L578 Notebook PDF
L578 Notebook PDF
TAB 3 Transducers
Arun G. Phadke
He is the author of more than a dozen papers dealing with transmission and
substation protection.
S. H. HOROWITZ
Consultant
Columbus, Ohio
Stan Horowitz is a graduate of the City College of New York, a member of the
National Academy of Engineering, Life Fellow of IEEE, past member of the IEEE
Executive Board, past chairman of the IEEE Power System Relaying Committee
and past chairman of CIGRE Committee 34-Protection and Control, editor-in-
chief of Computer Applications in Power.
Professor Emeritus
and
University of Wisconsin-Madison
Dr. Long received his B.S. and M.S. degrees from the University of Toledo in
1957 and 1962. He was employed from 1957 to 1960 by Doehler-Jarvis
Division, National Lead Company, as Project Engineer. He was Instructor,
Electrical Engineering at the University of Toledo from 1962-1966. In 1966 he
was awarded an NSF Science Faculty Fellowship to attend the University of
Wisconsin-Madison and received the Ph.D. from that institution in 1970.
In 1969 Dr. Long joined the Hughes Aircraft Company Research Laboratories
in Malibu, California, as a Member of the Technical Staff of the High Voltage
Systems Program. He has been with the Department of Engineering,
University of Wisconsin-Extension (now Department of Engineering
Professional Development, University of Wisconsin-Madison) since 1973,
serving as Program Director, Electric Power Systems. He was Professor and
Chairman from 1980 until 1983.
In 1983, while on leave from the University of Wisconsin, Dr. Long joined
ASEA as Director of their Power Systems Center in New Berlin, Wisconsin. He
was responsible for technical and managerial activities at the Center, a new
facility for the analysis and simulation of integrated ac/dc power systems. He
returned to the University in July 1985. In 1992 he was on sabbatical leave at
the Royal Institute of Technology, Stockholm, Sweden.
Professor Emeritus
Blacksburg, Virginia
Dr. Phadke has taught short courses for practicing power engineers at the
University of Wisconsin-Madison since 1970, and also lectures at other
universities in the United States and abroad. He is past Chairman of the
Power System Relaying Committee of IEEE, and is past Chair of the Technical
Committee of USNC CIGRE. Dr. Phadke is a member of HKN, Tau Beta Pi,
Sigma Xi, and a Fellow of IEEE. He received a Prize Paper Award from the
U.S. National Committee of CIGRE in 1986. An earlier paper received the
Outstanding Paper Award of the Power System Relaying Committee in 1978.
In 1986 he was honored by the Edison Electric Institute as Power Engineering
Professor of the year. In 1987, Dr. Phadke received the Distinguished
Service Award from the College of Engineering, University of
Wisconsin-Madison. He also received the 1991 Outstanding Power
Engineering Educator award from IEEE Power Engineering Society. Dr.
Phadke was elected to the National Academy of Engineering in 1993. He
received the IEEE Herman Halprin Award for Transmission and Distribution
for 2000. In 2006 he was awarded an honorary doctorate from the Institut
National Polytechnique de Grenoble, France. In 2008 he received the
Benjamin Franklin Medal in Electrical Engineering.
1
Modern Power System Protection: Applications
and Performance Analysis
TAB 1
Introduction to the Course
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
MODERN POWER SYSTEM PROTECTION
• Course Organization
1-1
• Course Organization
• Text books
• Other source material
• Course Organization
1-2
• Course Organization
• What is different
• Mathematical techniques
• Adaptive Relaying
• Course Organization
• Field Experiences
1-3
• Course Organization
ELEMENTS OF A
PROTECTION SYSTEM
Breaker Transducer
Relay
Battery
1-4
Modern Power System Protection: Applications
2
and Performance Analysis
TAB 2
Relaying Fundamentals
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
Fundamental References
Power System Relaying--Horowitz, Phadke
Art and Science of Protective Relaying--C.R. Mason
(Distributed by General Electric)
Applied Protective Relaying (distributed by ABB)
Protective Relaying for Electric Power Systems, Volumes I &II
-IEEE Press
Protective Relaying Systems- IEEE Standards Collection
2-1
Breaker-Insulating &/or cooling medium- oil, air, gas
2-2
Relays will perform correctly if the input signals agree with the setting of the
relay. The action may or may not be the desired system response.
2-3
The purpose of power system protection is to detect faults or abnormal operating
conditions.
In general, as faults occur, currents go up and voltages go down. Other changes
such as phase angle, harmonics and frequency may change and relay operating
principles may be based upon detecting these changes.
Differential relays operate on the theory that current in and out of equipment is
equal if no fault exists.
Distance relays measure the impedance to a fault.
Pilot relays provide a communication path between two terminals.
2-4
2-5
Relays will perform correctly if the input signals agree with the setting of the
relay. The action may or may not be the desired system response.
2-6
Note the difference between system reliability which is a term used by system planners and operators and relay reliability.
Selectivity is the major concern for relay reliability.
Speed-Instantaneous (not zero time);Time Delay (intentional); High Speed (>3cycles); Ultra High Speed (<4ms)
Primary vs Backup
Primary protection provides the fastest
clearing of a fault and removes the least system elements.
Backup protection may be slower and/or removes more elements than may be necessary
2-7
2-8
Contact status- !a" switches are normally open; !b" switches are normally
closed. (refers to position when relay is !on the shelf"}
Seal-in - isolates relay contact from trip current.
Time delay. Relay operating time is !instantaneous". Time is added with a timer.
Relays are designated by Standard Device Function Number; #e.g 50 is an
instantaneous relay, 51 is a time delay relay, 21 is an impedance relay, etc. See
Appendix.
2-9
Definition used by system operators and planners
2-10
System is reliably designed.
System security is stressed
when breakers are opened.
2-11
Relays are usually biased towards dependability because the system is robust
and must tolerate outages.
This concept changes when the system is stressed
2-12
Elements can be contacts of a relay or complete relay systems.
Combined circuit with electromechanical or solid state relays usually used only
by military and nuclear.
Digital relays may be more adaptable.
2-13
All elements must be encompassed by at least one zone. Good relaying practice
is to be sure important elements are included in two zones.
Zones must overlap.
Closed zone- all entry points are monitored. (differential, unit, absolutely
selective)
Open zone- degree of uncertainty,
2-14
2-15
Instantaneous-no intentional time delay
Time-delay-intentional delay. Can be internal or external.
High speed-50 ms or less.
Ultra High speed-not defined in standards-understood to be 1/4 cycle
2-16
Protection against a failed breaker. It is initiated by all relays that attempt to trip
the breaker. Connect to separate dc circuits. Inst. o/c relays determine that the
breaker has not interrupted the fault. Can supervise timer or be supervised by
timer.
2-17
Level Detector-simplest, fuse, overcurrent--pickup & time delay
Magnitude Comparison-compares ratio of operating quantities, not common for
transmission lines, used in hydro machines.
2-18
2-19
2-20
2-21
Plunger-type is instantaneous and operates on all harmonics,
including
dc. External timing device can be added.
2-22
Induction-disc requires two fluxes which can be derived from the same
current separated by an R-C circuit or a separate current or voltage input.
Only operates on ac and the two fluxes must be of the same frequency.
Time delay is obtained by adjusting the disc.
2-23
Note the abcissa is not current but a multiple of the current pickup. This
is done to make the relay characteristic universal, i.e. independent of the
specific relay.
The curves, however, are manufacturer specific.
2-24
Typical e-m relay for high speed relays.
Torque is developed by combinations of current and voltage which
determines the specific relay characteristics.
(see page 33)
2-25
The input current I is passed through the resistive shunt R, full-wave rectified and
filtered to remove the ripple and applied to a high gain amplifier A. The other
input of the summing amplifier is supplied with a reference voltage er. When the
input exceeds he reference setting, the amplifier output goes high. The timer can
provide immunity against spurious transient signals or can make the relay either
an instantaneous or a time delay overcurrent relay.
2-26
An electromechanical or electronic relay is actually an analog computer. It
accepts inputs, processes them to develop a torque or logic output. Modern
rugged, high performance digital computers can perform the same function. This
is done by sampling the analog signals and using an appropriate algorithm to
create suitable digital representations of the signals. This figure is a possible
configuration for a digiital relay.
2-27
Security of system is the actual operating configuration. Reclosing
restores system to normal configuration
Manual -from control device or SCADA
Automatic-High speed-within 1 sec.
Delayed-minutes
Interlocks-voltage, equipment,
Synchronizing-Full or Check
2-28
When one phase is opened in response to a single phase-to-ground fault,
the two healthy phases maintain synchronizing torque but also tend to
maintain the fault arc.
Shunt reactors may be used to extinguish the secondary arc.
Negative sequence is a concern
2-29
2-30
2-31
2-32
!"#$$%&'$(%)($*)+,$-./-0.*$1/%),%/$
2-33
2-34
2-35
Modern Power System Protection: Applications
and Performance Analysis
3
TAB 3
Transducers
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
TRANSDUCERS
TRANSDUCERS
• Current Transformers
• Voltage Transformers
3-1
TRANSDUCERS
• Standard ratings
• CTs 5 amp and 1 amp secondary
• VTs 120 volts line-line, 69.3 line-neutral
TRANSDUCERS
CURRENT TRANSFORMERS
• Stand-alone CTs
• more expensive
• higher accuracy
3-2
TRANSDUCERS
• Examples
10 C 600
10 T 200
• Multi-ratio CTs
TRANSDUCERS
!
Zm" n2 Zm
I1 I2
Z l2
I1!
I1 "
n
ZL Simplified
Zm Em EL
equivalent Circuit
3-3
TRANSDUCERS
I1 I2
Z l2 Current
Transformer
Zm Em ZL EL Phasor Diagram
Em
Zl2I2
El
I2
Im I1
TRANSDUCERS
Increasing
Em Ratio
Im
3-4
TRANSDUCERS
I1 I2
Solving the non-linear Z l2
problem
Zm Em ZL EL
Let Z = ZL+Zl2
The current source I1 in parallel with Z can be replaced
by a Thevenin voltage source:
Z Non-linear
Em
Em
I 1Z
Im linear
linear Non-linear
Im
TRANSDUCERS
3-5
TRANSDUCERS
I1 I2
Z l2 Assume linear Zm
Zm Em ZL EL I2 = I1 - Im
where Im = Em/Zm
• If Im is 0, there is no error of transformation,
and the CT is perfect.
TRANSDUCERS
3-6
TRANSDUCERS
VOLTAGE TRANSFORMERS
TRANSDUCERS
VOLTAGE TRANSFORMERS
• Two winding transformers
Similar to power transformers
• Capacitive Voltage Transformers
• Bushing type
3-7
TRANSDUCERS
• Equivalent Circuit and Steady State performance
C1
L T
Ld is the drain
C2 coil which blocks
ZF ZL power line carrier
signal.
Ld L and (C1+C2)
resonate at
C1 + C2 L T power
frequency
Eth ZF ZL 1
2#f =
L(C1+C2)
TRANSDUCERS
• The two-winding voltage transformer (PT)
has no significant steady state or transient
errors as far as relaying is concerned.
• The capacitive coupled voltage transformer (CVT)
has no significant steady state errors when the
inductance is tuned to (C1+C2).
• However, the tuning does not hold under
transient conditions, and transient errors of
the CVT need to be considered in relaying.
• Ferroresonance phenomena are important
for CVTs, and should be damped by a
properly designed ferroresonance suppression
circuit
3-8
Modern Power System Protection: Applications
and Performance Analysis
TAB 4
Transient Phenomena
Arun G. Phadke
4
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
TRANSIENT PHENOMENA
By
Arun Phadke
4-1
TRANSIENT PHENOMENA
E max
i ( t) " {sin( !t # % ), where
Z
X
Z " R 2 $ X 2 , and % " arctan
R
e(t)
i(t)
dc offset
&
Steady state Transient
TRANSIENT PHENOMENA
Current transformer saturation
'
Zm" n2 Zm
I1 I2
Z l2
I1'
I1 "
n
ZL Simplified
Zm Em EL
equivalent Circuit
4-2
TRANSIENT PHENOMENA
Current transformer saturation
I1 I2
Z l2 Assume linear Zm
Primary current
Zm Em ZL EL with a dc offset:
TRANSIENT PHENOMENA
Current transformer saturation
4-3
TRANSIENT PHENOMENA
Current transformer saturation
Flux
CT PERFORMANCE CALCULATION
4-4
Flux, Currents, and load voltage in per unit Flux, Currents, and load voltage in per unit
4-5
Flux, Currents, and load voltage in per unit Flux, Currents, and load voltage in per unit
4-6
TRANSIENT PHENOMENA
DC offset near a generator
TRANSIENT PHENOMENA
Current transformer saturation
IMPORTANT ISSUES
Time to saturate
Effect of burden impedance
Effect of transformer core size
4-7
TRANSIENT PHENOMENA
CVT subsidence transient
C1
A fault occurs at L T
the high voltage
terminal and
C2
the voltage collapses. ZF ZL
The question is, what
does the relay see?
Ld
C1 + C2 L T
Eth ZF ZL
TRANSIENT PHENOMENA
CVT subsidence transient
Consider the
C L equivalent circuit
obtained by
reflecting all
e'(t) Rc Lm Rb quantities on the
secondary side
of the ideal
transformer.
• The burden is assumed to be resistive for this
example.
• Rc is the core-loss component of the magnetizing
branch, and Lm is the magnetizing inductance.
• L and C are the tuning inductance and (C1+C2)
reflected on the secondary, and e'(t) is the Thevenin
voltage as seen on the secondary.
4-8
TRANSIENT PHENOMENA
CVT subsidence transient
C L
e2'(t) The circuit is entirely linear,
Rc Lm Rb and hence can be solved by
e'(t)
using LaPlace Transform.
TRANSIENT PHENOMENA
CVT subsidence transient
e'(t) e'(t)
e2'(t) e2'(t)
&+"+,-. &+"+0
Note that the subsidence transient is more dominant when
fault occurs at or near voltage zero. Also, a more complete
representation of the circuit components produces the
response shown in white for the case of &+"+,-.1
Subsidence transients are aperiodic and their zero crossings
are not related to the zero-crossings of the power frequency
voltage.
4-9
TRANSIENT PHENOMENA
Magnetizing Inrush currents
i(t)
e(t)
e(t)
2
2(t)
i(t)
Steady State
TRANSIENT PHENOMENA
i(t)
Magnetizing Inrush currents
e(t)
remanance
e(t)
2
2(t) i(t)
t=0
4-10
TRANSIENT PHENOMENA
Magnetizing Inrush currents
0 3 2,
a n /a
1
Harmonic
3 =604 3 =904 3 =1204
2 0.705 0.424 0.171
3 0.352 0.000 0.086
4 0.070 0.085 0.017
5 0.070 0.000 0.017
. … … …
. … … …
4-11
TRANSIENT PHENOMENA
Ferroresonance
unstable
decreasing
capacitance
ec OR
increasing ec
voltage
e el e
el
el = ec + e inductive
capacitive
TRANSIENT PHENOMENA
Ferroresonance small increase
in source voltage
source voltage
ec
current
e el
el = ec + e capacitor
voltage
4-12
TRANSIENT PHENOMENA
Ferroresonance
TRANSIENT PHENOMENA
Arcing in capacitive circuits
Circuit breaker
opening at E
current zero
E
I
4-13
TRANSIENT PHENOMENA
Arcing in capacitive circuits
Circuit breaker
opening at E
current zero
TRANSIENT PHENOMENA
Arcing in capacitive circuits
i = {E/s}/(sL+1/sC)
E 1/2 2
i = {E/(L/C) }{ !+/(s + ! 2 )}
2
e c = E { 1/s - s /(s + ! 2 )}
1/2
i(t) = {E/(L/C) }{sin !+t)
4-14
TRANSIENT PHENOMENA
Arcing in capacitive circuits
restrike
e source e
i
TRANSIENT PHENOMENA
Arcing in capacitive circuits 7e
3e
capacitor voltage
e source e
i
restrikes
4-15
TRANSIENT RECOVERY VOLTAGE
Superposition
complete circuit
I I
pre-opening opening
opening
-i
fault
e
breaker
4-16
TRANSIENT RECOVERY VOLTAGE
voltage across circuit breaker
i
fault
e
source
e
breaker
TRANSIENT PHENOMENA
Trapped charge oscillations
e line
e source
i
4-17
TRANSIENT PHENOMENA
Trapped charge oscillations
50 % compensation
X
l
= 2.0 X c Xc
e line
e source
i
TRANSIENT PHENOMENA
Trapped charge oscillations on transposed 3 phase line
3(X -X )
c1 c0
X c0
4-18
TRANSIENT PHENOMENA
Trapped charge oscillations on transposed 3 phase line
TRANSIENT PHENOMENA
Trapped charge oscillations on transposed 3 phase line
50 % compensation
3(X -X )
c1 c0
X c0
X = 2.0 X
l c1
4-19
TRANSIENT PHENOMENA
Trapped charge oscillations on transposed 3 phase line
TRANSIENT PHENOMENA
Trapped charge oscillations on UNTRANSPOSED
3 phase line
4-20
Modern Power System Protection: Applications
and Performance Analysis
TAB 5
Interpreting Oscillograms I
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
5
TRANSIENTS
•! AC and DC Saturation
•! Restrike
•! Switching Surge
•! Capacitor Switching
•! Ferroresonance
•! Overexcitation
•! Inrush Currents
•! Arcing Grounds
X Y Z
LINE 2 LINE 1
D C A X B
FAULT
OSC LINE CURRENT
BUS OSC
PT NEUTRAL
OSC
A-G FAULT
A
BUS PT
C
LINE CURRENT
C
DEAD TIME LINE
LOAD CURRENT
NEUTRAL CURRENT CHARGING
5-1
5-2
5-3
RESTRIKE
RESTRIKE
5-4
5-5
5-6
FERRORESONANCE
C1
L T
ZF ZL
C2
Ld SUPPRESSION CIRCUIT
SUPPLIED BY MANUFACTURE
105%
100%
EM
IM
5-7
5-8
5-9
5-10
5-11
6
Modern Power System Protection: Applications
and Performance Analysis
TAB 6
Non-Pilot Line Protection of Transmission Lines I & II
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
Transmission line protection using local voltages and currents.
