ANSI - ASHRAE - IESNA Standard 90.1-1999 With 90.1-2001 Highlights (PDFDrive)
ANSI - ASHRAE - IESNA Standard 90.1-1999 With 90.1-2001 Highlights (PDFDrive)
1-1999
with 90.1-2001 Highlights
1
Why is Standard 90.1 -1999 important?
90.1-1999
2
How is it different?
3
How is it different?
5
How have requirements changed?
6
How can I find out more about the differences?
7
How can I get a copy?
• Standard 90.1-1999
and the Standard 90.1-
1999 Users Manual are
available from ASHRAE
404-636-8400
www.ashrae.org
8
Section Organization
•Section 1 – Purpose
•Section 2 - Scope
•Section 3 - Definitions, Abbreviations, and Acronyms
•Section 4 - Administration and Enforcement
•Section 5 - Building Envelope
•Section 6 - Heating, Ventilating, and Air-Conditioning
•Section 7 - Service Water Heating
•Section 8 - Power
10
Standard 90.1 -1999
90.1-1999
•Section 9 - Lighting
•Section 10 - Other Equipment
•Section 11 - Energy Cost Budget Method
•Section 12 - Normative References
•Appendices A-D - Mostly envelope related
•Appendix E - Informative References
•Appendix F – Addenda Description Information
11
Section 1 - Purpose
The purpose of this standard
is to provide minimum
requirements for the energy-
efficient design of buildings
except low-rise residential
buildings
12
Section 2 - Scope
13
Section 2 – Scope (cont’d)
(cont’d)
• Envelope
• if heated by a heating system with an output capacity
$3.4 btu/h-ft2 or
• if cooled by a cooling system with a sensible output $5
btu/h-ft2
• Virtually all mechanical and lighting systems are
covered
14
Scope Exceptions
15
Section 3 - Definitions, Abbreviations, and
Acronyms
• 10.5 pages of definitions
• 1 page of abbreviations and acronyms
• Defined terms are italicized in text of standard
16
Section 4 – Administration and Enforcement
17
Section 4 – Administration and Enforcement
18
Building System Compliance Options
Prescriptive
Option
Envelope
Mandatory
Provisions Trade Off
Energy Code
Lighting (required for all Option Compliance
compliance options)
Mechanical
Energy Cost
Budget
HVAC
SWH
19
Envelope Compliance
Building System Compliance Options
Prescriptive
Option
Envelope
Mandatory
Provisions Trade Off
Energy Code
Lighting (required for all Option Compliance
compliance options)
Mechanical
Energy Cost
Budget
HVAC
SWH
20
Section 5 – Building Envelope
21
Section 5 – Building Envelope (cont’d)
(cont’d)
22
Scope
• Envelope components that enclose
• Conditioned space
• Semi-heated space
• Has a heating system with a capacity > 3.4 Btu/h.ft2 (10 W/m2)
of floor area but is not conditioned space
• Requirements apply to three types of spaces
• Nonresidential
• Residential
• Semi-heated
• Exceptions
Section 5.1.1
23
Semi-heated Space
Semi-heated
• Has a heating system with a capacity > 3.4
Btu/h.ft2 (10W/m2) of floor area but is not
conditioned space
Section 5.1.1
24
Climate
Section 5.1.3
25
Space -Conditioning Categories and Basis
Space-Conditioning
Envelope
Envelope Requirements
Requirements Are
Are Specified
Specified by
by Space-Conditioning
Space-Conditioning Categories
Categories
Section 5.1.4
26
Mandatory Provisions
• Insulation (Section 5.2.1) (Section 5.5.1)
• Installation 5.2.1.1 and 5.2.1.2 (Section 5.5.1.1)
• Substantial Contact (Section 5.5.1.2)
• Recessed equipment 5.2.1.3 (Section 5.5.1.3)
• Location of roof insulation (Section 5.5.1.4) and
insulation protection (Section 5.5.1.5).
Section 5.5.1.1
28
Mandatory
Mandatory Provisions
Provisions
Insulation - Substantial Contact
• Install insulation in a permanent manner in
substantial contact with inside surface
• Flexible batt insulation in floor cavities
• To be supported in a permanent manner by supports
no more than 24 in. o.c.
