch point V1H0 V1H5 Relay switch point in calibration/linearisation units
Fail-safe mode V1H1 V1H6 0: minimum fail-safe mode: — the relay
de-energises when the level drops below the
switch point, see Fig. 4.15.
1: maximum fail-safe mode — the relay
de-energises when the level rises above the
switch point, see Fig 4.16.
Hysteresis V1H2 V1H7 Range at end of which the relay energises again
Relay on alarm V1H3 V1H8 0: de-energised
1: as analogue output: see Table 4.2.
Relay assignment V1H4 V1H9 1: channel 1
2: channel 2

Relay on alarm The limit relays respond to an alarm according to the entry at V1H3/V1H8 (0 =
de-energise, 1 = as Table 4.2). When the relays are assigned to the external limit switch
(see Chapter 5) they always de-energises on alarm.

Table 4.2: Setting at V0H7 Minimum fail-safe mode Maximum fail-safe mode
Relay response on fault
condition when V1H3/V1H8 = 1. 0 = -10% (≤ -2 mA) Relay de-energises Relay energises
1 = +110% (≥ +22 mA) Relay energises Relay de-energises

32 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement

Example:
BA142_41

# Matrix Entry Remarks min. fail-safe mode,


1 V1H0 e.g. 10 Switch point relays 1a, 1b:
2 - »E« Register entry switch point 10%,
hysteresis 40%
3 V1H1 0 Min. fail-safe mode
4 - »E« Register entry
relay de-energises on
relay alarm
e.g. 50% energises
5 V1H2 e.g. 40 Hysteresis —
relay energises at 50
hysteresis.
e.g. 40%

rising r u a 6 - »E« Register entry


V1H2

11 12 13
21 22 23

de-energises 7 V1H3 0 De-energise on alarm


8 - »E« Register entry
switch
point e.g. 10% r u a
falling 11 12 13 9 V1H4 1 Assign to channel 1
21 22 23
V1H0 10 - »E« Register entry
Fig. 4.15:
Limit value relay: example for minimum fail-safe
mode

Example:
switch
# Matrix Entry Remarks max. fail-safe mode,
point
V1H5 1 V1H5 e.g. 90 Switch point relay 2a, 2b
relay
de-energises
2 - »E« Register entry switch point 90%
e.g. 90%
hysteresis 40%
3 V1H6 1 Max. fail-safe mode
hysteresis.

r u a
relay follows analogue
e.g. 40%

rising 31 32 33
4 - »E« Register entry
V1H7

41 42 43
output
5 V1H7 e.g. 40 Hysteresis —— assigned to channel 1
energises
relay energises at 50
e.g. 50% 6 - »E« Register entry
r u a
falling 31 32 33
41 42 43
7 V1H8 1 Follow outputs
8 - »E« Register entry
BA142_42

9 V1H9 1 Assign to channel 2


10 - »E« Register entry
Fig. 4.16:
Limit value relay: example for maximum fail-safe
mode

Note!
• The switch point and hysteresis are always entered in the units of calibration or
linearisation Note!

• A small hysteresis prevents faulty switching due to turbulence


• A large hysteresis allows two-point control of a pump with one relay
• For two pairs of relays on channel 1, the hystereses can set such that one pair of
relays de-energises just as the other energises.

Endress+Hauser 33
Chapter 4: Level Measurement Prolevel FMC 661

4.5 Measured value display


The measured value can be read at V0H0. In addition to this, several other fields contain
system information which might be needed, e.g., for trouble-shooting etc.. Table 4.3
summarises the displays.

Table 4.3: Channel 1 Measured value Remarks


Matrix positions of measured
value displays V0H0 Level or volume Display in %, m, ft, hl, m3, ft3, t etc. according to
calibration and/or linearisation.
The entries for the 0/4 mA and 20 mA value at V0H5
and V0H6 control the 10-step LCD bar diagram.
V0H8 Current measuring Displays the frequency which is actually measured
frequency channel 1 by the probe. Can be used as a fault check (must
change as level changes)
V0H9 Measured value before Indicates level before linearisation in the units used
linearisation for calibration
V8H7 Factor for calibration For operating mode 5, displays correction factor
correction used in calibration.
Can also be used to enter a density factor when
used with a Deltapilot S
V8H8 Current measuring Displays measuring frequency for Channel 2 when
frequency channel 2 operating modes 0, 2 and 5 are selected.
V9H0 Current error code Error code of fault with highest priority appears on
fault condition, alarm LED lights or blinks
V9H1 Last error code The previous error can be read and deleted here -
press »E« to delete
V9H3 Software version with The first two figures indicate the instrument, the last,
instrument code the software version; 33 = Version 3.3
V9H4 Rackbus address Indicates RS-485 address set at DIP-switches

4.6 Parameter locking


When all parameter entries have been made, the matrix can be locked by entering any
code number less that 670 or greater than 679 in V8H9.

Step Matrix Entry Remarks


1 V8H9 e.g. 888 Enter any code from 000 - 669 or from 680 - 999
2 - »E« Register entry

After locking, all entries can be displayed but not changed.


• The lock is released when a number between 670 and 679 is entered at V8H9.

Note your parameters! The instrument is now configured. Note your parameters in the table at the back of the
manual - if you have to replace the transmitter, these can be simply entered in the
replacement Prolevel FMC 661. For level probes on channel 1 there is no need to
recalibrate.

34 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch

5 Level Measurement with Limit Switch


This chapter describes the configuration of the Prolevel FMC 661 operating with an
external limit switch for:
• Level measurement with automatic calibration correction
The external limit switch can also be used for:
• Level measurement on channel 1 with level switching on channel 2
• Level limit switching on channel 2 only
The setting of the analogue output, relays, measured value display and parameter upload
and locking are described in Chapter 4.

