BA142FEN
BA142FEN
98a
016562-1000
valid for Software 1.x
prolevel
FMC 661
Level Measurement
Operating Instructions
Endress + Hauser
Nothing beats know-how
Short Instructions Prolevel FMC 661
Short Instructions
Operation
Selects vertical matrix position
4 yellow relay LEDs,
1 red alarm LED,
1 green operation LED LC display Selects horizontal matrix position
Registers entry
Table of Contents
Notes on Safety . . . . . . . . . . . . . 3
1 Introduction . . . . . . . . . . . . . . 5
1.1 Application . . . . . . . . . . . . . . . 6
1.2 Measuring system . . . . . . . . . . . . 7
1.3 Measuring principle . . . . . . . . . . . . 8
1.4 Functional description . . . . . . . . . . . 9
1.5 Technical data . . . . . . . . . . . . . 10
2 Installation . . . . . . . . . . . . . . 12
2.1 Probes and sensors . . . . . . . . . . . 13
2.2 Prolevel FMC 661 installation . . . . . . . 14
2.3 Transmitter wiring . . . . . . . . . . . . 15
2.4 Sensor connection . . . . . . . . . . . 16
2.5 Rackbus RS-485 option . . . . . . . . . 18
3 Controls . . . . . . . . . . . . . . . 19
3.1 Operating matrix . . . . . . . . . . . . 19
3.2 Keyboard and display . . . . . . . . . . 20
3.3 Commulog VU 260 Z . . . . . . . . . . 21
3.4 Rackbus RS-485 (option) . . . . . . . . 22
4 Level Measurement . . . . . . . . . . 23
4.1 Commissioning . . . . . . . . . . . . 23
4.2 Calibration . . . . . . . . . . . . . . 24
4.3 Analogue Outputs . . . . . . . . . . . 30
4.4 Relays . . . . . . . . . . . . . . . . 32
4.5 Measured value display . . . . . . . . . 34
4.6 Parameter locking . . . . . . . . . . . 34
6 Trouble-Shooting . . . . . . . . . . . 40
6.1 Fault recognition . . . . . . . . . . . . 40
6.2 Incorrect measurements . . . . . . . . . 42
6.3 Simulated operating mode . . . . . . . . 43
6.4 Exchanging transmitters and sensors . . . . 44
6.5 Repairs . . . . . . . . . . . . . . . . 45
7 Appendix . . . . . . . . . . . . . . . 46
7.1 Calibration and linearisation in volume units . 46
Index . . . . . . . . . . . . . . . . 48
Endress+Hauser 1
Table of Contents Prolevel FMC 661
2 Endress+Hauser
Prolevel FMC 661 Notes on Safety
Notes on Safety
The Prolevel FMC 661 is a field transmitter for level measurement which can be used Approved usage
with a variety of capacitance probes and hydrostatic sensors. It has been designed to
operate safely in accordance with current technical and safety standards, and must be
installed by qualified personnel according to the instructions in this manual.
The manufacturer accepts no responsibility for any damage arising from incorrect use,
installation or operation of the equipment. Changes or modifications to the equipment
not expressly approved in the operating manual or by the bodies reponsible for
compliance may void the user’s authority to operate the equipment.
The Prolevel FMC 661 transmitter is available with certificate of conformity for use with Certificates
probes and sensors operating in hazardous areas. The Table below indicates the
combinations available and conditions for installation. Full details can be taken from the
certificates. Please note that where quoted technical data differs from that listed in
Section 1.5, that in the certificate applies.
ZE 104F/00/d
for Germany
ZE 103F/00/d, e, f
for foreign countries
Endress+Hauser 3
Notes on Safety Prolevel FMC 661
Safety conventions
In order to highlight safety-relevant or alternate operation procedures in the manual the
following conventions have been used, each indicated by a corresponding icon in the
margin.
Note!
• A note highlights actions or procedures which, if not performed correctly, may
indirectly affect operation or may lead to an instrument response which is not
Note!
planned.
Caution!
• Caution indicates actions or procedures which, if not performed correctly, may lead
Caution! to personal injury or incorrect functioning of the instrument
Warning!
• A warning indicates actions or procedures which, if not performed correctly, will lead
Warning!
to personal injury, a safety hazard or destruction of the instrument
4 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction
1 Introduction
The Prolevel FMC 661 field transmitter measures level with hydrostatic pressure sensors
or capacitance probes. It may be installed, commissioned and maintained by authorised
personnel only. The operating manual must have been read and understood before the
equipment is installed: instructions are to be followed exactly.
Since it is not possible to describe all applications in detail, the standard application, In this manual
continuous level measurement, has been used as the basis for the functional description.
Other applications as listed in Section 1.1 are described in Chapter 5. The operating
instructions are structured as follows:
• Chapter 1: Introduction;
contains general information including application, measurement
principle, functional description and technical data.
• Chapter 2: Installation;
contains hardware configuration, installation instructions and
connection diagrams.
• Chapter 3: Controls;
describes operation with the front panel keys, Commulog VU 260 Z,
and via the Rackbus RS-485 interface.
• Chapter 4: Calibration and Operation;
tells you how to commission the Prolevel for the standard
application including calibration, linearisation, analogue outputs,
relays and locking the parameter matrix.
• Chapter 5: Level Measurement with Limit Switch;
describes the automatic calibration correction and other operating
modes of the Prolevel FMC 661.
• Chapter 6: Trouble-Shooting;
contains a description of the self-checking system with error
messages, the simulation feature as well as instructions for
configuration on replacement of the transmitter, probe or
electronic insert.
• Appendix: Contains a flowchart for calibration and linearisation using
volume units.
• Index: lists key words to help you find information quickly.
Short instructions for the standard set-up, continuous level measurement, which is used Short instructions
in 80% of applications, are to be found in the front cover. We advise you to commission
as described in Section 4.1. before using this procedure as this ensures that probes can
be exchanged without the need for re-calibration.
In addition to this manual, the following publications provide information on configuration Further documentation
of the Prolevel FMC 661.
• BA 028F Commulog VU 260 Z handheld terminal
• BA 134F Rackbus RS-485
The installation of the probes, electronic inserts and accessories is described in the
documentation accompanying these articles - see text for references. When installing
probes in explosion hazardous areas the instructions included in the accompanying
probe certification must also be observed.
Endress+Hauser 5
Chapter 1: Introduction Prolevel FMC 661
1.1 Application
Fig. 1.1:
Standard application showing hazardous area safe area
Prolevel FMC 661 controlling alarm
level measurement relay
➀ Capacitance probe Channel 1 0/4...20 mA
limit relays
➁ Hydrostatic probe 1
Bulk solids
Endress+Hauser
1 or
PROLEVEL
FMC 661 123.4
1A
1B
2A
V H
2B
3
+
_ E
Liquids
Channel 1
2
or
BA142_01
The Prolevel FMC 661 is designed for level measurement with a capacitance probe or
hydrostatic pressure sensor. A second channel allows level limit detection with a vibration
sensor, i.e. Liquiphant or Soliphant, or capacitance probe. The applications described
in this manual are as follows:
• Level or volume measurement …Chapter 4
• Level limit detection …Chapter 5
• Level measurement with automatic calibration correction …Chapter 5.
Prolevel transmitters may also be used for applications in explosion hazardous areas
and possess intrinsically-safe sensor circuits conforming to EEx ia IIC. A list of certificated
combinations is to be found in »Notes on Safety« preceding this chapter.
Fig. 1.2:
Left: hazardous area safe area hazardous area safe area
Prolevel FMC 661 with
Liquiphant limit switch channel 1 level
FMC 661 FMC 661
➀ Maximum fail-safe mode 1 1
➁ Minumum fail-safe mode Endress+Hauser
PROLEVEL
FMC 661 123.4
Endress+Hauser
Max 1A
V H
PROLEVEL
123.4
3
1B FMC 661
2A
2B 1A
3
+ 1B V H
_ E
2A
2B
3
+
_
Right: E
BA142_02 BA142_03
6 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction
Fig. 1.3:
The Prolevel FMC 661 can be
used as a stand-alone unit, see
Personal computer with Figs 1.1 and 1.2 or as part of
operating software, e.g. an operating system.