Section 5.5.1.2
29
Mandatory
Mandatory Provisions
Provisions
Recessed Equipment
Section 5.5.1.3
30
Mandatory
Mandatory Provisions
Provisions
Roof Insulation
• Roof Insulation
• Not installed on a suspended
ceiling with removable ceiling
panels
Section 5.5.1.4
31
Mandatory
Mandatory Provisions
Provisions
Insulation Protection
• Insulation Protection
• Cover exterior insulation with protective material
• Sunlight
• Moisture
• Landscaping operations
• Equipment maintenance
• Wind
• Access to attics and mechanical rooms without
damaging or compressing insulation
• Insulation materials in ground contact to have a water
absorption rate # 0.3% (ASTM C272)
Section 5.5.1.5
32
Mandatory
Mandatory Provisions
Provisions
Fenestration and Doors
• U-factors
• NFRC 100 or
• Assemblies listed in Appendix A
• SHGC
• NFRC 200 or
• Assemblies listed in Appendix A
• Visible Light Transmittance
• NFRC 200 when building
envelope trade-off option is
used
Section 5.5.2
33
U-Factor
U-Factor
34
Solar Heat Gain Coefficient (SHGC)
(SHGC)
• Exceptions
• SC x 0.86 is acceptable for overall fenestration area
(NFRC 300)
• SHGC of center of glass is acceptable (NFRC 300) for
overall fenestration area
• SHGC from A.8.1 for glazed wall systems in vertical
fenestration and skylights
• SHGC from A.8.2 for other vertical fenestration
• The glazing’s effectiveness in rejecting solar heat
gain
35
SHGC (cont’d)
(cont’d)
36
Visible Light Transmittance
• A measure of the amount
of visible light that passes
through fenestration
• Affected by:
• composition of the glass
• coatings
• internal shading devices
37
Mandatory
Mandatory Provisions
Provisions
Air Leakage
• Seal, caulk, gasket, or
weather-strip
• Openings and joints in
building envelope
• Fenestration and doors
per NFRC 400
• Loading docks in
climates > 3600 HDD
• Vestibules and doors
separating conditioned
space from exterior
Section 5.5.3
38
Mandatory
Mandatory Provisions
Provisions
Building Envelope Sealing
• Joints around fenestration and door frames
• Junctions between walls
• and foundations
• at building corners
• and structural floors or roofs
• and roof or wall panels
• Openings for utility services through roofs, walls, and floors
• Site-built fenestration and doors
• Building assemblies used as ducts or plenums
• Joints, seams, and penetrations of vapor retarders
• All other openings in the building envelope
Section 5.5.3.1
39
Mandatory
Mandatory Provisions
Provisions
Fenestration and Doors
• NFRC 400
• Labeled and certified by manufacturer
• Glazed swinging entrance doors and revolving
doors – not to exceed 1.0 cfm/ft2
• All other products – not to exceed 0.4 cfm/ft2
• Exceptions
• Field-fabricated fenestration and doors
• Garage doors – NAGDM 105
Section 5.5.3.2
40
Mandatory
Mandatory Provisions
Provisions
Loading Dock Weatherseals
• > 3600 HDD65
• Cargo doors and loading dock
doors equipped with
weatherseals
• To restrict infiltration when
vehicles are parked in the
doorway
Section 5.5.3.3
41
Mandatory
Mandatory Provisions
Provisions
Vestibules
• All exterior doors in tall
buildings in cold climates
must have a vestibule with
• Self-closing doors
• Interior and exterior doors
must not be open at the
same time
• Distance between interior
and exterior doors not
< 7 ft when in closed position
(remember ADA!)