6-1
Offers opportunity to examine many fundamental relaying considerations that apply in one degree or another to all power
system equipment.
Transmission lines exposed to short circuits between phases or phase and ground.
Factors that must be considered are fault magnitude, coordination, directionality and zones of protection..
6-2
Coordination begins with protective device closest to fault and allows time for it to clear the fault..
The relay operating characteristics (time vs multiples of pick up) is manufacturer sensitive
6-3
setting rules
Choose pickup
-phase relays--twice load, 1/3 minimum fault
-ground relays-no load concern-twice !normal
unbalance", 1/3 minimum fault.
Set time delay
6-4
Select CT ratio to give 5.0 amps secondary at maximum load-95/5=19/1. Not a
standard ratio- use 20/1 (100/5)
2x95=190/20-9.5 amp use 10.0 amp tap
10.0 amp tap=200 primary amp pick up.
200/95 = 2.1 xpu
Minimum fault = 600/200=3xpu
No coordination required. Set lever at 1/2
6-5
Pu at R2 =10 a. @1/2/dial
For R1-Use same CT ratio,
set at 10 amps but longer.
Operating time at 1500 amps/ 200 7.5x pu = 0.25 sec (Fig. 4.5).
Add 0.3 sec = .55 sec
@1500/200 =7.5 x pu = time dial of 1.5
6-6
Application of time delay setting rules means the closer to the source the longer the time to clear and the greater the fault
current.
Instantaneous relays correct this for most of the line section.
6-7
Avoid overreaching end of line
Rb @ 135% max fault =1350 amps primary-1350/20 = 67.5 amps
Check against min and max fault
800/1350 -0.59 xpu
1500/1350=1.1xpu Do not us inst.
Rab—135%x1500=2025/20=101.25amp sec.
Ok but may be a problem with saturation.
Change CT ratio to 40/1-1000/40=0.49 ng
3000/40=1.48 xpu ok but must recalculate TDOC
6-8
Contrasted with single-quantity relays, directional relays are actuated from 2
different, independent, sources either current-current relays or current-voltage
relays.
Current-current- the fault current and a polarizing current
Current voltage= the fault current and a polarizing voltage.
The polarizing quantity is constant regardless of the direction of the fault.
Negative sequence units are applied when mutual effects can cause zero
sequence to lose directionality.
Readily available today in digital relays
6-9
For phase faults, the polarizing quantity is almost invariably the system voltage at the relay location.Can be bus or line
side.
For ground faults, the operating current is derived from the residual circuit of the phase CTs. Since this can be any phase it
is necessary to obtain a related voltage
6-10
Current Polarizing is obtained from the neutral of a wye-grounded/delta
transformer.
Use all neutrals in station to allow for transformer maintenance. CT ratios are
inverse of transformer rating.
An autotransformer is not always a suitable polarizing source since the direction
of current in the neutral can be up or down depending on the system parameters.
(See page 96)
6-11
There are two ways to utilize directional o/c elements
1-directional element controls the operation of the overcurrent element.
2-overcurrent element can operate but directional element supervises
its operation and the relay cannot operate if the fault is in the non-trip direction.
6-12
Referring again to the diagram, with the directional o/c design, if a fault occurs in
the non-trip direction (breaker 4) the o/c element can pick up from the
contribution in that direction. Only the directional element prevents tripping
Breaker 4. If breaker 4 opens before breaker 1 than the reversal of current
through 4 will cause a race between the o/c element opening ad the directional
element closing. If the directional element wins the race, there will be a false trip.
With the directional control design, the o/c element will not pick up for faults in the
non-trip direction.
6-13
Digital relays include voltage memory
so the problem can be solved easier.
6-14
Distribution systems are becoming very similar to transmission systems, i. e.,
distributed generation is resulting in the direction of power flow for a fault
difficulty in dispatching generation with IPP#s and NUG#s
Clearing a fault now depends on removing all generators
6-15
Zf = E/ I = Apparent impedance seen b y the relay
Both System impedance and Distance Relay characteristic are plotted on the
same diagram.
As load changes characteristic circle changes. The larger the load, the smaller
the circle.
The relay operates for impedance within the characteristic
6-16
Impedance Relay-(Ohm) --Non-Directional. Used for fault detector.
Admittance Relay-(Mho)--Directional--. tripping relay.. Solid-state relay can be shaped to coincide with line angle .
Digital relay can have any shape it requires
Reactance Relay.--Insensitive to resistance- Used for short transmission lines
6-17
When fault resistance is same order of magnitude as line impedance:
Reactance Relay is not affected
Relay reach of Ohm and Mho relays are reduced.
6-18
Admittance (MHO) Relay, used as principal tripping relay in most relaying schemes.
Although not exact, the Angle of Maximum torque usually taken coincident with line angle
Typical line angles--138-345 kV--70-80 degrees
6-19
Most commonly used backup relay.
Zone 1 set for 80-90% of line section.and is instantaneous.
Zone 2 set for 120-180% of adjacent line section and has 15-30 cycle time delay
Zone 3 set to overreach adjacent line section and is set for 60 cycles or more
Zone 2 must not overreach adjacent line section#s zone 1.
6-20
Mho relay Zone 1 set for 80-90% of line section--Instantaneous.
Mho relay Zone 2 set for 125-150% line section--15-30 cycle time delay .
Must not overreach Zone 1 of adjacent line section.
6-21
Typical stepped distance protection. Note the possible load encroachment,
particularly into zone 3.
Zone 1 is instantaneous
Zone 2 has a time delay of 15 cycles
Zone 3 has a time delay of 30 cycles
This has led to many discussions and rule making.
Digital relays alleviate the problem to a considerable degree.
6-22
6-23
The traditional relaying bete noir for non-pilot transmission line relays .
Relays use local measurements which do not give the entire fault magnitude picture. The contribution from the tap is not
measured at the relay location.
6-24
Series Capacitor is used to improve maximum power transfer.
Pm=E/(xL-XC)
Introduces a discontinuity which effects impedance relays. Add time delay to
allow capacitor protective devices to operate.
Reactor is used to limit short circuit current or regulate voltage. Minimum impact
on relays
6-25
Modern Power System Protection: Applications
7
and Performance Analysis
TAB 7
Response of Distance Relays
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
RESPONSE OF DISTANCE RELAYS
Z = R + jX = E / I
I
E R
7-1
VISUALIZING IMPEDANCE RELAY RESPONSE
FROM PHASOR DIAGRAMS
If the current is
I = 1.0 + j0.0
Then, the impedance is equal to the voltage.
Z=E/I=E
This is the key to understanding the impedance
relay response:
• Draw voltage and current on the same phasor
diagram.
• Use units of secondary volts and amperes.
• Re-orient the complete phasor diagram so that
the current phasor is horizontal.
• Stretch or shrink the complete phasor diagram
until the current phasor fits in R = 1.0
Example:
Z = 2 ! 30"
= 1.732 + j 0.5
0.5
1.0 1.732
R (secondary ohms)
7-2
VISUALIZING IMPEDANCE RELAY RESPONSE
FROM PHASOR DIAGRAMS
More examples
5 1
R
2. Forward leading load 6
4 2
5. Forward fault
7-3
DISTANCE RELAYS IN UNFAULTED PHASES
Ec
Ea
I0
Eb
Unfaulted Ia
voltages and currents
Ia + mI0
Faulted
voltages and currents
7-4
DISTANCE RELAYS IN UNFAULTED PHASES
Ec
Ea
Ea
a-g relay
I0
Eb
Ia
Ia + mI0 Ia + mI0
Faulted
voltages and currents
Ib-Ic = 0 Ic-Ia = -Ia
Ea-Eb Ec-Ea
Ea
Ib-Ic = 0 X
a-g relay
b-c relay
a-g relay
Ea-Eb
c-a relay
b-c relay at #
7-5
MHO CHARACTERISTICS
AND POLARIZATION
Relay
E
DYNAMIC TESTING
Alternatives:
MHO CHARACTERISTICS
AND POLARIZATION
Relay E o = E - I Zr (operating
E quantity)
Ep = (polarizing quantity)
should have 90º or greater
between them
7-6
MHO CHARACTERISTICS
AND POLARIZATION
Relay
E
Epol = E
MHO CHARACTERISTICS
AND POLARIZATION
I
E
Relay
E
I
Zr
Zop = (E - I Zr)/I
= Zapp - Zr Zop = Zapp - Zr
Zp = Ep/I
Zpol = Zapp
7-7
MHO CHARACTERISTICS
AND POLARIZATION
MHO CHARACTERISTICS
AND POLARIZATION
Zs
I
Es Relay E
7-8
MHO CHARACTERISTICS
AND POLARIZATION
Relay
Es E
Zr Es
Zop = Zapp - Zr
E IZS
Zs Zpol = Zs + Zapp
I
MHO CHARACTERISTICS
AND POLARIZATION
7-9
MHO CHARACTERISTICS
AND POLARIZATION
Relay Zq
Eq
E
Zpol = -Zq - Zr + Zapp
Zq Eq = E +I(Zr+Zq)
Eq
Zr I
E
Zop = Zapp - Zr - I (Zr+Zq)
Zapp I (Zr+Zq) Eq
MHO CHARACTERISTICS
AND POLARIZATION
7-10
Modern Power System Protection: Applications
and Performance Analysis
8
TAB 8
Fault Location
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
FAULT LOCATION
By
Arun Phadke
Fault Location
8-1
Fault Location
Fault Location
8-2
Fault Location
IS kZ EF (1-k)Z IR
ES ER
IF RF
ES = EF + IS kZ
ER = EF + IR (1-k)Z
Fault Location
IS kZ EF (1-k)Z IR
ES j(1-k)YC ER
jkYC jkYC IF RF
2 2 2
j(1-k)YC
2
If the YC is the total charging susceptance of the line, it is
distributed as shown above in the two sections.
8-3
Fault Location
IS Z IR
ES jYC ER
jYC
2 2
Fault Location
8-4
Fault Location
• Single ended fault location
IS kZ (1-k)Z IR
EF
ES ER
IF RF
ES = EF + IS kZ = IS kZ + IF RF
Fault Location
RF
ZS IF ZR
- EF
ZR+ (1-k) Z ZR + ZS + Z
#IS = IF , or if IF = d #IS d=
ZR + ZS + Z ZR+ (1-k) Z
8-5
Fault Location
ES = IS kZ + d # IS RF
Fault Location
8-6
Fault Location
X
E
Z
1.0 R
I
Fault Location
IS kZ EF (1-k)Z IR
ES ER
IF RF
ES
ES = IS kZ + IF RF ZS =
IS
ZS
X
ES
RFIF kZ
IR ISkZ
IS R
1.0
IF
8-7
Fault Location
Fault Location
8-8
Travelling waves
i i
e
i i
x
Travelling waves
T1
T2-T1
T2
x = L/2 - v(T2-T1)/2
Beweley Diagram
8-9
Travelling waves
Each of the
%&'&( waves
produces three
components
at each discontinuity
Beweley Diagram
8-10
Modern Power System Protection: Applications
and Performance Analysis
TAB 9
Pilot Line Protection of Transmission Lines
Stanley H. Horowitz
9
Consultant
3143 Griggsview Court
Columbus, OH 43221
The primary weakness of non-pilot relaying is the inability to cover 100% of the
line instantaneously. To do this, and avoid overreaching the adjacent line
segment, it is necessary to use a communication link in which each end tells the
other end either the direction or the phase angle of the fault current.
9-1
Power line carrier is an on-off signal in the 10-490 kHz band. The frequency is
not licensed in the U.S.
Microwave operates at frequncies between 150MHz and 20GHz. Usually in a
frequency shift mode.
Communication cable can be telephony-type cable either owned or leased.
Fiber optic has virtually unlimited capacity and is present preferred
communication link. Installtaion practices vary.
9-2
9-3
9-4
Most common pilot relaying scheme in U.S. Not so in Europe or Asia.
No impedance to power frequency transfer.
High frequency (30-300kHz) trapped on line section.
CCVT used for coupling.
9-5
Fault detector can be directional (mho) or non-directional (ohm).
Tripping relay is directional (mho)
9-6
The non-directional blocking relay is an impedance relay centered at each relay
location.
It I set for at least 150% of the largest tripping element. It may result in
continuous carrier.
9-7
The directional blocking relay is a reversed mho relay set 150% beyond the
tripping relay of the remote terminal.
An electromechanical relay may be offset to cover the bus at the relay location.
9-8
In blocking scheme, blocking signal sent only when fault occurs. Failure such that
no signal is sent results in failure to block, i.e. a false trip.
Unblocking scheme uses a low energy continuous signal and frequency shifts
when fault occurs.
9-9
Each terminal only receives the remote transmitter.
Scheme is not secure- Can trip on noise.
Two sets can be used, requiring both receivers to operate.
9-10
Requires Ru functions that have the capability to be switched when trip signal is
received.
For internal fault, trip is initiated at local end and extends remote zone 1 reach
beyond beyond line to allow remote end to trip
9-11
PUTT-. Local instantaneous relay trips for close-in fault.
9-12
Differential scheme that compares the phase angle between currents at the two ends of the
line.
No voltage is required. No phase fault identification. No inherent backup. May require
distance relay for fault initiation.
9-13
Uses a metallic or fiber cable to compare a voltage signal developed at each end.
Voltage is derived from current at each end through a mixing circuit.
Depending on relay design can be a tripping or a blocking scheme.
9-14
There are two main types of current differential relaying
schemes.
The currents at each terminal are combined into a
composite signal which is compared at each terminal. Similar
to wire pilot.
Individual phase currents are sampled and
converted into a digital signal.Similar to phase comparison.
Current differential schemes are more sensitive than distance
relay schemes and they do not require a potential source.
They are not affected by system swings but do not have
inherent backup.
9-15
Current differential schemes tend to be more sensitive than distance type
schemes since they respond only to current. This makes them more dependable
at a cost to security.
The communication channel is a vital factor And must be highly dependable.
There is no inherent backup.
9-16
In a digital implementation, the traditional percentage restraint current differential
characteristic can be improved with an adaptive restraint based on fault current
9-17
Master-Remote configuration
Includes 2nd and 5th harmonics
Voltage inversion has no effect
Master station directs trip output
Can provide o/c, and distance functions
9-18
9-19
The Master relay receives current from all other relays and performs the
current differential calculation.
The Remote relay transmits current data but does not receive current data.
9-20
Typical current differential application on a three-terminal line.each relay
exchanges current differential with both remote terminals.
All relays operate in the Master mode.
Redundant channels increase dependability at a cost
9-21
An adaptive approach for charging current has been developed which allows the relay
setting to compensate for this factor.
A useful estimating number is 0.2 megohms per mile regardless of transmission line
voltage.
Short lines vs long lines
9-22
Allows multi-terminal protection by Master-Remote
configuration. Current value sent to all terminals
Includes 2nd and 5th harmonics for transformer
Protection.