Commutool, Commuwin, A RS-485 adapter or PC card
Commugraph allows direct connection to a
personal computer, the FXA 675
and gateway ZA 67x connection
to a supervisory system using
the Modbus, Profibus or FIP
protocol
Prolevel transmitters (and other units with Rackbus RS-485)
supervisory network
RS-485 adapter or PC card
Endress+Hauser Endress+Hauser Endress+Hauser
ZA 673
FXA 675
PROLEVEL
FMC 671 123.4 PROLEVEL
FMC 671
PROLEVEL
FMC 671
ON
1A 1A 1A
1B
2A
V H 1B
2A
1B
2A
2B 2B 2B
3
+ 3 3
_ E
1 RB/485
RACKBUS
2 PROFIBUS
The Prolevel may operate as a stand alone unit with standard 0/4…20 mA output; two
sets of two relays, freely assignable to channel 1 or 2, can be used to control pumps,
valves, annuciators etc.. Alternatively, the Prolevel may be operated remotely over the
optional Rackbus RS-485 interface, either direct from a personal computer or as part of
a process control system. Connection to Modbus, Profibus or FIP networks can be
realised through the gateways ZA 672, ZA 673 or ZA 674 respectively.
Endress+Hauser 7
Chapter 1: Introduction Prolevel FMC 661
2πε0εr x L pF (1)
Ctot = C1 + -------------
L d
ln (D/d)
whereby
Ctot = total capacitance
C1= capacitance of feed through
ε0= dielectric constant of air (8.85)
εr= rel. dielectric constant of product BA142_05
Fig. 1.5:
Measurement in conducting media
8 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction
Fig. 1.7:
Signal processing in the
frequency level volume
Prolevel FMC 661 for single
channel operation (level
zero point shift and/or limit switching)
Channel 1
Channel 2
switch point
hysteresis
min. / max. fail-safe mode
switching delay
BA142_08
Fig. 1.7 is a block diagram of the Prolevel FMC 661. The transmitter supplies the power
to the sensor. The capacitance or pressure measured by the sensor is converted into a
frequency signal by the electronic insert located in its head and transmitted to the Prolevel
over a two-core cable. The signal is then processed to provide six operating modes.
All measured values and the complete configuration can be accessed via the optional
Rackbus RS-485 interface.
If a fault condition is detected, e.g. a break in sensor - transmitter cable, the analogue Fail-safe operation
signal switches to -10 % or +110 % level or holds the last measured value. The alarm
relay de-energises and the red LED on the front panel lights. In addition, each set of
relays can be set to switch on or off as required.
Endress+Hauser 9
Chapter 1: Introduction Prolevel FMC 661
Analog output
Output: 0... 20 mA, switchable to 4... 20 mA
Signal underflow: -2 mA;
Signal overflow: + 22 ± 0.2 mA
Output on alarm: selectable +110%, -10% or hold
Current limitation: 23 mA
Temperature 0.3%/10 K of range end value
coefficient:
RFI (E = 10 V/m) 1%
Warm-up time: 1s
Output damping: 0 to 100 s, selectable
Max. load: 600 Ω
Load effect: negligible
Relays
Type: 5 relays with potential-free changeover contacts
Function: 2 pairs of two limit relays with freely selectable switch points and
hysteresis for operation in min. or max. fail-safe mode
1 alarm relay (de-energises on fault condition)
Switching capacity: 6 A, 250 VAC ; 750 VA at cos ϕ = 0.7, 1500 VA at cos ϕ = 1
6 A, 250 VDC; 200 W
10 Endress+Hauser
Prolevel FMC 661 Chapter 1: Introduction
Communication interface
Commulog VU 260 Z: 2 communication sockets in terminal compartment
Rackbus RS 485 optional interface for direct connection to a personal computer via
adapter or interface card, or to Rackbus via FXA 675 interface card
Rackbus address via 6-gang DIP-switch in terminal compartment
bus termination via 4-gang switch in terminal compartment
Power supply
Electrical connection
Cable entries: 5 pre-stamped cable entries Pg 16 each in bottom and rear of terminal
compartment
4 pre-stamped cable entries Pg 13.5 in bottom
Endress+Hauser 11
Chapter 2: Installation Prolevel FMC 661
2 Installation
This Chapter describes:
• Probes and sensors for the Prolevel FMC 661
• Installation of the Prolevel FMC 661
• Transmitter wiring
• Sensor connection.
• Hardware configuration for Rackbus RS-485 option.
Fig 2.1 shows the structure of the chapter.
Technicians and fitters It is assumed that suitably qualified personnel are to be used for the installation and
electrical connection of the system components. This is particularly important when the
sensors are to be installed in hazardous areas. Please note the following:
Warning!
• The Prolevel FMC 661 transmitter must be installed outside explosion hazardous
areas.
Warning!
• Observe the specifications in the certificates as well as local regulations when
mounting the sensors in hazardous areas
Fig. 2.1:
Structure of Chapter 2,
Installation 2.1 2.2 2.3
2.4 2.5
BA142_09
12 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation
Soliphant
DM 90 Z…92 Z TI 124F
BA042
Deltapilot S hydrostatic pressure sensors and EC 37 Z/47 Z inserts are supplied with the Sensor constants
sensor constants zero frequency »fo« and sensitivity »∆f« or »S«, see Fig. 2.2. For
Deltapilot S sensors the constants depend on the measuring range, see Table 2.2. Note
these constants and enter them into fields V3H5 and V3H6 during commissioning,
Section 4.1. This dispenses with the need for a recalibration of the transmitter on
replacement of the sensor or insert.
Fig. 2.2:
CA (pF) C(S)(pF) Location of sensor constants on
EC 37 Z/47 Z electronic insert
17 18 FMC 480 Z
and Deltapilot S DB 4x housing
d4 d2 FMC 470 Z
d4 / z4 d2 / z2 FMC 671 / 672 / 676 / 677 Z
7 8 HAA 420 Z
1 2 3 4 5 6
+ I
II
Ex I II
1 MHz
fo 475,3 57,2
sensor constants
S 6,805 0,652
EC10015EP 8
EC 47 Z
BA142_10
Endress+Hauser 13
Chapter 2: Installation Prolevel FMC 661
Fig. 2.3:
Dimensions in mm of Prolevel 292
106
FMC 661 housing
1" = 25.4 mm min. 52
ø 4.5
253
201
gap
min. 69
275.5
BA142_11
Location Where possible, find a shady, protected spot in which to mount the Prolevel transmitter:
• Nominal operating temperature: 0°C…+60°C
Use a protective hood or provide cooling if the ambient temperature exceeds +60°C. For
temperatures below -20°C insulate the instrument.
Mounting The Prolevel FMC 661, with IP 66 protective housing, can be mounted on a wall or post
outdoors or in the control room. Fig. 2.3 gives details for wall mounting.
• Post mounting:
Material: galvanised steel
(for 2" post Order No. 919 566-0000;
for 1" post: 919 566-1000);
stainless steel 1.4301 (≅ SS 304 H)
(for 2" post Order No. 919 566-0001;
for 1" post: 919 566-1001);
Weight: 1 kg
BA142_12
Fig. 2.4:
Post-mounting with all-weather cover
14 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation
Fig. 2.5:
L+ L-
Terminal assignments for
RS-485 [EEx ia] IIC
L1 N 1a 1b 2a 2b Prolevel FMC 661
B DGND A
-+ -+
ground externally
PE terminal strip
1 2 3 4 5 11 12 13 21 22 23 31 32 33 41 42 43 51 52 53 60 61 62 81 82 91 92
Commulog VU 260Z
bus switches
RxD/TxD-N
RxD/TxD-P
L+
L-
DGND
16...60 VDC
0/4...20 mA
Sensor 1
Sensor 2
RS-485
PE
L1
optional interface
N
relays channel 1
relays channel 2
85...253 VAC
20...55 VAC
level sensor
alarm relay
limit switch
current 1
BA142_13
Warning!