Fig. 5.1:
5.1 5.2 Summary: Corrected level
measurement and other
applications with an external limit
Corrected Level
switch
level measurement
measurement + limit switch

Correction by External limit


density factor switch only

4.3 4.4 4.5

V0H0 Measured
Analogue Relays values
output

4.6

Parameter lock

BA142_43

Endress+Hauser 35
Chapter 5: Level Measurement with Limit Switch Prolevel FMC 661

5.1 Level measurement with automatic calibration correction

Fig. 5.2:
Level measurement with capacitance probe
automatic calibration correction: channel 1 Endress+Hauser

for dielectric constant with PROLEVEL


FMC 671 123.4
1A
Endress+Hauser

V H
capacitance probes
PROLEVEL
1B
2A
2B
FMC 671 123.4
3
+ 1A

_ E
1B
2A
2B
V H
+
for density with hydrostatic
3

_ E

sensors
A capacitance probe can be
used instead of the Liquiphant
(applies to Multicap only)

Liquiphant
channel 2
Liquiphant
σ, ε ∆h
channel 2 ρ ∆h

channel 1
0%
0%

hydrostatic sensor

BA142_44

This level measurement mode employs a Liquiphant or capacitance probe on channel


2 to check the validity of the calibration on channel 1. If a descrepancy is found, e.g.
because of a change in dielectric constant for capacitance probes or in density for
hydrostatic sensors, the level display is corrected.

The level calibration is corrected every time the product passes the external limit switch,
i.e. uncovered ⇒ covered or covered ⇒ uncovered.
• If the measured level is less than the installation height of the external limit
switch when this is covered, the value at V8H3 or its volume equivalent is
displayed at V0H0 until the next automatic calibration,
• If the measured level is greater than the installation height of the external limit
switch when this is uncovered, the value at V8H3 or its volume equivalent is
displayed at V0H0 until the next automatic calibration.

Installation hints Install the external limit switch where:


• it is frequently covered and uncovered (increases frequency of correction)
• as near as possible to 100% (ensures greatest accuracy)
- we recommend a height between 70…90%.

Note!
• For Deltapilot S, always use a Liquiphant switch. The use of a capacitance limit
switch causes faulty operation.
Note!
• Product properties may not change during a filling operation, since there is no
means of continuous compensation.
• The external limit switch must operate with all densities (or dielectric constants)
encountered.
• If overspill must be avoided at all costs, a separate system must be installed.
• The automatic correction mode is not recommended for use with bulk solids.

36 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch

The standard method can be used for all probes and sensors: Standard method
• The switching delay (0…30 s) determines the delay between the covering or
uncovering and the switching of the Liquiphant (or capacitance probe).
• The installation height is the height above the 0% level expressed in the same
units (%, m, ft, hl, gal, tonnes etc.) as the subsequent calibration step.
The »full« calibration is carried out automatically when the product reaches the external
limit switch. Since the default display sensitivity is used during this time, the display at
V0H0 may be initially incorrect and analogue signal/relays not function as set.

Calibration in % Sensor calibration


# Matrix Entry Remarks capacitance limit switch
1 V9H5 Reset, enter probe + level sensor
V3H5/V3H6 constants, page 23

2 V8H0 5 Calibration correction


»Full« = 100%
3 - »E« Register entry
e.g. 75%
4 V8H2 e.g. 2 s Switching delay
5 - »E« Register entry
measuring range
height %

6 V8H3 e.g. 75% Installation height


installation

7 - »E« Register entry

8 V8H4 1 Sensor = Capacit.


9 - »E« Register entry
»Empty« = 0%
10 V8H5 0 Sensor uncovered
11 - »E« Register entry

Calibration in hl 12 V8H6 e.g. 1 Switch point in Hz


- »E« Register entry

»Full«, e.g. 2000 hl


»Empty« calibration
# Matrix Entry Remarks
13 V0H1 0 »Empty« level
14 - »E« Register entry
e.g. 1500 hl
measuring range

Note!
height "hl"
installation

• The sensor calibration for Liquiphant


limit switches is described on p. 38 Note!
• If the probe ist covered, V8H5 = 1
• V8H6: if the probe is top-mounted there
»Empty« 0 hl
is an additional delay (Table 5.1, p. 39).

BA142_45

• If appropriate, linearisation, p. 25…27 Next step…


Fig. 5.3:
Parameters for standard calibration, level • If appropriate, level offset, p. 25
measurement with automatic calibration correction • Analogue output and relays, p. 30…33,
— assign relays 2a/2b to channel 1.

Endress+Hauser 37
Chapter 5: Level Measurement with Limit Switch Prolevel FMC 661

Calibration with partially If the following calibration is initially carried out with a hydrostatic pressure sensor using
filled vessel water (ρ = 1.0), density can be measured and read off from V8H7.
• If the product changes, the system can be quickly adapted to the new
product by entering a its density at V8H7. This ensures that the correct level is
measured as the vessel is filled.

