SQM4 Synchro Models Literature
SQM4 Synchro Models Literature
Actuator SQM40.../SQM41...
The SQM40.../SQM41… and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!
Use
The SQM40.../SQM41... actuators are suited for driving oil pressure controller, butterfly
valves, dampers or for use on other applications that require rotary motion.
Areas of application are oil and gas burners of medium to higher capacity as well as
thermal process plants.
The actuators are used primarily for load-dependent control of the flow of gas, oil and
combustion air:
In connection with 3-position or modulating controllers (e.g. 4...20 mA), and/or ...
... directly by burner controls
CC1N7817en
Building Technologies Division
11.02.2016
Supplementary documentation
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Only qualified personnel may open, interfere with or modify the actuators!
Read the documentation on the actuators carefully and fully. If not observed,
dangerous situations might occur
The user must ensure that the actuators meet the requirements of the relevant
application standards
Safety-related applications are only available with Siemens burner controls!
All product-related activities (mounting, settings and maintenance) must be
performed by qualified and authorized personnel
Caution!
Risk of electric shock hazard – to disconnect the actuator from power, it may be
necessary to open more than one switch. Before performing maintenance work,
the actuator must be disconnected from power
The electrical connection between the conduit fittings is not made automatically.
It must be established on installation site
The connecting plate is made of plastic and does not provide earthing of the
conduit fittings. Earthing must be ensured by adequate washers and wire links
All cam switch settings must satisfy the requirements of the relevant application
standards
To provide protection against electric shock hazard, the connecting terminals must
have adequate touch protection. Make certain that non-insulated connections or
wires cannot be touched
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation even if they do not exhibit any damage
Static charges must be avoided since they can damage the actuator’s electronic
components when touched.
Recommendation: Use ESD equipment
2/29
Note!
Ensure correct direction of rotation!
0°
90°
5°
13
90° 0°
5°
13
Installation notes
Ensure that the electrical wiring is in compliance with national and local safety
regulation
Make certain that strain relief of the connected cables conforms to the relevant
standards (e.g. as per DIN EN 60730 and DIN EN 60335)
Ensure that spliced wires cannot get into contact with neighboring terminals. Use
adequate ferrules
Unused terminals of the SQM40.../SQM41... must be covered by dummy plugs
When making the wiring, the AC 120 V or AC 230 V section must be separated
from other voltage sections, thus ensuring protection against electric shock hazard
The connection between the actuator drive shaft and the relevant controlling
element must be form-fitted
Only plastic versions of cable glands may be used
3/29
Note!
The connection of fuel valves is only permitted on fused output terminals, see chapter
Connection diagrams. For this purpose, specific unit variants are available fitted with
a unit-internal, non-replaceable fuse. The unit-internal fuse is used to protect each
switching contact from welding in the event of external short-circuit. In addition,
please note that the maximum current load for the fused output terminals is reduced,
see chapter Connection diagrams.
SQM4x.x1xxxx SQM4x.x3xxxx
SQM4x.x2xxxx SQM4x.x6xxxx
SQM4x.x4xxxx
SQM4x.x7xxxx
SQM4x.x5xxxx: SQM4x.x8xxxx:
Mains voltage range
X2
7817z09e/0315
Note
SELV or PELV depends on the safety class of the connected components. In the
case of PELV, the relevant component is connected to protective earth.
4/29
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic electrical controls for household and similar use DIN EN 60730-2-14
Part 2-14:
Special requirements on electric actuators
Automatic electrical controls for household and similar use DIN EN 60730-1
Part 1: General requirements
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
Lifetime
The actuator has a designed lifetime* of 250,000 start cycles
(close open close) under load with the rated torque in the entire rotation angle
range, which under normal operating conditions in heating mode corresponds to
approx.
10 years of usage (starting from the date of manufacture on the device type plate). This
lifetime is based on the endurance tests specified in standard EN 298.
A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor - www.afecor.org).
The designed lifetime is based on use of the actuator according to the manufacturer’s
Data Sheet. After reaching the designed lifetime in terms of the number of startup
cycles, or the respective time of usage time, the actuator is to be replaced by
authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery.