• Make electrical connections with the power supply switched off!
• The PE terminal strip must be grounded externally (contact protection)!
• When wiring up probes and sensors in explosion hazardous areas, observe the Warning!
The terminal strip for cable diameters up to 2.5 mm2 is located in a separate connection Terminal strip
compartment. Fig. 2.5 shows the wiring diagram for the Prolevel FMC 661 (Terminal 3 is
reserved for the internal protective ground):
• Remove the plastic cover from the front of the connection compartment
• Press out the pre-stamped cable entries as required
bottom: 5 x Pg 16, 4 x Pg 13.5; rear: 4 x Pg 16.
The power requirements are printed on the nameplate at the right-hand side of the Power
nameplate, see also Section 1.5, "Technical Data".
• If the specifications on the nameplate do not correspond to those of your
power supply, do not connect up - you may damage the instrument!
• Connect the protective ground to the metallic terminal strip provided at the left
— this ensures safe isolation and contact protection.
• Current output, relay outputs, power connection and sensor input are all
electrically isolated from one another.
Only one non-floating device can be connected to the current output. Analogue outputs
• There is no limit to the number of floating devices, other than that imposed by
considerations of the maximum load of 600 Ω.
For the switching capacity of the relays see the technical data in Section 1.5. Relays
• Relays 1a and 1b are normally assigned to channel 1
• Relays 2a and 2b are normally assigned to channel 2.
The assignment can be changed by software, see Section 4.4.
Endress+Hauser 15
Chapter 2: Installation Prolevel FMC 661
Sensor cable Use commercial 2-core installation cable, max. line resistance 25 Ω/core, for the sensor/
transmitter cable — the Prolevel satisfies the quoted EMC standards with this cable.
Level probes and The Prolevel FMC 661 can be operated with a variety of sensor types, each requiring a
sensors, channel 1 different electronic insert. For Channel 1, continuous level measurement:
• EC 37 Z or EC 47 Z for capacitance and Multicap probes
EB 17 or EB 27 P for Deltapilots S
Level limit switch, The level limit switch may be a vibration probe — Liquiphant (liquids) or Soliphant (solids)
channel 2: — or a capacitance probe, with electronic insert
• EC 16 Z/EC 17 Z for Multicap probes
EC 17 Z for other capacitance probes
• EL 17 Z for Liquiphant probes
EM 17 Z for Soliphant probes
Fig. 2.6:
Connection diagram for Channel 1 Channel 2
81 82 91 92
electronic inserts Insert bridge if
Left: Capacitance/Multicap conductive
EC 37 Z/EC 47 Z build-up on probe
Insert bridge for
Right: Capacitance/Multicap
Range II (standard) Insert bridge
EC 17 Z
Remove for Range I (see instructions)
Ground Ground
connection connection
BA142_14 BA142_15
EC 37 Z and EC 47 Z The electronic inserts EC 37 Z and EC 47 Z have two measuring ranges which can be
selected by inserting a bridge between terminals 4 and 5 of the insert, see Fig 2.6. Full
instructions on selection of the insert are to be found in Publication E 07.80.06/1c.
• Note the zero frequency fo____ and sensitivity S_____on the insert for the
range you have selected.
EC 17 Z The EC 17 Z electronic insert can be used at Channel 2 with capacitance and Multicap
probes for limit level switching. The connection diagram is shown in Fig. 2.6. Technical
information is given in Publication E 11.84.04/1a.
EC 16 Z The EC 16 Z electronic insert is for use on channel 2 with the Multicap probes with active
build-up compensation. Wire it up as described in the Technical Information Sheet
TI 170F delivered with the insert.
16 Endress+Hauser
Prolevel FMC 661 Chapter 2: Installation
BA142_56
Fig. 2.7:
Connection diagram for Deltapilot S with
FEB 17/FEB 17 P electronic insert
BA142_16
Fig. 2.8:
Connection diagram for Liquiphant/Soliphant
electronic inserts EL 17 Z/EM 17 Z
Endress+Hauser 17
Chapter 2: Installation Prolevel FMC 661
Fig. 2.9:
Rackbus RS-485 topologies
showing setting of bus 150Ω
termination resistance A 1
OFF
ON 2
OFF
ON E OFF
ON
Rt
Inset: Rpull 60 61 62 60 61 62 60 61 62
Suggestion for wiring the bus
Master PE
60 61 62
Rt PE
Data A
Data B
B 1
OFF
ON
L1 60 61 62 PE
Rpull Screen
Master 150Ω
OFF Rt
2 ON E OFF
Rt ON
PE
60 61 62 60 61 62
L2 (> L1)
PE
BA142_19/20
Wiring the bus Up to 25 Prolevel FMC 661 transmitters can be connected to the Rackbus RS-485.
Instructions for wiring and grounding the bus are to be found in Operating Instructions
BA 134F which is delivered with Prolevel instruments having the Rackbus RS-485 option.
The Prolevel can be wired as indicated in the inset in Fig. 2.9.
Note!
• Terminal 61 is connected internally to the PE ground terminal strip
• The screening must be grounded and have electrical continuity throughout — read
Note!
BA 134F for grounding instructions
-+ -+
• Set the address at DIP-switch SW1
(Example: 2 + 8 = 10) terminal compartment SW2
Fig. 2.10:
DIP-switches for bus address and termination
18 Endress+Hauser
Prolevel FMC 661 Chapter 3: Controls
3 Controls
This Chapter describes how the Prolevel FMC 661 transmitter is operated. It is divided
into the following sections:
• Operating matrix
• Keyboard and display
• Commulog VU 260 Z handheld terminal
• Rackbus RS-485.
Fig. 3.1:
Prolevel FMC 661 display Prolevel FMC 661
Parameter matrix operation with
Parameter at current matrix Current matrix position function of V and H keys.
position The complete matrix has 10 x 10
fields, although not all are used
Pressed together
Move to V0H0
Fig. 3.2:
Commulog display Commulog VU 260 Z display and
key functions
Parameter
The Tag No. and measurement
Bar chart of Diagnostics key - press units are entered in the VA level
analogue signal to display error which can be accessed by the
message when icon Commulog or via the Rackbus
blinks RS-485 interface only
Endress+Hauser 19
Chapter 3: Controls Prolevel FMC 661
Fig. 3.3:
Matrix position indicator
Front panel of the
Prolevel FMC 661 transmitter Measured value display
Fig. 3.1 shows the LC-display with matrix of the Prolevel FMC 661, Fig. 3.3 its front panel.
Table 3.1 below describes the function of the operating keys.
• Changes are not possible if the matrix has been locked (Section 4.6).
• Non-flashing parameters are either read-only indications or locked entry fields.
Parameter entry
• Select the digit to be changed.
The digit at the extreme left is selected and flashes.
• Move to the next digit by pressing »⇒« again. When the last digit
is reached »⇒« selects the leftmost digit again.
+ • To change the position of the decimal point, press down both
»⇒« and »+«. The decimal point moves 1 space to the right.
• Increases the value of the flashing digit
20 Endress+Hauser
Prolevel FMC 661 Chapter 3: Controls
FMC 671 Z
L+ L- RS-485
L1 N 1a 1b 2a 2b B DGND A
-+ -+
Warning!
power and relay terminals
are live!
Warning! Warning!
Function keys
Matrix selection
terminal compartment keys
BA142_25
The Prolevel FMC 661 without keyboard can be configured with the Commulog VU 260 Z
handheld terminal, Figs 3.2 and 3.4. A full description of Commulog operation is to be
found in Operation Instructions BA 028. Table 3.2 summarizes the key functions.
Warning!