Sensor calibration
Liquiphant limit switch + # Matrix Entry Remarks
level probe 1 V9H5 Reset, enter probe V0H1, V8H7
V3H5/V3H6 constants, page 23

2 V8H0 5 Calibration correction


100%
3 - »E« Register entry

4 V8H2 e.g. 2 s Switching delay e.g. 75%


5 - »E« Register entry

measuring range
6 V8H3 e.g. 75% Installation height

installation
7 - »E« Register entry

height
8 V8H4 0 Sensor = Liquiphant
9 - »E« Register entry
»Empty« e.g. 10%

0%
Level calibration
# Matrix Entry Remarks
10 V8H7 1 At »empty« level,
set corr. factor to 1
11 - »E« Register entry

12 V0H1 e.g. 10% »Empty« level V0H2, V8H7


13 - »E« Register entry

14 V8H7 1 At »full« level


»Full« e.g. 90%
set corr. factor to 1
15 - »E« Register entry

16 V0H2 e.g. 90% »Full« level


measuring range

17 - »E« Register entry

Note!
• The best accuracy is attained when the
difference between »full« and »empty« 0%
Note!
levels is as great as possible.
• If the operating mode is temporarily
quit, the Prolevel measures by using BA142_46
the sensitivity V3H2 x V8H3. The
indication remains correct as long as Fig. 5.4:
Parameters for calibration with partially filled vessel
the same product is in the tank.

Next step… • If appropriate, linearisation, p. 25…27


• Analogue output and relays, p. 30…33
— assign relays 2a/2b to channel 1.

38 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch

5.2 External limit switch

Fig. 5.5:
capacitance probe Level measurement and limit
channel 1 switching on separate channels
Endress+Hauser

PROLEVEL
FMC 661 123.4
1A
1B
2A
V H
2B
3
+
_ E

Liquiphant
channel 2
max. fail-safe mode

hydrostatic
sensor

BA142_47

Operating mode 0 (V8H0 = 0) of the Prolevel FMC 661 allows level measurement on Level measurement with
channel 1 and separate level switching on channel 2: level switching

# Matrix Remarks
1 V9H5/V3H5/V3H6 Reset, enter sensor constants

2 V8H0 Select and register operating mode 0 (=0)

3 V0H1…V0H7 Level calibration, analogue output, Chapter 4.

4 V8H2…V8H6 Calibrate limit switch, capacitance p. 37, Liquiphant p 38.

5 V1H0…V1H4, V1H6 Set relays, for limit switch set fail-safe mode only

Operating mode 2 (V8H0 = 2) provides level limit switching on channel 2 only. The limit Level limit switching
switch calibration is as described under "Sensor calibration", capacitance probes p. 37,
Liquiphant, p 38. For a top-mounted capacitance switch there is an additional delay, see
Table 5.1:
• Set the relay fail-safe mode only
• If V1H4 = 2 (channel 2), copy the values in V1H5/V1H7 to V1H0/V1H2.

Product Dielectric Conductivity Switch point Table 5.1:


Switch point deviation as a
constant εr
with ground tube without ground function of product for top
tube mounted capacitance probes and
default value of 1 Hz = 5 pF
Solvents, oil, fuel <3 low ca. 150 mm ca. 500 mm
dry bulk solids <3 low ca. 350 mm
(cable probe)
moist bulk solids >3 medium ca. 150 mm
(cable probe)

Endress+Hauser 39
Chapter 6: Trouble-Shooting Prolevel FMC 661

6 Trouble-Shooting
The Prolevel FMC 661 provides a number of aids for setting up and operating the module
correctly. This Chapter contains the following:
• Fault recognition system
• Error message and trouble-shooting tables
• Simulated operating mode
• Commissioning replacement transmitters and sensors
• Repairs.

Fig. 6.1:
Trouble-shooting and fault
elimination for the 6.1 6.2
Prolevel FMC 661 Fault recognition 0% !! Incorrect
measurement

Table 6.1 Table 6.2 6.3


Error messages Trouble-shooting Simulation

6.4 External limit switch


Maintenance and Level
repair Volume

BA142_48

6.1 Fault recognition

Alarms If the Prolevel FMC 661 transmitter recognizes a fault condition where further
measurement is impossible, i.e. an alarm:
• the red alarm LED lights (LED 3) and the alarm relay trips
• the limit value relays assume respond according to the setting in V1H3/V1H8.
• the code for a diagnostic message is to be found in V9H0.
If several faults occur together, the code for the one with the highest priority is displayed.
The others can be called up by pressing the »+« or »-« key when field V9H0 is selected.

If the cause of the fault is rectified, its code is no longer displayed:


• the code for the last fault rectified is retained in V9H1
• this message can be cleared by pressing the »E« key.
If the power fails, all relays de-energise.

Warnings If the Prolevel FMC 661 transmitter has detected a fault condition where further
measurement is possible, i.e. a warning:
• the red alarm LED flashes but the transmitter functions as normal, however,
depending on the fault the measured value may be incorrect
• the alarm relay remains energised
• the appropriate code is to be found in V9H0.

The codes and error messages are listed in Table 6.1 in the order of their priority.

40 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting

Table 6.1:
Code Type Cause and Remedy Error messages
Prolevel FMC 661
E 101-106 Alarm Fault in instrument electronics
- Call Endress+Hauser Service

E 107 Alarm Battery voltage too low


- Make back-up of entered parameters immediately
- Have battery changed at once by trained personel or ring for service

E 201-202 Alarm Fault in probe on channel 1 (f < 35 Hz; f > 3000 Hz)
- Check probe and electronic insert

E 301-302 Alarm Fault in probe on channel 2 (f < 35 Hz; f > 3000 Hz)
- Check probe and electronic insert

E 400 Alarm Fault in probe on channels 1 + 2


- Check probe, electronic insert and wiring

E 401 Alarm Fault in probe or wiring, channel 1


- Check probe, electronic insert and wiring
- Incorrect operating mode

E 402 Alarm Fault in probe or wiring, channel 2


- Check probe, electronic insert and wiring
- Incorrect operating mode

E 600 Warning PFM transmission internal code check


- can be ignored if it appears only briefly

E 601 Warning PFM transmission internal code check


- can be ignored if it appears only briefly

E 602 Warning Linearisation does not rise monotonously (volume does not increase
with level)
- Check and re-enter correct values, reactivate linearization