With series compensation, voltage inversion has no effect
Master station directs trip output
Can provide o/c, and distance functions provided
voltage is connected to relay
9-23
Modern Power System Protection: Applications
and Performance Analysis
TAB 10
Transformer Protection
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
10
Transformer Protection
Part 1
FUSE COORDINATION
10-1
•! Category I Transformers
10000
9000
8000
7000
6000
5000
4000
3000
2000
THROUGH-FAULT PROTECTION CURVE
FOR FAULTS WHICH WILL OCCUR
1000 FREQUENTLY OR INFREQUENTLY
900
800
700
600
500
400
300
200
100
90
80
70
TIME (seconds)
60
50
40
CATEGORY I TRANSFORMERS
30
5 to 500 kVA Single-Phase
20 15 to 500 kVA Three-Phase
10
9
8
7
6
5
4
3
DOT-DASH CURVE
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 2 3 4 5 6 7 8 9 10 20 30 40 50
•! Category II Transformers
10000
9000
8000
7000
6000 THROUGH-FAULT PROTECTION CURVE FOR THROUGH-FAULT PROTECTION CURVE FOR
5000
4000 FAULTS WHICH WILL OCCUR FREQUENTLY FAULTS WHICH WILL OCCUR INFREQUENTLY
(TYPICALLY MORE THAN 10 IN A (TYPICALLY NOT MORE THAN 10 IN A
3000
TRANSFORMER LIFETIME) TRANSFORMER LIFETIME)
2000
1000
900
800
700
600
500
400
300
200
TIME (seconds)
100
90
80
70
60
50
40
30
20
10
9
8
7
6
2 12 12 10 8 7 6 5 4 4
% TRANSFORMER IMPEDANCE THIS CURVE MAY ALSO BE USED FOR BACKUP
1
PROTECTION WHERE THE TRANSFORMER IS
0.9 EXPOSED TO FREQUENT FAULTS NORMALLY
0.8 CLEARED BY HIGH-SPEED RELAYING
0.7
0.6
0.5
0.4
CATEGORY II TRANSFORMERS
0.3 501 to 1667 kVA Single-Phase
501 to 5000 kVA Three-Phase
0.2
0.1
1 2 3 4 5 6 7 8 9 10 20 30 40 50 2 3 4 5 6 7 8 9 10 20 30 40 50
10-2
•! Category III Transformers
10000
9000
8000
7000
6000 THROUGH-FAULT PROTECTION CURVE FOR THROUGH-FAULT PROTECTION CURVE FOR
5000
4000 FAULTS WHICH WILL OCCUR FREQUENTLY FAULTS WHICH WILL OCCUR INFREQUENTLY
(TYPICALLY MORE THAN 5 IN A (TYPICALLY NOT MORE THAN 5 IN A
3000
TRANSFORMER LIFETIME) TRANSFORMER LIFETIME)
2000
1000
900
800
700
600
500
400
300
200
TIME (seconds)
100
90
80
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
12 12 10 8 7 6 5 4 4
% TRANSFORMER IMPEDANCE THIS CURVE MAY ALSO BE USED FOR BACKUP
1
PROTECTION WHERE THE TRANSFORMER IS
0.9 EXPOSED TO FREQUENT FAULTS NORMALLY
0.8 CLEARED BY HIGH-SPEED RELAYING
0.7
0.6
0.5
0.4
CATEGORY III TRANSFORMERS
0.3 1668 to 10000 kVA Single-Phase
5001 to 30000 kVA Three-Phase
0.2
0.1
1 2 3 4 5 6 7 8 9 10 20 30 40 50 2 3 4 5 6 7 8 9 10 20 30 40 50
•! Category IV Transformers
10000
9000
8000
7000
6000
5000
4000
3000
2000
THROUGH-FAULT PROTECTION CURVE
FOR FAULTS WHICH WILL OCCUR
1000 FREQUENTLY OR INFREQUENTLY
900
800
700
600
500
400
300
200
TIME (seconds)
100
90
80
70
60
50
40
30
CATEGORY IV TRANSFORMERS
20 Above 10000 kVA Single-Phase
Above 30000 kVA Three-Phase
10
9
8
7
6
5
4
3
2 12 12 10 8 7 6 5 4
4
% TRANSFORMER IMPEDANCE
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 2 3 4 5 6 7 8 9 10 20 30 40 50 2 3 4 5 6 7 8 9 10 20 30 40 50
10-3
INRUSH
7.8%
IMP
Transf 3Ph 7500 kVA Thermal A347.22
65E
115KV
7.5MVA 12KV 65E-Total Clear
1,000 60,000
10 600
65E-Total Cle ar
.1 6
.01 .6
1100
1,0000
10,0000
100,0000
1,000,0000
10-4
1,000 60,000
.01 .6
100
1,000
10,000
100,000
1,000,000
FIGURE 4
Current in Amperes
1,000 60,000
INRUSH
100 6,000
12.5 KV OC
TAP 8, TD 3
Tr 3Ph 12000 kVA Thermal A555.56 Time In Cycles (60-hz basis)
10 12% 600
Time In Seconds
IMP
51 20/1
Tr 3Ph 12000 kVA M echanical A555.56
1
115KV 12% 51 HI SIDE 60
60/1
OC 115KV
12/16/20 MVA
N TAP 8, TD 3
.1
60/1 O G 6
.01 .6
100
1,000
10,000
100,000
1,000,000
Current in Amperes
10-5
1,000 60,000
GRD COORDINATION
FDR,
300PU,TAP 4, TD 4
TD 8.00
12.5KV
240PU, TD 4.00
4000A
.01 .6
FAULT
100
1,000
10,000
100,000
1,000,000
Current in Amperes
1,000 60,000
GRD COORDINATION
10 600
160PU, TD 3.00
.1 6
300
300PU, TD 88.00
00
240PU, TD 4.00
.01 .6
00
00
00
00
00
10
1,00
10,00
100,00
1,000,00
Curre nt in Ampe re s
10-6
230 KV
TAP 5 51 300/5
60 MVA
( 151 A )
25 MVA 40 MVA
(1047A) (335 A) 87
TAP 5 51 2000/5 51 600/5
13.8 KV 69 KV
O G G O
1,000 60,000
60 MVA = 151 A @ 230 KV
THERMAL DAMAGE
100 6,000
MECHANICAL DAMAGE
1 60
300PU, TD 3
.1 6
25MVA = 1047 A @ 13.8 KV
2000PU, TD 3.00
.01 .6
1,000
10,000
100,000
1,000,000
Current in Amperes
10-7
10-8
Transformer Protection
Part 2
10-9
Transformer Fusing
•! Normally used at 10MVA and below
•! Reference transformer damage curves IEEE
C37.90
•! Selected to fit below damage curve
•! Fuses must be coordinated with relays
13KV
8378 A
10-10
FAULT CURRENTS IN 69KV FUSE FOR
3 O FAULTS ON THE 13KV BUS
13KV
3701 A
13KV
9633 A
10-11
FAULT CURRENTS IN 69KV FUSE FOR
GRD. FAULTS ON THE 13KV BUS
ON 100 MVA BASE
SYSTEM !Z" 20% CASE 1, 4 % = 33 %
427 A CASE 2, 12 % = 100 %
FUSE SIZE 125 A
= 15 MVA @ 69KV
BANK = 12 MVA GRD. FAULT ON 13KV BUS
CASE 1, I = 1047 A @ 69KV
CASE 2, I = 427 A @ 69KV
13KV
3930 A
427 A 427 A
X 3930 A
10-12
1 0 0 ,0 0 0 6 ,0 0 0 ,0 0 0
1 ,0 0 0 6 0 ,0 0 0
697
100 6 ,0 0 0
10 600
T ran sfo
f rm er 3 P h 1 2 0 0 0 k VA T h erm all A 1 0 0 .44 1
1 60
427
GR D
B K 12%%
.1 1047 6
GR D
B K 4% 1 2 5 E -T o t al Clear
.0 1 .6
10 0
1,00 0
10,00 0
100,00 0
Current in Amperes
10-13
FAULT CURRENTS IN 69KV FUSE FOR
FAULTS ON THE 13KV BUS
ON 100 MVA BASE
SYSTEM !Z" 20% CASE 2, 12 % = 100 %
381 A 381 A
FUSE SIZE 125 A
= 15 MVA @ 69KV
BK 12 MVA
X
7016 A
10-14
•! Transformer Differential Relays
Percentage Differential
PROTECTED
ZONE
(PHASE A)
OP
R1 R2
87T
10-15
External Fault
PROTECTED
ZONE
(PHASE A)
OP
R1 R2
87T
Internal Fault
PROTECTED
ZONE
(PHASE A)
OP
R1 R2
87T
10-16
Current Matching
5
OPERATING
COIL
R1 5 R2
10 5
RESTRAINT
COILS
Current Matching
RELAY
INPUT
MATCHING
CTS
TAPS
ELECTRONICS
OPERATE RESTRAINT
COMPARATOR
10-17
ANSI Standard 3 Phase
Transformer
X1-X3
H3 X3
H2 X2
H1 X1
H0
H2 X2
X1
H1 H3
X3
87
T
10-18
Phase Shift Compensation
1 A 1 A
C C
3 3 2 B 3 3 3 2 B 3
1 A 1 A
3 3 3 3
2 B 2 B
0 0
3 C 3 C
0 0
3 3
0
C C
0 0 3 6 6 3
3 3
B B
3 3 3 3
A A
10-19
•! Percentage Differential Characteristic
2.33
10-20
Magnetizing Inrush
ie
Æ
ÆR ÆR Time
Transformer Transformer
Deenergized Reenergized
at This Point at This Point
Magnetizing Inrush
is
!Max
!1
+!Max
ie
! !R !R
Time
!Max
Transformer Transformer
Deenergized Reenergized
at This Point at This Point
10-21
Inrush Waveform
DEAD SPOT
SUB. 202
500/230kV TX 2
500kV Current
A Phase
B Phase
C Phase
10-22
Sympathetic Inrush
IE
IS XS SOURCE
IP
RS
IE IP
T2 T1
IS
Overexcitation
OPEN
A) G S
S - POWER SYSTEM
10-23
•! Figure 17 in Transformer Protection Application Guide
%
100
M agnetizing current Im
80
I3 (% of I1 )
60
IM (% of In )
40
I5(% of I1 )
20
I7 (% of I1 )
Autotransformer Application
R1
R2 0P
R3
10-24
Bus/Transformer Application
CS
R1 R2 R3 R4
0P
R5
Bus/Transformer Application
1 2 3 4
30A 20A R1
20A
0P
R2
0
10-25
CT Error Produces Incorrect
Operation
20A OPERATING
POINT
OPERATING
OPERATI NG
ZONE
20A
MAXIMUM RESTRAINT
10-26
Sudden Pressure Relay (SPR)
under oil
GAS
TANK WALL
SPR
VALVES
TOP VIEW
SPR
SPR
10-27
Sudden Pressure Relay (SPR)
Gas Space
GAS SPR
SPR
3 8 EQUALIZER PORT
63X
63
63X
63 TRIP AND/OR
86 ALARM
86 86
RESISTORS
DETERMINED
BY BATTERY
VOLTAGE
(-)
63-FAULT PRESSURE RELAY
63X-FAULT PRESSURE AUXILIARY RELAY
10-28
Sudden Pressure and Gas
Accumulation Relay
OIL LEVEL BUCKHOLZ RELAY
BUCKHOLZ RELAY
10-29
115kV A
•! Application CS
•! Examples
T1 T2
30
MVA
RG
RG
D
13.8
C kV
N.C. F2
F1
115kV A
•! DIFFERENTIAL CS
300/5
T1 T2
30 87
MVA T
RG
2000/5 RG
D
13.8
C kV
N.C. F2
F1
10-30
115kV A
•! PARTIAL CS
•! DIFFERENTIAL
T1 T2
30
MVA
RG
RG
2000/5
51N- 51
3
B
D
13.8
C kV
N.C. 2000/5 F2
F1
115kV A
•! GROUND CS
•! PROTECTION
T1 T2
200/5 30
MVA
RG
51N- RG
2
2000/5
51N-
3
B
D
13.8
C kV
N.C. 2000/5 F2
F1
10-31
115kV A
•! PHASE CS
•! OVERCURRENT 50/
51
300/5
T1 T2
30
MVA
RG
RG
2000/5
D
C 13.8
kV
N.C. 2000/5 F2
F1
115kV A
•! GROUND CS
•! DIFFERENTIAL
T1 T2
200/5
30
MVA
RG
RG
2000/5
87N
POL
D
13.8
C kV
N.C. 2000/5 F2
F1
10-32
115kV A
•! GROUND
CS
•! DIFFERENTIAL
•! Bkr C Open
200A
T1 T2
200/5
30
External O-G Fault MVA
200A RG
5A
RG
0.5A
2000/5
87N 200A
5A
POL
5A
87N 5A 5A 0.5A
OP 0.5A
10/1 51N- 51
ACT 3
0A B
D
13.8
C kV
OPEN 2000/5 F2
F1
200A
115kV A
•! GROUND
CS
•! DIFFERENTIAL
•! Bkr C Closed
200A
T1 T2
200/5
30
MVA
200A RG
5A
200A RG 200A
2000/5
200A
5A 87N
POL 5A 0.5A
87N 5A 5A 1.0A
OP 0.5A
1/10 51N- 51
ACT 3
0A B 0.5A
0.5A
D
13.8
C kV
N.C. 2000/5 F2
200A
F1
External O-G Fault
400AMPS
10-33
115kV A
•! GROUND
CS
•! DIFFERENTIAL
•! Bkr C Closed
200A
T1 T2
200/5
30
External O-G Fault MVA
RG
5A
RG
0.5A
2000/5
200A
5A 87N 0.5A
POL
87N 5A 5A
OP 0.5A
1/10 51N- 51
ACT 3 200A
0A B
0.5A
0.5A
D
13.8
C kV
N.C. 2000/5 F2
200A
F1
400AMPS
115kV A
•! GROUND
CS
•! DIFFERENTIAL
•! Bkr C Closed
200A
T1 T2
200/5
30
MVA
Internal O-G Fault 200A RG
5A
400AMPS
200A RG
200A
2000/5 0.5A
5A 87N
POL 5A
200A
F1
10-34
115kV A
•! CURRENT CS
•! REVERSAL
T1 T2
200/5
30
MVA
RG
RG
67
2000/5
67N 67N
POL OP
1/10 ACT
51N- 51
3
B
D
13.8
C kV
N.C. 2000/5 F2
F1
67
POL
115kV A
•! CURRENT
•! REVERSAL CS
•! 13.8kV
•! Phase
•! Fault
T1 T2
200/5 30
MVA
RG
5A 2000A
RG
67
2000/5
67N 67N
POL OP
2000A
1/10 ACT 5A
51N- 51
3
B
5A 5A
D
13.8
C kV
N.C. 2000/5 F2
F1 2000A
67
POL
4000A
10-35
OPEN
115kV A
•! CURRENT PHASE P2 P1
•! REVERSAL FAULT CS G2 G1
•! 115kV Phase
•! Fault -
•! CS Fails to Open
T1 T2
200/5 30
MVA
RG
2000A
RG
67
2000/5 REVERSE
67N 67N
POL OP
2000A
1/10 ACT
5A
51N- 51
3
B
5A
D
13.8
C kV
N.C. 2000/5 F2
F1 2000A
67
POL
115kV A
•! 115kV
CS
•! RESIDUAL
•! GROUND 51N-
1
T1 T2
30
MVA
RG
RG
D
13.8
C kV
N.C. F2
F1
10-36
115kV A
•! Combine all P2 P1
•! relays and CS G2 G1
63
T1 T2
30 87
MVA T
RG 86-
51N- 1
2 RG
67N 67
POL
67N
87N OP
POL
87N
0P
51N- 51
3
D
13.8
C kV
N.C. F2
F1
Power Transformer:
50 MVA 138/69kV ! - Wye
10-37
•! Differential Protection Connection Two-Winding Wye-Delta
Transformer Bank
•! (138kV, 69kV, 50MVA)
FULL LOAD
209A RELAY
4.18A
250/5
250/5 500/5
10-38
Differential Protection Connection Two-Winding Wye-
Delta Transformer Bank
(138kV, 69kV, 50MVA)
250/5 500/5
10-39
•! Transformer Differential Relays
•! Load Tap Changing Transformer (10%)
Power Transformer:
230 / 69 / 13.8kV
230kV = 60MVA Wye
69kV = 40MVA Wye
13.8kV = 25MVA Delta
10-40
DIFFERENTIAL PROTECTION FOR
MULTIWINDING TRANSFORMERS
150/5 400/5
150/5 400/5
10-41
•! Transformer Differential Relays
•! CT Ratio Selection
Sources 52 52 Sources
52
Difference
Current
Fault
OP
R R
10-42
•! Potential loss of restraint that may result by paralleling
circuits in differential protection (full restraint)
Breaker open
Transformer
Sources 52 52 Sources
52
Fault
OP
R R
Auto or
Three Winding
Transformer
Bank
52 52
OP
R R
R R
10-43
•! Single-line differential connections for multiple connections to
transformers
52 52
Transformer
Bank
52 52
OP
R R
R R
10-44
Relay Operation Analysis 1
X Y Z
LINE 2 LINE 1
D C A X B
FAULT
OSC LINE CURRENT
BUS OSC
PT NEUTRAL
OSC
A-G FAULT
A
BUS PT
C
LINE CURRENT
C
DEAD TIME LINE
LOAD CURRENT
NEUTRAL CURRENT CHARGING
10-45
CATEGORIZING REC' CARRIER
"A" GOOD, "B" QUESTIONABLE
FAULT
RECLOSE TIME
LOAD
A CARRIER OFF
INTERNAL FAULT
LOAD LOAD
CARRIER ON
A
EXTERNAL FAULT
B
CARRIER "ON".
B TRIP DELAYED
CARRIER "OFF". CARRIER "OFF".
2 CYCLES AT
RECLOSURE
INTERNAL FAULT
10-46
CATEGORIZING REC' CARRIER
"A" GOOD, "B" QUESTIONABLE
FAULT
B
LOAD
ON ON
B OFF OFF
INTERNAL FAULT
EXT. FAULT
EXT. BKR. "A" TRIP EXT.LINE "1" REEN.