Section 5.5.3.4
42
Vestibule Exceptions
• Non-entrance doors
(mechanical/electrical
rooms)
• Vehicle and material
handling doors and
adjacent personnel doors
OR revolving doors
• All doors in climates < 1800
HDD65 OR in buildings
< 4 stories
• All doors that open into
spaces < 3000 ft2 OR into
dwelling units
43
Building Envelope Prescriptive Option
Section 5.3
44
Designers
• Specify
• R-values for walls, floors, and
roofs
• U-factors for opaque doors
• U-factor and SHGC for
fenestration, OR
• Use
• Pre-calculated assemblies
from Appendix A
45
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Opaque Areas
• Compliance
• Meet or exceed minimum R-values in table
• Only R-value of insulation, not to include air films, etc
OR
• Meet maximum U-factor, C-factor, or F-factor for the entire
assembly
OR
• Perform area-weighted average U-factor, C-factor, or F-
factor
• Only if there are multiple assemblies within a single class of
construction for a single space-conditioning category
Section 5.3.1
46
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Roof Insulation
• Meet or exceed minimum R-value in table
• Skylight curbs insulated to level of roofs with
insulation entirely above deck or R-5, whichever is
less
• Roofs with insulation entirely above deck
• R-value is for continuous insulation
• Interruptions for mechanical equipment # 1% of surface
of the total roof area
Section 5.3.1.1
47
Roof Insulation (cont’d)
(cont’d)
Section 5.3.1.2
49
Above -Grade Wall Insulation (cont’d)
Above-Grade (cont’d)
Section 5.3.1.3
51
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Floor Insulation
• Meet or exceed values in appropriate table in Appendix B
• Mass floors
• R-value is for continuous insulation
• If framing is used, compliance is based on maximum assembly
U-factor
• Steel joist floors
• R-value is for uncompressed insulation or spray-on insulation,
but is also acceptable for continuous insulation
• Wood-framed and others
• R-value is for uncompressed insulation, but is also acceptable for
continuous insulation
Section 5.3.1.4
52
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Slab-on-Grade Floor Insulation
Slab-on-Grade
• Meet or exceed values in appropriate table in Appendix B
(includes R-value and depth or width of insulation)
• Be installed around the perimeter to the distance specified
• Inside foundation wall – extend downward from top of slab a minimum
distance specified or to the top of the footing, whichever is less
• Outside foundation wall – extend from top of the slab or downward to at
least the bottom of the slab and then horizontally to a minimum distance
specified
Section 5.3.1.5
53
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Opaque Doors
• Meet or exceed maximum U-factors in appropriate table
in Appendix B
Section 5.3.1.6
54
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Fenestration
Section 5.3.2
55
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Fenestration Area
• Total vertical fenestration
area to be < 50% of gross
wall area
• Including both fixed and
operable vertical fenestration
• Total skylight area to be <
5% of gross roof area
• Including glass skylights,
plastic skylights with a curb,
and all skylights without a
curb
Section 5.3.2.1
56
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Fenestration U -Factor
U-Factor
Section 5.3.2.2
57
Envelope
Envelope Prescriptive
Prescriptive Option
Option
Fenestration SHGC
• Vertical fenestration
• SHGC values < Table 5.3 (Appendix A-18) for
appropriate total vertical fenestration area
• Skylights
• SHGC values < Table 5.3 (Appendix A-18) for
appropriate total skylight area
• No SHGC requirements for semiheated spaces or for
buildings in climates > 10800 HDD65
• No criteria in the for Visible Light Transmittance in
Prescriptive Building Envelope Option, but there are
minimum criteria in the Trade-Off Option (5.3.2.4)
Section 5.3.2.3
58
Overhangs
• Standard credits permanent
overhangs by adjustment to
SHGC
• Size of overhang is
determined by projection
factor
59
Building Envelope Trade -Off Option
Trade-Off
• Building complies if
• It satisfies the provisions of 5.1 and 5.2
• Envelope performance factor (EPF) of proposed building is #
EPF of budget building
• EPF considers only the building envelope components and is
calculated using procedures in Normative Appendix C
• Schedules of operation, lighting power, equipment power,
occupant density, and mechanical systems to be the same for
both the proposed building and the budget building
Section 5.4
60
Mechanical Compliance
Building System Compliance Options
Prescriptive
Envelope Option
Mandatory
Lighting Provisions Trade Off