• The power and relay terminals in the terminal compartment are live!. Warning!
Endress+Hauser 21
Chapter 3: Controls Prolevel FMC 661
Fig. 3.5:
Parameter entry in configuration
software V0H2
full calibration
4 x 5 field portion of
matrix scrolled on
7.00 m 7.00
monitor
parameter entry
H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V0
V1
V2
V3
V4
V5
V6
V7
Selection of V8
vertical position
V9
V0… VA
VA
Selection of horizontal
position H0 … H9
BA142_26
Prolevel FMC 661 transmitters with Rackbus RS-485 interface can be configured from a
personal computer using one of the Endress+Hauser operating programs:
• Fieldmanager 485 Version 5.0 and Commugraph 485 if connected to the
computer via a RS-485/RS-232C converter or RS-485 card.
• Commuwin, Commutec operating program, Commutool if connected via the
FXA 675 and gateway ZA 67x.
The operation corresponds to that of the keyboard version. Full details of the programs
can be taken from, e.g. Operating Instructions BA 134F, which is delivered with all
Prolevel transmitters with Rackbus RS-485 interface.
Note!
Note! • The Prolevel appears in all programs with the designation "FMC 671 Z"
22 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
4 Level Measurement
This chapter is concerned with the level measurement functions (operating mode 1 in
V8H0, default) of the Prolevel FMC 661; the principle sections describe:
• Commissioning
• Calibration: — for upright cylindrical tanks
— for horizontal cylindrical tanks
— for tanks with conical outlet
— dry calibration for hydrostatic sensors
• Analogue outputs
• Relays
• Display of measured values
• Locking the parameter matrix.
With the exception of the dry calibration, the configuration procedure is independent of
whether a hydrostatic pressure sensor or capacitance probe is connected to the Prolevel.
4.2
Calibration Calibration
Standard horizontal "Dry"
calibration
conical ρgh calibration
cylinder tank
4.3
Analogue
output
BA142_27
4.1 Commissioning
When programming the Prolevel for the first time, reset the module to the factory based
parameters, see Table in back cover. Then enter the probe constants fo and S (∆f) —
measured at 25°C. This ensures that the EC 37 Z/EC 47 Z electronic insert or Deltapilot
can be replaced without the need for recalibration, see Section 6.4.
3 V3H5 e.g. 475.3 Enter zero frequency fo (offset) of electronic insert or sensor
4 - »E« Register entry
Endress+Hauser 23
Chapter 4: Level Measurement Prolevel FMC 661
4.2 Calibration
This section describes three methods of calibration which require the tank or silo to be
filled and the entry of:
• an »empty« level at V0H1 and
• a »full« level at V0H2.
The fourth method can be used to make a »dry« calibration for hydrostatic sensors. For
horizontal cylinders and tanks with conical outlet, users requiring a volume or weight
measurement can activate the linearisation procedure.
Note!
• Prolevel is not bound to specific level units: during calibration it merely assigns the
Note!
numbers entered to the measured frequencies for »empty« and »full«.
1) Standard calibration
for upright cylinders # Matrix Entry Remarks V0H1
1 V0H1 E Tank empty, current capacitance probe
level in your units
2 - »E« Register entry
Note!
Note! • The calibration can be performed in
Deltapilot
reverse order.
• For bulk solids (capacitance probes!),
the probe measures the depth of
emersion in the product only. Account
V0H2
for any filling mound or outflow
depression by the entered levels.
• Density correction, see p. 29. »Full« level F
(60… 100%)
After calibration If the product level is entered in %:
• % level is displayed at V0H0
• the 0/4…20 mA signal range
corresponds to 0…100% level
• relays 1a and 1b switch at 90% in
maximum fail-safe mode.
Fig. 4.2:
Parameters for standard calibration
24 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
2) Calibration for
# Matrix Entry Remarks horizontal cylinders
V0H1 1 V0H1 E Tank empty, current
100% for entries in % level in %, m, ft
2 - »E« Register entry
»Empty« level E
(0… 40%) After calibration the level can be read off at
V0H0 in %, ft or m.
0% for entries in %
A volume measurement can be made by Linearisation, horizontal
calling the linearisation table for horizontal cylinder
V0H2 cylinders. Two parameters are entered:
100% »Full« level F • Tank diameter, D
(60… 100%)
• Tank volume, V.
D (V2H7)
The linearisation starts at the tank bottom. Offset
Empty If the zero point of the calibration does not
calibration E start at the same point you must now enter
E = 0? a negative offset in the units of calibration.
OFF (V3H4)
Zero point for linearisation
# Matrix Entry Remarks
BA142_29 1. V3H4 –OFF Offset, m or ft
2 - »E« Register entry
Fig. 4.3:
Parameters for calibration and linearisation in a
horizontal cylinder
• Volume is displayed at V0H0 After linearisation
• Level is displayed at V0H9
• Density correction, p. 29.
Note!
• For linearisation volume => level,
see Appendix, p 46.
Note!
Endress+Hauser 25
Chapter 4: Level Measurement Prolevel FMC 661
26 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
0% = start of linearisation
12 V2H5 »E« Next table no.*
— springs to V2H3
Note!
• On error E602 or E604, correct table. Re-activate linearisation in V2H0.
Note!
Set analogue output and relays in volume or weight units, p. 30…33. Next step…
V2H0 = 1, 3
• Enter "0" in V2H0: The linearisation is
de-activated but the table remains
H1 V1
H2 V2 stored
H3 V3
... ... — Enter 1 (horizontal cylinder) or
...
Hn
...
Vn
3 (linearisation table) to re-activate.
Fig. 4.6:
De-activating a linearisation
Endress+Hauser 27
Chapter 4: Level Measurement Prolevel FMC 661
Caution!
• The sensor constants must have been entered as per Section 4.1.
Caution! • Check the calibration during the first filling of the tank! If your calculations are
incorrect the levels measured will be incorrect also!
display sensitivity
mbar/digit, V3H2
For 0.45 m water, display = 0%,
For 10.45 m water, display = 100%
Span (0%…100%) = 10 m
• pzero = 10 x 1.0 x 9.807 x 0.45
= 44.13 mbar offset
V3H1
pspan = 10 x 1.0 x 9.807 x 10.00
sensor zero, f0 f (Hz)
= 980.7 mbar frequency (V3H5)
• Offset = pzero = 44.13 mbar BA142_33
Sensor calibration
# Matrix Entry Remarks
1 V0H2 e.g. 100 Full level (100%) display
2 - »E« Register entry
»Full« e.g. 10.45 m
3 V3H1 e.g. 44.13 Offset in mbar 100 VH
00
Fig. 4.8:
Parameters for dry calibration, display in %
28 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
Calculate the pressure in mbar acting at the sensor for the desired »empty« level and Example: display in hl
the span (»full« - »empty«): display for pzero ≠ 0
pmbar = 10 x ρ (kg/dm3) x g (m/s2) x ∆h (m)
For 0.0 m water, display = 50 hl
For 10.0 m water, display = 2000 hl
Span (50…2000 = 1950) = 10 m
• pzero = 10 x 1.0 x 9.807 x 0.0 = 0.0 mbar
p1950 = pspan = 10 x 1.0 x 9.807 x 10.00 = 980.7 mbar
• Offset = pzero = = 0.0 mbar
Sensitivity = pspan/span = 980.7/1950 = 0.5029 mbar/hl
Sensor calibration
display # Matrix Entry Remarks
»Full« e.g. 10 m 1 V0H2 e.g. 2000 Full level (100%)
2000 VH
00 2 - »E« Register entry
span = 2000 - 50 = 1950
Fig. 4.9:
Parameters for dry calibration, display in hl
Set analogue outputs and relays in the units used for calibration, e.g. hl, see p. 30…33. Next step…
If the product changes after calibration, the measurement can be corrected by entering Density correction for
a density factor at V8H7: hydrostatic sensor
Factor = old factor x new density
old density
The measured value is divided by the factor before display.