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
5/29
Coupling Shaft can be manually disengaged from the motor by operating the coupling
(coupling pin (K1))
Automatic reengagement
Disengagement of drive shaft / motor by pressing coupling pin «K1»
Electrical RAST3.5 screw terminals are factory supplied, depending on the PCB variant
connections RAST5 screw terminals are factory supplied, depending on the PCB variant
Optional: Insulation displacement connectors
Cable entry by means of 2 openings in the connector cover supplied.
The cable glands are not included in the scope of delivery
Large openings in the housing allow easy cable installation
Drive shaft Different shaft versions available, shafts are supplied assembled
Drive shaft is not replaceable
Actuator fixing Mounting holes on the lower side of the housing (shaft side), such as actuators
SQM45... / SQM48... using M5 screws, or alternatively as actuators SQM10... /
SQM20... front mounting using M5 self-tapping screws (see chapter Dimensions).
6/29
No. of switches
Switch version
Article no. Type
US / Canada
Double 135°
Diagram no.
Diagram no.
No. of relay
Double 90°
Torque ¹) /
Clockwise
Electronic
3-position
2-position
Shaft no.
clockwise
Counter-
AC120V
AC230V
version
EU
BPZ:SQM40.025A21 SQM40.025A21 2,5 Nm / 5 s 2 4 5
BPZ:SQM40.115R11 SQM40.115R11 5 Nm / 15 s 1 3 5
BPZ:SQM40.115R13 SQM40.115R13 5 Nm / 15 s 1 3 5
BPZ:SQM40.141A21 SQM40.141A21 5 Nm / 15 s 4 3 1
BPZ:SQM40.144R11 SQM40.144R11 5 Nm / 15 s 4 3 4
BPZ:SQM40.145A21 SQM40.145A21 5 Nm / 15 s 4 3 5
BPZ:SQM40.145R11 SQM40.145R11 5 Nm / 15 s 4 3 5
BPZ:SQM40.155R11 SQM40.155R11 5 Nm / 15 s 5 4 5
BPZ:SQM40.155R13 SQM40.155R13 5 Nm / 15 s 5 4 5
BPZ:SQM40.161A20 SQM40.161A20 5 Nm / 15 s 6 6 1
BPZ:SQM40.165A20 SQM40.165A20 5 Nm / 15 s 6 6 5
BPZ:SQM40.165A21 SQM40.165A21 5 Nm / 15 s 6 6 5
BPZ:SQM40.165R11 SQM40.165R11 5 Nm / 15 s 6 6 5
BPZ:SQM40.171A20 SQM40.171A20 5 Nm / 15 s 7 5 1 1
BPZ:SQM40.175A21 SQM40.175A21 5 Nm / 15 s 7 5 1 5
7/29
No. of switches
Switch version
Article no. Type
US / Canada
Double 135°
Diagram no.
Diagram no.
No. of relay
Double 90°
Torque ¹) /
Clockwise
Electronic
3-position
2-position
Shaft no.
