SQM4 Synchro Models Literature

This document provides information on electromotoric actuators models SQM40 and SQM41. The actuators can generate up to 18 Nm of torque and are used to control dampers and valves in applications like oil and gas burners. They have running times from 5 to 65 seconds and different shaft and electrical connection options. Safety guidelines are provided for installation and use.

Uploaded by

Đất Rồng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views29 pages

SQM4 Synchro Models Literature

This document provides information on electromotoric actuators models SQM40 and SQM41. The actuators can generate up to 18 Nm of torque and are used to control dampers and valves in applications like oil and gas burners. They have running times from 5 to 65 seconds and different shaft and electrical connection options. Safety guidelines are provided for installation and use.

Uploaded by

Đất Rồng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

7 817

Actuator SQM40.../SQM41...

Actuators for air and gas SQM40...


dampers SQM41...

 Electromotoric actuator up to 18 Nm torque


 Clockwise and counterclockwise variants
 Running times from 5 up to 65 seconds
 Different shaft ends available
 Electronic version with analog control input
 Internal position indication
 Drive shaft can be disengaged
 Variants with UL and CSA approval, as well as GL marine approval

The SQM40.../SQM41… and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!

Use
The SQM40.../SQM41... actuators are suited for driving oil pressure controller, butterfly
valves, dampers or for use on other applications that require rotary motion.
Areas of application are oil and gas burners of medium to higher capacity as well as
thermal process plants.

The actuators are used primarily for load-dependent control of the flow of gas, oil and
combustion air:
 In connection with 3-position or modulating controllers (e.g. 4...20 mA), and/or ...
 ... directly by burner controls

CC1N7817en
Building Technologies Division
11.02.2016
Supplementary documentation

Product type Type of documentation Documentation number


SQM45... / SQM48... Data Sheet N7814
SQM10... / SQM20... Data Sheet N7812
ASZ... Data Sheet N7921
ASZ22.3x Mounting Instruction 74 319 0921 0 (M7921)

Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!

Only qualified personnel may open, interfere with or modify the actuators!

 Read the documentation on the actuators carefully and fully. If not observed,
dangerous situations might occur
 The user must ensure that the actuators meet the requirements of the relevant
application standards
 Safety-related applications are only available with Siemens burner controls!
 All product-related activities (mounting, settings and maintenance) must be
performed by qualified and authorized personnel

Caution!
 Risk of electric shock hazard – to disconnect the actuator from power, it may be
necessary to open more than one switch. Before performing maintenance work,
the actuator must be disconnected from power
 The electrical connection between the conduit fittings is not made automatically.
It must be established on installation site
 The connecting plate is made of plastic and does not provide earthing of the
conduit fittings. Earthing must be ensured by adequate washers and wire links
 All cam switch settings must satisfy the requirements of the relevant application
standards

 To provide protection against electric shock hazard, the connecting terminals must
have adequate touch protection. Make certain that non-insulated connections or
wires cannot be touched
 Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
 Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation even if they do not exhibit any damage
 Static charges must be avoided since they can damage the actuator’s electronic
components when touched.
Recommendation: Use ESD equipment

Notes on use in North America


 Use of flexible conduit including adequate accessories is mandatory
 Use of copper wiring is mandatory
 All circuits of class 2 must use cables type CL3, CL3R, CL3P or comparable types,
OR
All circuits are wired according to class 1 (electrical light or power circuits)

2/29

Building Technologies Division CC1N7817en


11.02.2016
Mounting notes
 Ensure that the relevant national safety regulations and notes on standards are
complied with
 In geographical areas where DIN regulations apply, the mounting and installation
requirements of VDE must be satisfied, especially DIN/VDE 0100, 0550 and
DIN/VDE 0722
 Make certain that the actuator is not exposed to direct solar radiation
 Required tightening torques for the fixing screws of the
- housing cover: 3.5 Nm
- connecting cover: 2 Nm

 Note!
Ensure correct direction of rotation!

SQM40… (left, CCW) SQM41… (right, CW)


90°


13
90° 0°

13

Installation notes
 Ensure that the electrical wiring is in compliance with national and local safety
regulation
 Make certain that strain relief of the connected cables conforms to the relevant
standards (e.g. as per DIN EN 60730 and DIN EN 60335)
 Ensure that spliced wires cannot get into contact with neighboring terminals. Use
adequate ferrules
 Unused terminals of the SQM40.../SQM41... must be covered by dummy plugs
 When making the wiring, the AC 120 V or AC 230 V section must be separated
from other voltage sections, thus ensuring protection against electric shock hazard
 The connection between the actuator drive shaft and the relevant controlling
element must be form-fitted
 Only plastic versions of cable glands may be used

3/29

Building Technologies Division CC1N7817en


11.02.2016
Electrical connection
 The actuators must always be powered via a prefuse of max. 6.3 AT
(as per DIN EN 6012- 2/5)
 For the protective earth connection, the housing of all variants has a marked PE
connecting terminal. A tightening torque of 1.2 Nm must be observed for fitting the
screw
 The supplied RAST3.5 connectors or RAST5 connectors must be used with screw
terminals for electrical connections. A tightening torque of 0.25 Nm must be
observed for fitting the screw

 Note!
The connection of fuel valves is only permitted on fused output terminals, see chapter
Connection diagrams. For this purpose, specific unit variants are available fitted with
a unit-internal, non-replaceable fuse. The unit-internal fuse is used to protect each
switching contact from welding in the event of external short-circuit. In addition,
please note that the maximum current load for the fused output terminals is reduced,
see chapter Connection diagrams.