Note!
Note!
• For an automatic density correction using an additional external limit switch see
»Calibration Correction« in Chapter 5
Endress+Hauser 29
Chapter 4: Level Measurement Prolevel FMC 661
mA
in normal operation.
Example: 0
0% (V0H5) level % 100% (V0H6)
4… 20 mA # Matrix Entry Remarks
BA142_36
1 V0H3 1 4… 20 mA
2 - »E« Register entry Fig. 4.10:
Selection of analogue signal range, V0H3
Example:
Output damping # Matrix Entry Remarks
0 < t < 100
1 V0H4 20 Damping 20 s
2 - »E« Register entry
30 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
level Example:
# Matrix Entry Remarks 4 mA = 20%,
V0H5 1 V0H5 20 4mA value, 20 % 20 mA = 80%
2 - »E« Register entry
0%
0/4 mA 20 mA 3 V0H6 80 20 mA value, 80%
4 - »E« Register entry
BA142_38
Fig. 4.12:
Value for 4 mA and 20 mA, V0H5 and V0H6 Note!
• Set in calibration/linearisation units
• When V0H3 = 0, V0H5 = 0 mA value Note!
Caution!
• If setting 2 is chosen, the fault recognition system on the 0/4…20 mA signal line is
Caution!
effectively deactivated. Although the transmitter recognises a fault, i.e. the alarm
relay de-energises and the associated LED lights, the signal output to any follow-up
instrumentation appears to indicate a correct measured value.
Endress+Hauser 31
Chapter 4: Level Measurement Prolevel FMC 661
4.4 Relays
Fig. 4.14:
Relay LEDs as a function of relay
status: Limit relays
limit relay: lit, energised 1a, 1b , 2a, 2b
out, de-energised yellow LEDs
alarm relay (default setting):
lit, de-energised
out, energised
r ua r ua r ua
1a 11 12 13 11 12 13 11 12 13
1b 21 22 23 21 22 23 21 22 23
2a 31 32 33 31 32 33 31 32 33
2b 41 42 43 41 42 43 41 42 43
normal operation power failure: de-energised
Alarm relay 3
red LED
r ua r ua r ua
3 51 52 53 51 52 53 51 52 53
normal operation fault power failure: de-energised
BA142_40
Operating modes The Prolevel FMC 661 has five independent relays with potential-free changeover
contacts. Relays 1a, 1b, 2a and 2b are limit relays, relay 3 is an alarm relay which always
de-energises on fault condition. Relays 1a and 1b are set together, as are 2a and 2b.
Five parameters set the limit relays, Table 4.1 summarises their function:
Relay on alarm The limit relays respond to an alarm according to the entry at V1H3/V1H8 (0 =
de-energise, 1 = as Table 4.2). When the relays are assigned to the external limit switch
(see Chapter 5) they always de-energises on alarm.
Table 4.2: Setting at V0H7 Minimum fail-safe mode Maximum fail-safe mode
Relay response on fault
condition when V1H3/V1H8 = 1. 0 = -10% (≤ -2 mA) Relay de-energises Relay energises
1 = +110% (≥ +22 mA) Relay energises Relay de-energises
32 Endress+Hauser
Prolevel FMC 661 Chapter 4: Level Measurement
Example:
BA142_41
11 12 13
21 22 23
Example:
switch
# Matrix Entry Remarks max. fail-safe mode,
point
V1H5 1 V1H5 e.g. 90 Switch point relay 2a, 2b
relay
de-energises
2 - »E« Register entry switch point 90%
e.g. 90%
hysteresis 40%
3 V1H6 1 Max. fail-safe mode
hysteresis.
r u a
relay follows analogue
e.g. 40%
rising 31 32 33
4 - »E« Register entry
V1H7
41 42 43
output
5 V1H7 e.g. 40 Hysteresis —— assigned to channel 1
energises
relay energises at 50
e.g. 50% 6 - »E« Register entry
r u a
falling 31 32 33
41 42 43
7 V1H8 1 Follow outputs
8 - »E« Register entry
BA142_42
Note!
• The switch point and hysteresis are always entered in the units of calibration or
linearisation Note!
Endress+Hauser 33
Chapter 4: Level Measurement Prolevel FMC 661
Note your parameters! The instrument is now configured. Note your parameters in the table at the back of the
manual - if you have to replace the transmitter, these can be simply entered in the
replacement Prolevel FMC 661. For level probes on channel 1 there is no need to
recalibrate.
34 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch
Fig. 5.1:
5.1 5.2 Summary: Corrected level
measurement and other
applications with an external limit
Corrected Level
switch
level measurement
measurement + limit switch
V0H0 Measured
Analogue Relays values
output
4.6
Parameter lock
BA142_43
Endress+Hauser 35
Chapter 5: Level Measurement with Limit Switch Prolevel FMC 661
Fig. 5.2:
Level measurement with capacitance probe
automatic calibration correction: channel 1 Endress+Hauser
V H
capacitance probes
PROLEVEL
1B
2A
2B
FMC 671 123.4
3
+ 1A
_ E
1B
2A
2B
V H
+
for density with hydrostatic
3
_ E
sensors
A capacitance probe can be
used instead of the Liquiphant
(applies to Multicap only)
Liquiphant
channel 2
Liquiphant
σ, ε ∆h
channel 2 ρ ∆h
channel 1
0%
0%
hydrostatic sensor
BA142_44
The level calibration is corrected every time the product passes the external limit switch,
i.e. uncovered ⇒ covered or covered ⇒ uncovered.
• If the measured level is less than the installation height of the external limit
switch when this is covered, the value at V8H3 or its volume equivalent is
displayed at V0H0 until the next automatic calibration,
• If the measured level is greater than the installation height of the external limit
switch when this is uncovered, the value at V8H3 or its volume equivalent is
displayed at V0H0 until the next automatic calibration.
Note!
• For Deltapilot S, always use a Liquiphant switch. The use of a capacitance limit
switch causes faulty operation.
Note!
• Product properties may not change during a filling operation, since there is no
means of continuous compensation.
• The external limit switch must operate with all densities (or dielectric constants)
encountered.
• If overspill must be avoided at all costs, a separate system must be installed.
• The automatic correction mode is not recommended for use with bulk solids.
36 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch
The standard method can be used for all probes and sensors: Standard method
• The switching delay (0…30 s) determines the delay between the covering or
uncovering and the switching of the Liquiphant (or capacitance probe).
• The installation height is the height above the 0% level expressed in the same
units (%, m, ft, hl, gal, tonnes etc.) as the subsequent calibration step.
The »full« calibration is carried out automatically when the product reaches the external
limit switch. Since the default display sensitivity is used during this time, the display at
V0H0 may be initially incorrect and analogue signal/relays not function as set.
Note!
height "hl"
installation
BA142_45
Endress+Hauser 37
Chapter 5: Level Measurement with Limit Switch Prolevel FMC 661
Calibration with partially If the following calibration is initially carried out with a hydrostatic pressure sensor using
filled vessel water (ρ = 1.0), density can be measured and read off from V8H7.
• If the product changes, the system can be quickly adapted to the new
product by entering a its density at V8H7. This ensures that the correct level is
measured as the vessel is filled.
Sensor calibration
Liquiphant limit switch + # Matrix Entry Remarks
level probe 1 V9H5 Reset, enter probe V0H1, V8H7
V3H5/V3H6 constants, page 23
measuring range
6 V8H3 e.g. 75% Installation height
installation
7 - »E« Register entry
height
8 V8H4 0 Sensor = Liquiphant
9 - »E« Register entry
»Empty« e.g. 10%
0%
Level calibration
# Matrix Entry Remarks
10 V8H7 1 At »empty« level,
set corr. factor to 1
11 - »E« Register entry
Note!
• The best accuracy is attained when the
difference between »full« and »empty« 0%
Note!
levels is as great as possible.
