The IC70CX is a multifunction controller for boiler with heat pump with functions for sanitary hot water.
3. IC70CX features
N° OF KEYS
6
RELAY OUTPUT
4
DIGITAL INPUT
1 Config
PROBES
2 (NTC o Ptc) Config
SERIAL OUTPUT
TTL (ModBusRtu protocol)
SUPPLY
230 Vac (± 10%)
110 Vac (± 10%) Opt
DISPLAY
3 digit with decimal point
OTHER
Buzzer Opt
Config. = configurable by parameter
Opt = optional
= standard
4.2 Keys
MEANING
Enable/disable the compressor (press 3 seconds)
Start manual defrost
SET Set point visalization
To read max. stored temperature;
in programming mode it browses the parameter codes or increases the
displayed value;
to enable the anti-legionella cycle.
To read min stored temperature;
in programming mode it browses the parameter codes or decreases the
displayed value.
Switch on/off the controller
7. Parameter programming
NOTE: the new value is stored even if the procedure ends for time out.
7.2 How to change a parameter value in the hidden menu (Pr2 level)
1. Enter the Programming mode by pressing the Set + keys for 3 seconds (“°C” or “°F” LED starts blinking).
2. When a parameter is showed, press Set + for 7 seconds; “Pr2” label is showed followed by first parameter on the
list.
3. Select the parameter to change, then press the “SET” key to display its value.
4. Use or to change its value.
5. Press “SET” to store the new value and move to the following parameter.
NOTE: the new value is stored even if the procedure ends for time out.
Each parameter present in the HIDDEN MENU can be removed or moved into “THE FIRST LEVEL” (user level) by pressing
“SET + ”.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
By pressing key it is possible to switch off (if previously was ON) or switch on (if previously was ON) the instrument.
After a power on is possible to delay the loads regulation setting C01 parameter.
The type of the probes can be selected by C05 parameter:
C05=PTC PTC probes are used
C05=NTC NTC probes are used
For °C visualization it is possible to choose if the temperature has to be showed with decimal point or not:
C07=DE temperatures are showed with decimal point
C07=°F temperatures are showed without decimal point
12.1 Compressor
The compressor is used to maintain the set point temperature (S01 parameter).
It is possible to set a minimum OFF time (parameter C02) to avoid consecutive short cycles of the compressor.
If the regulation probe is faulty, the compressor will run with ON/OFF cycles defined by C03 and C04 parameters.
Heaters can be used to integrate the compressor to produce hot water; to the compressor contribution is possible to add
electrical heaters contribution if the boiler temperature falls below a determined value set by parameter.
It is possible to set an ambient temperature (parameter S08) under witch the heaters, if not previously ON, are switched ON.
It is also possible to switch OFF the compressor if the ambient temperature falls below a determined temperature (parameter
S10).
12.5 Fan
12.7 Defrost
To disable the defrost set parameter d05=0.
Three defrost operation mode are selectable:
d01=EL defrost with electrical heaters (compressor OFF in defrost and dripping time)
d01=in hot gas defrost (compressor On in defrost and OFF during dripping time)
d01=Cr reversing gas cycle defrost
Defrost is done by interval time set by d03 parameter; if d06>0, the defrost is delayed by this time.
The defrost lasts maximum d05 time; when d05 time is elapsed and the defrost is still ongoing, it ends.
If d05=0, the defrost is disabled.
During defrost the high and lower temperature alarm (HA and LA) are disabled; after defrost the alarms detection restart after
20 minutes (time fixed and not modifiable).
After the defrost the dripping time starts and lasts d07 time.
Defrost visualization:
parameter d08 = rt default temperature visualization (parameter C22)
parameter d08= it default temperature when defrost is started
parameter d08= SEt set point visualization
parameter d08= dEF “dEF” label visualization
End defrost:
• Step1: when the end defrost conditions are satisfied, the compressor is switched off
• Step 2: the 4-way valve (defrost relay) is switched off after d11 seconds (counted from Step 1)
• Step 3: after further d11 seconds the controller will return to the heating mode
The counting of time between two defrosts is reset.