Marking of the SQM40... / SQM41... connection areas:

SQM4x.x1xxxx SQM4x.x3xxxx
SQM4x.x2xxxx SQM4x.x6xxxx
SQM4x.x4xxxx
SQM4x.x7xxxx
SQM4x.x5xxxx: SQM4x.x8xxxx:
Mains voltage range
X2

Mains voltage range


X1, X2, X3
SELV / PELV
X1

7817z09e/0315

 Note
SELV or PELV depends on the safety class of the connected components. In the
case of PELV, the relevant component is connected to protective earth.

4/29

Building Technologies Division CC1N7817en


11.02.2016
Cam settings
The mechanical setting facility for the cams is physically separated from the connection
terminals. When the actuator is disconnected from power, the switches can be adjusted
via a scale. The cams can be changed via adjusting screws. The scale indicates the
angles of the switching points.

Standards and certificates


Applied directives:
 Low-voltage directive 2006/95/EC
 Electromagnetic compatibility EMC (immunity) *) 2004/108/EC
*) The compliance with EMC emissions requirements must be checked after the actuator
has been installed in the work equipment.

Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
 Automatic electrical controls for household and similar use DIN EN 60730-2-14
Part 2-14:
Special requirements on electric actuators
 Automatic electrical controls for household and similar use DIN EN 60730-1
Part 1: General requirements

EAC Conformity mark (Eurasian Conformity mark)

ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007

For types marked with R


Example: SQM40.264R10
For use in US/Canada where the power supply lines require a
connection facility for flexible conduit, the actuator's product no.
includes type suffix «R» (see following example). These products
are UL-listed.

For types marked with 36 or 38


Examples: SQM4x.36xA2x, SQM4x.38xA2x
For marine applications, environmental category A.

Lifetime
The actuator has a designed lifetime* of 250,000 start cycles
(close  open  close) under load with the rated torque in the entire rotation angle
range, which under normal operating conditions in heating mode corresponds to
approx.
10 years of usage (starting from the date of manufacture on the device type plate). This
lifetime is based on the endurance tests specified in standard EN 298.
A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor - www.afecor.org).

The designed lifetime is based on use of the actuator according to the manufacturer’s
Data Sheet. After reaching the designed lifetime in terms of the number of startup
cycles, or the respective time of usage time, the actuator is to be replaced by
authorized personnel.

* The designed lifetime is not the warranty time specified in the Terms of Delivery.

Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.

5/29

Building Technologies Division CC1N7817en


11.02.2016
Mechanical design
Housing  Lower housing part made of die-cast aluminum
 Housing cover made of impact-proof and heat-resistant plastic

Drive motor  Synchronous motor

Coupling  Shaft can be manually disengaged from the motor by operating the coupling
(coupling pin (K1))
 Automatic reengagement
Disengagement of drive shaft / motor by pressing coupling pin «K1»

Coupling pin "K1"

Earth terminal „PE“

Earthing connection  Earth terminal (PE) with screw fitting

Cam shaft drive  Non-reactive gear

Adjustment of  With adjustable cams


switching points  Scales beside the cams indicate the angle of the switching point

Position indicator  Internally


– Scale 0...135° at the end of the cam assembly
– Scale range to direction of rotation with arrow marking for SQM41 or with
marking
in slot die for SQM40

Electrical  RAST3.5 screw terminals are factory supplied, depending on the PCB variant
connections  RAST5 screw terminals are factory supplied, depending on the PCB variant
 Optional: Insulation displacement connectors
 Cable entry by means of 2 openings in the connector cover supplied.
The cable glands are not included in the scope of delivery
 Large openings in the housing allow easy cable installation

Gear train Maintenance-free gearwheels and bearings.

Drive shaft  Different shaft versions available, shafts are supplied assembled
 Drive shaft is not replaceable

Actuator fixing Mounting holes on the lower side of the housing (shaft side), such as actuators
SQM45... / SQM48... using M5 screws, or alternatively as actuators SQM10... /
SQM20... front mounting using M5 self-tapping screws (see chapter Dimensions).

6/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (other types on request)

Direction of Regional Operating Potentio-

running time ¹) for 90°


PCB
rotation version voltage meter

No. of switches
Switch version
Article no. Type

US / Canada

Double 135°
Diagram no.

Diagram no.

No. of relay

Double 90°
Torque ¹) /
Clockwise

Electronic

3-position

2-position

Shaft no.
clockwise
Counter-

AC120V

AC230V
version

EU
BPZ:SQM40.025A21 SQM40.025A21  2,5 Nm / 5 s 2 4 5   

BPZ:SQM40.065A23 SQM40.065A23  2,5 Nm / 5 s 6  6 5   

BPZ:SQM40.115R11 SQM40.115R11  5 Nm / 15 s 1 3 5   
BPZ:SQM40.115R13 SQM40.115R13  5 Nm / 15 s 1 3 5   

BPZ:SQM40.141A21 SQM40.141A21  5 Nm / 15 s 4 3 1   
BPZ:SQM40.144R11 SQM40.144R11  5 Nm / 15 s 4 3 4   
BPZ:SQM40.145A21 SQM40.145A21  5 Nm / 15 s 4 3 5   
BPZ:SQM40.145R11 SQM40.145R11  5 Nm / 15 s 4 3 5   
BPZ:SQM40.155R11 SQM40.155R11  5 Nm / 15 s 5 4 5   
BPZ:SQM40.155R13 SQM40.155R13  5 Nm / 15 s 5 4 5   