• If the operating mode is temporarily
quit, the Prolevel measures by using BA142_46
the sensitivity V3H2 x V8H3. The
indication remains correct as long as Fig. 5.4:
Parameters for calibration with partially filled vessel
the same product is in the tank.
38 Endress+Hauser
Prolevel FMC 661 Chapter 5: Level Measurement with Limit Switch
Fig. 5.5:
capacitance probe Level measurement and limit
channel 1 switching on separate channels
Endress+Hauser
PROLEVEL
FMC 661 123.4
1A
1B
2A
V H
2B
3
+
_ E
Liquiphant
channel 2
max. fail-safe mode
hydrostatic
sensor
BA142_47
Operating mode 0 (V8H0 = 0) of the Prolevel FMC 661 allows level measurement on Level measurement with
channel 1 and separate level switching on channel 2: level switching
# Matrix Remarks
1 V9H5/V3H5/V3H6 Reset, enter sensor constants
5 V1H0…V1H4, V1H6 Set relays, for limit switch set fail-safe mode only
Operating mode 2 (V8H0 = 2) provides level limit switching on channel 2 only. The limit Level limit switching
switch calibration is as described under "Sensor calibration", capacitance probes p. 37,
Liquiphant, p 38. For a top-mounted capacitance switch there is an additional delay, see
Table 5.1:
• Set the relay fail-safe mode only
• If V1H4 = 2 (channel 2), copy the values in V1H5/V1H7 to V1H0/V1H2.
Endress+Hauser 39
Chapter 6: Trouble-Shooting Prolevel FMC 661
6 Trouble-Shooting
The Prolevel FMC 661 provides a number of aids for setting up and operating the module
correctly. This Chapter contains the following:
• Fault recognition system
• Error message and trouble-shooting tables
• Simulated operating mode
• Commissioning replacement transmitters and sensors
• Repairs.
Fig. 6.1:
Trouble-shooting and fault
elimination for the 6.1 6.2
Prolevel FMC 661 Fault recognition 0% !! Incorrect
measurement
BA142_48
Alarms If the Prolevel FMC 661 transmitter recognizes a fault condition where further
measurement is impossible, i.e. an alarm:
• the red alarm LED lights (LED 3) and the alarm relay trips
• the limit value relays assume respond according to the setting in V1H3/V1H8.
• the code for a diagnostic message is to be found in V9H0.
If several faults occur together, the code for the one with the highest priority is displayed.
The others can be called up by pressing the »+« or »-« key when field V9H0 is selected.
Warnings If the Prolevel FMC 661 transmitter has detected a fault condition where further
measurement is possible, i.e. a warning:
• the red alarm LED flashes but the transmitter functions as normal, however,
depending on the fault the measured value may be incorrect
• the alarm relay remains energised
• the appropriate code is to be found in V9H0.
The codes and error messages are listed in Table 6.1 in the order of their priority.
40 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting
Table 6.1:
Code Type Cause and Remedy Error messages
Prolevel FMC 661
E 101-106 Alarm Fault in instrument electronics
- Call Endress+Hauser Service
E 201-202 Alarm Fault in probe on channel 1 (f < 35 Hz; f > 3000 Hz)
- Check probe and electronic insert
E 301-302 Alarm Fault in probe on channel 2 (f < 35 Hz; f > 3000 Hz)
- Check probe and electronic insert
E 602 Warning Linearisation does not rise monotonously (volume does not increase
with level)
- Check and re-enter correct values, reactivate linearization
E 610 Warning Calibration fault, channel 1 (»empty« level > »full« level)
- Repeat calibration
Endress+Hauser 41
Chapter 6: Trouble-Shooting Prolevel FMC 661
Trouble-shooting table Table 6.2 summarises the most common operating errors which lead to incorrect
measurement by the Prolevel transmitter.
42 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting
The level simulation mode takes the last measured value as default value in V9H7.
Example:
# Matrix Entry Significance Simulation of volume
1 V8H0 6 Select simulation and current by entry of
V9H7 2 - »E« Register entry level in V9H7
volume, current mA
Example:
# Matrix Entry Significance Simulation of current by
V9H8 1 V8H0 6 Select simulation entry of volume in V9H8
2 - »E« Register entry
current mA
volume units
Example:
BA142_49
# Matrix Entry Significance Simulation of covered
Fig. 6.2: 1 V8H0 7 Select simulation external limit switch
Simulation mode 2 - »E« Register entry
Endress+Hauser 43
Chapter 6: Trouble-Shooting Prolevel FMC 661
FMC 661 transmitter If the Prolevel FMC 661 has to be exchanged, the replacement need not be recalibrated.
Simply enter the settings which you have noted in the Table at the back of the manual.
For versions with Rackbus RS-485 interface, the parameters can be downloaded from
the computer.
• Sequences requiring a particular order must be re-entered in that order
• Any linearisation must be manually reactivated by entering the mode in V2H0.
Capacitance probes For level measurement, provided the sensor constants were entered before calibration,
with EC 37 Z/EC 47 Z it is not necessary to recalibrate the instrument when the electronic insert is replaced.
On replacement:
• the zero frequency (or offset) fo and
• sensitivity S
for the range selected (default Range II) must be entered at V3H5 and V3H6 respectively.
Fig. 2.2 shows where the information is to be found on the EC 37 Z and EC 47 Z inserts.
• If a different range is selected, the transmitter must be recalibrated.
• If the constants were not entered a recalibration is necessary.
Procedure
Step Matrix Entry Significance
1 V3H5 e.g. 57.2 Enter zero frequency (offset)
2 - »E« Register entry
EC 17 Z insert If the capacitance probe was used for limit switching on channel 2, a recalibration is
necessary.
Deltapilot S Provided a »dry« calibration was made or the sensor constants were entered before
calibration, it is not necessary to recalibrate the instrument when the electronic insert is
replaced. The measurement can be taken up again as soon as the new constants have
been entered in the matrix.
• If the old sensor constants were not entered, the system must be recalibrated.
44 Endress+Hauser
Prolevel FMC 661 Chapter 6: Trouble-Shooting
6.5 Repairs
Should the Prolevel FMC 661 transmitter or its sensor need to be repaired by
Endress+Hauser, please send it to your nearest Service Centre with a note containing
the following information:
• An exact description of the application for which it was used.
• The physical and chemical properties of the product measured.
• A short description of the fault.
Caution!
• Special precautions must be observed when sending probes for repair:
Caution!
• Remove all visible traces of product from the probe.
• If the product can impair health, i.e. is corrosive, poisonous, carcinogenic,
radioactive etc., please check that the probe is thoroughly decontaminated.
• If the last traces of dangerous products cannot be removed, e.g. product has
penetrated into fissures or diffused into plastic parts, we kindly ask you not to
send the probe for repair.
Endress+Hauser 45
Chapter 7: Appendix Prolevel FMC 661
7 Appendix
5 V3H6 ∆f Sensitivity
6 - »E« Register entry
Note!
Note! • D determines the level units at V0H9
• If V =100 is entered, the calibration
must be made in % volume units
zero point for calibration
After linearisation • Volume is displayed at V0H0 BA142_50
• Level is displayed at V0H9
Fig. 7.1:
Parameters for calibration and linearisation in a
Next step… Set analogue output and relays in volume horizontal cylinder
units, see p. 30…33.
46 Endress+Hauser
Prolevel FMC 661 Chapter 7: Appendix
9 V2H1 0 Manual
V0H1
10 - »E« Register entry
V0H2
18 V2H0 3 Activate "manual"
19 - »E« Register entry
»Full« volume F
(60… 100%) 20 V0H1 E Tank empty, current
volume in hl, gal…
21 - »E« Register entry
Note!
• First pair ~ 0 % level, in %, m, ft.
Note!
zero point of calibration last pair ~ 100 % level, in %, m, ft.
• On error E602 or E604, correct table.
BA142_51 Re-activate linearisation in V2H0.