Energy Code
(required for all Option Compliance
compliance options)
Mechanical
Energy Cost
HVAC Budget
SWH
Simplified
Section 6.1 Approach
61
Simplified Approach Option
• Limited to…
• Buildings with 1 or 2 stories
• Buildings < 25,000ft2
• Single-zone systems
• Air-cooled or evaporatively cooled only
Section 6.1
62
Simplified Approach (cont’d)
(cont’d)
• Economizer Trade-off
Option
• Limited to:
• System size
• Climate (Cooling Degree-
Days)
• Minimum Cooling Efficiency
(EER)
Section 6.1.3
63
Simplified (cont’d)
(cont’d)
64
HVAC Mandatory Provisions
Section 6.2
65
Equipment Covered
66
Equipment Covered for the First Time in 90.1
67
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
Mechanical Equipment Efficiency
Section 6.2.2
69
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
Controls
• Zone Thermostatic controls (Section 6.2.3.1)
• Required for each zone
• Dead Band controls
• Set Point Overlap Restrictions
• Off-Hour controls (Section 6.2.3.2)
• Automatic Shutdown
• Setback Controls
• Optimum Start Controls
• Shutoff Damper Controls
• Zone Isolation
Section 6.2.3
70
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
Controls (cont’d)
(cont’d)
Section 6.2.3
71
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
Controls (cont’d)
(cont’d)
Section 6.2.3.1.2
73
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Set Point Overlap Restriction
Section 6.2.3.1.3
74
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Off -Hour Controls
Off-Hour
• Systems with heating/cooling capacity > 65,000 Btu/h
and fan > ¾ hp
• Shall have the following off-hour controls
• automatic shutdown
• setback controls
• optimum start controls
• shutoff damper controls
• zone isolation
• Exceptions, HVAC systems
• serving hotel/motel guestrooms
• intended to operate continuously
Section 6.2.3.2
75
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Automatic Shutdown
Section 6.2.3.2.1
76
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Setback Controls
Section 6.2.3.2.2
77
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Optimum Start Controls
Section 6.2.3.2.3
78
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Shutoff Damper Controls
• Motorized dampers for outdoor air supply and exhaust
systems
• Ventilation outside air dampers to be capable of
automatically shutting off during
• Preoccupancy building warm up, cool down, and setback
(Except when ventilation reduces energy costs or when ventilation must be
supplied to meet code requirements)
• Supply and exhaust dampers to have maximum leakage
rate of 3 cfm/ft2 at 1.0 in. w.g. when tested in accordance
with AMCA Standard 500
Section 6.2.3.2.4
79
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Shutoff Damper Controls - Exceptions
Section 6.2.3.3.3
80
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Zone Isolation
Section 6.2.3.2.4
81
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Stair and Shaft Vents
• Motorized dampers
• Can be automatically closed during normal building
operation
• Interlocked to open as required by fire and smoke
detection systems
Section 6.2.3.3.1
82
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Gravity Hoods, Vents, and Ventilators
Section 6.2.3.3.2
83
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Heat Pump Auxiliary Heat Control
Section 6.2.3.4
84
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Enclosed Parking Garage Ventilation
Deleted - 2001
• Garage ventilation fan systems with total design
capacity > 30,000 cfm to have at least one
• Automatic control capable of staging fans or modulating
fan volume as required to maintain CO levels below
ASHRAE Standard 62 (only applies to garages used
predominantly by gasoline-powered vehicles)
• Automatic control complying with 6.2.3.2.1 that’s
capable of shutting off fans or reducing fan volume
during periods when garage is not in use
Section 6.2.3.5 –
Deleted (2001) 85
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Humidifier Preheat
Section 6.2.3.5
86
HVAC
HVAC Mandatory
Mandatory Provisions/Controls
Provisions/Controls
Humidification and Dehumidification
Section 6.2.3.7
88
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
HVAC System Construction and Insulation
Section 6.2.4
89
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
General
Section 6.2.4.1.2
91
HVAC
HVAC Mandatory
Mandatory Provisions/HVAC
Provisions/HVAC Insulation
Insulation
Duct Sealing
• Table 6.2.4.3A
• Requirements of
6.2.4.4
• Standard industry
practice
Section 6.2.4.2.1
92
HVAC
HVAC Mandatory
Mandatory Provisions/HVAC
Provisions/HVAC Insulation
Insulation
Duct Leakage Tests
• Designed > 3 in. w.c.