clockwise
Counter-
AC120V
AC230V
version
EU
BPZ:SQM40.185R11 SQM40.185R11 5 Nm / 15 s 8 6 5
BPZ:SQM40.215R11 SQM40.215R11 10 Nm / 30 s 1 3 5
BPZ:SQM40.215R13 SQM40.215R13 10 Nm / 30 s 1 3 5
BPZ:SQM40.235A20 SQM40.235A20 10 Nm / 30 s 3 4 3 5
BPZ:SQM40.241A21 SQM40.241A21 10 Nm / 30 s 4 3 1
BPZ:SQM40.241R11 SQM40.241R11 10 Nm / 30 s 4 3 1
BPZ:SQM40.244A21 SQM40.244A21 10 Nm / 30 s 4 3 4
BPZ:SQM40.244R11 SQM40.244R11 10 Nm / 30 s 4 3 4
BPZ:SQM40.245A11 SQM40.245A11 10 Nm / 30 s 4 3 5
BPZ:SQM40.245A21 SQM40.245A21 10 Nm / 30 s 4 3 5
BPZ:SQM40.245R11 SQM40.245R11 10 Nm / 30 s 4 3 5
BPZ:SQM40.247A21 SQM40.247A21 10 Nm / 30 s 4 3 7
BPZ:SQM40.255A21 SQM40.255A21 10 Nm / 30 s 5 4 5
BPZ:SQM40.255R11 SQM40.255R11 10 Nm / 30 s 5 4 5
BPZ:SQM40.255R13 SQM40.255R13 10 Nm / 30 s 5 4 5
BPZ:SQM40.261A11 SQM40.261A11 10 Nm / 30 s 6 6 1
BPZ:SQM40.261A20 SQM40.261A20 10 Nm / 30 s 6 6 1
BPZ:SQM40.261A21 SQM40.261A21 10 Nm / 30 s 6 6 1
BPZ:SQM40.261R11 SQM40.261R11 10 Nm / 30 s 6 6 1
8/29
No. of switches
Switch version
Article no. Type
US / Canada
Double 135°
Diagram no.
Diagram no.
No. of relay
Double 90°
Torque ¹) /
Clockwise
Electronic
3-position
2-position
Shaft no.
clockwise
Counter-
AC120V
AC230V
version
EU
BPZ:SQM40.265A11 SQM40.265A11 10 Nm / 30 s 6 6 5
BPZ:SQM40.265A20 SQM40.265A20 10 Nm / 30 s 6 6 5
BPZ:SQM40.265A21 SQM40.265A21 10 Nm / 30 s 6 6 5
BPZ:SQM40.265R11 SQM40.265R11 10 Nm / 30 s 6 6 5
BPZ:SQM40.267A20 SQM40.267A20 10 Nm / 30 s 6 6 7
BPZ:SQM40.271A20 SQM40.271A20 10 Nm / 30 s 7 5 1 1
BPZ:SQM40.274R10 SQM40.274R10 10 Nm / 30 s 7 5 1 4
BPZ:SQM40.275A20 SQM40.275A20 10 Nm / 30 s 7 5 1 5
BPZ:SQM40.275A21 SQM40.275A21 10 Nm / 30 s 7 5 1 5
BPZ:SQM40.275R10 SQM40.275R10 10 Nm / 30 s 7 5 1 5
BPZ:SQM40.281A20 SQM40.281A20 10 Nm / 30 s 8 6 1
BPZ:SQM40.285R11 SQM40.285R11 10 Nm / 30 s 8 6 5
BPZ:SQM40.317A23 SQM40.317A23 18 Nm / 65 s 1 3 7
BPZ:SQM40.317R11 SQM40.317R11 18 Nm / 65 s 1 3 7
BPZ:SQM40.317R13 SQM40.317R13 18 Nm / 65 s 1 3 7
BPZ:SQM40.357R11 SQM40.357R11 18 Nm / 65 s 5 4 7
BPZ:SQM40.357R13 SQM40.357R13 18 Nm / 65 s 5 4 7
S55452-D301-A100 SQM40.367A10 18 Nm / 65 s 6 6 7
BPZ:SQM40.387A20 SQM40.387A20 18 Nm / 65 s 8 6 7
BPZ:SQM40.387A23 SQM40.387A23 18 Nm / 65 s 8 6 7
9/29
No. of switches
Switch version
Article no. Type
US / Canada
Double 135°
Diagram no.
Diagram no.
No. of relay
Double 90°
Torque ¹) /
Clockwise
Electronic
3-position
2-position
Shaft no.