BPZ:SQM40.161A20 SQM40.161A20  5 Nm / 15 s 6  6 1  

BPZ:SQM40.165A20 SQM40.165A20  5 Nm / 15 s 6  6 5  
BPZ:SQM40.165A21 SQM40.165A21  5 Nm / 15 s 6  6 5   
BPZ:SQM40.165R11 SQM40.165R11  5 Nm / 15 s 6  6 5   
BPZ:SQM40.171A20 SQM40.171A20  5 Nm / 15 s 7  5 1 1  

BPZ:SQM40.175A21 SQM40.175A21  5 Nm / 15 s 7  5 1 5   

7/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (other types on request) (cont’d)

Direction of Regional Operating Potentio-

running time ¹) for 90°


PCB
rotation version voltage meter

No. of switches
Switch version
Article no. Type

US / Canada

Double 135°
Diagram no.

Diagram no.

No. of relay

Double 90°
Torque ¹) /
Clockwise

Electronic

3-position

2-position

Shaft no.
clockwise
Counter-

AC120V

AC230V
version

EU
BPZ:SQM40.185R11 SQM40.185R11  5 Nm / 15 s 8  6 5   
BPZ:SQM40.215R11 SQM40.215R11  10 Nm / 30 s 1 3 5   
BPZ:SQM40.215R13 SQM40.215R13  10 Nm / 30 s 1 3 5   
BPZ:SQM40.235A20 SQM40.235A20  10 Nm / 30 s 3  4 3 5  
BPZ:SQM40.241A21 SQM40.241A21  10 Nm / 30 s 4 3 1   
BPZ:SQM40.241R11 SQM40.241R11  10 Nm / 30 s 4 3 1   
BPZ:SQM40.244A21 SQM40.244A21  10 Nm / 30 s 4 3 4   
BPZ:SQM40.244R11 SQM40.244R11  10 Nm / 30 s 4 3 4   
BPZ:SQM40.245A11 SQM40.245A11  10 Nm / 30 s 4 3 5   
BPZ:SQM40.245A21 SQM40.245A21  10 Nm / 30 s 4 3 5   
BPZ:SQM40.245R11 SQM40.245R11  10 Nm / 30 s 4 3 5   
BPZ:SQM40.247A21 SQM40.247A21  10 Nm / 30 s 4 3 7   
BPZ:SQM40.255A21 SQM40.255A21  10 Nm / 30 s 5 4 5   
BPZ:SQM40.255R11 SQM40.255R11  10 Nm / 30 s 5 4 5   
BPZ:SQM40.255R13 SQM40.255R13  10 Nm / 30 s 5 4 5   
BPZ:SQM40.261A11 SQM40.261A11  10 Nm / 30 s 6  6 1   
BPZ:SQM40.261A20 SQM40.261A20  10 Nm / 30 s 6  6 1  
BPZ:SQM40.261A21 SQM40.261A21  10 Nm / 30 s 6  6 1   
BPZ:SQM40.261R11 SQM40.261R11  10 Nm / 30 s 6  6 1   

8/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (other types on request) (cont’d)

Direction of Regional Operating Potentio-

running time ¹) for 90°


PCB
rotation version voltage meter

No. of switches
Switch version
Article no. Type

US / Canada

Double 135°
Diagram no.

Diagram no.

No. of relay

Double 90°
Torque ¹) /
Clockwise

Electronic

3-position

2-position

Shaft no.
clockwise
Counter-

AC120V

AC230V
version

EU
BPZ:SQM40.265A11 SQM40.265A11  10 Nm / 30 s 6  6 5   
BPZ:SQM40.265A20 SQM40.265A20  10 Nm / 30 s 6  6 5  
BPZ:SQM40.265A21 SQM40.265A21  10 Nm / 30 s 6  6 5   
BPZ:SQM40.265R11 SQM40.265R11  10 Nm / 30 s 6  6 5   
BPZ:SQM40.267A20 SQM40.267A20  10 Nm / 30 s 6  6 7  
BPZ:SQM40.271A20 SQM40.271A20  10 Nm / 30 s 7  5 1 1  
BPZ:SQM40.274R10 SQM40.274R10  10 Nm / 30 s 7  5 1 4  
BPZ:SQM40.275A20 SQM40.275A20  10 Nm / 30 s 7  5 1 5  
BPZ:SQM40.275A21 SQM40.275A21  10 Nm / 30 s 7  5 1 5   
BPZ:SQM40.275R10 SQM40.275R10  10 Nm / 30 s 7  5 1 5  
BPZ:SQM40.281A20 SQM40.281A20  10 Nm / 30 s 8  6 1  
BPZ:SQM40.285R11 SQM40.285R11  10 Nm / 30 s 8  6 5   
BPZ:SQM40.317A23 SQM40.317A23  18 Nm / 65 s 1 3 7   
BPZ:SQM40.317R11 SQM40.317R11  18 Nm / 65 s 1 3 7   
BPZ:SQM40.317R13 SQM40.317R13  18 Nm / 65 s 1 3 7   
BPZ:SQM40.357R11 SQM40.357R11  18 Nm / 65 s 5 4 7   
BPZ:SQM40.357R13 SQM40.357R13  18 Nm / 65 s 5 4 7   
S55452-D301-A100 SQM40.367A10  18 Nm / 65 s 6  6 7  
BPZ:SQM40.387A20 SQM40.387A20  18 Nm / 65 s 8  6 7  
BPZ:SQM40.387A23 SQM40.387A23  18 Nm / 65 s 8  6 7   

9/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (other types on request) (cont’d)

Direction of Regional Operating Potentio-

running time ¹) for 90°


PCB
rotation version voltage meter

No. of switches
Switch version
Article no. Type

US / Canada

Double 135°
Diagram no.