• Leak tested
• Representative sections $
25% of the total installed duct
area shall be tested
• Ratings > 3 in. w.c. to be
identified on drawings
• Maximum permitted duct
leakage
• Lmax = CLP0.65
Where Lmax = maximum permitted
leakage in cfm/100 ft2 duct
surface area
Section 6.2.4.2.2
93
HVAC
HVAC Mandatory
Mandatory Provisions/HVAC
Provisions/HVAC Insulation
Insulation
Piping Insulation
• Table 6.2.4.1.3
• Exceptions
• Factory-installed
• Piping conveying fluids
• design operating temperature range between 60°F-105°F, inclusive
• that haven’t been heated or cooled through the use of nonrenewable
energy or where heat gain or heat loss will not increase energy usage
• Hot water piping between shut off valve and coil, not > 4 ft in
length, when located in conditioned spaces
• Pipe unions in heating systems (steam, steam condensate, and hot
water)
Section 6.2.4.1.3
94
HVAC
HVAC Mandatory
Mandatory Provisions
Provisions
Completion Requirements
• Record drawings
• Operating and maintenance
manuals
• System balancing
• System commissioning
Section 6.2.5
95
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
Drawings
• Record drawings of actual installation to building owner
within 90 days of system acceptance and include, as a
minimum
• Location and performance data on each piece of equipment
• General configuration of duct and pipe distribution system
including sizes
• Terminal air or water design flow rates
Section 6.2.5.1
96
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
Manuals
Section 6.2.5.2
97
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
System Balancing
Section 6.2.5.3.1
98
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
Air System Balancing
Section 6.2.5.3.2
99
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
Hydronic System Balancing
• Proportionately balanced to minimize throttling losses
• Pump impeller trimmed or pump speed adjusted to meet
design flow conditions
• Each system to have either the ability to measure
differential pressure increase across the pump or have
test ports at each side of the pump
• Exceptions
• Pumps with pump motors # 10 hp
• When throttling results in < 5% of the nameplate hp draw, or 3 hp,
whichever is greater, above that required if the impeller was
trimmed
Section 6.2.5.3.3
100
HVAC
HVAC Mandatory
Mandatory Provisions/Completion
Provisions/Completion Req
Req
System Commissioning
Section 6.2.5.4
101
HVAC Prescriptive Path
Section 6.3
102
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Economizers
• Climate and size dependent (Table 6.3.1)
• There are LOTS of exceptions
• Can use air economizers
• 100% of design supply air
• Sequenced with mechanical cooling equipment
• High limit shutoff
• Dampers
• Can use water economizers
• 100% of expected system cooling load
• Maximum pressure drop
Section 6.3.1
103
HVAC
HVAC Prescriptive
Prescriptive Path/Air
Path/Air Economizers
Economizers
Design Capacity
Section 6.3.1.1.1
104
HVAC
HVAC Prescriptive
Prescriptive Path/Air
Path/Air Economizers
Economizers
Control Signal
Section 6.3.1.1.2
105
HVAC
HVAC Prescriptive
Prescriptive Path/Air
Path/Air Economizers
Economizers
High Limit Shutoff
Section 6.3.1.1.3
106
HVAC
HVAC Prescriptive
Prescriptive Path/Air
Path/Air Economizers
Economizers
Dampers
Section 6.3.1.1.4
107
HVAC
HVAC Prescriptive
Prescriptive Path/Air
Path/Air Economizers
Economizers
Relief of Excess Outside Air
Section 6.3.1.1.5
108
HVAC
HVAC Prescriptive
Prescriptive Path/Water
Path/Water Economizers
Economizers
Design Capacity
Section 6.3.1.2.1
109
HVAC
HVAC Prescriptive
Prescriptive Path/Water
Path/Water Economizers
Economizers
Maximum Pressure Drop
Section 6.3.1.2.2
110
HVAC
HVAC Prescriptive
Prescriptive Path/Water
Path/Water Economizers
Economizers
Integrated Economizer Control
Section 6.3.1.3
111
HVAC
HVAC Prescriptive
Prescriptive Path/Water
Path/Water Economizers
Economizers
Economizer Heating System Impact
Section 6.3.1.4
112
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Simultaneous Heating and Cooling Limitation
Section 6.3.2
113
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Simultaneous Heating and Cooling Limitation (cont’d)
(cont’d)
114
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Zone Controls
Section 6.3.2.1
115
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Zone Controls - Exceptions
• Zones for which volume of air that is reheated, recooled,
or mixed is no greater than the larger of the following
• Volume of outside air to meet 6.1.3 of ASHRAE 62 for the zone
• 0.4 cfm/ft2 of zone conditioned floor area with several conditions
• 30% of zone design peak supply