15. Parameters
S 17 Sun(0) ÷ SAt(6) -
Day to activate anti legionella cycle nu(7)
C 03
0 ÷ 255 (min.) 1 minute
Compressor ON time if regulation faulty probe
C 17 dEF(0) - FAn(1) -
-
Second relay configuration ALr(2) - AUS(3) -
C 18 OnF(4)- -FAn(1)
dEF(0) HEt(5)-
ALr(2) - AUS(3) - -
Third relay configuration OnF(4) - HEt(5)
C 19 dEF(0) - ALr(1) -
Fourth relay configuration
C 20
Not used
C 21 Not used
C 22 Not used
F 01 C_n(0) - O_n(1) - -
Fan operating mode C_Y(2) - O_Y(3)
F 02 -55.0°C ÷ 50.0°C 1°C / 1°F
Fan stop temperature -67°F ÷ 122°F
F 03 Fan delay after defrost 0 ÷ 255 (min.) 1 minute
F 05 Fan off time with compressor off 0÷15 (min.) 1°C / 1°F
A 01
rE(0) - Ab(1) -
Temperature alarms configuration
A 02 nP(0) - P1(1) - P2(2) -
P3(3) - P4(4) -
Probe selection for temperature alarms
A 03 °C[0.0° ÷ 50.0° o ALL
0,1°C / 1°F
Set point maximum temperature alarm ÷ 150,0°]
°F[0° ÷ 90°
°C[0.0° o ALL
÷ 50.0° o -÷
A 04
302°]
55.0° ÷ ALU] 0,1°C / 1°F
Set point minimum temperature alarm °F[0° ÷ 90° o -67.0°
A 05 [0,1°C ÷÷25,5°C]
ALU] [1°F
Differential for temperature alarm
÷ 45°F]
A 06 Temperature alarm delay 0 ÷ 255 (min.) 1 minute
A 07
n(0) - Y(1)
Compressor and heaters off in case of low temperature alarm
A 08
n(0) - Y(1)
Compressor and heaters off in case of high temperature alarm
A 09 Temperature alarm detection delay at start up 0 ÷ 24H0(144) 10 minutes
A 10
nP(0) - P1(1) - P2(2) -
Probe selection for temperature alarm 2 P3(3) - P4(4)
A 11
[-55.0°C ÷ 150,0°C]
Low temperature alarm 2 set point (absolute temperature) [-67°F ÷ 302°F]
A 12
[-55.0°C ÷ 150,0°C]
High temperature alarm 2 set point (absolute temperature) [-67°F ÷ 302°F]
0,1°C / 1°F
A 16
Compressor and heaters switched off in case of low temperature alarm 2 n(0) - Y(1)
A 17
Compressor and heaters switched off in case of high temperature alarm 2 n(0) - Y(1) -
A 19
Digital input 1 alarm delay 0 ÷ 255 (min.) 1 minute
REGULATION
S01 Set point Regulation set point (S3 S04)
S02 Differential (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point
S03 Minimum Set Point: (- 50°C÷C01/-58°F÷C01): Set the minimum value for set point
S04 Maximum Set Point: (S01÷110°C/ S01÷230°F). Set the maximum value for set point.
S05 Set point resistance for integration to compressor Set point activation of the resistance as integration to the
compressor
S06 Differential resistance for integration to compressor (0,1°C 25,5°C): Differential for resistence regulation as
integration to the compressor
S07 Resistance activation delay: delay to switch on the resistence
S08 Set point resistance on evaporator probe: Set point for resistance activation
S09 Differential resistance on evaporator probe: Differential for resistance regulation
S10 Set point to switch off compressor on evaporator probe: Set point to switch off the compressor if evaporator
temperature falls below a determined temperature
S11 Differential to switch on compressor on evaporator probe: Differential of compressor de-activation
S12 Set point for anti legionella cycle: Set point of the anti legionella cycle
S13 Time to reach anti legionella set point: maximum time to reach the anti-legionella set point
S14 Anti legionella cycle at start-up; this parameter allow to enable the anti legionella cycle at the power on
S15 Antilegionella start time; hour of anti legionella cycle activation
S16 Antilegionella duration; the anti legionella temperature has to be maintained for this time;
S17 Day to activate anti legionella cycle; day of anti legionella cycle activation
COMPRESSOR
C01 Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the instrument and
inhibits any output activation for the period of time set in the parameter.
C02 Anti-short cycle delay: (0÷50 min) minimum interval between compressor stop and following restart.
C03 Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case of faulty
thermostat probe. With CO3=0 compressor is always OFF.
C04 Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is OFF in case of faulty
thermostat probe. With CO4=0 compressor is always active.
CONFIGURATION
C05 Type of probe: (Ptc = probe PTC; ntc= probe NTC).
C06 Temperature measurement unit: °C = Celsius; °F = Fahrenheit.
When the measurement unit is changed, temperature set point and hysteresis have to be checked and modified if
necessary.
C07 Resolution (only for °C): (in = 1°C; dE = 0.1 °C) allows decimal point displaying.
C08 Evaporator probe presence (P2): (n = Not present: defrost stops by time; y = present: defrost stops by temperature).
C09 Pb3 probe presence
C10 Pb4 probe presence
C11 Pb1 Thermostat probe calibration: (-12.012.0°C) allows to adjust reading value of thermostat probe
C12 Pb2 Evaporator probe calibration (P2): (-12.012.0°C) allows to adjust reading value of evaporator probe
18. Connections
TTL / Hotkey: TTL seral port to connect an Hotkey (for parameter programming) or to connect a Personal Computer for
parameters programming using Wizmate software