Diagram no.

No. of relay

Double 90°
Torque ¹) /
Clockwise

Electronic

3-position

2-position

Shaft no.
clockwise
Counter-

AC120V

AC230V
version

EU
BPZ:SQM40.387R11 SQM40.387R11  18 Nm / 65 s 8  6 7   

BPZ:SQM41.141A21 SQM41.141A21  5 Nm / 15 s 4 3 1   
BPZ:SQM41.145A21 SQM41.145A21  5 Nm / 15 s 4 3 5   
BPZ:SQM41.161A20 SQM41.161A20  5 Nm / 15 s 6  6 1  

BPZ:SQM41.165R11 SQM41.165R11  5 Nm / 15 s 6  6 5   
BPZ:SQM41.185R11 SQM41.185R11  5 Nm / 15 s 8  6 5   

BPZ:SQM41.241A11 SQM41.241A11  10 Nm / 30 s 4 3 1   
BPZ:SQM41.241A21 SQM41.241A21  10 Nm / 30 s 4 3 1   
BPZ:SQM41.241R11 SQM41.241R11  10 Nm / 30 s 4 3 1   
BPZ:SQM41.244A21 SQM41.244A21  10 Nm / 30 s 4 3 4   
BPZ:SQM41.244R11 SQM41.244R11  10 Nm / 30 s 4 3 4   
BPZ:SQM41.245A11 SQM41.245A11  10 Nm / 30 s 4 3 5   
BPZ:SQM41.245A21 SQM41.245A21  10 Nm / 30 s 4 3 5   
BPZ:SQM41.245R11 SQM41.245R11  10 Nm / 30 s 4 3 5   

10/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (other types on request) (cont’d)

Direction of Regional Operating Potentio-

running time ¹) for 90°


PCB
rotation version voltage meter

No. of switches
Switch version
Article no. Type

US / Canada

Double 135°
Diagram no.

Diagram no.

No. of relay

Double 90°
Torque ¹) /
Clockwise

Electronic

3-position

2-position

Shaft no.
clockwise
Counter-

AC120V

AC230V
version

EU
BPZ:SQM41.254R11 SQM41.254R11  10 Nm / 30 s 5 4 4   
BPZ:SQM41.261A11 SQM41.261A11  10 Nm / 30 s 6  6 1   
BPZ:SQM41.261A21 SQM41.261A21  10 Nm / 30 s 6  6 1   
BPZ:SQM41.261R11 SQM41.261R11  10 Nm / 30 s 6  6 1   
BPZ:SQM41.264A21 SQM41.264A21  10 Nm / 30 s 6  6 4   
BPZ:SQM41.264R11 SQM41.264R11  10 Nm / 30 s 6  6 4   
BPZ:SQM41.265R11 SQM41.265R11  10 Nm / 30 s 6  6 5   
BPZ:SQM41.267A21 SQM41.267A21  10 Nm / 30 s 6  6 7   
BPZ:SQM41.271R10 SQM41.271R10  10 Nm / 30 s 7  5 1 1  
BPZ:SQM41.275A21 SQM41.275A21  10 Nm / 30 s 7  5 1 5   
BPZ:SQM41.275R10 SQM41.275R10  10 Nm / 30 s 7  5 1 5  
BPZ:SQM41.285R11 SQM41.285R11  10 Nm / 30 s 8  6 5   
BPZ:SQM41.357A23 SQM41.357A23  18 Nm / 65 s 5 4 7   
BPZ:SQM41.357R11 SQM41.357R11  18 Nm / 65 s 5 4 7   
BPZ:SQM41.367A21 SQM41.367A21  18 Nm / 65 s 6  6 7   
BPZ:SQM41.387R11 SQM41.387R11  18 Nm / 65 s 8  6 7   

1) Specifications apply to ambient temperatures of 23 °C and a mains voltage of AC 120 V or


AC 230 V and a mains frequency of 50 Hz. With a mains frequency of 60 Hz, the running times are approx. 17% shorter. Torques lower by the same rate.

11/29

Building Technologies Division CC1N7817en


11.02.2016
Type summary (cont´d) (other types on request) (cont’d)

 Note
Not all types of actuators are available ex stock. Additional versions are available on
request.

Drive shafts: Max. Shaft


Type of drive shaft
torque no.
 10 mm, woodruff key as per DIN 6888 10 Nm 1
 9.5 mm, square shaft 15 Nm 4
 10 mm D type shaft, compatible with SQM45... 10 Nm 5
 14 mm with parallel key as per DIN 6885, compatible with SQM48... 20 Nm 7

13/29

Building Technologies Division CC1N7817en


11.06.2016
Accessories

Accessories must be ordered as separate items:

Mounting plate ASK33.1


For mounting the SQM40... / SQM41... onto the VKP... proportional controlling
element
See Mounting Instruction 74 319 0843 0 (M7646)

Mounting kit ASK33.4


For fitting SQM40... / SQM41... to the butterfly valve VKF41.xxC
See Mounting Instruction 74 319 0916 0 (M7813 / 7814)

Front cover (on request)


For making the connections for the power supply lines
- For 1/2" NPT protective sleeve AGA45.11
- For metric cable gland AGA45.12

 Note!
Front covers AGA45.11 and AGA45.12 are only to be used as replacements.
The corresponding AGA45... version is factory-prefitted onto the SQM40... /
SQM41...