• 300 cfm for zones whose peak flow rate totals no more than 10%
of the total fan system flow rate
• Any higher rate that can be demonstrated to jurisdiction to reduce
overall system annual energy usage…
• Zones where special pressurization relationships, cross-
contamination requirements, or code-required minimum
circulation rates are such that the variable air volume
systems are impractical
116
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic System Controls
Section 6.3.2.2
117
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Three-Pipe System
Three-Pipe
Section 6.3.2.2.1
118
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Two-Pipe Changeover System
Two-Pipe
Section 6.3.2.2.2
119
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic (Water Loop) Heat Pump Systems
Section 6.3.2.2.3
120
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Dehumidification
Section 6.3.2.3
121
Dehumidification Exceptions
122
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Humidification
Section 6.3.2.4
123
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Air System Design and Control
Section 6.3.3
124
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Fan Power Limitation
• Table 6.3.3.1
• Allowable fan system power may be adjusted if
• Air systems require air treatment or filtering systems with pressure
drops > 1 in. w.c. when filters are clean, or heat recovery coils or
devices, or direct evaporative humidifiers/coolers, or other devices
to serve process loads in the airstream
• If
• design room temperature – supply air temp at cooling design
condition = > 20°F, allowable fan system power may be adjusted
Section 6.3.3.1
125
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Part-Load Fan Power Limitation
Part-Load
Section 6.3.3.2.1
126
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Static Pressure Sensor Location
Section 6.3.3.2.2
127
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Set Point Reset
Section 6.3.3.2.3
128
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic System Design and Control
Section 6.3.4
129
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic Variable Flow
Section 6.3.4.1
130
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic Variable Flow - Exceptions
• Systems where
• Minimum flow is < minimum flow required by
equipment manufacturer for proper operation of
equipment served by the system
• Total pump system power # 75 hp
• Systems that include # 3 control valves
131
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Pump Isolation
Section 6.3.4.2
132
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Chilled and Hot Water Temperature Reset Controls
Section 6.3.4.3
133
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hydronic Heat Pump
Section 6.3.4.4
134
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Heat Rejection Equipment
Section 6.3.5.2
136
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Exhaust Air Energy Recovery
Section 6.3.6.1
137
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Exhaust Air Energy Recovery Exceptions
Section 6.3.6.2
139
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Kitchen Hoods (Exhaust)
• Hoods > 5000 cfm to be provided with makeup air
sized for at least 50% of exhaust air volume that is
a) unheated or heated to more than 60°F and b)
uncooled or cooled without the use of mechanical
cooling
• Exceptions
• Where hoods are used to exhaust ventilation air that
would otherwise exfiltrate or be exhausted by other fan
systems
• Certified grease extractor hoods that require a face
velocity no greater than 60 fpm
Section 6.3.7.1
140
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Fume Hoods (Exhaust)
Section 6.3.7.2
141
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Radiant Heating Systems
Section 6.3.8
142
HVAC
HVAC Prescriptive
Prescriptive Path
Path
Hot Gas Bypass Limitation
Section 6.3.9
143
Section 7 - Service Water Heating
• General (Section 7.1)
• Mandatory Provisions (Section 7.2)
• Sizing of systems Load Calculations
• Equipment efficiency
• Service hot water piping insulation
• System controls
• Pools
• Heat traps
• Space heating and water heating
• Service water heating equipment
• Prescriptive Path (Section 7.3)
144
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Sizing of Systems Load Calculations
Section 7.2.1
145
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Equipment Efficiency
• Table 7.2.2
• Equipment not listed in Table 7.2.2 has no minimum
performance requirements
• Exception
• Water heaters and hot water supply boilers > 140 gal storage