E 604 Warning Linearisation has less than two sets of values


- Enter more values, reactivate linearization

E 606 Warning No stored factory linearization (V2H6 = 0)


- Select another linearisation function at V2H0

E 608 Warning Value in V0H5 greater than that in V0H6


- Check input

E 610 Warning Calibration fault, channel 1 (»empty« level > »full« level)
- Repeat calibration

E 613 Warning Instrument in simulation mode, channel 1


- Switch back when finished

E 614 Warning Instrument in simulation mode, channel 2


- Switch back when finished

Endress+Hauser 41
Chapter 6: Trouble-Shooting Prolevel FMC 661

6.2 Incorrect measurements

Trouble-shooting table Table 6.2 summarises the most common operating errors which lead to incorrect
measurement by the Prolevel transmitter.

Table 6.2: Sensor/ Fault Cause and remedy


Trouble shooting table for
channel
incorrect function without error
message Capacitance Measured value wrong • Incorrect calibration? Check measured
Channel 1 value before linearisation, V0H9
- if not correct, check whether full and empty
calibration correct V0H1/V0H2
- If correct, check linearization parameters
- Check operating mode, V8H0
• Change in product
- recalibrate for new product
• Probe damaged, bent or pressed to side of
vessel
- check and remedy
• Condensation in connection compartment
Deltapilot S Measured value wrong • Incorrect calibration? Check measured
Channel 1 value before linearisation, V0H9
- if not correct, check whether full and empty
calibration correct V0H1/V0H2
- If correct, check linearization parameters
- Check operating mode, V8H0
• Change in density of product
- recalibrate
- for Mode 0, 1, 5, enter new density at V8H7
• Sensor damaged
- check and remedy
Capacitance Relays do not trip correctly • Incorrect settings, e.g. configured in wrong
or Deltapilot S units
Channel 1 - Check correct units used for all relay settings
- Check relay assignments, V1H4, V1H9
- Simulate settings in simulation mode - see
Section 6.3, if the relays LEDs switch, check
wiring
Capacitance Does not switch correctly • Incorrect calibration?
Channel 2 - V1H7 ≥ V8H6?
- change in product, build-up on probe
• Build-up on probe
- wire electronic insert for build-up, see
Section 2.4
• Settings wrong
- type of probe, fail-safe function, switching
delay
• Probe damaged, bent or pressed to side of
wall
Liquiphant Does not switch correctly • Build-up on probe
Soliphant - clean regularly
Channel 2 • Settings wrong
- type of probe, fail-safe function, switching
delay
• Probe damaged or bent

42 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting

6.3 Simulated operating mode


This function is intended primarily for checking the correct function of the system:
• Enter 6 at V8H0 to activate the simulation mode for level measurement
• Enter 7 at V8H0 to activate the simulation mode for level switching
• Enter 0 at V8H0 to terminate simulation and resume normal measurements.
When the simulation mode is activated, the alarm relay flashes (Warning E613 or E614).
The following simulations are possible:

Matrix Entry Simulated variable


V9H6 (V8H0 = 7) 0 = switch uncovered External limit switch
100 = switch covered for Liquiphant values reversed
V9H7 (V8H0 = 6) Level Level, current, volume
V9H8 (V8H0 = 6) Volume Volume, current
V9H9 (V8H0 = 6) Current Current

The level simulation mode takes the last measured value as default value in V9H7.

Example:
# Matrix Entry Significance Simulation of volume
1 V8H0 6 Select simulation and current by entry of
V9H7 2 - »E« Register entry level in V9H7
volume, current mA

3 V9H7 e.g. 80% Enter level


4 - »E« Register entry

5 V9H8 **.** Volume for level

6 V9H9 **.** Current for level

7 V8H0 e.g. 1 Measurement mode


8 - »E« Register entry
level units

Example:
# Matrix Entry Significance Simulation of current by
V9H8 1 V8H0 6 Select simulation entry of volume in V9H8
2 - »E« Register entry
current mA

3 V9H8 e.g. 500 Volume = 500 hl

4 V9H9 **.** Current for volume

5 V8H0 e.g. 1 Measurement mode


6 - »E« Register entry

volume units
Example:
BA142_49
# Matrix Entry Significance Simulation of covered
Fig. 6.2: 1 V8H0 7 Select simulation external limit switch
Simulation mode 2 - »E« Register entry

3 V9H6 100 Switch covered

4 V8H0 e.g. 0 Measurement mode


5 - »E« Register entry

Endress+Hauser 43
Chapter 6: Trouble-Shooting Prolevel FMC 661

6.4 Exchanging transmitters and sensors

FMC 661 transmitter If the Prolevel FMC 661 has to be exchanged, the replacement need not be recalibrated.
Simply enter the settings which you have noted in the Table at the back of the manual.
For versions with Rackbus RS-485 interface, the parameters can be downloaded from
the computer.
• Sequences requiring a particular order must be re-entered in that order
• Any linearisation must be manually reactivated by entering the mode in V2H0.

Capacitance probes For level measurement, provided the sensor constants were entered before calibration,
with EC 37 Z/EC 47 Z it is not necessary to recalibrate the instrument when the electronic insert is replaced.
On replacement:
• the zero frequency (or offset) fo and
• sensitivity S
for the range selected (default Range II) must be entered at V3H5 and V3H6 respectively.
Fig. 2.2 shows where the information is to be found on the EC 37 Z and EC 47 Z inserts.
• If a different range is selected, the transmitter must be recalibrated.
• If the constants were not entered a recalibration is necessary.