Connector sets (on request)


With screw terminals for replacement:
- For SQM4x.x1xxxx AGA45.1
- For SQM4x.x4xxxx AGA45.4
- For SQM4x.x2xxxx, SQM4x.x5xxxx AGA45.5
- For SQM4x.x3xxxx, SQM4x.x6xxxx, SQM4x.x7xxxx, SQM4x.x8xxxx AGA45.6

Potentiometers (on request)


For retrofitting
- For SQM40... / SQM41...: Double potentiometer 2*1000 , 90° ASZ22.32
- For SQM40...: Double potentiometer 2*1000 , 135° ASZ22.35
- For SQM41...: Double potentiometer 2*1000 , 135° ASZ22.34
Refer to Data Sheet N7921.

 Note!
ASZ22... potentiometers are only intended for the retrofitting onto SQM40... /
SQM41... types with the end number 0 (SQM4x.xxxx0).

For all SQM40... / SQM41... types with the end number 1 (SQM4x.xxxx1) or 3
(SQM4x.xxxx3), the potentiometers are already factory installed.

14/29

Building Technologies Division CC1N7817en


11.02.2016
Technical Data
General unit data Operating voltage
- SQM4x.xxxA1… AC 120 V -15%/+10%
- SQM4x.xxxA2… AC 230 V -15%/+10%
- SQM4x.xxxR1… AC 120 V -15%/+10%
Operating frequency 50…60 Hz ±6%
Drive motor Synchronous motor
Power consumption 10 VA
Operating angle Between 0° and max. 90° or between 0°
and max. 135°, depending on the type
Mounting position Optional
Degree of protection IP66
Safety class I
External overload fuse Max. 6.3 AT (slow) to DIN EN 60127-2/5
Internal overload fuse 2 AT (slow), depending on the type, non-
exchangeable
Cable entry 2 x M16 without thread or
2 x ½” NPT thread, depending on the type
Wire cross-sectional area of the 0.5...2.5 mm²
connecting wires, including earth terminal
(PE)
Direction of rotation Facing the shaft end (mounting surface):
 SQM40... Counterclockwise (CCW)
 SQM41... Clockwise (CW)
Torque 2.5 Nm / 5 Nm / 10 Nm / 18 Nm,
depending on type 1)
Torque tolerance -25%
Each valid at the tolerance limits of
temperature and operating voltage
Holding torque 50%
Of the torque for types with 5 Nm, 10 Nm,
and 18 Nm torque
36%
Of the torque for types with 2.5 Nm torque
Running time 5 s, 15 s, 30 s and 65 s, depending on
type 1)
Running time tolerance +10%
Pause time at change in direction of >100 ms
rotation, zero-current state
End and auxiliary switches
 Type To DIN 41636
 Switching voltage AC 24...250 V
 Switching capacity See specifications in chapter Connection
diagrams
Number of end switches 2
Number of auxiliary switches Max. 4, depending on type
Drive shaft Supplied as standard, non-exchangeable
Weight Approx. 2 kg
Temperature of the mounting surface Max. 60 °C
Rated surge voltage Overvoltage category III in accordance
with DIN EN 60730-1 chapter 20
Backlash between the actuator motor and
actuator shaft
- ex works <1°
- after 250,000 cycles <1.2°
1) Specifications apply to ambient temperatures of 23 °C and a mains voltage of AC 120 V or
AC 230 V and a mains frequency of 50 Hz. With a mains frequency of 60 Hz, the running times are
approx. 17% shorter. The torques lower by the same rate

15/29

Building Technologies Division CC1N7817en


11.02.2016
Technical Data (cont´d)
Lifetime 250,000 start cycles (close  open 
close) under load with the rated torque in
the entire rotation angle range.
2,000,000 control cycles under load with
75% of rated torque in rotation angle
range of 10°

Analog inputs General


Linearity <5% of the control range
Control range 0...90° or 0...135°, depending on type
Voltage setpoint DC 2...10 V
X1-1 (U-IN), X1-2 (GND)
- Umin DC 2 V
- Umax DC 10 V
Input impedance ≥5 k
Current setpoint DC 4...20 mA
X1-3 (I-IN), X1-2 (GND)
- Imin DC 4 mA
- Imax DC 20 mA
Input impedance ≤500 
Impedance setpoint 0...135 
X1-4, X1-5, X1-6 (GND)
- RNominal 135  ±5%

For use in North Cross-sectional area of the power supply lines


America SQM4x.x1xxxx / SQM4x.x4xxxx / Class 1, min. AWG 16
SQM4x.x5xxxx, (X2), (PE) Suited for 105 °C
SQM4x.x6xxxx / SQM4x.x7xxxx / Max. 2.5 mm² or AWG 14
SQM4x.x8xxxx, (X1)/(X2)/(X3), (PE)
SQM4x.x1xxxx / SQM4x.x2xxxx Class 2, min. AWG 22
SQM4x.x4xxxx / SQM4x.x5xxxx (X1) Suited for 105 °C
Max. 1 mm² or AWG 18
NEMA classification NEMA4 (in progress)
Outdoor use
Attention!
Waterproof cable conduits and cable
glands are required (e.g. type DWTT/7 or
QCRV2/8)

Environmental conditions Storage DIN EN 60721-3-1


Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...60 °C
Humidity <95% r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K3
Mechanical conditions Class 2M2
Temperature range -20...60 °C
Humidity <95% r.h.
Operation DIN EN 60721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M4
Temperature range -20...60 °C
-15...+60 °C for 18 Nm design
Humidity <95% r.h.