clockwise
Counter-
AC120V
AC230V
version
EU
BPZ:SQM40.387R11 SQM40.387R11 18 Nm / 65 s 8 6 7
BPZ:SQM41.141A21 SQM41.141A21 5 Nm / 15 s 4 3 1
BPZ:SQM41.145A21 SQM41.145A21 5 Nm / 15 s 4 3 5
BPZ:SQM41.161A20 SQM41.161A20 5 Nm / 15 s 6 6 1
BPZ:SQM41.165R11 SQM41.165R11 5 Nm / 15 s 6 6 5
BPZ:SQM41.185R11 SQM41.185R11 5 Nm / 15 s 8 6 5
BPZ:SQM41.241A11 SQM41.241A11 10 Nm / 30 s 4 3 1
BPZ:SQM41.241A21 SQM41.241A21 10 Nm / 30 s 4 3 1
BPZ:SQM41.241R11 SQM41.241R11 10 Nm / 30 s 4 3 1
BPZ:SQM41.244A21 SQM41.244A21 10 Nm / 30 s 4 3 4
BPZ:SQM41.244R11 SQM41.244R11 10 Nm / 30 s 4 3 4
BPZ:SQM41.245A11 SQM41.245A11 10 Nm / 30 s 4 3 5
BPZ:SQM41.245A21 SQM41.245A21 10 Nm / 30 s 4 3 5
BPZ:SQM41.245R11 SQM41.245R11 10 Nm / 30 s 4 3 5
10/29
No. of switches
Switch version
Article no. Type
US / Canada
Double 135°
Diagram no.
Diagram no.
No. of relay
Double 90°
Torque ¹) /
Clockwise
Electronic
3-position
2-position
Shaft no.
clockwise
Counter-
AC120V
AC230V
version
EU
BPZ:SQM41.254R11 SQM41.254R11 10 Nm / 30 s 5 4 4
BPZ:SQM41.261A11 SQM41.261A11 10 Nm / 30 s 6 6 1
BPZ:SQM41.261A21 SQM41.261A21 10 Nm / 30 s 6 6 1
BPZ:SQM41.261R11 SQM41.261R11 10 Nm / 30 s 6 6 1
BPZ:SQM41.264A21 SQM41.264A21 10 Nm / 30 s 6 6 4
BPZ:SQM41.264R11 SQM41.264R11 10 Nm / 30 s 6 6 4
BPZ:SQM41.265R11 SQM41.265R11 10 Nm / 30 s 6 6 5
BPZ:SQM41.267A21 SQM41.267A21 10 Nm / 30 s 6 6 7
BPZ:SQM41.271R10 SQM41.271R10 10 Nm / 30 s 7 5 1 1
BPZ:SQM41.275A21 SQM41.275A21 10 Nm / 30 s 7 5 1 5
BPZ:SQM41.275R10 SQM41.275R10 10 Nm / 30 s 7 5 1 5
BPZ:SQM41.285R11 SQM41.285R11 10 Nm / 30 s 8 6 5
BPZ:SQM41.357A23 SQM41.357A23 18 Nm / 65 s 5 4 7
BPZ:SQM41.357R11 SQM41.357R11 18 Nm / 65 s 5 4 7
BPZ:SQM41.367A21 SQM41.367A21 18 Nm / 65 s 6 6 7
BPZ:SQM41.387R11 SQM41.387R11 18 Nm / 65 s 8 6 7
11/29
Note
Not all types of actuators are available ex stock. Additional versions are available on
request.
13/29
Note!
Front covers AGA45.11 and AGA45.12 are only to be used as replacements.
The corresponding AGA45... version is factory-prefitted onto the SQM40... /
SQM41...
Note!
ASZ22... potentiometers are only intended for the retrofitting onto SQM40... /
SQM41... types with the end number 0 (SQM4x.xxxx0).
For all SQM40... / SQM41... types with the end number 1 (SQM4x.xxxx1) or 3
(SQM4x.xxxx3), the potentiometers are already factory installed.
14/29
15/29
Notice!
Condensation, formation of ice, and ingress of water are not permitted. If this is
not observed, there is a risk of loss of safety functions and a risk of electric
shock.
16/29
Apply operating voltage only on terminals «a» and «c». Conductive plastic
potentiometers can be destroyed if operating voltage is applied incorrectly between «a
b» or «b c».
If the potentiometer specified for 90° is operated outside of the effective range of angular
rotation of 90°, no valid signal will be present at the wiper contact (interrupted circuit).
This can happen if the switch position of the switching cam I for high-fire is configured for
over 90°.
The 90° version ASZ22.32 can be used for both directions of rotation, SQM40...