LOAD
LOAD
ON
A GOOD OFF
LINE 1 TRIP
LINE 2 TRIP
LOAD
ON
B BAD OFF
10-47
X Y Z
LINE 2 LINE 1
D C A X B
FAULT
OSC LINE CURRENT
BUS OSC
PT NEUTRAL
OSC
A-G FAULT
BUS PT A
C
LINE CURRENT
C
DEAD TIME LINE
LOAD CURRENT
NEUTRAL CURRENT CHARGING
!"#$%&'()(*%+&,$'"#(&*-+
!""+%&&./+!0"+12$-#(&*"03$+
A
B
A MAGNITUDE
B
D.C. OFFSET
RESTRIKE
10-48
3 ~ BKR 5 ~ BKR z2
PRE
FAULT 1000 A
z1
FAULT FAULT
z1
Z1 + Z2 + CARRIER
z3
3 ~ BKR
PRE
FAULT z1 z2 z3
800A
z2
FAULT Z2 + CARRIER
z1
EXPECTED
TARGETS
3000 A Z1
Z2 + CARRIER
INSTANTANEOUS
OVERCURRENT
10-49
z1 z2 z3
3 ~ BKR
PRE
FAULT
600A
FAULT
30 CYCLES
B z2
TARGETS Z2 TIME
INDICATIONS: z1
BKR. @ !A" TRIPPED TO :
A
1) CLEAR STUCK BKR @ !B"
2) BACKUP LOCAL BKR. FAILURE AT !B:
R R
LINE PT
BUS PT
FAULT CURRENT
BUS VOLTAGE
LINE VOLTAGE
10-50
LINE POTENTIAL WITH LINE REACTOR
FAULT
A X B
R R
LINE PT
BUS PT
FAULT CURRENT
LINE VOLTAGE
RECLOSING TIME
FAULT
A X 161 KV LINE
B
R R
BKRS A @ B TRIP BKRS A @ B RECLOSE
LOAD LOAD
TIMING WAVE
10-51
CURRENT REVERSAL
14000 A
X A B Y
2000 A
X
LINE 1
2000 A 2000 A
LINE 2
2000 A OSC
C D
P P
G G
8000 A
2000 A
OSC
INITIAL FAULT
"D" BLOCKS "C"
CURRENT REVERSAL
X A B Y
6000 A
X
LINE 1
1000 A 1000 A
LINE 2
4000 A OSC
C D
P P
OSC
"C" BLOCKS "D"
10-52
CURRENT REVERSAL
X A B Y
LINE 1
LINE 2
OSC
C D
P P
NEUTRAL CURRENT
@ STATION Y
3000A
10-53
W1 W2
W1
OSCILOGRAPHY FROM
OP MICRO-PROCESSOR RELAY
W2
CT ROLLED
0
NOTE 30 SHIFT AS A RESULT OF
CONNECTING CTS WYE-WYE ACROSS
A DELTA-WYE TRANSFORMER
MOTOR
W1 W2
R
W1
OP
W2
0 OSCILOGRAPHY FROM
R 30 SHIFT
MICRO-PROCESSOR RELAY
CT CORRECTED
MOTOR
10-54
10-55
10-56
51X FAST BUS PROTECTION
10-57
SOLUTION
0 BLOCKING
672P 2~ SIGNAL
10-58
Relay Operation Analysis 2
10-59
Three-Winding Transformer
!Zero-Sequence Equivalent"
Zp Zs
Zt
100MVABASE
Zps = 15%, Zpt = 43.3%, Zst = 11.67%
CALCULATIONS
Zp = 1/2 (+15 + 43.3 - 11.67) = +23.3%
Zs = 1/2 (+15 - 43.3 + 11.67) = - 8.3%
Zt = 1/2 ( -15 + 43.3 - 11.67) = +20.0%
10-60
Calculations
161 KV BANK 69 KV
SYS SYS
10 23.3 - 8.3 30
Z0
P0 S0
20
161 KV BANK 69 KV
SYS
CALCULATIONS SYS
Z 1 = Z 2 1.0 23.3 - 8.3 10
1 + 1 = 1 X
P1 S1
X Y Z Z
1 + 1 = 1
10 10 Z Z0 10 23.3 - 8.3 30
Y
2 = 1 =Z=5 P0 S0
10 Z 20
1 1 1 1 1 1
+ = + =
1 25 Z1 21.7 20 Z0
1 1
1 + .04 = ! Z 1 = 0.96 .046 + .05 = ! Z0 = 10.4
Z1 Z0 23.3
1 1 1 33.7
+ =
33.7 10 Z0
1
.03 + .10 = Z ! Z 0 = 7.7
0
Z g = Z1+Z2+Z0 = 2 (0.96) + 7.7 = 9.62 = 3.2
3
3
10-61
161 KV BANK 69 KV
SYS SYS
10-62
161 KV BANK 69 KV
SYS SYS
69 KV GRD. FAULT
S 1754 A
P
T
15,789 A
CALCULATIONS 2,256 A
14,035 A
69 KV FAULT @ S1 & S0 300/5 600/5
39 A 117 A
Z1 16 .0625
10 .1 79 A
6.15 .1625
10-63
Current Distribution
8620 A P S 1754 A
S P
T T
11,206 A 15789 A
19 A 79 A
T
11,206 A
P 2586 A 2891 A P
START START
G 19 A G
DIR DIR
G G
10.8 A 12 A
10-64
CT SATURATION CAUSES REVERSED
POLARIZATION OF LINE GROUND RELAY
500 KV 161 KV
X
E
Z A
FAULT
C
CT SAT
C -G
CARRIER B C
500 KV
NEUTRAL
STA. NEUTRAL
BKR B C CURRENT
500 KV NEUTRAL
STA. NEUTRAL
LINE Z CARRIER
BKR. E C! CURRENT
500 KV NEUTRAL
STA. NEUTRAL
LINE Z CARRIER
10-65
D.C. OFFSET
PRIMARY AND
A SECONDARY CURRENT
PRIMARY CURRENT
SECONDARY CURRENT
500 KV
400 MVA DITTO DITTO DITTO
NEUTRAL
REACTOR 400
FAILURE 1 MVA G 2
3
1
2
3
4
A!
B!
C!
10-66
RESTRIKE PHENOMENA
VOLTAGE
DIELECTRIC
TIME a
INTERRUPTER
LIGHTNING RESTRIKE LINE BAYONET
b
LINE FAULT
c
BUS FAULT
TANK
10-67
RESTRIKE
RESTRIKE
TANK FLASHOVER
FAULT TO TANK
(Bus Fault)
RESTRIKE ACROSS
INTERRUPTER
10-68
10-69
P
P P
START G
0.5 A
G G DIR
G
1A
ASSUME PU OF
G G ALL GRD RELAYS
P P P P
300/5 600/5
G G G G
1A
G G G G
P P
START G
0.5 A
G G DIR
G
1A
ASSUME PU OF
G G ALL GRD RELAYS
P P P P
300/5 600/5
G G G G
1A
G G G G
10-70
AIR BLAST BREAKER
X
LINE RELAYS
RESISTOR FAILED
B.F. RELAYS
10-71
10-72
Va
Vb
Vc
CHARLESTON
Ic BOWATER ATHENS
Vb ATH
Ir
In
MOTORS
Va
Vb
Vc
CHARLESTON
Ic BOWATER ATHENS
Vb ATH
Ir
In
MOTORS
10-73
Va
Vb
Vc
CHARLESTON
Ic BOWATER ATHENS
Vb ATH
UNDER FREQ = 58HZ
Ir TRIP TIME = 40CY
UNDER VOLT = 85%
In
MOTORS TRIP TIME = 60CY
DFR DFR
5L92 5L94
5MB1
87 87
B BS Lightning
Arrestor
Transformer
T1
To 230 kV
10-74
A Real World Signal (During Lightning Storm)
10-75
11
Modern Power System Protection: Applications
and Performance Analysis
TAB 11
Transmission Station Design
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
11-1
Simplest, least cost, least flexible maintenance, requires outage of line.
11-2
To maintain a breaker switch all breakers to bus 1, bypass the breaker
and use bus tie breaker as line breaker. During switching, Bus differential is
disabled. Bus tie line relays must accommodate all settings.
11-3
Most expensive. Most flexible..
No switching required.
Allows any bus or breaker to be removed without outage
Bus fault affects only one bus.
11-4
Usually a breaker-and a-half station in transit.
11-5
Breaker-and-a-half is most commonly used EHV bus arrangement . Allows same
flexibility as 2-bus,2-breaker scheme at lower cost.
No switching required for maintenance
Bus faults do not effect system integrity
11-6
Actually the line relays consists of duplicate primary and backup relays.
The middle breaker, therefore, has 4 set of CTs plus metering.
No switching required for maintenance.
11-7
Loss of remote ends results in loss of intermediate loads.
As systems mature it is increasingly difficult for remote ends to see all faults
because of infeed.
11-8
When conditions are normal, the bridge is balanced and no current flows in the relay.
When an external fault occurs, if all of the CT!s reproduce the current accurately, the
is still balanced.
When an internal fault occurs, the balance is disrupted and current will flow through the
relay.
If the CT!s do not reproduce the current accurately, the error will flow through the relay
and it must be set above this error.
11-9
Avoids reduced protection from setting above error current
Relays have restraint and operating coils
Use one restraint coil for each phase of each source circuit
Use on operating coil per phase
Required operating current is proportional to the current in the restraint windings
11-10
This relay design avoids the CT core saturation by assuming
complete CT saturation
The relay discriminates between internal and external faults by the relative
magnitude of the voltage across junction points
11-11
External fault on line C-CT will saturate
and produce no secondary current.
11-12
V87B =2 x 60 a = 120 volts
11-13
V 87B = 70 x 2600 = 182 kV
Limited by the variable resistor
11-14
Uses Linear couplers (air core mutual reactors)
11-15
Moderately high impedance relay is a variation of the High Impedance relay.
Directional Impedance relay looks back through the bus a short distance into
connected circuits. Requires directional, relay fault detector and timer. All
contacts connected in series.
11-16
Modern Power System Protection: Applications
12
and Performance Analysis
TAB 12
Bus, Capacitor, and Reactor Protection
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
!"#$%&'(()*+(
&,,&-./0/-!+(
12-1
SINGLE BREAKER - SINGLE BUS
1 2
A B
BUS
C D
3 4
FIGURE B1
12-2
DOUBLE BUS WITH BUS TIE
BUS A DIFF ZONE
BUS B DIFF ZONE
BUS A BUS B
T
F1 F2 F3 F4
1 2 3 4
FIGURE B2
12-3
DOUBLE BUS - SINGLE BREAKER
BUS 1
BUS 2
F3 F4
BUS 2 DIFF ZONE
FIGURE B3
(NORMAL)
F1 F2
BUS 1
BUS 2
F3 F4
BUS 2 DIFF
ZONE
FIGURE B4
(F1 OFF LINE)
12-4
DOUBLE BUS - SINGLE BREAKER
FIGURES B3 AND B4
HIGH FLEXIBILITY
12-5
DOUBLE BUS - DOUBLE BREAKER
BUS 1 DIFF. ZONE
BUS 1
A1 B1 C1
A2 B2 C2
BUS 2
BUS 2 DIFF. ZONE
FIGURE B5
12-6
RING BUS
LINE 2
A B
LINE 1 1 2
4 3 LINE 3
C D
LINE 4
FIGURE B6
RING BUS
ADD LINE 5 AND BREAKER "E"
LINE 2 LINE 5
A E B
LINE 1 1
2
4 5 3 LINE 3
C D
LINE 4
FIGURE B7
12-7
RING BUS
FIGURES B6 AND B7
ADVANTAGES
HIGH FLEXIBILITY
MORE COMMON AT HIGH VOLTAGES
MINIMUM NUMBER OF BREAKERS
ECONOMICAL
EASY TO EXPAND RING (FIGURE B7)
RING BUS
FIGURES B6 AND B7
DISADVANTAGES
WITH RING OPEN (BKR. MAINTENANCE), A
FAULT MAY SPLIT RING
FOR A BREAKER FAILURE A REMOTE
BREAKER MUST CLEAR THE FAULT
DURING BREAKER MAINTENANCE RELAYS
MUST REMAIN IN SERVICE
MUST USE LINE PT'S
ALL FAULTS MUST TRIP TWO BREAKERS
CURRENTS IN LOOP MAY NOT BALANCE
12-8
BREAKER - AND - A - HALF
BUS 1 DIFF ZONE
BUS 1
T T
LINE 1 LINE 2
BANK
T T
DIFF
ZONE
LINE 3
T T
BUS 2
FIGURE B8
BUS 1
T T
LINE 1 LINE 2
BANK
T T
DIFF
ZONE
LINE 3
T T
BUS 2
FIGURE B8
12-9
BREAKER - AND - A - HALF
FIGURE B9
COMMENTS
GOOD OPERATING FLEXIBILITY
REQUIRES MORE BKRS. THAN RING BUS
LINE SIDE POTENTIALS
RELAYS MUST REMAIN IN SERVICE
FOR BREAKER OUTAGE
"B2" OUT FOR MAINT. A FAULT ON
LINE 2 WILL ALSO INTERRUPT LINE 3
A BUS FAULT WILL NOT INTERRUPT
LINES
12-10
MAIN AND TRANSFER
BUS
LR LR
SR
A C
LO
BK
B I
TRANSFER
BUS
BUS
LO BK
OC I
13 KV
BK
69 KV
FIGURE B10
12-11
A C
MAIN
BUS
BUS
B
BK
13 KV
69 KV
LR LR
SR
A C
LO
BK 1A 1A
B I
2A TRANSFER
BUS
BUS
2A LO BK
3.5A OC I
13 KV 2A BK POSITION
BK NORMAL
1.75A 69 KV 1.75A
FIGURE B11
12-12
MAIN AND TRANSFER BUS
161 KV MAIN BUS
LR LR
SR
A C
LO
BK 1A 1A
B I
2A TRANSFER
BUS
BUS
2A LO BK
3.5A OC I
13 KV 2A INTERMEDIATE
BK POSITION
69 KV 1.75A
1.75A
FIGURE B12
A C
MAIN
BUS
B
BK
13 KV
69 KV
12-13
MAIN AND TRANSFER BUS
LR LR
SR
A C
LO
BK 1A 1A
B I
Z
TRANSFER
BUS
Y X BUS
LO BK
3.5A OC I
13 KV 2A INTERMEDIATE
BK LO SEQUENCE
1.75A 69 KV 1.75A
FIGURE B13
LR LR
SR
A C
LO
BK 0.5A 1A
B I
Z
0.5A TRANSFER
BUS
1A
Y X BUS
LO BK
3.5A OC I
13 KV 2A BKRS A & B
BK PARALLELED
69 KV 1.75A
1.75A
FIGURE B14
12-14
TRANSFER
BUS
B A C
L L
S
MAIN
BUS
BK
13 KV
69 KV
LR LR
SR
A C
LO
BK 1A
B I
Z
1A TRANSFER
BUS
1A
Y X BUS
LO BK
3.5A OC I
13 KV 2A SWITCHING
BK FINISHED
69 KV 1.75A
1.75A
FIGURE B15
12-15
TRANSFER
BUS
B A C
L L
S
MAIN
BUS
BK
13 KV
69 KV
•!NORMAL
•!SELECTOR SWITCH IN THE BANK "BK" POSITION
•! ( FIG B11 )
•!START ( FIG B12 )
•!OPEN TRIP - CUT - OUT - SWITCH "TCO" TO BOTH BUS
AND BANK DIFF. RELAYS
PLACE SELECTOR SWITCH IN THE INTERMEDIATE "INT"
POSITION
•!CLOSE "TCO" TO BANK DIFFERENTIAL RELAY
•!DIFFERENTIAL PROTECTION IS NOW EXTENDED TO
LINE SIDE CTS AND THE LOW SIDE OF EACH
TRANSFORMER WINDING
12-16
LINE "OFF" SEQUENCE FIGURE B13
12-17
12-18
+,-./011-,2#34*5+.14),4#4*3657+#
!"!#$%#
!'#$%#
'(#)%*#
"(#)%*#
'(#)%*#
"&#$%#
!#
389::/;<=><=?#39@=ABC9D:9#6DE:>@=F:#
,GH<I@J:=K#
P# S#
T#
L#
12-19
3ME<F@J#%@JH:AN#!"!O"&O!'PI#39@=ABC9D:9#6DE:>@=F:#C=#6KA#1;=#
Q@A:#
GIVEN: MVA RATING = 60 / 80 / 100#
161 / 69 = 60 MVA#
161 / 13 = 30 MVA#
69 / 13 = 30 MVA#
Zps = 9%, Zpt = 13%, Zst = 3.5%#
100MVABASE
# #
Zps = 15%, Zpt = 43.3%, Zst = 11.67%#
CALCULATIONS#
Zp = 1/2 (+15 + 43.3 - 11.67) = +23.3%#
Zs = 1/2 (+15 - 43.3 + 11.67) = - 8.3%#
Zt = 1/2 ( -15 + 43.3 - 11.67) = +20.0%#
'#
513,S#.*T-3#0T44,53#0*-0T-*3615+#*4,#Q*+,2#
+,-./011-,2#4*3657#1.#34*5+.14),4#
!"!#$%#
!'#$%#
R(#)%*#
!((#)%*#
R(#)%*#
4,-*U#VT#Q*+,2#15#W.1*X#4*3657+#
"&#$%#
Y#
12-20
0@JFHJ@ZC=A#
161 KV# BANK# 69 KV#
SYS# SYS#
NOTE: FULL LOAD @ 161 KV = 100,000 = 372 AMP X 1.25 = 465 AMP
161X 3# (APPROX. RELAY P.U.)