capacity don’t have to meet standby loss requirements when
• Tank surface is thermally insulated to R-12.5, and
• A standing pilot light isn’t installed, and
• Gas- or oil-fired water heaters have a flue damper or fan-assisted combustion
Section 7.2.2
146
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Service Hot Water Piping Insulation
• Table 6.2.4.5, Section 6
• Circulating water heater
• Recirculating system piping, including supply and return
piping
• Nonrecirculating storage system
• First 8 ft of outlet piping
• Inlet pipe between storage tank and heat trap
• Externally-heated pipes (heat trace or impedance
heating)
Section 7.2.3
147
SWH
SWH Mandatory
Mandatory Provisions
Provisions
System Controls
• Temperature Controls
• Temperature Maintenance Controls
• Outlet Temperature Controls
• Circulating Pump Controls
Section 7.2.4
148
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Temperature Controls
Section 7.2.4.1
149
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Temperature Maintenance Controls
Section 7.2.4.2
150
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Outlet Temperature Controls
Section 7.2.4.3
151
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Circulating Pump Controls
Section 7.2.4.4
152
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Pools
• Pool heaters to have readily
accessible on-off switch
• Pool heaters fired by
natural gas to NOT have
continuously burning pilot
lights
• Vapor retardant pool covers
required (unless recovered
or solar heat)
• Time switches required
Section 7.2.5
153
SWH
SWH Mandatory
Mandatory Provisions
Provisions
Heat Traps
Section 7.2.6
154
SWH
SWH Prescriptive
Prescriptive Path
Path
Space Heating and Water Heating
• Gas- or oil-fired space heating boiler system (complying with Section
6) is allowed to provide total space heating and water heating when
ONE of the following conditions is met
• Single boiler or component that is heating the service water has a standby
loss in Btu/h not exceeding
• (13.3 x pmd + 400) / n; where pmd is probable maximum demand in gal/h and
n is the fraction of the year when outdoor daily mean temperature is > 64.9°F
• Jurisdiction agrees use of a single heat source will consume less energy
than separate units
• Energy input of the combined boiler and water heater system is
< 150,000 Btu/h
• Instructions for determining standby loss are included in this Section
Section 7.3.1
155
SWH/Prescriptive
SWH/Prescriptive Path
Path
Service Water Heating Equipment
Section 7.3.2
156
Section 8 - Power
• Voltage drop
• Completion requirements
157
Voltage Drop
Section 8.2.1
158
Completion Requirements
• Owner gets information about the building’s electrical
system
• Record drawings of actual installation within 30 days
• Single-line diagram of electrical distribution system
• Floor plans showing location of distribution equipment and areas
served by equipment
• Manuals
• Submittal data stating equipment nameplate rating
• O&M manuals for equipment
• Qualified service agency
• Complete narrative and schematic of system as it’s normally
intended to operate
Section 8.2.2
159
Lighting Compliance
Building System Compliance Options
Prescriptive
Envelope Option
Mandatory
Lighting Provisions Trade Off
Energy Code
(required for all Option Compliance
compliance options)
Mechanical
Energy Cost
HVAC Budget
SWH
Section 9 160
Section 9 - Lighting
• General Application (Section 9.1)
• Mandatory Provisions (Section 9.2)
• Lighting controls
• Tandem wiring
• Exit signs
• Installed interior lighting power
• Luminaire wattage
• Exterior building grounds lighting
• Prescriptive Path (Section 9.3)
• Interior Lighting Power Allowance
• Building Area Method
• Space-by-Space Method
• Exterior Lighting Power Allowance
161
Lighting General Application
• Interior spaces of buildings
• Exterior building features
• Exterior grounds lighting powered through building
• Exceptions
• Emergency lighting
• Lighting required by life safety statute
• Lighting within living units of buildings
• Decorative gas lighting
162
Lighting Changes Between
90.1 -1989 and 90.1
90.1-1989 -2001
90.1-2001
• More efficient lighting
• Less power allowed
• No lighting control credits
• Lighting power allowance now based only on connected
lighting power
• No control points for spaces
• No separate lighting controls for daylighted
spaces
163
Lighting Changes Between
90.1 -1989 and 90.1
90.1-1989 -2001 (cont’d)
90.1-2001 (cont’d)
• New construction
• Existing nonresidential and high-rise residential
• If $ 50% of existing luminaires are replaced
• If renovation increases lighting power