Fig. 7.2:
Parameters for calibration and linearisation in a tank • Volume/weight is displayed at V0H0 After linearisation
with conical outlet • Level is displayed at V0H9
Endress+Hauser 47
Prolevel FMC 661 Index
Index
A M
Alarm 31 - 32, 40 Max. fail-safe mode 33
All-weather cover 14 Measured value display 34
Ambient temperature 14 Measuring system 7
Analogue output 13, 30, 31 Mechanical specifications 11
4 mA and 20 mA values 31 Min. fail-safe mode 33
output damping 30 Mounting 14
output on alarm 31
signal range 30
Application 6
O
Operating matrix 19
Operating mode 9, 36, 39
B Operating parameters back cover
Bus address and termination 18 Output characteristics 10 - 11
C P
Calibration Parameter lock 34
»dry« for hydrostatic sensors 28 Post mounting 14
horizontal cylinders 25 Power supply 18
level 24 Probes and sensors 13
level measurement with calibration correction 37 - 38
upright cylinders 24
Certificates 3
Commulog VU 260 Z 18, 19, 21
R
Controls 19 - 22 Rackbus RS-485 15, 18, 22
Relays 9, 15, 32, 40
alarm relay 40
D assignment 32
Deltapilot sensors 44 fail-safe mode 32
Density correction 28 - 29, 38 hysteresis 32
min. and max. fail-safe mode 33
operating modes 32
E relay on alarm 32
Electronic inserts 16 switch point 32
Environment 11 Remote operation 18
Error messages 41 Repairs 45
External limit switch 39
S
G Safety 3
General specifications 10 Sensor cable 16
Sensor constants 12, 23, 44
I Sensors, exchange of 44
Input characteristics 10 Simulated operation 43
Installation 12 - 18
T
K Technical data 10
Keyboard and display 20 Terminal resistance 18
Trouble-shooting 40 - 45
L
Level limit switching 39 W
Level measurement 23 - 34 Warning 4, 40
Level measurement with level switching 39 Wiring
Linearisation 46 - 47 Rackbus RS-485 18
Deletion of value pairs 27 Sensors 16
horizontal cylindrical tanks 25, 46 Transmitter 15
semi-automatic with controlled filling 27
tanks with conical outlet 47
Location 14
48 Endress+Hauser
Prolevel FMC 661 Operating matrix
Operating Matrix
H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V0
V1
V2
V3
V4
V5
V6
V7
V8
V9
Display field
H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V4
V5
V6
V7
Display field
Endress+Hauser
Operating matrix Prolevel FMC 661
Parameter Matrix
H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
V0 Measured Empty Full Select Output Value for Value for Safety Actual Measured
Calibration value calibration calibration current damping 0/4 mA 20 mA alarm measuring value
Channel 1 0=0…20mA (s) 0 = -10% frequency before
1=4…20mA 1=+110% channel 1 linearization
2=Hold
V1 Relay 1 Relay 1 Relay 1 Relay 1 Select Relay 2 Relay 2 Relay 2 Relay 2 Select
Limit value switching fail-safe mode hysteresis at alarm Relay 1 switching fail-safe mode hysteresis at alarm Relay 2
Channel 1 point 0 = min. 0 = de-energise 1 = channel 1 point 0 = min. 0 = de-energise 1 = channel 1
1 = max. 1 = as V0H7 2 = channel 2 1 = max. 1 = as V0H7 2 = channel 2
Linearisation
V2 0=linear
Level input Table No. Input Input Next Diameter Volume
Linearisation 1= hor. cylinder mode Volume/ Level Table No. for for
3=manual
Channel 1 4=clear 3
0=manual (1…30) Weight horizontal horizontal
1=auto. cylinder cylinder
V3 Calibration Offset Sensitivity Zero offset Offset Sensitivity For Service For Service
Extended mode value of device of device only only
Calibration 0=level (zero (0 mA D/A 20 mA D/A
Channel 1 1= volume frequency) calibration) calibration)
V4
V5
V6 .
V7
0 = level/switch
V8 1= level
Switch Sensor Type of Calibration Calibration Factor for Actual Security
Operating 2 = switch delay time position for sensor EC 17 Z EC 17 Z calibration frequency locking
5 = corr. level
mode 6 = sim. FMC
(s) corr. cal. 0=DL 17 Z 0=free Switch point correction measuring < 670 or
7 = sim. FTC 1=EC 17 Z 1=covered 0.1…100 Hz channel 2 > 679
Display field
Endress+Hauser
Luxembourg Bolivia Papua-Neuguinea
Europe ❑ Endress+Hauser S.A./N.V. Tritec S.R.L. SBS Electrical Pty Limited
Brussels Cochabamba Port Moresby
Austria Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53 Tel. (0 42) 5 69 93, Fax (0 42) 5 09 81 Tel. 53 25 11 88, Fax 53 25 95 56
❑ Endress+Hauser Ges.m.b.H. Brazil
Netherland Philippines
Wien ❑ Samson Endress+Hauser Ltda.
❑ Endress+Hauser B.V. Brenton Industries Inc.
Tel. (01) 8 80 56-0, Fax (01) 8 80 56-35 Sao Paulo
Naarden Makati Metro Manila
Belarus Tel. (0 35) 6 95 86 11, Fax (0 35) 6 95 88 25 Tel. (0 11) 5 36 34 55, Fax (0 11) 5 36 30 67 Tel. (2) 8 43 06 61-5, Fax (2) 8 17 57 39
Belorgsintez Norway Canada
Minsk Singapore
❑ Endress+Hauser A/S ❑ Endress+Hauser Ltd. ❑ Endress+Hauser (S.E.A.) Pte., Ltd.
Tel. (01 72) 26 31 66, Fax (01 72) 26 31 11 Tranby Burlington, Ontario Singapore
Belgium Tel. (0 32) 85 10 85, Fax (0 32) 85 11 12 Tel. (9 05) 6 81 92 92, Fax (9 05) 6 81 94 44 Tel. 4 68 82 22, Fax 4 66 68 48
❑ Endress+Hauser S.A./N.V. Poland Chile
Brussels South Korea
Endress+Hauser Polska Sp. z o.o. DIN Instrumentos Ltda. ❑ Endress+Hauser (Korea) Co., Ltd.
Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53 Warszawy Santiago Seoul
Bulgaria Tel. (0 22) 7 20 10 90, Fax (0 22) 7 20 10 85 Tel. (02) 2 05 01 00, Fax (02) 2 25 81 39 Tel. (02) 6 58 72 00, Fax (02) 6 59 28 38
INTERTECH-AUTOMATION Portugal Colombia
Sofia Taiwan
Tecnisis - Tecnica de Sistemas Industriais Colsein Ltd. Kingjarl Corporation
Tel. (02) 65 28 09, Fax (02) 65 28 09 Linda-a-Velha Bogota D.C. Taipei R.O.C.
Tel. (01) 4 17 26 37, Fax (01) 4 18 52 78 Tel. (01) 2 36 76 59, Fax (01) 6 10 78 68 Tel. (02) 7 18 39 38, Fax (02) 7 13 41 90
Croatia
❑ Endress+Hauser GmbH+Co. Romania Costa Rica
Zagreb Romconseng SRL EURO-TEC S.A. Thailand
Tel. (01) 6 60 14 18, Fax (01) 6 60 14 18 Bucharest San Jose ❑ Endress+Hauser Ltd.
Tel. (01) 4 10 16 34, Fax (01) 4 10 16 34 Tel. 2 96 15 42, Fax 2 96 15 42 Bangkok
Cyprus Tel. (2) 9 96 78 11-20, Fax (2) 9 96 78 10
I+G Electrical Services Co. Ltd. Russia Ecuador
Nicosia Endress+Hauser Moscow Office Insetec Cia. Ltda. Vietnam
Tel. (02) 48 47 88, Fax (02) 48 46 90 Moscow Quito Tan Viet Bao Co. Ltd.