161 KV RELAY PU FOR 13 KV FAULT = 828 / 465 = 1.78 #
R#
+1-T3615######
Q4,*$,4##.*6-T4,##4,-*U+##65+3*--,2##15##*--###
############################!'#$%##Q4,*$,4+##
"#
12-21
741T52#Q*5$#+6[,#
3UV60*--U#[67/[*7#741T52657#Q*5$+#*4,#+6[,2#+1#3\*3#W[(X#6+##
51#-*47,4#3\*5#'#36),+#3\,#V1+636%,##%*-T,#31#V4,%,53#3\,##
T5.*T-3,2#V\*+,+#.41)#,]0,,2657#!^'#V,4#T563#%1-3*7,^#
3\,4.14,S##[!##_##[L#`#Y'^'a##_#[(#`#'#]#Y'^'#`#!'(a#
.41)#3\6+##67#`#######YYY!#*)V,4,+############`####"!R!#*)V,4,+#b#!'#$%#
#############################(^Y''##c#(^Y''#c#!^'(#O#'##
#
.41)##67###`##'#6(###`#6!##c##6L##c##6(####S##6!###_##6L####_##6(###`#"!R!##`#L(R(##*)V,4,+#
############################################################################################'#
3\T+#S######L(R(##*)V,4,+######`###Lde#*)V,4,+##65#!"!#$%#V\*+,#W03f+X##
##################!"!#O#!^e'###
####################!'#
#
#
e#
Lde#*# Lde#*#
!"!#$%#
!'#$%#
]# '(#)%*#
"(#)%*#
"!R!#*#
'(#)%*#
5#
"&#$%#
d#
12-22
GROUNDING BANKS
GROUNDING BANK
13 KV
161 KV
c
a A
69 KV
b C
B
51N
FIGURE Z 1
12-23
ZIG – ZAG GROUNDING BANK
13 KV
161 KV
A
69 KV
C
b B
a
51N
FIGURE Z 2
161 KV
a b c c
A
69 KV
C
b B
a
A B C
51N
FIGURE Z 2
12-24
Overcurrent relays are commonly used to provide protection for
grounding banks as shown in figure 9.33c
51
51 51
51N
FIGURE Z 3
12-25
ZIG – ZAG GROUNDING BANK
0A
0A
900 A x
15 A
51
51 51
15 A
900 A NOTE: ALL CT!S
300 / 5
15 A
51N
FIGURE Z 5
5A 300A=I 0
900 A 51
5A 5A 300A=I 0
3I0
51 51
300 A 300 A 300 A NOTE: ALL CT!S
300 / 5
15 A
51N
FIGURE Z 6
12-26
ZIG – ZAG GROUNDING BANK
1 1
0
2 2 2 2
0
1 1
10 A 5A
300A=I 0
5A 51 300A=I 0
600 A 5A 5A
15A
15A
900 A x 51 51
15 A
51N
FIGURE Z 7
X
900 A 5A 5A 5A
15 A
3I0
5A 10 A 15 A
R
300 A 300 A 300 A O
0A
R
15 A
900 A
EXTERNAL FAULT
NOTE: ALL CT!S
15 A
300 / 5 51N
FIGURE Z 8
12-27
ZIG – ZAG DIFFERENTIAL PROTECTION
0A
10 A 5A 5A
600 A
10 A
0A
900 A X
R
300 A 300 A 300 A O
15 A
R
900 A
INTERNAL FAULT
NOTE: ALL CT!S
51N 15 A
300 / 5 FIGURE Z 9
51 51
51 51 51 51
51N
FIGURE Z 10
12-28
ZIG-ZAG GRD. BANK RATINGS
FIGURE Z 11
•!THEREFORE:
IG = 4374 / 1.05 / 3 = 12,497 A
PURCHASE ZIG – ZAG BANK WITH
A 10 SECOND RATING = 13,000 A
ASSUME A LOAD UNBALANCE NOT TO EXCEED A
CONTINUOUS RATING OF 200A PER PHASE
OR 600A IN NEUTRAL
FIGURE Z 12
12-29
CONSIDER TWO ZIG-ZAG BANKS
FIGURE Z 13
FIGURE Z 14
12-30
!"#$$%&'()*(+',$
A 26
Z3
21 OHMS 21
66.4 KV
C
RELAY REACH @ BREAKER !A"
120,000 / 2554 A = 47 OHMS
26 OHMS
X FAULT = 2554 A
D ON 230 KV SYS.
12-31
5 OHMS BUS & B.U.
116.8 KV
A A
1600 A 1600 A
21 OHMS 21 OHMS
52
Z3
B B
21
83.2 KV
C
RELAY REACH @ BREAKER !A"
116,800 / 1600 A = 73 OHMS
26 OHMS
THIS IS CALLED !APPARENT OHMS"
ACTUAL OHMS = 47 OHMS
X FAULT = 3200 A
D ON 230 KV SYS.
12-32
BUS & B.U.
C
RELAYS AT !A" CAN NO
LONGER REACH FAULT AT !D"
X
D
12-33
DOUBLE BUS WITH BUS TIE BUS A
BUS B
12-34
ZIG - ZAG BUS WITH TRANSFER BUS
TRANSFER BUS
BU
S
BU
TRANSFER BUS
G Z2 Z1
S
BU
12-35
ZIG - ZAG BUS BREAKER FAILURE & B.U.
OHMS
15 23 9 4
BF Z1 Z2 Z3 G
TRANSFER BUS
G Z2 Z1
S
BU
TRANSFER BUS
G Z2 Z1
S
BU
12-36
BREAKER - & - A - HALF BUS
! N0 !
E CONSIDER
D OPEN
BK Z
BUS Y
12-37
BREAKER - & - A - HALF BUS
BUS X
CONSIDER
X
E OPEN X
J H BREAKER !H" FAILURE
BK T BUS !X" BKRS
!E" & !J" OPEN
F X
G BREAKER !G" OPENS
DEENERGIZING BK !T"
RING BUS
A D
ZA ZB OC ZD
DIFF
12-38
RING BUS
B E
A D
ZA ZB OC ZF ZD
ZE
DIFF
F
A B
R
R
BUS
DIFF
BK R
DIFF
12-39
12-40
BUS DIFFERENTIAL
•! HIGH IMPEDANCE
–! Pros and Cons
•! LOW IMPEDANCE
–! Pros and Cons
•! CONCLUSIONS
NUMERICAL RELAY
I1#
I2#
I1#+ I1# + I1# + I1# = IDIFF
I3#
I4#
I1 I2 I3 I4
12-41
I differential
TRIP AREA
PERCENT RESTRAINT
I differential
TRIP AREA
12-42
CT "X#
BUS
DIFF
CT "Y# CT "X#
FAULT X
12
11 2
10 TRIP
9
8 5
7
6
5
4 HIGH
3 FAULT
2 RESTAIN
1 1
0
1 2 3 4 5 6 7 8 9 10 11
6
( I1+ I2 + I3 ) * ( I - K )
RRELAY
RCT
RSTAB
X FAULT ( I1+ I2 + I3 ) * ( K )
I1 I2 I3 I4
RCT RRELAY + RSTAB
K =
RRELAY + RSTAB
0.5 * ( 0.01 + 200 )
0.5 + ( 0.01 + 200 )
K = = 0.0025
0.01 + 200
12-43
X FAULT
IM IM IM
RRELAY
RCT
VARISTOR RSTAB
VOLTAGE
EXCITATION CURVE
VARISTOR CLIP VOLTAGE 800 V
ASSUME CT!S C400
MAGNITZING CURRENT HIGH
X FAULT
IM IM IM
RRELAY
RCT
VARISTOR RSTAB
I1 NO SOURCE INPUT
( WORST CASE )
800V
40 AMP X 200 OHM = 8000 V TRANSFORMER
EXCITATION CURVE
VARISTOR CLIP VOLTAGE 400 V 400V
ASSUME CT!S C800
VOLTAGE
12-44
REQUIREMENTS FOR HIGH IMPEDANCE DIFFERENTIAL RELAYS
4.! WIRING INSULATION MUST BE RATED HIGER THAN THE VARISTOR VOLTAGE LIMIT
6.! EACH BUS ZONE NEEDS A DEDICATED RELAY WITH DEDICATED CT!S
SWITCHING OF CT!S
12-45
12-46
!"#"!$%&'((#'&%)!%$&*(
PROTECTION CONSIDERATIONS
12-47
BASIC CAPACITOR BANK CONNECTIONS
B B
C
C C
!CAN" FAILURE AT !B" RESULTS IN A 1.73 % INCREASE
IN VOLTAGE & CURRENT ACROSS CAPACITORS !A" & !C"
AND A 3 FOLD INCREASE IN POWER CONSUMPTION ON
REMAINING CAPACITORS AT !A" & !C" UNTIL !B" FUSE
OPENS. THEN VOLTAGE REDUCES TO 0.867 OF NOMINAL
12-48
DISTRIBUTION CAPACITOR PROTECTION
GROUNDED
A A
C C
!CAN" FAILURE AT !B" RESULTS IN A BLOWN FUSE AT
!B" AND NOMINAL VOLTAGE ACROSS REMAINING FUSES.
HOWEVER, SYSTEM IS SUBJECTED TO HIGH GROUND
FAULTS AT THE STATION.
SOLUTION:
PLACE TWO CANS IN
SERIES PER PHASE
C
12-49
DISTRIBUTION CAPACITOR PROTECTION
UNGROUNDED
A
C
PARALLEL CONNECTION
OF CAPACITOR UNITS
12-50
EXTERNALLY FUSED CAPACITORS
12-51
CAPACITOR FUSING
CAPACITOR UNIT CASE RUPTURE WILL
BE AVOIDED IF, FOR ALL NUMBER OF
SERIES GROUPS OF PACKS SHORTED,
THE TOTAL CLEARING TIME OF THE
FUSE IS LESS THAN THE TIME
PERMITTED ON THE CASE RUPTURE
CURVE.
CAPACITOR FUSING
12-52
CAPACITOR FUSING
12-53
CAPACITOR FUSING
I2t = kE2 C3
L
I2t = kE2 C3
L
EXAMPLE:
Single 1200 KVAR , 13.8 kv , With Two 200KVAR Capacitor Units
Per Phase with an available station short circuit current of 5000 amperes
12-54
CAPACITOR FUSING
Example: Outrush Currents For Nearby Faults
12-55
69KV
Es
Es
BANK = 12 MVA Er IX
7% = 58% on I IR
13KV
100mva Base
Er Es
Es
Formula: IX
% Rise = Kvar ( jX) Er
I IR
105
Unity PF
! = 5400 (58) = 3.1 %
105
C 51
50
12-56
GROUNDED UNBALANCED PROTECTION
•!PROVIDES NO COMPENSATION
FOR INHERENT CAPACITOR
BANK UNBALANCES
•!PROVIDES COMPENSATION
FOR INHERENT CAPACITOR
BANK UNBALANCES
•!BLOCKS GROUND
HARMONIC CURRENTS
VR
12-57
UNGROUNDED UNBALANCED PROTECTION
VLN
ASSUME 14 CANS IN EACH
PARALLEL GROUP
TASK:
CALCULATE VO FOR ONE CAN FAILURE
VO 3 P VLN
FROM: VO =
2 F + ( 3 S )( P-F )
VR
WHERE:
P = # OF CANS IN PARALLEL GROUP
VLN = LINE TO NEUTRAL VOLTAGE
F = # OF CANS !OUT" IN PARRALEL GROUP
S = # OF SERIES GROUPS
VO = 23,433 VOLTS
23,433
VO PER UNIT =
22,130 (RATED)
12-58
UNGROUNDED UNBALANCED PROTECTION
VLN EXAMPLE:
ASSUME 14 CANS IN EACH VLN = 66,394 VOLTS (115 KV O TO O)
PARALLEL GROUP P = 14
F = 2 ( CHANGE )
S = 3
3 P VLN
FROM: VO =
2 F + ( 3 S )( P-F )
VO
VO = 24,898 VOLTS
24,898
VO PER UNIT =
VR 22,130 (RATED)
F VLN
FROM: VR =
2 F + ( 3 S )( P-F )
VO
F =1
66,394
VR = = 558 VOLTS
VR 119
F =2
2 X 66,394
VR = = 1186 VOLTS
112
12-59
12-60
LARGE !EHV" CAPACITOR BANK
OVERCURRENT RELAYS
GROUNDED WYE MIN. PU.
52 50 135 % OF NOMINAL PHASE !I"
51N
51 UNGROUNDED WYE MIN. PU.
BUS DIFF 50 125 % OF NOMINAL PHASE !I"
51 INST. RELAYS SET TO OVERRIDE
INRUSH OR OUTRUSH TRANS.
59B REDUNDANT OVERCURRENTS
SHUNT
CAP. TRIP CAP. BANK INST. FOR
27B
BANK SEVERE OV CONDITIONS.
VOLT PROVIDE TIMER TO OVERRIDE
DIFF TRANSIENT OVERVOLTAGES
RELAY
DETECTS LOSS OF SYS. VOLT.
TRIPS WITH TIME DELAY
UNBAL
PROT
RELAY
12-61
LARGE !EHV" CAPACITOR BANK
UNBALANCE CONTINUED
52 50 FAILURE TO PROVIDE MAY CAUSE:
51N
51
•!EXCESSIVE DAMAGE TO BANK
BUS DIFF 50 •!ADVERSE SYSTEM EFFECTS
51 •!DAMAGE TO OTHER EQUIPMENT
•!UNAVAILABILITY OF DAMAGED
59B EQUIPMENT
SHUNT •!CASE RUPTURE, DISCHARGE OF
CAP. LIQUID AND FIRE
27B
BANK
VOLT
DIFF
RELAY
UNBAL
PROT
RELAY
12-62
A A
B B
C C
12-63
INTERNALLY FUSE CAPACITORS
12-64
FUSELESS CAPACITORS
12-65
12-66
!"#$%&!''(!&%"$%)&*'
!"#$%&!+'''',!-'.'%-("'
500 KV
13 KV
X
161 KV A A A
RES
PD PD PD
12-67
!"#$%&!'''(!)'*'%)+"'',-%.'''/!(0'%!#1230'
RES
52
PHASE OV
SHIFTER
59
SUM - AMP
FIGURE 1
RES
52 Phase
Shifter
OV
59
SUM - AMP
FIGURE 2
12-68
VOLTAGE UNBALANCE SCHEME
(!)''%)+"''!"#$%&!2''%4!1*%&*'%4!1''
3#45%2'
12-69
!"#$%&!''&6"!$4!!0'+!&%"$%-&1'
X
50 51
50 51
50 51
TRIPS !X"
52
!"#$%&!'',)//"!"*%)#0'
X
50 51
DITTO
50 51
50 51
87
52 TRIPS !X"
12-70
!"#$%&!''2+5-%*'+.#2"'
%.!""'*'+.#2"''2"12-1/'
51
51 51 51
12-71
DRY - TYPE
REACTORS
ADDITIONAL CONSIDERATIONS:
12-72
OIL - IMMERSED REACTORS
500 KV LINE
SWITCHER OR BREAKER
52
50 51
50 51
50 51
50G 51G
TRIPS !52"
12-73
500 KV REACTOR DIFFERENTIAL PROTECTION
X Y
TRIPS !52"
52 IF !52" IS A SWITCH
ALL REACTOR RELAYS
DITTO MUST TRIP !X" AND
TRANSFER TRIP !Y"
87R
87O WITH RESTRAINT
87R
ADDITIONAL CONSIDERATIONS:
12-74
Modern Power System Protection: Applications
and Performance Analysis
13
TAB 13
Rotating Machinery Protection
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
There are probably more failures in Rotating Equipment than in any other
electrical equipment.
Both electrical and mechanical failures have to be considered.
Frequency of failures may be low, but the consequences in cost and the effect on
system performance is very high.
Principles of protection are relatively simple
13-1
In evaluating rotating machinery protection we must analyze the usual electrical
faults such as short circuits but we must also consider abnormal operating
conditions (and here we must determine what is abnormal and whether
corrective action is possible) and electrical or mechanical problems.
13-2
All major generating units and large motors are protected by differential relays.
All motors are protected by TDOC relays. Large motors may use instantaneous
or differential relays.
Negative sequence relays are required for unbalanced system conditions,
V/Hz is a function of flux conditions which. in turn, is a function of system or
machine voltage and frequency or speed.
Mechanical devices protect against temperature, vibration and other mechanical
problems.
13-3
Concern is cost and delay in restarting.
Alarms and oscilographs vital to determine if a fault exists.
Sequential tripping is a sequence of closing the steam valves before opening the
circuit breakers. Mechanical failures usually require sequential tripping.
Cost of restarting a 1300 MW unit in 1990 was $250,000, not including the cost
of energy replacement
13-4
Almost universal protection for stator faults of large generators uses a differential
connection. Modern differential relays have extreme sensitivity ( 0.2 amps) with
fault current in tens of amperes. No incentive to change to solid state or digital.
However, other advantages such as data recording influences the decision to
change.
13-5
To accommodate heavy loads or errors in the current transformer output a
straight overcurrent relay is replaced by a percentage differential relay. The
greater the through current, the more operating current is required.
In e-m relays there must be current in both restraint windings to operate correctly.
13-6
Operating current = I1-I2
Restraint current = (I1 + I2) / 2
13-7
Method of grounding effects the amount of protection provided. Solidly grounding
provides enough ground current to operate any differential relay.
Refer to page 168 (3rd edition)
13-8
Adding neutral impedance limits ground current to minimize damage but too
great an impedance and the differential relay will not operate.
Balance between limiting fault current and providing enough current to operate a
relay.
Relay must be set above 3rd harmonic
13-9
The most common grounding scheme for large units. Secondary resistance is
reflected back into the primary as the inverse of the square of the transformer
ration. Limits fault current with sufficient voltage for relaying
Does not see 100% of the winding. There are many schemes to cover 100% of
the winding.