(counterclockwise) and SQM41... (clockwise).
The 135° versions ASZ22.34 and ASZ22.35 are each intended for a particular direction
of rotation.
The direction of rotation of the potentiometer must correspond with the direction of
rotation of the actuator as follows:
ASZ22.34 can only be used with SQM41... (clockwise)
ASZ22.35 can only be used with SQM40... (counterclockwise)
17/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d13/1013
Mains voltage terminals Dimensioning
1
X1-1 2...10 V Input max. DC 10 V
VI V to X1-5
I
xxxx
X1-2 4...20 mA Input max. 20 mA
M to X1-5
4-20mA
0-135? X1-3 0...135 1 Input
2-10V
0...135 2
GND
X1-4 Input
X1-5 0...135 3 (GND) Input
7 1 6 4 2 3 5 X2 1 2 3 4 5 X1
X2-1 Open (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-2 Move to low-fire (V) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Low-fire position reached Output AC 120 V / AC 230 V
(V) max. 10 mA, cos >0.9
X2-4 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-6 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-7 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.
18/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d21/0415
Low-voltage terminals Dimensioning
2 5
X1-1 4...20 mA Input max. 20 mA
I VI V to X1-2
xxxx
X1-2 GND Input ---
M
4-20mA
IV
Mains voltage terminals Dimensioning
GND
X2-1 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
5 43 1 2 8 7 6 9 X2 1 2 X1
X2-2 Open, high-fire (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-4 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9
X2-6 Low-fire position / ignition Output AC 120 V / AC 230 V
load position reached (V / max. 10 mA, cos >0.9
VI)
X2-7 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9*
X2-8 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-9 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.
19/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d14/1013
Mains voltage terminals Dimensioning
3
X1-1 Free --- ---
R X1-2 Controller, open Input AC 120 V / AC 230 V
K-B
K-A
K-C
I II III max. 1 A, cos >0.9
M
X1-3 Controller release Input AC 120 V / AC 230 V
xxxx
max. 1 A, cos >0.9
b1 VI
a2
a1 X1-4 Auxiliary switch AUX (VI) Input AC 120 V / AC 230 V
b2
max. 1 A, cos >0.9 **
c1
4 1 2 5 3 3 2 1 5 6 4 X1 1 2 3 X3
X1-5 Neutral Input AC 120 V / AC 230 V
X2
max. 1 A, cos >0.9
X1-6 Auxiliary switch AUX (VI) Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9 **
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.
20/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d18/1013
Low-voltage terminals Dimensioning
4
X1-1 2...10 V Input max. DC 10 V
I VI V to X1-2
xxxx
X1-2 GND Input
M X1-3 4...20 mA Input Max. 20 mA to X1-2
X1-4 0...135 1 Input
4-20mA
0-135?
2-10V
GND
GND
X1-5 0...135 2 Input
X1-6 0...135 3 (GND) Input
1 6 4 2 3 5 X2 1 23 4 5 6 X1
* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.
Range adjustment Adjust the range of the analog signal to match the switch positions (min. and max.
position):
1. Set cam I to the required high-fire position (e.g. 85°; position is indicated on the scale
next to the cam).
2. Set cam V to the required low-fire position (e.g. 20°).
3. Preset the signal at the analog input according to the required high-fire position
(e.g. 20 mA).
4. Turn the potentiometer for maximum angular rotation
a) clockwise, if the actuator has not yet reached its maximum angular rotation, or
b) counterclockwise until the actuator starts
5. Preset the signal at the analog input according to the low-fire position (e.g. 4 mA).
6. Turn the potentiometer for minimum angular rotation
a) counterclockwise, if the actuator has not yet reached its minimum angular
rotation, or
b) clockwise until the actuator starts
21/29
Min.
0°
7817z08e/0315
Note!
When starting up, the direction of rotation of the potentiometer setting must be
observed:
90° / 135°
Max.
Min.
0°
7817z10/0713
Note
The working range of the potentiometer setting, shown as an example for the current
input 4...20 mA.
90° / 135°
Setpoint (I/mA)
max.