Procedure
Step Matrix Entry Significance
1 V3H5 e.g. 57.2 Enter zero frequency (offset)
2 - »E« Register entry

3 V3H6 e.g. 0.652 Enter sensitivity


4 - »E« Register entry

EC 17 Z insert If the capacitance probe was used for limit switching on channel 2, a recalibration is
necessary.

Deltapilot S Provided a »dry« calibration was made or the sensor constants were entered before
calibration, it is not necessary to recalibrate the instrument when the electronic insert is
replaced. The measurement can be taken up again as soon as the new constants have
been entered in the matrix.
• If the old sensor constants were not entered, the system must be recalibrated.

The new sensor constants are found in table 2.2., p. 13.


• fo is the zero frequency (or offset)
— the zero frequency may also be read from V0H8 when the probe is
unpressurised. This value gives slightly better accuracy, since it accounts for
the orientation of the probe.
• ∆f is the sensitivity

Liquiphant No recalibration is necessary if the Liquiphant is exchanged.

44 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting

6.5 Repairs
Should the Prolevel FMC 661 transmitter or its sensor need to be repaired by
Endress+Hauser, please send it to your nearest Service Centre with a note containing
the following information:
• An exact description of the application for which it was used.
• The physical and chemical properties of the product measured.
• A short description of the fault.

Caution!
• Special precautions must be observed when sending probes for repair:
Caution!
• Remove all visible traces of product from the probe.
• If the product can impair health, i.e. is corrosive, poisonous, carcinogenic,
radioactive etc., please check that the probe is thoroughly decontaminated.
• If the last traces of dangerous products cannot be removed, e.g. product has
penetrated into fissures or diffused into plastic parts, we kindly ask you not to
send the probe for repair.

Endress+Hauser 45
Chapter 7: Appendix Prolevel FMC 661

7 Appendix

7.1 Calibration and linearisation in volume units


Use the following two procedures if you can calibrate in volume units only but still require
a linearisation.

Linearisation, horizontal The parameters must be entered in the


cylinder order below. Two parameters are entered:
• Tank diameter, D V (V2H8)
• Tank volume, V.

# Matrix Entry Remarks


1 V9H5 670 Reset D (V2H7)
2 - »E« Register entry

3 V3H5 fo Zero frequency


4 - »E« Register entry

5 V3H6 ∆f Sensitivity
6 - »E« Register entry

7 V3H0 1 Volume units V0H1


8 - »E« Register entry 100% = V (V2H8)

9 V2H7 D Tank diameter,


%, m or ft
10 - »E« Register entry
probe or
11 V2H8 V Tank volume*, sensor
hl, gal… covered
12 - »E« Register entry »Empty« vol. E
(0… 40%)
13 V2H0 1 Activate linearisation
14 - »E« Register entry zero point for calibration

15 V0H1 E Tank empty, current


volume in hl, gal…
V0H2
16 - »E« Register entry
»Full« vol. F
17 V0H2 F Tank full, current (60… 100%)
volume in hl, gal…
18 - »E« Register entry

Note!
Note! • D determines the level units at V0H9
• If V =100 is entered, the calibration
must be made in % volume units
zero point for calibration
After linearisation • Volume is displayed at V0H0 BA142_50
• Level is displayed at V0H9
Fig. 7.1:
Parameters for calibration and linearisation in a
Next step… Set analogue output and relays in volume horizontal cylinder
units, see p. 30…33.

46 Endress+Hauser
Prolevel FMC 661 Chapter 7: Appendix

You require a linearisation table, H/V or Linearisation for tanks


V2H0...V2H5 H/G, max. 30 pairs in increasing order with conical outlet
H
• Level H in %, m or ft
8 • Volume V or weight G in customer units.

7 # Matrix Entry Remarks


6 1 V9H5 670 Reset
5
4 2 - »E« Register entry
3
2
1 3 V3H5 fo Zero frequency
V/G 4 - »E« Register entry

V2H3 V2H4 5 V3H6 ∆f Sensitivity


6 - »E« Register entry
V/G1 H1
V/G2… H2… 7 V3H0 1 Volume units
V/G30 H30 8 - »E« Register entry

9 V2H1 0 Manual
V0H1
10 - »E« Register entry

11 V2H2 1 Table no.


12 - »E« Register entry

13 V2H3 V/G1… 30 Volume/weight*


14 - »E« Register entry
probe or sensor
covered 15 V2H4 H1… 30 Level m or ft*
16 - »E« Register entry
»Empty« volume E
(0… 40%) 17 V2H5 »E« Next table no.*
— springs to V2H3

zero point of calibration = *Repeat #13… 17 until all values entered


zero point of linearisation

V0H2
18 V2H0 3 Activate "manual"
19 - »E« Register entry
»Full« volume F
(60… 100%) 20 V0H1 E Tank empty, current
volume in hl, gal…
21 - »E« Register entry

22 V0H2 F Tank full, current


volume in hl, gal…
23 - »E« Register entry

Note!
• First pair ~ 0 % level, in %, m, ft.
Note!
zero point of calibration last pair ~ 100 % level, in %, m, ft.
• On error E602 or E604, correct table.
BA142_51 Re-activate linearisation in V2H0.
Fig. 7.2:
Parameters for calibration and linearisation in a tank • Volume/weight is displayed at V0H0 After linearisation
with conical outlet • Level is displayed at V0H9

Set analogue output and relays in volume Next step…


or weight units, p. 30…33.