• Control devices can’t control
• > 2500 ft2 in spaces < 10,000 ft2
• > 10,000 ft2 in spaces > 10,000 ft2
• Control must be readily accessible and located so
occupants can see the controlled lighting
165
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Lighting Control
Section 9.2.1
166
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Space Control
Section 9.2.1.2
167
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Exterior Lighting Control
• Photocells or astronomical time switch required
• Seven-day electrically-driven, mechanical clocks with trippers,
astronomical dial, and four-hour spring-wound storage
• Seven-day or calendar year, electronic programmable time switches
with astronomic correction and battery backup
• Any of the timers above with a photocell (in place of astronomical
correction)
• Exceptions – lighting for
• Covered vehicle entrances
• Exits from buildings or parking structures
(where required for safety, security, or eye adaptation)
Section 9.2.1.3
168
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Additional Control
• Many special lighting applications must be
controlled separately
• Display/accent lighting
• Case lighting
• Hotel/motel guest room lighting
• Task lighting
• Nonvisual lighting
• Demonstration lighting
Section 9.2.1.4
169
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Tandem Wiring
Section 9.2.2
170
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Tandem Wiring Exceptions
Section 9.2.2
171
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Exit Signs
• Exit signs operating at > 20 W must have a source
efficacy $ 35 lumens/W
• LED lamps okay
• CF lamps with electronic ballasts usually okay
• Majority of incandescent lamps not okay
Section 9.2.3
172
Efficacy
173
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Installed Interior Lighting Power
• Includes all permanent and portable interior lighting
intended for general, ambient, or task illumination
• Includes lamp, power used by ballast, the control (when
applicable), current regulators, and any other power draws
associated with the lighting system
• Exception
• If 2 or more independently operating lighting systems in a space can be
controlled to prevent simultaneous operation, can base IILP on lighting
system with highest wattage
Section 9.2.4
174
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Luminaire Wattage
Section 9.2.5
175
Lighting Power Development Concept
176
Lighting
Lighting Mandatory
Mandatory Provisions
Provisions
Exterior Building Grounds Lighting
178
Lighting Power Allowance Exemptions
179
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Building Area Method
• Used for projects involving
• An entire building
• A single, independent, and separate occupancy in a multi-
occupancy building
• Gross lighted area is multiplied by allowance from Table
9.3.1.1
• Limitations
• Insensitive to specific space functions and room configurations
• Generally is more restrictive
• Does not apply to all building types - but “selection of a
reasonably equivalent type” is permitted
Section 9.3.1.1
180
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Gross Lighted Area
181
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Building Area Allowances
• Table 9.3.1.1
Lighting Power
Building Type
Density (W/ft2)
Dormitory 1.5
182
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Space -by-Space Method
Space-by-Space
Section 9.3.1.2
183
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Additional Interior Lighting Power
Section 9.3.1.2.1
184
Lighting
Lighting Prescriptive
Prescriptive Path
Path
Exterior Building Lighting Power
• Sum of all lighting power allowances for applicable exterior applications
• Building Surface Requirements
• Building entrance with canopy – 3 W/ft2
• Building entrance – 33 W/linear ft
• Building exit – 20 W/linear ft
• Building facades – 0.25 W/ft2
• Exceptions, when equipped with a control device
• Specialized signal, directional, and market lighting associated with
transportation
• Public monuments
• Registered historic landmark structures or buildings
• Lighting integral to advertising signage
Section 9.3.2
185
Section 10 - Other Equipment
186
Section 11 - Energy Cost Budget Method
187
Section 12 - Normative References
188
Assembly U -Factor, C
U-Factor, -Factor, and
C-Factor,
F-Factor Determination
F-Factor
Normative
Appendix A
189
Building Envelope Criteria
Normative
Appendix B
190
Methodology for Building Envelope
Trade -Off Option in Subsection 5.4
Trade-Off
Normative
Appendix C
191
Climate Data
Normative
Appendix D
192
Informative References
Informative
Appendix E
193