13-10
Third harmonic is introduced into the generator winding at the neutral or phase
end and the voltage is measured.
13-11
Overvoltage is prevented by voltage regulator and excitation logic.
Undervoltage is not a problem except for auxiliary bus (constant KVA loads).
Frequency variations affect turbine blades
Problems occur when unit is off-line.
13-12
Industry standards control generators. No standards for k for motors but is
usually around 40.
Basic question is to determine the cause of the unbalance. For generators this is
usually external to the unit, probably on the system.
For motors this would be in the supply system or fused disconnects, etc.
13-13
Field circuit of modern generators are ungrounded.
Single ground has no effect, second ground produces flux distortion, vibration,
iron heating.
Relays used to alarm and allow ground to be
13-14
When a Synch. Generator loses excitation it runs as an induction generator with
system providing reactive support. Without damper windings, rotor iron overheats
and unit can go unstable. Despite complexity of event, impedance swing is
known.
13-15
13-16
5/23/11
13-17
Impedance-type relays can detect impedance swing into the generator portion of
the R=X diagram.
Trip or Alarm?
Underexcitation can occur just after the unit is connected to the system. The
voltage is matched to the system but is not increased as load is increased. The
alarm will remind the operator. It is more common today to put the voltage
regulator in service prior to parallelling.
13-18
A cross-compound unit consists of two shafts which must be synchronized during
start-up to allow the unit to be synchronized to the system.
Excitation is applied when the unit is on turning gear. A fault at speeds less than
synchronous cannot be detected by the differential relays.
A tandem unit (single shaft) does not need excitation until the unit is at
synchronous speed.
13-19
Without steam flow, last stages of turbine heat up.
For hydro units, if water is above the tailrace, reverse power is low; if below the
tailrace, the reverse power is high.
Solution is not to trip immediately.
Attempt to correct the problem
13-20
The problem is almost always when unit is off line.
If separate protection is used, transformer protection is by inverse time-delay and
generator protection is provided by the manufacturer in the excitation system.
13-21
At low frequencies, e-m disc differential relays are not operative.
Plunger-type relays and induction disc relays are inserted during start-up. Solid-
state and digital relays may not have the same problem.
Required for cross-compound units or inadvertent energization of tandem units.
13-22
This circuit is applicable during start-up of a cross compound unit to allow the
instantaneous relay to operate at less than 55Hz, but is cut out above 55Hz.
The circuit is also applicable if the unit is inadvertently connected to the system
when on turning gear or coming up to synchronous speed.
13-23
Common, catastrophic misoperation. Inadvertent closing of circuit breaker or
switches while unit is on turning gear.
Potential for shaft damage following reclosing, especially when sub-synchronous
resonance is possible
13-24
Usually, generators do not have overload protection. Motors always have.
Problem is heating. Analog relays do not replicate heating limits. Digital relays
can solve thermodynamics.
13-25
Unequal output of CTs may be due to non-simultaneous starting currents,
unequal CT burdens
13-26
If 3-phase conductors are passed through the window, the secondary current is
proportional to (Ia + Ib +Ic) = 3Io.
Cable shields must be grounded outside the toroid. See Power System Relaying
pages 64 and 174.
The relay must be made insensitive to capacitor inrush, lightning arrester or
surge protection current.
13-27
Unit connected generator requires start-up source.
Requires transferring from start-up to unit when synchronized and transfer back
again when shutting down.
Transfer procedures vary from instantaneous to time delay.
Generator breaker avoids the problem.
13-28
Decision to use instantaneous or differential relay depend on the margin between
relay setting and minimum bus fault current.
For differential relay the two ends of the motor winding must be brought out to
accommodate the CTs.
13-29
CT ratio is selected to provide some margin above trip setting so meters will not
read off scale.
Set 51 relay @ 125%x245-306.25. If motor is vital use 115% service
factor=352.5a. Use 400/5 CT.
TDOC sees 352.5/80=4.4a. Use 5.0a. Tap
Set time delay @1609/400=4xpu above .97 sec. Set 1.5 time lever.
Set 50 relay above 1.7x 1609=2735 pri.amp=34.19 sec amp-use 35a. pu.
20000/(35x80) =7.14 xpu—good
51G set at 1/3 minimum ground fault of 1200a.
1200/80= 15a. #1 dial
13-30
As with the 2000HP motor; pickup of 51 is 1.15x1.25x918=1320a.
Select CT ratio of 1500/5. 51 relay pickup is 1320/300=3.7a. Time delay must
exceed 3 seconds—use #6 dial.
51G set at 1/3 x1200/300=1.33a.
Set at 1.0 amp #1 dial
With toroid also set at 1.0a,but instantaneous.
Setting 50 relay is a problem. If set at 1.7x5512-9370a. --But minimum 4kv bus
fault is 20000a.-- 20000/9370=2.1xpu. No good
Use differential relay (87) set at lowest setting!
13-31
13-32
GENERATOR PROTECTION
13-33
13-34
Limited by Core & 0.85 PF
1200 30 psig
Field Heating
15 psig
0.5 psig
900 0.90 PF
Limited by
600
Stator Heating
MVA REACTIVE
300
0 MEGAWATTS
300 600 900 1200 1500
F-net
Eg
Eg
Et
Et
Lagging PF Leading PF
It
13-35
500 kv
Browns Ferry Nuclear Plant
22 kv
4kv
22,500 / 2.5 22,500 / 2.5
STATION
SERVICE
DIFF
2.5 / 5
85 kva
22kv / 120 0.18 OHM
720 AMP OV
13-36
WATTS BAR HYDRO
13-37
WATTS BAR HYDRO
OVER CURRENT
PH, GR, NEG SEQ
OVER
50 VOLT FREQ
VOLTS / SYC UNDER PH, GR OVER
HERTZ CK VOLT NEG SEQ UNDER 87 DIFF
24 25 27 59 81
NEG OC GR
GEN SEQ PH TIME
OC GR OC
32 78 40 46 50 51G 21P 60
DIR OUT LOSS LOSS
PWR OF OF FIELD OF
STEP POT
NEUT
50N 51N 87N DIFF 64G
I OC TIME OC
PH DIST 100 %
VOLT REST STATOR
TIME OC GROUND
MICROPROCESSOR BENEFITS
•! EVENTS REPORTS
•! SEQUENTIAL EVENTS RECORDER
•! BREAKER WEAR MONITOR
•! STATION BATTERY MONITOR
•! METERING
13-38
WILSON HYDRO
OC
GEN GEN
OPEN
3500 A
875 A
8 OHM
2 OHM
OC OC
NC
NC NC
LINK ?
NC
SEQUOYAH
SECONDARY FAULT CURRENT = 138.6 V / 0.312 OHMS
= 444 AMP
GEN
81 % ABOVE BANK RATING
24,000 / 240
75 kVA 444 A 0.156 OHM
OV
0.156 OHM
4.44 A
13-39
SEQUOYAH
SECONDARY FAULT CURRENT = 138.6 V / 0.078 OHMS
= 1777 AMP
GEN
328 % ABOVE BANK RATING
BANK EXPLODED
24,000 / 240
75 kVA 1777 A
OV
SEQUOYAH
SECONDARY FAULT CURRENT = 138.6 V / 0.078 OHMS
= 1777 AMP
GEN
328 % ABOVE BANK RATING
OC
BANK EXPLODED
13-40
AUXILIARY BUS TRANSFERS
13-41
13-42
STARTUP UNIT
TRANSFORMER TRANSFORMER
EA
IB IA
B NO EU NC A
X Y Z
13-43
STARTUP UNIT
TRANSFORMER TRANSFORMER
VA (A-B)
IA IA
VB (A-B)
1522 NO NC 1112
X Y Z
13-44
13-45
13-46
13-47
13-48
13-49
UNDERFREQUENCY LOAD SHEDDING
AND REACTOR COOLANT PUMPS
13-50
SYSTEM LOAD SHEDDING
INITIALLY REACTOR COOLANT PUMPS WERE SET TO TRIP
BEFORE SYSTEM LOAD SHEDDING WAS INITIATED.
THE FINAL AGREEMENT ALLOWED THE REACTOR COOLANT
PUMPS TO TRIP AFTER ALL ATTEMPTS HAD BEEN MADE
TO SHED SYSTEM LOAD.
THE UNDERFREQUENCY LOAD SHEDDING PHILOSOPHY
IS AS FOLLOWS:
13-51
13-52
PUMP STORAGE PLANT
INVERTER
1 4 00 2400 4800 7200
2 5
3 6 1
6
2
THYRISTORS 4
3
S N MACHINE 5
2 4
INVERTER
CONTROL 3
ENCODER
THYR 6
5
THYR 1
13-53
START BUS
161 kv CURRENT
COMMUTATION REACTORS
23 kv
550 v
S
4kv
STATION
G M SERVICE
50 kva
23kv / 120 Sa
OV OV
IEEE C37.102
A)! Plunger type current relay
B)! Induction overcurrent relay
C)! Generator differential relay
D)! Generator ground relay
E)! Harmonic restraint differential relay
F)! Plunger type voltage relay
13-54
IEEE C37.102
A)! Plunger type current relay
B)! Induction overcurrent relay
C)! Generator differential relay
D)! Generator ground relay
E)! Harmonic restraint differential relay
F)! Plunger type voltage relay
13-55
Modern Power System Protection: Applications
and Performance Analysis
TAB 14
Power System Protection
14
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
RELAYING FOR STABILITY
A.G. Phadke
LOSS-OF-FIELD RELAYING
14-1
LOSS-OF-FIELD RELAYING
Es!" E1 E2 !0
Xs Xt
LOSS-OF-FIELD RELAYING
Pe = {[EsE2]/[Xs+Xt]} sin"
Pe
The steady-state
stability limit is
(-#/2) < " < (#/2) -#/2
#/2 "
This is shown on
the accompanying
sinusoidal P-" curve.
14-2
LOSS-OF-FIELD RELAYING
P1 + jQ1 = E1 I1*
LOSS-OF-FIELD RELAYING
E2 1 1 E2 1
2 $
P [Q & 1 { & }] [ 1 { $ 1 }]2
2 ' P
1 1 2 X X 2 X X
t s t s
14-3
LOSS-OF-FIELD RELAYING
Q P0 ' 0
2 X
E1 1 & 1
Q0 ' { }
2 Xt Xs R
2
E 1 $ 1
S0 '
1
(P0,Q0) { }
2 Xt Xs
(R0,X0)
P
R ' 0
S0 0
X ' & (X & X ) / 2
0 t s Z0
Z ' (X t $ X s ) / 2
0
Loss of field
Es E1
If
jXs
I 1,
Es, * If, If
Es* If
x jXsI1
+ E1
I1
14-4
Loss of field
I 1, Field current If
Es, * If, If
Es* If Field voltage
x jXsI1
+ E1
[cos+ /x]!-+
I1
&+ 1/x
E1 =1.0
I1 =[x/cos+]!+
Z = [cos+ /x]!-+
LOSS-OF-FIELD RELAYING
14-5
FUNDAMENTAL PRINCIPLES OF STABILITY SWINGS
Es!" E1 E2 ER !0
RELAY
Xs Xt XR
d 2" ESER
M ' Pm & sin "
dt 2 (X S $ X t $ XR )
Es!" E1 E2 ER !0
RELAY
RELAY
Xs Xt XR
" Unstable
-# swing HOW DOES
THE
# Stable swing DISTANCE
RELAY
RESPOND?
time
14-6
PHASOR DIAGRAMS DURING STABILITY SWINGS
Es!" E1 I E2 ER !0
RELAY
RELAY
Xs Xt XR
(ES & ER )
I' ' & jB(ES & ER )
j(X S $ X t $ XR )
3 X t $ XR 0 3 X t $ XR 0
E1 ' ES & jX SI ' ES 2 / $ ER 21 & /
1 (X S $ X t $ XR ) . 1 (X S $ X t $ XR ) .
' k1ES $ (1 & k1 )ER
similarly
3 XR 0 3 XR 0
E 2 ' ER $ jXR I ' ES 2 / $ ER 21 & /
1 (X S $ X t $ XR ) . 1 (X S $ X t $ XR ) .
' k 2ES $ (1 & k 2 )ER
E1
-jBES "
"
k1ES E2
jBER
k2ES
ER
I (1-k1)ER (1-k2)ER
14-7
PHASOR DIAGRAMS DURING STABILITY SWINGS
ES
E1
E2
ER
S 1 C 2 R
ES E1 Ec E2 ER
14-8
PHASOR DIAGRAMS DURING STABILITY SWINGS
ER ER
E2 E2
E1 E1
EC EC
ES ES
I I
R Impedance diagram
XR
2
O
C
Xt
S
1
XS
S 1
1+j0 C
2
Phasor diagram R
I
14-9
PHASOR DIAGRAMS DURING STABILITY SWINGS
R
O’
2
O
C
1
"
S "4’
2
C
t3 t2 t1 t4
1 t6 t5 t7
S Stable swing
14-10
PHASOR DIAGRAMS DURING STABILITY SWINGS
t1 t2 t3 t4 t5 t6 t7
t7 t6 t5 t4 t3 t2 t1
Un-stable swing
14-11
OUT OF STEP RELAYING
• Out-of-step blocking
G1 5 L1 + L2
• Out-of-step tripping
G2 5 L3 + L4 + L5
Desired split
G1 Block here G2
Trip here
L1 L2 L3 L4 L5
DYNAMICS OF
POWER SYSTEM FREQUENCY
14-12
Outline
• Frequency dynamics
• Load restoration
Speed Steam
governor Valve
f
HP LP
f0
Supplementary Generator
(reset) control
load
14-13
• Control of power system frequency
• Tie-line bias control (steady-state)
T0
f0 Pre-disturbance balance
ACE
T0
Tie-line flow
14-14
• Control of power system frequency
frequency
Catastrophic
changes.
What are the Supplementary control action
dynamics?
What to do?
• Frequency dynamics
J2, S2
J1, S1
Ji, Si
14-15
• Frequency dynamics (catastrophic changes)
f Individual rotor
responses
(transient stability oscillations)
Aggregate response
time
J0 ' 8JS
i i
"' 8" S i i
8S i 8S i
d2 "
J0 2 ' Tm & Te
dt
Here Tm and Te are aggregate mechanical and
electrical torques on the rotors
d2 "
9J0 2 ' 9Tm & 9Te ' Pm & Pe Multiplying both
dt sides by aggregate
' 8 Gi & 8 Li rotor speed 9
14-16
• Frequency dynamics (catastrophic changes)
1
J0 92s
H0 ' 2
S0
Substituting for J0 in terms of H0
df fs2 (8 Gi ) 3 8 Li & 8 Gi 0
f '& 2 /
dt 2H0 S0 1 8 Gi .
df pLfs2
f '&
dt 2H0
14-17
• Frequency in an islanded system
f0
Such a decay
rate is
unrealistic!
t
f
L ' [L 0 & (1 $ L 0 )d(1 & )]
f0
14-18
• Frequency in an islanded system
df p f
f '& [L 0 & (1 $ L 0 )d(1 & )]fs2
dt 2H0 f0
The solution to this equation, with f = f0 at t=0 is
3 L0 0 3 1 0
( f0 & f ) & f0 2 & 1/ ln2 /'
1 (1 $ L 0
)d . 1 1 & ( f0
& f )(1 $ L 0
)d / L f
0 0.
p f 2
(1 $ L 0 )d s t
2H0 f0
As t ; < the frequency reaches a limit
f0
frequency dependent
load
f<
constant
load
14-19
• Frequency in an islanded system
L3 > L2 > L1
f0
L1
L2
L3
t
The actual decay must be determined by simulating
the event(s) in detail. Typically, stability programs
with extended capabilities are necessary.
14-20
• Load shedding and generator tripping
Range
f0
of
safe
Load operation
shedding
must Simulation
be completed Safety margin of events
in this
window
t
Relay and breaker
operating times
14-21
• Load shedding and generator tripping
• Generator tripping generally based upon
certain network conditions detected by
loading conditions, switch and breaker
positions, etc.