Endress+Hauser 47
Prolevel FMC 661 Index

Index

A M
Alarm 31 - 32, 40 Max. fail-safe mode 33
All-weather cover 14 Measured value display 34
Ambient temperature 14 Measuring system 7
Analogue output 13, 30, 31 Mechanical specifications 11
4 mA and 20 mA values 31 Min. fail-safe mode 33
output damping 30 Mounting 14
output on alarm 31
signal range 30
Application 6
O
Operating matrix 19
Operating mode 9, 36, 39
B Operating parameters back cover
Bus address and termination 18 Output characteristics 10 - 11

C P
Calibration Parameter lock 34
»dry« for hydrostatic sensors 28 Post mounting 14
horizontal cylinders 25 Power supply 18
level 24 Probes and sensors 13
level measurement with calibration correction 37 - 38
upright cylinders 24
Certificates 3
Commulog VU 260 Z 18, 19, 21
R
Controls 19 - 22 Rackbus RS-485 15, 18, 22
Relays 9, 15, 32, 40
alarm relay 40
D assignment 32
Deltapilot sensors 44 fail-safe mode 32
Density correction 28 - 29, 38 hysteresis 32
min. and max. fail-safe mode 33
operating modes 32
E relay on alarm 32
Electronic inserts 16 switch point 32
Environment 11 Remote operation 18
Error messages 41 Repairs 45
External limit switch 39

S
G Safety 3
General specifications 10 Sensor cable 16
Sensor constants 12, 23, 44
I Sensors, exchange of 44
Input characteristics 10 Simulated operation 43
Installation 12 - 18
T
K Technical data 10
Keyboard and display 20 Terminal resistance 18
Trouble-shooting 40 - 45

L
Level limit switching 39 W
Level measurement 23 - 34 Warning 4, 40
Level measurement with level switching 39 Wiring
Linearisation 46 - 47 Rackbus RS-485 18
Deletion of value pairs 27 Sensors 16
horizontal cylindrical tanks 25, 46 Transmitter 15
semi-automatic with controlled filling 27
tanks with conical outlet 47
Location 14

48 Endress+Hauser
Prolevel FMC 661 Operating matrix

Operating Matrix

Operating and default parameters


Enter your operating parameters in the matrix below.

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0

V1

V2

V3

V4

V5

V6

V7

V8

V9

Display field

The default parameters are as indicated below.

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 0.0 100.0 0 1 0.0 100.0 1

V1 90.0 1 2.0 0 1 90.0 1 0.1 0 2

V2 0 0 1 0.0 0.0 1 100 100

V3 0 0.0 10.0 0.0 0.0 1.0

V4

V5

V6

V7

V8 1 1 90.0 1 0 1.0 1.0 670

V9 E E 532 0 0.0 0.0 0.0 0.0

Display field

Endress+Hauser
Operating matrix Prolevel FMC 661

Parameter Matrix

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0 Measured Empty Full Select Output Value for Value for Safety Actual Measured
Calibration value calibration calibration current damping 0/4 mA 20 mA alarm measuring value
Channel 1 0=0…20mA (s) 0 = -10% frequency before
1=4…20mA 1=+110% channel 1 linearization
2=Hold

V1 Relay 1 Relay 1 Relay 1 Relay 1 Select Relay 2 Relay 2 Relay 2 Relay 2 Select
Limit value switching fail-safe mode hysteresis at alarm Relay 1 switching fail-safe mode hysteresis at alarm Relay 2
Channel 1 point 0 = min. 0 = de-energise 1 = channel 1 point 0 = min. 0 = de-energise 1 = channel 1
1 = max. 1 = as V0H7 2 = channel 2 1 = max. 1 = as V0H7 2 = channel 2

Linearisation
V2 0=linear
Level input Table No. Input Input Next Diameter Volume
Linearisation 1= hor. cylinder mode Volume/ Level Table No. for for
3=manual
Channel 1 4=clear 3
0=manual (1…30) Weight horizontal horizontal
1=auto. cylinder cylinder

V3 Calibration Offset Sensitivity Zero offset Offset Sensitivity For Service For Service
Extended mode value of device of device only only
Calibration 0=level (zero (0 mA D/A 20 mA D/A
Channel 1 1= volume frequency) calibration) calibration)

V4

V5

V6 .

V7

0 = level/switch
V8 1= level
Switch Sensor Type of Calibration Calibration Factor for Actual Security
Operating 2 = switch delay time position for sensor EC 17 Z EC 17 Z calibration frequency locking
5 = corr. level
mode 6 = sim. FMC
(s) corr. cal. 0=DL 17 Z 0=free Switch point correction measuring < 670 or
7 = sim. FTC 1=EC 17 Z 1=covered 0.1…100 Hz channel 2 > 679

V9 Current Last Instrument Rackbus Reset to Simulation Simulation Simulation Simulation


Service diagnostic diagnostic and address default frequency level volume current
and code code Software values
Simulation E=clear version 670…679

Units Units Display Display


VA Tag. No. Tag No. channel 1 channel 1 channel 1 channel 1
VU 260 Z channel 1 channel 2 before after before after
linearisation linearisation linearisation linearisation
ZA 672
only