Notice!
Condensation, formation of ice, and ingress of water are not permitted. If this is
not observed, there is a risk of loss of safety functions and a risk of electric
shock.

16/29

Building Technologies Division CC1N7817en


11.02.2016
Technical Data (cont´d)
Conductive plastic Resistance 2*1000  double potentiometer with
potentiometer separated resistance tracks
Operating voltage DC 10 V
Permissible hysteresis 0.3% of 90° or of 135°, depending on type
Total resistance tolerance ±20%
Effective angular rotation 90° or 135°, depending on type
Terminal strip Triple-pole
For cross-sectional areas of 0.5...1 mm²
Wiper current rating Max. 100 µA
Transfer resistance of wiper contact Max. Rü  100 
Linearity (referred to Rges = 1000 ) 1%
Smoothness (alpha = 10°) / microlinearity <0.5%
Life cycle Approx. 2 million positioning cycles
Temperature coefficient 0.4 /K

Conductive plastic a b c Potentiometer drawn in start position (as


potentiometer supplied).
connection diagram
Terminal markings:
a = high end of potentiometer
b = potentiometer wiper
c = low end of potentiometer

Apply operating voltage only on terminals «a» and «c». Conductive plastic
potentiometers can be destroyed if operating voltage is applied incorrectly between «a 
b» or «b  c».

The polarity of the potentiometer end pickups «a  c» must be observed in order to


achieve the correct signal direction to the potentiometer wiper «b».

If the potentiometer specified for 90° is operated outside of the effective range of angular
rotation of 90°, no valid signal will be present at the wiper contact (interrupted circuit).
This can happen if the switch position of the switching cam I for high-fire is configured for
over 90°.

The 90° version ASZ22.32 can be used for both directions of rotation, SQM40...
(counterclockwise) and SQM41... (clockwise).

The 135° versions ASZ22.34 and ASZ22.35 are each intended for a particular direction
of rotation.

The direction of rotation of the potentiometer must correspond with the direction of
rotation of the actuator as follows:
 ASZ22.34 can only be used with SQM41... (clockwise)
 ASZ22.35 can only be used with SQM40... (counterclockwise)

17/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals
SQM4x.x1xxxx Electronic version

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d13/1013
Mains voltage terminals Dimensioning
1
X1-1 2...10 V Input max. DC 10 V
VI V to X1-5
I

xxxx
X1-2 4...20 mA Input max. 20 mA
M to X1-5
4-20mA
0-135? X1-3 0...135  1 Input
2-10V

0...135  2
GND
X1-4 Input
X1-5 0...135  3 (GND) Input
7 1 6 4 2 3 5 X2 1 2 3 4 5 X1
X2-1 Open (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-2 Move to low-fire (V) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Low-fire position reached Output AC 120 V / AC 230 V
(V) max. 10 mA, cos >0.9
X2-4 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-6 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-7 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9

Mains voltage terminals Dimensioning


X2-1 Open (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-2 Move to low-fire (V) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Low-fire position reached Output AC 120 V / AC 230 V
(V) max. 10 mA, cos >0.9
X2-4 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-6 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-7 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9

* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.

Range adjustment See SQM4x.x4xxxx in this chapter.

18/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)
SQM4x.x2xxxx Electronic version, only for types with 5 seconds running time

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d21/0415
Low-voltage terminals Dimensioning
2 5
X1-1 4...20 mA Input max. 20 mA
I VI V to X1-2

xxxx
X1-2 GND Input ---
M

4-20mA
IV
Mains voltage terminals Dimensioning

GND
X2-1 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
5 43 1 2 8 7 6 9 X2 1 2 X1
X2-2 Open, high-fire (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-4 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9
X2-6 Low-fire position / ignition Output AC 120 V / AC 230 V
load position reached (V / max. 10 mA, cos >0.9
VI)
X2-7 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9*
X2-8 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-9 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA

* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.

Range adjustment See SQM4x.x4xxxx in this chapter.

19/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)
SQM4x.x3xxxx 2-position version with 2 end switches and 2 auxiliary switches, 3 relays

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d14/1013
Mains voltage terminals Dimensioning
3
X1-1 Free --- ---
R X1-2 Controller, open Input AC 120 V / AC 230 V

K-B
K-A

K-C
I II III max. 1 A, cos >0.9
M
X1-3 Controller release Input AC 120 V / AC 230 V

xxxx
max. 1 A, cos >0.9
b1 VI
a2
a1 X1-4 Auxiliary switch AUX (VI) Input AC 120 V / AC 230 V
b2
max. 1 A, cos >0.9 **
c1
4 1 2 5 3 3 2 1 5 6 4 X1 1 2 3 X3
X1-5 Neutral Input AC 120 V / AC 230 V
X2
max. 1 A, cos >0.9
X1-6 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9 **

X2-1 Fan supply voltage Input AC 120 V / AC 230 V


max. 1 A, cos >0.9
X2-2 Mains voltage, close Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-3 Low-fire controller Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-4 Fan motor Output AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Free --- ---

X3-1 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V


NO contact max. 1 A, cos >0.9 **
X3-2 Open (I) / close (II), Input AC 120 V / AC 230 V
changeover relay K-C max. 1 A, cos >0.9
X3-3 Operation, changeover Input AC 120 V / AC 230 V
relay K-B max. 1 A, cos >0.9

Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.