Load
Time delay
restoration
Step 2
f0
Step 1
Step 1
Step 2
Step 3
Step 4
Step 5
Load
shedding
14-22
• Summary
14-23
Modern Power System Protection: Applications
and Performance Analysis
TAB 15
Interpreting Oscillograms II
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
15
CT SATURATION 1
15-1
15-2
15-3
FACTORS INFLUENCING TIME TO
SATURATE
SATURATION VOLTAGE
•! HIGHER VOLTAGE RATING, LONGER TIME TO SATURATE
TURNS RATIO
•! INCREASE IN TURNS RATIO REDUCES FLUX DENSITY AND
INCREASES TIME TO SATURATE
15-4
A B C
15-5
15-6
CT SATURATION 2
BK 2 BK 1
T
I
E
BUS 2 BUS 1
LINE B LINE A
15-7
51
OL
BK 2 T BK 1
I
BUS 2 E BUS 1 51 51N
L B LA
DITTO BUS 1
BUS 2 DIFF
2.5 A 5A
BK 1
T
BUS 1
NO
LINE A
EXTERNAL FAULT
10 A
C
BUS
DIFF
5A
AB C
15-8
BUS DIFF
2.5 A
CONNECTIONS
2.5 A 5A
BK 1
T
BUS 1
LINE A
0A
C
BUS
DIFF
AB C 5A
5A
A
5A
OPEN BK 1
5A 5A C
T
BUS 1
A
BUS
C DIFF
LINE A
5A
CONSIDER 2000A
PHASE TO PHASE
EXTERNAL FAULT
X X 5A
AB C
BUS DIFF CONNECTIONS
15-9
1.67A 1000 A
BUS DIFF
CONNECTIONS
4000/5 5/6.67
10L800 3.34A
1.67 A
1000 A BK 1
5 ALL AUX
7.5 CTS T 200
T
3000/5 5.0A
BUS 1
C 800
2000/5
10L800 C
ASSUME 2000 A
FLOW THROUGH LINE A BUS
DIFF
LINE !A" 2000 A
AND 1000 A IN
BKRS !T" & !BK 1" 2000/5
10L800
A B C 5.0A
100 AMPS
BAD CT GOOD CT
100/5 CTS SOURCE
5A
5A
SCOPE
4/1 1/4
1 OHM CL STEP R STEP CL 1 OHM
DOWN UP
3 OHMS 3 OHMS
15-10
100 AMPS
BAD CT GOOD CT
100/5 CTS SOURCE
5A
5A
SCOPE
4/1 1/4
1 OHM CL STEP R STEP CL 1 OHM
DOWN UP
6 OHMS 6 OHMS
100 AMPS
BAD CT GOOD CT
100/5 CTS SOURCE
5A
5A
SCOPE
4/1 1/4
1 OHM OP STEP R STEP OP 1 OHM
DOWN UP
15-11
BUS#1 OL Current Waveform #1
50000
A Phase Current
40000 C Phase Current
B Phase Current
30000 Ground Current
20000
10000
Am ps
-10000
-20000
-30000
-40000
BUS 2 BUS 1
-50000
Tim e (m illiseconds)
15-12
BUS#1 OL
50000
40000
Phase A Current
30000 Phase C Current
Phase B Current ~300 ms
20000 time-gap
Ground Current
betw een
10000 w avefor
0
Am ps
-10000
-20000
-30000
-40000
-50000
-60000
Tim e (m illiseconds)
BUS 2 BUS 1
BUS#1 OL
50000
40000
Phase A Current
30000 Phase C Current
Phase B Current ~300 ms
20000 time-gap
Ground Current
betw een
10000 w avefor
0
Am ps
-10000
-20000
-30000
-40000
-50000
-60000
Tim e (m illiseconds)
BUS 2 BUS 1
15-13
DIFF & OL (A Phase only)
40000
30000
20000
10000
0
Am ps
-10000
-20000
-30000
-40000
-50000
-60000
BUS 2 BUS 1
Tim e (m illiseconds)
OL A PH DIFF A PH
40000
30000
20000
10000
PRI AMPS
0
1
11
21
31
41
51
61
71
81
91
101
111
121
131
141
151
161
-10000
-20000
-30000
-40000
-50000
CYCLES
15-14
DIFF & OL (C Phase only)
50000
10000
Am ps
-10000
-20000
-30000
8000
Phase A Current
Phase C Current
4000
A
Am ps
2000 BK
T
C
0
BUS 1 A
-2000 C BUS
LA DIFF
-4000
-6000 X X
Tim e (m illiseconds) B
A C
15-15
Differential Current Waveform #1
10000
8000
Phase A Current
Phase C Current
4000
A
Am ps
2000 BK
T
C
0
BUS 1 A
-2000 C BUS
LA DIFF
-4000
-6000 X X
Tim e (m illiseconds) B
A C
30000
Phase A Current
Phase C Current
20000 Phase B Current
10000
Am ps
-10000 A
BK
-20000 T
C
BUS 1 A
-30000
C BUS
Tim e (m illiseconds)
LA DIFF
X X
B
A C
15-16
Differential Current Waveform #2
40000
30000
Phase A Current
Phase C Current
20000 Phase B Current
10000
Am ps
-10000 A
BK
-20000 T
C
BUS 1 A
-30000
C BUS
Tim e (m illiseconds)
LA DIFF
X X
B
A C
BUS#1 DIFF
40000
Phase A Current
30000 Phase C Current
Phase B Current
20000
~285 ms
time-gap
10000
betw een
Am ps
w avefor
BK
-10000
T
BUS 1 A
-20000
BUS
C
A LA DIFF
-30000
Tim e (m illiseconds)
C
X X
B
A C
15-17
10000 DIFF A DIFF C
8000
6000
4000
2000
0
-2000 1 11 21 31 41 51 61 71 81 91 101 111 121 131 141
-4000
-6000
CYCLES
30000
20000
10000
0
1
10
19
28
37
46
55
64
73
82
91
100
109
118
127
136
-10000
-20000
-30000
CYCLES
15-18
BUS#1 OL Voltage Waveform #1
50000
A Phase Voltage C Phase Voltage B Phase Voltage
40000
30000
20000
10000
Volts
-10000
-20000
-30000
-40000
-50000
Tim e (m illiseconds)
15-19
16
Modern Power System Protection: Applications
and Performance Analysis
TAB 16
Introduction to Computer Relaying
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
COMPUTER RELAYING FUNDAMENTALS
• Papers by Rockefeller,
& by Morrison and colleagues
16-1
INTRODUCTION TO COMPUTER RELAYING
Power Supply
ROM/ Mass
RAM E2 PROM
PROM memory
16-2
INTRODUCTION TO COMPUTER RELAYING
• Surge Filtering
Surges induced on wiring connected to the
relays. Wiring includes power supply, analog
and digital inputs.
• Industry standards define the requirements:
• IEEE standard: C37.90a, generally called the
SWC standard.
Oscillatory wave: 1-1.5 MHz, 2.5-3 kV, decay
to half value in greater than 6 !sec.
Unidirectional (Fast Transient) 4-5 kV, rise time
less than 10 nsec, decay to half value in 100-200
nsec.
Signal wires
16-3
INTRODUCTION TO COMPUTER RELAYING
16-4
INTRODUCTION TO COMPUTER RELAYING
Apparent signal
frequency from
sampled data: 0
0 fs 2fs Frequency
Gain
fc frequency
16-5
INTRODUCTION TO COMPUTER RELAYING
Gain
frequency fc time
16-6
MOTIVATION FOR COMPUTER RELAYING
Event
Event
No. 1
No. 2
Sir Adam
Beck No. 2
3
6
2 1 7
5 4
10
9 8
16-7
MOTIVATION FOR COMPUTER RELAYING
1
3
• Economic incentives
16-8
INTRODUCTION TO COMPUTER RELAYING
16-9
Modern Power System Protection: Applications
17
and Performance Analysis
TAB 17
Adaptive Protection Principles
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
Adaptive relaying had its start with the acceptance of digital relays.
All settings are a compromise limited by necessity of not tripping during
emergency load conditions.
Dependability vs Security
Relays may need to change characteristics to suit prevailing system conditions.
This predetermined characteristic is based upon assumptions embodied in off-
line studies
17-1
NERC identified outage causes-70% involved relays or associated devices.
Increased use of digital devices permits adaptability.
Hidden failures are relay problems that are not evident until some other event
occurs. e.g directional element or timing device becomes inoperative. Adaptive
relays can analyze circuit
17-2
Hidden failures can be corrected by monitoring and internal or external control
Settings are usually made under system normal conditions. When system state
changes, assumptions and margins are incorrect.
17-3
TDOC setting assumes some value of maximum load and minimum fault. When
system is abnormally stressed these values may not be correct.
Voltage during a fault or the direction of the fault relative to the relay are good
indicators for a correct trip.
Depending on the logic used in the digital relay, load can be removed from the
algorithm or load power factor can be used to ignore it.
17-4
Blinders limit operation of impedance relay but create a complex
tripping circuit.
Easier with digital logic than analog contacts.
Load can be determined by power factor or voltage.
Load power factor vs fault power factor a good discriminator
Continuous load monitor can subtract it from algorithm.
17-5
Elements can be contacts of a relay or relay systems.
Combined circuit used by military and nuclear.
Under normal system conditions relays should be dependable.
Under stressed system relays should be secure.
Adaptive relaying seeks to convert the parallel scheme to the series scheme.
17-6
With S/N, all protection systems operate in parallel
providing redundancy and backup.
17-7
A hidden failure does not imply a bad relay design, a misapplied relay, or an
error in calibration. These factors should be unlikely or should be discovered
in normal engineering reviews.
A hidden failure occurs as a random event, and by definition is undetected by
normal alarms or monitoring.
For example, a fault on the power system may lead to a fault detector to pick up
in several relays, and thus armed, a relay could have a failed subsystem of a
nature which would lead to a second undesirable operation, starting the system
on the way to a cascading failure.
17-8
If Z1 fails closed a trip is immediate. If Z1 fails to close backup or redundant
relays will cause a trip. This is not a hidden failure.
17-9
Not all hidden failures are equally likely.
17-10
For o/c relays, when the remote breaker opens, the current will change.
In the non-adaptive case, the instantaneous relay must be set above the worst
case current, i.e. the system configuration that provides the maximum fault
current. For any other configuration the current may be less and the relays may
not pick up.
With adaptive relaying, system configuration can be communicated to all
terminals and the resulting current change when the remote breaker opens can
be determined and the relay settings changed accordingly.
For impedance relays, zone 1 must be set less than 100% of the line
When remote breaker opens, zone 1 setting can be adjusted to cover 100% of
the line. This is same as zone accelerating scheme.
17-11
Relay at A sees VA/IA but does not monitor Ic. Ic affects the Impedance to the
fault. Setting must be a compromise to assure that coordination is maintained.
Set Zone 1 without infeed
Set Zone 2 and Zone 3 with infeed
Adaptive relays communicate all current values to all relays
17-12
Instantaneous or zone 1 relays must never overreach the end of the line.
TDOC and zone 2 relays must always overreach the end of the line to cover the
area not protected instantaneously.
Zone 2 relay of one line must not overreach zone 1of adjacent line.
17-13
Cold Load Pickup is that condition which may occur following an outage of
several minutes to several hours. When the circuit is reenergized the diversity of
cyclic loads is lost. The inrush may be greater than normal load levels for that
circuit. Instantaneous and/or TDOC may operate.
Conventional solution leaves circuit without protection after initial trip. Results in
possible unnecessary trip if setting is below relay pickup.
17-14
A Smart Grid Includes:
Sensors, Meters, Distribution automation,
Communication, Advanced analysis, Active
participation by customers and utility, !green"
generation, storage.
!!
17-15
The utility and consumer must work closely together.
Federal, State and local are watchdogs to protect
costs and service
FERC and NERC establish rules and parameters
Vendors provide equipment and service
Advocacy groups protect environment
17-16
Non-adaptive
Hot line reclose used to pick up a load from the system
Dead line reclose used to pick up a line from a station
Full synchronizing required for generators
Check synchronizing required if two systems can be separated. May also be use
to control the load angle across a breaker
1 phase vs 3 phase reclosing is used to prevent torsional vibration of generator
shafts or to mitigate stability problems.
Adaptive
Provide detecting component or functional error and initiate correction
17-17
Pilot Wire (aerial or buried systems)
band width from 0 (dc) to 4 kHz
line length limited to maintain bandwidth
Power Line Carrier
operates from 30-300 kHz
provision for one 4 kHz channel
transmission over several hundred miles
Microwave
operates from 150 MHz to 20 GHz
provision for many 4 kHz channels
transmission limited to line of sight (can use repeaters)
Fiber Optic Links
virtually unlimited channel capacity
17-18
Attracting most attention in industry and research laboratories.
Load shedding and islanding
FACTS and SVC
Active Working Groups
17-19
Modern Power System Protection: Applications
and Performance Analysis
18
TAB 18
Distribution System Protection
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
!"#$%"&'$"()*+%($,-$"()*
TAPPED SUBSTATION
C A
B
E F S
18-1
C
$./0123.45.*!675.508/9* A
87T
D
E F S
$./0123.45.*!675.508/9*/0:**
;<=>*&?1*!675.508/9* A
B
87T
D
87B
E F S
18-2
,96460/@5*&.5/=5.*!!"A**
&BC/11*&.5/=5.*!&"*
A
B
87T
87B
E F S
,96460/@5*&.5/=5.*!!"A**
&BC/11*&.5/=5.*!&"*
A
87T
87B
E F S
18-3
&BC/11*&.5/=5.*!&"*
A
50
51
B
RESTRICT TRANSF.
DIFF. AND ADD HIGH
87T
SIDE PHASE OVER-
CURRENT RELAYS
50
51 87B
E F S
%543D5*EF&A*,G@50:*%5/HI*32*EF$*
A
87T
E F S
18-4
J::*+I/15*%59/B1*KLMK;*
A
50
51
87T
50
51
E F S
B 51
CYCLES
50
E 51
B 50
E 50
13 KV BUS FAULT
CURRENT
18-5
Add Ground Feeder Relays 50N/51N
A
50
51
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
N.3?0:*(D5.H?..50@*+.3@5H830*
!E" LOW SET
51N
CURRENT
18-6
Add Station Backup Ground Relay 51G
A
50
51
B
51G
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
CURRENT
18-7
Add High Side Ground Relay
50 50 50N
51 51N
51
B
50N 51G
51N
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
!"#$%&'()*%+,'-.'!/"'01'2#'!"#$%&'
3)4-5'6%,.-44)&'-.'7-88)&'($9,.-:#%'
250 A 1200 A
50
C 51 51
B 50
CYCLES
51
50N
B 51 51N
C51N
C 50N
B 50
CURRENT
18-8
!"#$%&'()*%+,'-.'!/"'01'!"#$%&'3)4-5'
!6%,.-44)&"'-.'7-8'(.-:#%'
60 A 90 A 250 A
1200 A
50
C 51 51
B 50
CYCLES
51
B 51 50N
51N
B 51N 50N
51N
C51N
C 50N
B 50N B 50
CURRENT
J::*&/H=?C*N.3?0:*#O6@HI*
50 GS
51
50 50N
51 51N
B
50N
51N
51G
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
18-9
J::*&/H=?C*N.3?0:*#O6@HI**
[email protected]/@5*P3H/830"*
50 50 50N
51 51 51N
B
GS
50N 51G
51N
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
%5C9/H5*&.5/=5.*O6@I*-6.H?6@*#O6@HI5.*
50 GS
51
RATCHET
BY PASS CIRCUIT
SWITCHER
50N
51N
51G
50
51
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
18-10
%5C9/H5*&.5/=5.*O6@I*N.3?0:*#O6@HI*
/0:*Q(!*
50 MOD
51
GS
50N
51N 51G
50
51
87T AUX
UV
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
F S
J::*-/C/[email protected]*
50 MOD
51
GS
50N
51N 51G
50
51
87T
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
18-11
!""#!$"#%&"#!'()"#*+,%-.#%&"##
/01#2301#%&"#24""+8+..46+#*+,%-.#
OTHER TAPPED
SUBSTATIONS
50 MOD
51 R
GS
50N
51N
51G SUD
PRE IOC
Z
HOT
SPOT 87T AUX
AUX
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
7/(#8+6.4.#(9+6:466+&1#);%6%:1+6<.=:.#
7 IMP. RELAY SET TO PICK UP
AT 29 MVA @ 68 DEGREES
REACTANCE OHMS @ 13 KV
6 BANK OC SET TO
PICK UP AT 29 MVA
5
4
Z PICK UP
3
!MHO"
2
29 MVA
1
42 MVA
1 2 3 4 5 6 7 8
RESISTANCE OHMS @ 13 KV
18-12
!"#$%&'()($#*&'+)''&,-$./0'0+-&'1(2+($
7 397 ACSR.