Display field

Endress+Hauser
Luxembourg Bolivia Papua-Neuguinea
Europe ❑ Endress+Hauser S.A./N.V. Tritec S.R.L. SBS Electrical Pty Limited
Brussels Cochabamba Port Moresby
Austria Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53 Tel. (0 42) 5 69 93, Fax (0 42) 5 09 81 Tel. 53 25 11 88, Fax 53 25 95 56
❑ Endress+Hauser Ges.m.b.H. Brazil
Netherland Philippines
Wien ❑ Samson Endress+Hauser Ltda.
❑ Endress+Hauser B.V. Brenton Industries Inc.
Tel. (01) 8 80 56-0, Fax (01) 8 80 56-35 Sao Paulo
Naarden Makati Metro Manila
Belarus Tel. (0 35) 6 95 86 11, Fax (0 35) 6 95 88 25 Tel. (0 11) 5 36 34 55, Fax (0 11) 5 36 30 67 Tel. (2) 8 43 06 61-5, Fax (2) 8 17 57 39
Belorgsintez Norway Canada
Minsk Singapore
❑ Endress+Hauser A/S ❑ Endress+Hauser Ltd. ❑ Endress+Hauser (S.E.A.) Pte., Ltd.
Tel. (01 72) 26 31 66, Fax (01 72) 26 31 11 Tranby Burlington, Ontario Singapore
Belgium Tel. (0 32) 85 10 85, Fax (0 32) 85 11 12 Tel. (9 05) 6 81 92 92, Fax (9 05) 6 81 94 44 Tel. 4 68 82 22, Fax 4 66 68 48
❑ Endress+Hauser S.A./N.V. Poland Chile
Brussels South Korea
Endress+Hauser Polska Sp. z o.o. DIN Instrumentos Ltda. ❑ Endress+Hauser (Korea) Co., Ltd.
Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53 Warszawy Santiago Seoul
Bulgaria Tel. (0 22) 7 20 10 90, Fax (0 22) 7 20 10 85 Tel. (02) 2 05 01 00, Fax (02) 2 25 81 39 Tel. (02) 6 58 72 00, Fax (02) 6 59 28 38
INTERTECH-AUTOMATION Portugal Colombia
Sofia Taiwan
Tecnisis - Tecnica de Sistemas Industriais Colsein Ltd. Kingjarl Corporation
Tel. (02) 65 28 09, Fax (02) 65 28 09 Linda-a-Velha Bogota D.C. Taipei R.O.C.
Tel. (01) 4 17 26 37, Fax (01) 4 18 52 78 Tel. (01) 2 36 76 59, Fax (01) 6 10 78 68 Tel. (02) 7 18 39 38, Fax (02) 7 13 41 90
Croatia
❑ Endress+Hauser GmbH+Co. Romania Costa Rica
Zagreb Romconseng SRL EURO-TEC S.A. Thailand
Tel. (01) 6 60 14 18, Fax (01) 6 60 14 18 Bucharest San Jose ❑ Endress+Hauser Ltd.
Tel. (01) 4 10 16 34, Fax (01) 4 10 16 34 Tel. 2 96 15 42, Fax 2 96 15 42 Bangkok
Cyprus Tel. (2) 9 96 78 11-20, Fax (2) 9 96 78 10
I+G Electrical Services Co. Ltd. Russia Ecuador
Nicosia Endress+Hauser Moscow Office Insetec Cia. Ltda. Vietnam
Tel. (02) 48 47 88, Fax (02) 48 46 90 Moscow Quito Tan Viet Bao Co. Ltd.
Tel., Fax: see Endress+Hauser GmbH+Co. Tel. (02) 25 12 42, Fax (02) 46 18 33 Ho Chi Minh City
Czech Republic Instruments International Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27
❑ Endress+Hauser GmbH+Co. Guatemala
Praha Slovak Republic ACISA Automatizacion Y Control Industrial S.A.
Tel. (0 26) 6 78 42 00, Fax (0 26) 6 78 41 79 Transcom Technik s.r.o. Ciudad de Guatemala, C.A.
Bratislava Tel. (02) 34 59 85, Fax (02) 32 74 31 Iran
Denmark Tel. (7) 5 21 31 61, Fax (7) 5 21 31 81 Telephone Technical Services Co. Ltd.
❑ Endress+Hauser A/S Mexico Tehran
Søborg Slovenia ❑ Endress+Hauser I.I. Tel. (0 21) 8 74 67 50, Fax(0 21) 8 73 72 95
Tel. (31) 67 31 22, Fax (31) 67 30 45 Endress+Hauser D.O.O. Mexico City
Ljubljana Tel. (5) 5 68 96 58, Fax (5) 5 68 41 83 Israel
Estonia Tel. (0 61) 1 59 22 17, Fax (0 61) 1 59 22 98 Instrumetrics Industrial Control Ltd.
Elvi-Aqua Paraguay Tel-Aviv
Tartu Spain Incoel S.R.L. Tel. (03) 6 48 02 05, Fax (03) 6 47 19 92
Tel. (7) 42 27 26, Fax (7) 42 27 27 ❑ Endress+Hauser S.A. Asuncion
Barcelona Tel. (0 21) 21 39 89, Fax (0 21) 2 65 83 Jordan
Finland Tel. (93) 4 80 33 66, Fax (93) 4 73 38 39 A.P. Parpas Engineering S.A.
❑ Endress+Hauser Oy Uruguay Amman
Espoo Sweden Circular S.A. Tel. (06) 5 53 92 83, Fax (06) 5 53 92 05
Tel. (90) 8 59 61 55, Fax (90) 8 59 60 55 ❑ Endress+Hauser AB Montevideo
Sollentuna Tel. (02) 92 57 85, Fax (02) 92 91 51 Kingdom of Saudi Arabia