Range adjustment See SQM4x.x4xxxx in this chapter.

20/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)
SQM4x.x4xxxx Electronic version

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d18/1013
Low-voltage terminals Dimensioning
4
X1-1 2...10 V Input max. DC 10 V
I VI V to X1-2

xxxx
X1-2 GND Input
M X1-3 4...20 mA Input Max. 20 mA to X1-2
X1-4 0...135  1 Input
4-20mA
0-135?
2-10V
GND

GND
X1-5 0...135  2 Input
X1-6 0...135  3 (GND) Input
1 6 4 2 3 5 X2 1 23 4 5 6 X1

Mains voltage terminals Dimensioning


X2-1 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-2 Move to low-fire (V) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Position reached Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
X2-4 Closing/ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-6 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA

* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.

Range adjustment Adjust the range of the analog signal to match the switch positions (min. and max.
position):

1. Set cam I to the required high-fire position (e.g. 85°; position is indicated on the scale
next to the cam).
2. Set cam V to the required low-fire position (e.g. 20°).
3. Preset the signal at the analog input according to the required high-fire position
(e.g. 20 mA).
4. Turn the potentiometer for maximum angular rotation
a) clockwise, if the actuator has not yet reached its maximum angular rotation, or
b) counterclockwise until the actuator starts
5. Preset the signal at the analog input according to the low-fire position (e.g. 4 mA).
6. Turn the potentiometer for minimum angular rotation
a) counterclockwise, if the actuator has not yet reached its minimum angular
rotation, or
b) clockwise until the actuator starts

Modulation always takes place between high- and low-fire.

Also, it is possible to define a closed position or a separate ignition position by setting


cam VI (independent of cam V, e.g. for defining a position higher than the low-fire
position).

21/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)

Max. potentiometer (high-fire)


90° / 135°
Max.

Min.

Min. potentiometer (low-fire)

7817z08e/0315

 Note!
When starting up, the direction of rotation of the potentiometer setting must be
observed:

90° / 135°
Max.

Min.

7817z10/0713

 Note
The working range of the potentiometer setting, shown as an example for the current
input 4...20 mA.

90° / 135°
Setpoint (I/mA)
max.
(V) (I)
20
18
16
14
12
10
8
6
4
2
30 60 90 120 135
Positioning angle (°)
0
10 20 30 40 50 60 70 80 90
0° 7817d04e/0315

min.

22/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)
SQM4x.x5xxxx Electronic version

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d21/0415
Low-voltage terminals Dimensioning
2 5
X1-1 4...20 mA Input max. 20 mA
I VI V to X1-2

xxxx
X1-2 GND Input ---
M

4-20mA
IV
Mains voltage terminals Dimensioning

GND
X2-1 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
5 43 1 2 8 7 6 9 X2 1 2 X1
X2-2 Open / high-fire (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-4 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Auxiliary switch AUX (IV) / Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9
X2-6 Low-fire position / ignition Output AC 120 V / AC 230 V
load position reached (V, max. 10 mA, cos >0.9
VI)
X2-7 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-8 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-9 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA

* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.

Range adjustment See SQM4x.x4xxxx in this chapter.

23/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)
SQM4x.x6xxxx 3-position version with 2 end switches and 4 auxiliary switches

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d15/1013
Mains voltage terminals Dimensioning
6
X1-1 Move to ignition position Input AC 120 V / AC 230 V
I II III (III) max. 1 A, cos >0.9

xxxx
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
M NO contact max. 1 A, cos >0.9
X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
IV V VI
max. 1 A, cos >0.9
X1-4 Neutral AC 120 V / AC 230 V
max. 1 A, cos >0.9
3 2 6 4 5 1 X1 5 4 3 1 2 X2 2 3 1 X3
X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9

X2-1 Auxiliary switch AUX (V) Input AC 120 V / AC 230 V


max. 1 A, cos >0.9
X2-2 Auxiliary switch AUX (V) Output AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-3 Open position reached (I) Output AC 120 V / AC 230 V
max. 0.3 A, cos >0.8
X2-4 Close position reached (II) Output AC 120 V / AC 230 V
max. 0.3 A, cos >0.8
X2-5 Ignition position reached Output AC 120 V / AC 230 V
(III) max. 0.3 A, cos >0.8

X3-1 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V


NO contact max. 1 A, cos >0.9 **
X3-2 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9 **
X3-3 Auxiliary switch AUX (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 **

Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.

Range adjustment See SQM4x.x4xxxx in this chapter.