REACTANC E OHM S @ 13 KV
6 11.4 MI. BANK OC MODIFIED
TO PICK UP AT 42 MVA
5
7.7 MI. 1/0 ACSR.
4
Z PICK UP
3
!MHO"
2
29 MVA
1
42 MVA
1 2 3 4 5 6 7 8
RESISTANCE OHMS @ 13 KV
"01@/99*"4C5:/0H5*%59/B1*/@*&.5/=5.*!-"*
C
OTHER TAPPED
SUBSTATIONS
GS
Z1 R
C
Z2 S
Z3 SUD
51G IOC
PRE
Z
50N HOT
51N SPOT 87T AUX
50 50N 51N
51 51N
E HIGH
SET
LOW
SET
18-13
C
Z1
C
S
Z2
E 51 IOC Z
Z3
Z3 120 CY 50N
51N 87T
50
51
Z 100 CY
E
CYCLES
Z2 25 CY
IOC 15 CY
E 50
CURRENT 13 KV BUS FAULT
-33.:60/830*J430R*SA*"(-A*/0:*
"4C5:/0H5*%59/B1*/@*&.5/=5.*!-"*
E 51
Z3 120 CY
Z 100 CY
CYCLES
!REMOVAL OF E 50 Z2 25 CY
COULD RESULT IN
IOC 15 CY
UNDESIRABLE BANK
TRIP" 13 KV BUS FAULT
CURRENT
18-14
-33.:60/830*J430R*SA*"(-A*/0:*
"4C5:/0H5*%59/B1*OI50*!,KL*&93H=5:"*
E 51
Z3 120 CY
Z 100 CY
CYCLES
Z2 60 CY
IOC 40 CY
13 KV BUS FAULT
CURRENT
SUBSTATION
BREAKER 1A 3B 2A 2B
FAULT
70L 50L X
LOAD LOAD LOAD LOAD
1A 2A 1B 2B
18-15
18-16
18-17
POLE - TOP RECLOSER COORDINATION
SUBSTATION SECTIONALIZER
BREAKER 1A 3B 2A 2B
FAULT
70L 50L S X
LOAD LOAD LOAD LOAD
1A 2A 1B 2B
Z2
RATCHET
BY PASS CIRCUIT
Z3 SWITCHER
50N
51N GS
BATTERY CHARGER
18-18
TWO CIRCUIT SWITCHERS IN SERIES
D
Z1
Z2
CIRCUIT
A SWITCHER
Z3
CIRCUIT
50N
B SWITCHER
51N
BATTERY CHARGER
BATTERY CONTROL OF CS
D 28 A START
Z1 15 A - 5 SEC
M
Z2
RATCHET
BY PASS CIRCUIT
Z3 SWITCHER
8A
50N
60 MS
51N
STATION BATTERY
CHARGER
18-19
TRANSFORMER FUSE PROTECTION
427 A 427 A
X 3930 A
X 0A
18-20
FUSE CONDITIONS
Normal Fuse
M M
X X
3930 A 0A
18-21
TRANSFORMER SWITCHER PROTECTION
MOTOR CONTACTS CLOSED
ALL CONTACTS CLOSED TWO GAS CONTACTS OPEN
M M
X X
3930 A 0A
REVIEW
18-22
REVIEW
18-23
18-24
DISTRIBUTED GENERATION
DISTRIBUTED GENERATION
D
Z VA
VB
OSC ABC VC
51G
50
51
50N 87T
51N
OSC N 50 50N
51 51N
E F S
18-25
DISTRIBUTED GENERATION
VA
VB
VC
18-26
Modern Power System Protection: Applications
and Performance Analysis
TAB 19
Operating Problems Affecting Human Safety
19
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
RESPONSIBILITY
LIABILITY
ETHICS
IN PROTECTION DESIGN
A RELAYING NIGHTMARE
DEFICIENCIES
•! Design
•! Control schemes
•! First line protection
•! Operating procedures
•! Backup protection
•! Responsibilities
19-1
161 kv
13.8 kv
440 v
460 v
STATION
SERVICE
161 kv
13.8 kv
440 v
460 v
STATION
SERVICE
19-2
161 kv
87T
50 21
T
13.8 kv
440 v S
G 460 v
STATION
SERVICE
161 kv
87T
T 50 21
13.8 kv
440 v S
G
460 v
STATION
SERVICE
19-3
161 kv
87T
21
CLOSED SWITCH TO
T 50
ENERGIZE EXCITATION
TRANSFORMER
134 MVA (6.5%)
13.8 kv
440 v S
G 460 v
STATION
SERVICE
19-4
161 kv
87T
61 A
50 21
T
13.8 kv
X S
G 714 A 22,400 A 460 v
STATION
SERVICE
714.4963
1,000 60,000
10 600
Time In Seconds
1 60
0.5524
.1 6
.01 .6
1,000
100
10,000
Current in Amperes
19-5
618.0164
1,000 60,000
10 600
Time In Seconds
1
0.9757 60
.1 6
65E-TOTAL CLEAR
.01 .6
1,000
100
10,000
Current in Amperes
19-6
1,000 60,000
100 6,000
618.0000
1 60
TYPE 65E FUSE ON 13.8 KV SIDE
OF EXCITATION TRANSFORMER
DIFF. TIME = 0.42 SEC. = 25 CYC.
.1 6
714.0000 65E-TOTAL CLEAR
3 PHASE
.01 .6
100
1,000
10,000
Current in Amperes
19-7
19-8
BKR. FAILURE
OFF
WHEN BKRS.
"G! & "S! OPEN
161 kv
87T
4,430 A LOCAL REMOTE
T 50 21 OFF ON
87T 87T
50 50
134 MVA (6.5%) 21 43 L / R 21
BKR!T!
13.8 kv
X S
G 51,650 A
460 v
STATION
SERVICE
OUTCOME
19-9
134 MVA BANK FAILURE
•! Tank ruptured
•! Oil on fire
•! Thick smoke
•! Pump storage plant
•! All men trapped
51641.6367
10,000 600,000
1,000 60,000
OCCURRED IN APPROX.
15 SECONDS
Time In Seconds
100 6,000
14.7342
10 600
5.5793
3Ph 134000 kVA Thermal A5606.46
100,000
1,000,000
Current in Amperes
19-10
19-11
A RELAYING NIGHTMARE
DEFICIENCIES
•! Design
•! Control schemes
•! First line protection
•! Operating procedures
•! Backup protection
•! Responsibilities
19-12
DESIGN
o! BREAKER FAILURE
o! WHY KEY TO THE POSITION OF GENERATOR
AND STATION SERVICE BREAKERS ?
CONTROL SCHEMES
19-13
FIRST LINE PROTECTION
13.8 kv
51,650 A
19-14
EXTEND DIFFERENTIAL
87T
50 21
T
13.8 kv
S
440 v
G 460 v
STATION
REMOVE FUSES SERVICE
OPERATING PROCEDURES
19-15
OBSERVATIONS
•! Breaker Failure
•!DO NOT KEY TO POSITION OF OTHER BRKS.
161 kv
87T
61 A CHARGE
T 50 21 CONTRACTOR SHOULD
HAVE ANTICIPATED LBS
FAILURE AND ACTIVATED
134 MVA (6.5%) THE BF SCHEME.
13.8 kv
LBS
X S
G 714 A 22,400 A 460 v
STATION
SERVICE
19-16
OBSERVATIONS
•! Breaker Failure
OBSERVATIONS
•! Breaker Failure
19-17
1,000 60,000
100 6,000
618.0000
Time In Cycles (60-hz basis)
PHASE-PHASE
10 600
Time In Seconds
1 60
TYPE 65E FUSE ON 13.8 KV SIDE
OF EXCITATION TRANSFORMER
DIFF. TIME = 0.42 SEC. = 25 CYC.
.1 6
714.0000 65E-TOTAL CLEAR
3 PHASE
.01 .6
100
1,000
10,000
Current in Amperes
19-18
OBSERVATIONS
•! Breaker Failure
161 kv
TRANSFER BUS
13.8 kv
440 v
460 v
STATION
SERVICE
19-19
5 OHMS
80.9 KV APPARENT OHMS EFFECT
A
50.61 KV
X FAULT = 2410 A
AT 161 KV
D
5 OHMS
76.38 KV
APPARENT OHMS EFFECT
A A
1657 A 1657 A
21 OHMS 21 OHMS
B B
FAULT = 3314 A
X AT 161 KV
D
19-20
SETTING GROUPS
1) Normal
2) Extend Reach of 50
161 kv
3) Reduce Time of 21
87T
50 21 4) Breaker Failure Not
T
Dependent On Position
Of L/R Switch
134 MVA (6.5%)
13.8 kv
440 v S
G 460 v
STATION
SERVICE
RESPONSIBILITY
o! FOR COORDINATION ?
o! CONTRACTOR
o! UTILITY
o! FOR PROTECTION ?
o! CONTRACTOR
o! UTILITY
19-21
ONE LAST THING
2 – 3 MINUTES LATER
A THOUGHT
19-22
Modern Power System Protection: Applications
and Performance Analysis
TAB 20
Distribution Transformer Excitation
John R. Boyle
Principal Engineer
PSA/Power System Analysts
496 Pine Ridge Drive
Signal Mountain, TN 37377
20
69 KV
A
P B C
G
G IN
M 13 KV
IA, IB, IC
PT
E S
V
VA, VB, VC
LONG LINE
URBAN INDUSTRIAL
P A B C
G
IN
IA, IB, IC
E S
VA, VB, VC
URBAN INDUSTRIAL
20-1
P A B C
G IN
IA, IB, IC
E S
VA, VB, VC
URBAN INDUSTRIAL
P A B C
G IN
IA, IB, IC
E S
VA, VB, VC
URBAN INDUSTRIAL
20-2
20-3
P A B C
G
IN
IC
E S
VC
URBAN INDUSTRIAL
P B C
G IN = 233A
IN = 254A G IN
180 HZ (IN = 305A) VC = 7.03KV
M VC = 7.80KV
IC = 910A
IC = 423A PT
E S
V
LONG LINE
VC = 7.73KV
VC = 8.58KV
URBAN INDUSTRIAL
DEENERGIZED
20-4
LOAD
COMP.
134
132
130
128
126
124 126
122 124
120
118
116
114
20-5
VP
VS
LOAD
VP
IX LAGING PF
VS
IR
I=910A VP
IX UNITY PF
VS VS
IR
I=910A
VP
I=423A IX LEADING PF
VS
IR
VS
69KV
EACH BANK = 12 MVA OPEN
7% = 58% on 100mva Base
THEREFORE TWO BANKS
EQUAL 29% OPEN
13KV
Formula:
10,800 KVAR
% Rise = Kvar ( jX)
105
20-6
20-7
P A B C
G IN 8.5KV
7.5KV
URBAN INDUSTRIAL
EXCITATION CURRENT
20-8
THINGS TO CONSIDER
•! Reduce Regulator Compensation & Float Pt
•! Reduce Regulator Time To Move
•! Replace Regulator Backup Ground Relay
To One That Rejects High Harmonics
•! Purchase Low Loss Transformers
•! Trip Capacitors When Voltage Goes to Zero
(may not be practical)
20-9
21
Modern Power System Protection: Applications
and Performance Analysis
TAB 21
Phasor Estimating and the Smart Grid
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
GPS SYNCHRONIZED MEASUREMENTS
IN
POWER SYSTEMS AND THEIR APPLICATIONS
A.G. Phadke
TOPICS PRESENTED
• Introduction to phasors
• Sources of synchronization
21-1
• Introduction to phasors
Imaginary
!
Real
t=0
• The starting time defines the phase angle of the phasor.
• This is arbitrary.
• However, differences between phase angles are
independent of the starting time.
cosines
sines
functions
xn
xn-1
.
.
x1
#2
Phasor X = --!
N
xk(cosk" - j sink")
t
21-2
• Sampling process, Fourier filter for phasors
• Least-squares on a period
• Cross-correlation with sine and cosine
• Kalman filters (under many circumstances)
#2
Xc - jXs = --"
N
xk(cosk! - j sink!)
Phasor X = (AXc+BXs)+j(CXc+DXs)
t
"1 "2
"2 = "1 + k$
t "1
The non-recursive phasor rotates in the forward
direction, one sample angle per sample.
21-3
• Recursive phasor calculations
"2 = "1
t "1
The recursive phasor remains fixed if the input
waveform is constant.
• A mechanical analogy
Cosine
Xr
Xa = Xr + jXi
Xi
Newest
data sample Sine
21-4
• Effect of noise on phasor calculations
• Random Noise
Size of circle of
Circle of
uncertainty
uncertainty
True Phasor
Measurement
data window
Substation A Substation B
At different locations
21-5
• Sources for Synchronization
• Pulses
• Radio
• GOES
• GPS
GPS
receiver
Analog
Inputs Phase-locked
oscillator Modems
21-6
• Frequency measurement with phasors
Positive sequence
voltage at %
3-phase voltages
at %
"
frequency
%'%(
d"&dt
time
•Redundant measurements
21-7
• State estimation with phasor measurements
Measurements
Present practice
are scanned
and are NOT
simultaneous
Measurements
are primarily
P, Q, |E| = [Z]
Measurements
Control
Center are non-linear
functions of the
state E :
Z = h(E)
Iterative weighted least square solution
[Z - Zk] = [ * h ]k )Ek
*E
21-8
• State estimation with phasor measurements
It is possible to
obtain phasors
from widely
Monitoring
or control
separated locations.
site
21-9
USES OF PHASOR MEASUREMENTS
ADVANCED CONTROL FUNCTIONS
Present system: model based controls
Controller
Measurements Controlled
Device
Controlled
Device
21-10
• Improved control with synchronized phasors
PSS
PMU
Generator power
PMUs distributed
in seven regions
of the country.
The tie lines of the region broken with the rest of the
country disconnected if angle separation exceeds limits.
21-11
• Improved control with synchronized phasors
Power
System
• Stabilizing a network
Georgia
Out of step
condition
21-12
• Adaptive protection with synchronized phasors
Blocking
Tripping
Zone
and Timer
settings
21-13
• Adaptive protection with synchronized phasors
S-PMU S-PMU
Relay Relay
Pre-fault
Post-fault
Interval
Prediction
Observation
Interval
21-14
• Future prospects
National
Center
Regional
Center
21-15
HOW TO DISPLAY WIDE AREA PHASORS
+
1
Center Of Angles
+2
Center Of Angles
+
1
+2
21-16
21-17
Modern Power System Protection: Applications
22
and Performance Analysis
TAB 22
Blackouts: Causes and Countermeasures
Stanley H. Horowitz
Consultant
3143 Griggsview Court
Columbus, OH 43221
System is stressed beyond normal conditions
Generator and/or transmission line outages
Control room operators trained to respond to abnormal conditions provided
information is timely and correct
Additional system elements are lost
System loses synchronism, low voltage, low frequency
Insufficient or delayed response
Blackout
22-1
22-2
Blackouts follow the same experience curve as natural disasters.
Expect an event affecting 50 million people every 38 years.!
22-3
Five 230kV lines from Adam Beck Hydro plant in New York were feeding Ontario Province at
peak load (5:16PM). A load change from a tap changer in NY increased the load to Ontario
slightly. A third zone relay set for breaker failure two line sections away operated. This relay
was set in 1956 and never revised. As one line tripped, the remaining 4 lines increased their
load and each in turn tripped, separating Canada from the US, The reversal of power had
unanticipated results. Several transmission lines in New York were overloaded and tripped.
The governing oil system at Adam Beck tried to follow the load change and tripped all units,
several loss-of-field relays in New England misoperated, probably from a blooming of their
characteristics with the voltage changes, severely reducing generation and reactive support.
The entire New England and New York area went black. NYC took several days to restore all
of its load
22-4
22-5
22-6
On a double circuit tower line feeding power to NYC from Indian Point Nuclear
plant, a steam power plant and interconnections with New England, two severe
lightning storms within ten minutes of each other cut off all power into the City.
Lightning hit phase 1 on one circuit and flashed across the tower arm to phase 3
of the other circuit, causing a phase-to-phase-to ground on both circuits.
A directional relay had been calibrated recently but in returning the cover to the
electromechanical relay the directional contact was bent and could not operate.
All High Speed Reclosing on the CON ED system was removed as a result of
the subsynchronous resonance studies. The check synchronizing settings were
reduced to 10 degrees. As a result, none of the lines reclosed in the 10 minutes
between faults.
A breaker failure relay timer was corrupted by adding several auxiliary relays in
parallel to obtain additional circuit breaker auxiliary contact. This caused several
breakers at the Indian Point Station to operate
Some NYC load may have been saved, enough to match the local generation,
22-7
22-8
Replaced the 1965 Blackout as a defining event.
Occurred after several units tripped for a number of reasons, tree
trimming was lax and resulted in many line outages. Key element,
however, was the failure in the First Energy control room to recognize
what was happening. The technicians working on the monitoring
computer went to lunch, leaving the computer shut down, the operators
ignored messages from the PJM and AEP control rooms that there
were excessive line and unit outages and to drop load.
22-9
A major contributor to cascading outages is the effect of the zone distance relay particularly
third zone.
22-10
Blinders limit operation of impedance
relay but create a complex tripping circuit. Easier with digital logic than with analog
contacts.
Load power factor vs. fault power factor is a good discriminator. Continuous load
monitor can subtract it from the algorithm.
Load encroachment is a logic entry
22-11
A key outage occurred on the Sammis-Star line separating the First Energy System from AEP.
22-12
One of the recommendations of NERC was to eliminate the
third zone completely. This chart shows where such a move is not always advisable.
22-13
22-14
22-15
22-16
22-17
22-18
22-19
Modern Power System Protection: Applications
and Performance Analysis
23
TAB 23
More Intelligent Controls
Arun G. Phadke
Professor Emeritus
Virginia Polytechnic Institute and State University
Bradley Dept. of Elect. Engineering
Center For Power Engineering
Blacksburg, VA 24061-0111
PRESENTATION OUTLINE:
1. Rare Events
3. Analysis of Causes
4. Countermeasures
Loss of synchronism
and blackout
23-1
MORE INTELLIGENT CONTROLS
• High speed
protection equipment
GPS
receiver
Analog
Inputs Phase-locked
oscillator Modems
23-2
ADVANCED CONTROL FUNCTIONS
Phasor based: Feedback based control
Controller
Measurements
Controlled
Device
Adaptive Relaying
Or
Breakers
To Circuit
Protection
And
No 2
Vote
Protection
No 3
23-3
Remedial Action Schemes
• Wide Area Protection Schemes
SPS or RAS
• System Protection Schemes came into being as
control functions which required protection system
interventions.
• Often the inputs may be derived from protection
systems, and certainly the outputs of protection systems
are used to execute the controls.
23-4
Design of a ductile system instead of a brittle system
Brittle
System
Initiating event
Ductile
System
Initiating event
To achieve ductility,
• New network elements
• New configurations
• Renewable architectures
Brittle
System
23-5
EFFECTS OF OPEN ACCESS AND DEREGULATION
23-6
Modern Power System Protection: Applications
and Performance Analysis
TAB 24
Notebook Paper
24