France Tel. (08) 6 26 16 00, Fax (08) 6 26 94 77 Anasia
❑ Endress+Hauser USA Jeddah
Huningue Switzerland ❑ Endress+Hauser Inc. Tel. (02) 6 71 00 14, Fax (02) 6 72 59 29
Tel. 89 69 67 68, Fax 89 69 48 02 ❑ Endress+Hauser AG Greenwood, Indiana
Reinach/BL 1 Tel. (3 17) 5 35-71 38, Fax (3 17) 5 35-14 89 Kuwait
Germany Tel. (0 61) 7 15 62 22, Fax (0 61) 7 11 16 50
❑ Endress+Hauser Meßtechnik GmbH+Co. Kuwait Maritime & Mercantile Co. K.S.C.
Venezuela Safat
Weil am Rhein Turkey H. Z. Instrumentos C.A.
Tel. (0 76 21) 9 75-01, Fax (0 76 21) 9 75-5 55 Tel. 2 43 47 52, Fax 2 44 14 86
Intek Endüstriyel Ölcü ve Kontrol Sistemleri Caracas
Istanbul Tel. (02) 9 79 88 13, Fax (02) 9 79 96 08 Lebanon
Great Britain Tel. (02 12) 2 75 13 55, Fax (02 12) 2 66 27 75
❑ Endress+Hauser Ltd. Nabil Ibrahim
Manchester Jbeil
Ukraine
Tel. (01 61) 2 86 50 00, Fax (01 61) 9 98 18 41 Industria Ukraïna Asia Tel. (3) 25 40 51, Fax (9) 94 40 80
Kiev Sultanate of Oman
Greece Tel. (44) 2 68 52 13, Fax (44) 2 68 52 13 China
I & G Building Services Automation S.A. ❑ Endress+Hauser Shanghai Mustafa & Jawad Sience & Industry Co.
Athens Instrumentation Co. Ltd. L.L.C.
Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14 Shanghai Ruwi
Africa Tel. (0 21) 64 64 67 00, Fax (0 21) 64 74 78 60 Tel. 60 20 09, Fax 60 70 66
Hungary
Mile Ipari-Elektro Egypt ❑ Endress+Hauser Beijing Office United Arab Emirates
Budapest Anasia Beijing Descon Trading EST.
Tel. (01) 2 61 55 35, Fax (01) 2 61 55 35 Heliopolis/Cairo Tel. (0 10) 68 34 40 58, Fax (0 10) 68 34 40 68 Dubai
Tel. (02) 4 17 90 07, Fax (02) 4 17 90 08 Tel. (04) 35 95 22, Fax (04) 35 96 17
Iceland Hong Kong
Vatnshreinsun HF Morocco ❑ Endress+Hauser (H.K.) Ltd. Yemen
Reykjavik Oussama S.A. Hong Kong Yemen Company for Ghee and Soap Industry
Tel. (05) 88 96 16, Fax (05) 88 96 13 Casablanca Tel. 25 28 31 20, Fax 28 65 41 71 Taiz
Tel. (02) 24 13 38, Fax (02) 40 26 57 Tel. (04) 23 06 64, Fax (04) 21 23 38
Ireland India
Flomeaco Company Ltd. Nigeria ❑ Endress+Hauser India Branch Office
Kildare J F Technical Invest. Nig. Ltd. Mumbai
Tel. (0 45) 86 86 15, Fax (0 45) 86 81 82 Lagos Tel. (0 22) 6 04 55 78, Fax (0 22) 6 04 02 11
Australia + New Zealand
Tel. (1) 62 23 45 46, Fax (1) 62 23 45 48
Italy Indonesia Australia
❑ Endress+Hauser Italia S.p.A. South Africa PT Grama Bazita GEC Alsthom LTD.
Cernusco s/N Milano ❑ Endress+Hauser Pty. Ltd. Jakarta Sydney
Tel. (02) 92 10 64 21, Fax (02) 92 10 71 53 Sandton Tel. (21) 7 97 50 83, Fax (21) 7 97 50 89 Tel. (02) 96 45 07 77, Fax (02) 97 43 70 35
Tel. (0 11) 4 44 13 86, Fax (0 11) 4 44 19 77
Jugoslavia Japan New Zealand
Meris d.o.o. Tunisia ❑ Sakura Endress Co., Ltd. EMC Industrial Instrumentation
Beograd Controle, Maintenance et Regulation Tokyo Auckland
Tel. (11) 4 44 29 66, Fax (11) 43 00 43 Tunis Tel. (04 22) 54 06 11, Fax (04 22) 55 02 75 Tel. (09) 4 44 92 29, Fax (09) 4 44 11 45
Tel. (01) 79 30 77, Fax (01) 78 85 95
Latvia Malaysia
Raita Ltd. ❑ Endress+Hauser (M) Sdn. Bhd.
Riga Petaling Jaya, Selangor Darul Ehsan All other countries
Tel. (02) 25 47 95, Fax (02) 7 25 89 33 America Tel. (03) 7 33 48 48, Fax (03) 7 33 88 00
❑ Endress+Hauser GmbH+Co.
Lithuania Argentina Pakistan Instruments International
Agava Ltd. ❑ Endress+Hauser Argentina S.A. Speedy Automation D-Weil am Rhein
Kaunas Buenos Aires Karachi Germany
Tel. (07) 20 24 10, Fax (07) 20 74 14 Tel. (01) 5 23 80 08, Fax (01) 5 22 05 46 Tel. (0 21) 7 72 29 53, Fax (0 21) 7 73 68 84 Tel. (0 76 21) 9 75-02, Fax (0 76 21) 97 53 45

http://www.endress.com

Endress + Hauser
❑ Members of the Endress+Hauser group 12.97/MTM

BA 142F/00/en/07.98a
016562-1000
CCS/CV4.2

You might also like