Tel., Fax: see Endress+Hauser GmbH+Co. Tel. (02) 25 12 42, Fax (02) 46 18 33 Ho Chi Minh City
Czech Republic Instruments International Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27
❑ Endress+Hauser GmbH+Co. Guatemala
Praha Slovak Republic ACISA Automatizacion Y Control Industrial S.A.
Tel. (0 26) 6 78 42 00, Fax (0 26) 6 78 41 79 Transcom Technik s.r.o. Ciudad de Guatemala, C.A.
Bratislava Tel. (02) 34 59 85, Fax (02) 32 74 31 Iran
Denmark Tel. (7) 5 21 31 61, Fax (7) 5 21 31 81 Telephone Technical Services Co. Ltd.
❑ Endress+Hauser A/S Mexico Tehran
Søborg Slovenia ❑ Endress+Hauser I.I. Tel. (0 21) 8 74 67 50, Fax(0 21) 8 73 72 95
Tel. (31) 67 31 22, Fax (31) 67 30 45 Endress+Hauser D.O.O. Mexico City
Ljubljana Tel. (5) 5 68 96 58, Fax (5) 5 68 41 83 Israel
Estonia Tel. (0 61) 1 59 22 17, Fax (0 61) 1 59 22 98 Instrumetrics Industrial Control Ltd.
Elvi-Aqua Paraguay Tel-Aviv
Tartu Spain Incoel S.R.L. Tel. (03) 6 48 02 05, Fax (03) 6 47 19 92
Tel. (7) 42 27 26, Fax (7) 42 27 27 ❑ Endress+Hauser S.A. Asuncion
Barcelona Tel. (0 21) 21 39 89, Fax (0 21) 2 65 83 Jordan
Finland Tel. (93) 4 80 33 66, Fax (93) 4 73 38 39 A.P. Parpas Engineering S.A.
❑ Endress+Hauser Oy Uruguay Amman
Espoo Sweden Circular S.A. Tel. (06) 5 53 92 83, Fax (06) 5 53 92 05
Tel. (90) 8 59 61 55, Fax (90) 8 59 60 55 ❑ Endress+Hauser AB Montevideo
Sollentuna Tel. (02) 92 57 85, Fax (02) 92 91 51 Kingdom of Saudi Arabia
France Tel. (08) 6 26 16 00, Fax (08) 6 26 94 77 Anasia
❑ Endress+Hauser USA Jeddah
Huningue Switzerland ❑ Endress+Hauser Inc. Tel. (02) 6 71 00 14, Fax (02) 6 72 59 29
Tel. 89 69 67 68, Fax 89 69 48 02 ❑ Endress+Hauser AG Greenwood, Indiana
Reinach/BL 1 Tel. (3 17) 5 35-71 38, Fax (3 17) 5 35-14 89 Kuwait
Germany Tel. (0 61) 7 15 62 22, Fax (0 61) 7 11 16 50
❑ Endress+Hauser Meßtechnik GmbH+Co. Kuwait Maritime & Mercantile Co. K.S.C.
Venezuela Safat
Weil am Rhein Turkey H. Z. Instrumentos C.A.
Tel. (0 76 21) 9 75-01, Fax (0 76 21) 9 75-5 55 Tel. 2 43 47 52, Fax 2 44 14 86
Intek Endüstriyel Ölcü ve Kontrol Sistemleri Caracas
Istanbul Tel. (02) 9 79 88 13, Fax (02) 9 79 96 08 Lebanon
Great Britain Tel. (02 12) 2 75 13 55, Fax (02 12) 2 66 27 75
❑ Endress+Hauser Ltd. Nabil Ibrahim
Manchester Jbeil
Ukraine
Tel. (01 61) 2 86 50 00, Fax (01 61) 9 98 18 41 Industria Ukraïna Asia Tel. (3) 25 40 51, Fax (9) 94 40 80
Kiev Sultanate of Oman
Greece Tel. (44) 2 68 52 13, Fax (44) 2 68 52 13 China
I & G Building Services Automation S.A. ❑ Endress+Hauser Shanghai Mustafa & Jawad Sience & Industry Co.
Athens Instrumentation Co. Ltd. L.L.C.
Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14 Shanghai Ruwi
Africa Tel. (0 21) 64 64 67 00, Fax (0 21) 64 74 78 60 Tel. 60 20 09, Fax 60 70 66
Hungary
Mile Ipari-Elektro Egypt ❑ Endress+Hauser Beijing Office United Arab Emirates
Budapest Anasia Beijing Descon Trading EST.
Tel. (01) 2 61 55 35, Fax (01) 2 61 55 35 Heliopolis/Cairo Tel. (0 10) 68 34 40 58, Fax (0 10) 68 34 40 68 Dubai
Tel. (02) 4 17 90 07, Fax (02) 4 17 90 08 Tel. (04) 35 95 22, Fax (04) 35 96 17
Iceland Hong Kong
Vatnshreinsun HF Morocco ❑ Endress+Hauser (H.K.) Ltd. Yemen
Reykjavik Oussama S.A. Hong Kong Yemen Company for Ghee and Soap Industry
Tel. (05) 88 96 16, Fax (05) 88 96 13 Casablanca Tel. 25 28 31 20, Fax 28 65 41 71 Taiz
Tel. (02) 24 13 38, Fax (02) 40 26 57 Tel. (04) 23 06 64, Fax (04) 21 23 38
Ireland India
Flomeaco Company Ltd. Nigeria ❑ Endress+Hauser India Branch Office
Kildare J F Technical Invest. Nig. Ltd. Mumbai
Tel. (0 45) 86 86 15, Fax (0 45) 86 81 82 Lagos Tel. (0 22) 6 04 55 78, Fax (0 22) 6 04 02 11
Australia + New Zealand
Tel. (1) 62 23 45 46, Fax (1) 62 23 45 48
Italy Indonesia Australia
❑ Endress+Hauser Italia S.p.A. South Africa PT Grama Bazita GEC Alsthom LTD.
Cernusco s/N Milano ❑ Endress+Hauser Pty. Ltd. Jakarta Sydney
Tel. (02) 92 10 64 21, Fax (02) 92 10 71 53 Sandton Tel. (21) 7 97 50 83, Fax (21) 7 97 50 89 Tel. (02) 96 45 07 77, Fax (02) 97 43 70 35
Tel. (0 11) 4 44 13 86, Fax (0 11) 4 44 19 77
Jugoslavia Japan New Zealand
Meris d.o.o. Tunisia ❑ Sakura Endress Co., Ltd. EMC Industrial Instrumentation
Beograd Controle, Maintenance et Regulation Tokyo Auckland
Tel. (11) 4 44 29 66, Fax (11) 43 00 43 Tunis Tel. (04 22) 54 06 11, Fax (04 22) 55 02 75 Tel. (09) 4 44 92 29, Fax (09) 4 44 11 45
Tel. (01) 79 30 77, Fax (01) 78 85 95
Latvia Malaysia
Raita Ltd. ❑ Endress+Hauser (M) Sdn. Bhd.
Riga Petaling Jaya, Selangor Darul Ehsan All other countries
Tel. (02) 25 47 95, Fax (02) 7 25 89 33 America Tel. (03) 7 33 48 48, Fax (03) 7 33 88 00
❑ Endress+Hauser GmbH+Co.
Lithuania Argentina Pakistan Instruments International
Agava Ltd. ❑ Endress+Hauser Argentina S.A. Speedy Automation D-Weil am Rhein
Kaunas Buenos Aires Karachi Germany
Tel. (07) 20 24 10, Fax (07) 20 74 14 Tel. (01) 5 23 80 08, Fax (01) 5 22 05 46 Tel. (0 21) 7 72 29 53, Fax (0 21) 7 73 68 84 Tel. (0 76 21) 9 75-02, Fax (0 76 21) 97 53 45
http://www.endress.com
Endress + Hauser
❑ Members of the Endress+Hauser group 12.97/MTM
BA 142F/00/en/07.98a
016562-1000
CCS/CV4.2