(V) (I)
20
18
16
14
12
10
8
6
4
2
30 60 90 120 135
Positioning angle (°)
0
10 20 30 40 50 60 70 80 90
0° 7817d04e/0315
min.
22/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d21/0415
Low-voltage terminals Dimensioning
2 5
X1-1 4...20 mA Input max. 20 mA
I VI V to X1-2
xxxx
X1-2 GND Input ---
M
4-20mA
IV
Mains voltage terminals Dimensioning
GND
X2-1 Open position reached (I) Output AC 120 V / AC 230 V
max. 10 mA, cos >0.9
5 43 1 2 8 7 6 9 X2 1 2 X1
X2-2 Open / high-fire (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-3 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
NO contact max. 1 A, cos >0.9
X2-4 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X2-5 Auxiliary switch AUX (IV) / Output AC 120 V / AC 230 V
NC opener max. 1 A, cos >0.9
X2-6 Low-fire position / ignition Output AC 120 V / AC 230 V
load position reached (V, max. 10 mA, cos >0.9
VI)
X2-7 Close / ignition (VI) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9 *
X2-8 Neutral Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
X2-9 Controller release Input AC 120 V / AC 230 V
max. 60 mA / 30 mA
* Only the control lines to the burner controls or to the control unit may be
connected at the marked terminals.
It is not permitted to connect additional external loads, such as signal
lamps.
23/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d15/1013
Mains voltage terminals Dimensioning
6
X1-1 Move to ignition position Input AC 120 V / AC 230 V
I II III (III) max. 1 A, cos >0.9
xxxx
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
M NO contact max. 1 A, cos >0.9
X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
IV V VI
max. 1 A, cos >0.9
X1-4 Neutral AC 120 V / AC 230 V
max. 1 A, cos >0.9
3 2 6 4 5 1 X1 5 4 3 1 2 X2 2 3 1 X3
X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.
24/29
SQM4x.x7xxxx 2-position version with 2 end switches and 3 auxiliary switches, 1 relay
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d16/1013
Mains voltage terminals Dimensioning
7
X1-1 Move to ignition position Input AC 120 V / AC 230 V
I II III (III) max. 1 A, cos >0.9
xxxx
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
M NO contact max. 1 A, cos >0.9
X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
IV K-A VI
a1 max. 1 A, cos >0.9
X1-4 Neutral AC 120 V / AC 230 V
max. 1 A, cos >0.9
3 2 6 4 5 1 X1 5 4 3 1 2 X2 2 3 1 X3
X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.
25/29
Note!
For the sake of clarity, the plug-in contacts do not appear in sequential order in the circuit diagram.
Consecutive numbers are printed on the unit, however, e.g. 1…7.
7817d17/1013
X1-1 Move to position (III) Input AC 120 V / AC 230 V
8 max. 1 A, cos >0.9
X1-2 Auxiliary switch AUX (IV) Output AC 120 V / AC 230 V
I II III
NO contact max. 1 A, cos >0.9
xxxx
M X1-3 Auxiliary switch AUX (IV) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
IV V VI X1-4 Neutral Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
inductive
32 6 4 5 1 X1 4 3 5 1 2 X2 2 3 1 X3 X1-5 Closing (II) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
X1-6 Opening (I) Input AC 120 V / AC 230 V
max. 1 A, cos >0.9
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cosφ >0.8 inductive.
26/29
7817z12e/0315
Pay attention
to markings!
1 35
1 35
0
0
30
30
90
90
0 60 0 0 60
0
13 30 13 30
6
6
5 90 5 90
Note!
The setting of the switch positions must be checked before startup.
27/29
28/29
SQM40.../SQM41…
93.5
9.5
3 blind holes (10 mm deep)
for self-tapping screws M5
5 deep
Shaft no.
2.5 +0.1
SQM4x.xx4xxx Square 4
8.5 -0.005
SQM4x.xx5xxx D-shaft 5
1.9 +0.1
2016 Siemens AG Building Technologies Division, Berliner Ring 23, D-76437 Rastatt
Subject to change! 29/29