24/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)

SQM4x.x7xxxx 2-position version with 2 end switches and 3 auxiliary switches, 1 relay

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

7817d16/1013
Mains voltage terminals Dimensioning
7
X1-1 Move to ignition position Input AC 120 V / AC 230 V
I II III (III) max. 1 A, cos >0.9

xxxx
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
M NO contact max. 1 A, cos >0.9
X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
IV K-A VI
a1 max. 1 A, cos >0.9
X1-4 Neutral AC 120 V / AC 230 V
max. 1 A, cos >0.9
3 2 6 4 5 1 X1 5 4 3 1 2 X2 2 3 1 X3
X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9

X2-1 Mains voltage Input AC 120 V / AC 230 V


max. 1 A, cos >0.9
X2-2 Open / close relay Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-3 Open position reached (I) Output AC 120 V / AC 230 V
max. 0.3 A, cos >0.8
X2-4 Close position reached (II) Output AC 120 V / AC 230 V
max. 0.3 A, cos >0.8
X2-5 Ignition position reached Output AC 120 V / AC 230 V
(III) max. 0.3 A, cos >0.8

X3-1 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V


NO contact max. 1 A, cos >0.9 **
X3-2 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9 **
X3-3 Auxiliary switch AUX (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 **

Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.

Range adjustment See SQM4x.x4xxxx in this chapter.

25/29

Building Technologies Division CC1N7817en


11.02.2016
Connection diagrams and connection terminals (cont’d)

SQM4x.x8xxxx 3 position version with 2 end switches and 4 auxiliary switches

Note!
 For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.

Mains voltage terminals Dimensioning

7817d17/1013
X1-1 Move to position (III) Input AC 120 V / AC 230 V
8 max. 1 A, cos >0.9
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
I II III
NO contact max. 1 A, cos >0.9

xxxx
M X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
IV V VI X1-4 Neutral Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
inductive
32 6 4 5 1 X1 4 3 5 1 2 X2 2 3 1 X3 X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9

X2-1 Auxiliary switch AUX (V) Input AC 120 V / AC 230 V


max. 1 A, cos >0.9
X2-2 Auxiliary switch AUX (V) Input AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-3 Position reached (I / II / III) Output AC 120 V / AC 230 V
max. 0.3 A, cos >0.8
X2-4 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9
X2-5 Auxiliary switch AUX (V) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9

X3-1 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V


NO contact max. 1 A, cos >0.9 **
X3-2 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9 **
X3-3 Auxiliary switch AUX (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 **

Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.

Range adjustment See SQM4x.x4xxxx in this chapter.

26/29

Building Technologies Division CC1N7817en


11.02.2016
Position indication, preadjustment and coloring of the cams

Position indication SQM40... Position indication SQM41...


External angle scale Internal angle scale
Marking in slot shape Arrow marking

7817z12e/0315
Pay attention
to markings!

1 35

1 35
0

0
30

30
90

90
0 60 0 0 60

0
13 30 13 30
6

6
5 90 5 90

 Note!
The setting of the switch positions must be checked before startup.

SQM4x.x1xxxx Electronic version


SQM4x.x4xxxx Cam Color Position Preadjustment
Cam I Red High-fire 90°
Cam II Blue Not used ---
Cam III Orange Not used ---
Cam IV Yellow Not used ---
Cam V Black Low-fire 15°
Cam VI Green OFF / ignition 0°

SQM4x.x3xxxx 2 position version


Cam Color Position Preadjustment
Cam I Red High-fire 90°
Cam II Blue OFF / low-fire 0°
Cam III Orange Ignition position 15°
Cam IV Yellow Not used ---
Cam V Black Not used ---
Cam VI Green Auxiliary switch 30°

SQM4x.x2xxxx Electronic version


SQM4x.x5xxxx Cam Color Position Preadjustment
Cam I Red High-fire 90°
Cam II Blue Not used ---
Cam III Orange Not used ---
Cam IV Yellow Auxiliary switch 30°
Cam V Black Low-fire 30°
Cam VI Green OFF / ignition 0°

27/29

Building Technologies Division CC1N7817en


11.02.2016
Position indication, preadjustment and coloring of the cams (cont’d)

SQM4x.x6xxxx 3 position version


SQM4x.x8xxxx Cam Color Position Preadjustment
Cam I Red High-fire 90°
Cam II Blue OFF / low-fire 0°
Cam III Orange Ignition position 15°
Cam IV Yellow Auxiliary switch 30°
Cam V Black Auxiliary switch 30°
Cam VI Green Auxiliary switch 30°

SQM4x.x7xxxx 3 position version


Cam Color Position Preadjustment
Cam I Red High-fire 90°
Cam II Blue OFF / low-fire 0°
Cam III Orange Ignition position 15°
Cam IV Yellow Auxiliary switch 30°
Cam V Black Not used ---
Cam VI Green Auxiliary switch 30°

28/29

Building Technologies Division CC1N7817en


11.02.2016
Dimensions
Dimensions in mm

SQM40.../SQM41…
93.5

9.5
3 blind holes (10 mm deep)
for self-tapping screws M5

6 +0.1 4 through holes for


screws M5

5 deep

SQM4x.xxxAxxx connecting cover

SQM4x.xxxRxxx connecting cover

Shaft no.
2.5 +0.1

Slot for woodruff key


SQM4x.xx1xxx 3x3.7 series A
Din6888 1

10.6 9.5 h11

SQM4x.xx4xxx Square 4
8.5 -0.005

SQM4x.xx5xxx D-shaft 5
1.9 +0.1

SQM4x.xx7xxx Slot for parallel key


A5x3x28 DIN6885 T3 7 7817m01e/0216

 2016 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change! 29/29

Building Technologies Division CC1N7817en


11.02.2016