0% found this document useful (0 votes)
65 views

Test format-UPS (Inverter)

The document is a test report for a UPS panel produced by Hangzhou Zhonhen Electric Co., Ltd. It tests the panel against specifications for electrical characteristics, appearance and assembly, display functions, and more. All test results met standards. The panel was approved to leave the factory after passing inspection.

Uploaded by

Zahidul zahid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views

Test format-UPS (Inverter)

The document is a test report for a UPS panel produced by Hangzhou Zhonhen Electric Co., Ltd. It tests the panel against specifications for electrical characteristics, appearance and assembly, display functions, and more. All test results met standards. The panel was approved to leave the factory after passing inspection.

Uploaded by

Zahidul zahid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

Factory Test Report

Project Name: Power Grid Network Strengthening Project under PGCB (PGCB/GtoG/01)

Buyer: Jiangsu Etern Co.,Ltd

Production Name: UPS(inverter) Panel

Type and specification:IGBT(inverter)

Standard:IEC60146

Inspection Date:

Place of inspection: Zhejiang,China

Hangzhou Zhonhen Electric Co., Ltd.

Page 1 of 3
UPS (inverter) Panel Test Report
Product NO.:

No. Check Item Standard Result

1.1 Insulation Voltage 2820VDC/ 1min


1.2 Insulation resistance ≥2MΩ/500VDC
Live part Safety check
1.3 Leakage Current ≤3.5mA
1.4 Resistance to earth ≤0.1Ω
R
No-load Y /
B /
230±2.3V(Normal Mode)
R
Full-load Y /
B /
R
2.1 Output Voltage No-load Y /
B /
230±2.3V(DC POWER Mode)
R
Full-load Y /
B /
Electrical characteristics
R
Voltage harmonic<2% Full-load Y /
B /
R
Full-Load Input Voltage Y /
B /
R
2.2 Input Characteristics Full-Load Input Current Y /
B /
R
Current Harmonic<15% Full-load Y /
B /
2.3 Dynamic voltage transient range A. Dynamic voltage transient range between 207V and
253V.
2.4 Transient recovery time B. Transient recovery time ≤111ms.

2.5 low DC warning function Low DC warning on LCD(<110V)

2.6 Low DC protection function Low DC shutdown(<88V)

2.7 Time to Utility/Battery transfer 0 ms


Electrical characteristics
2.8 Time to Bypass /Inverter transfer <3 ms

2.9 Charge Current 0.1C

2.10 Output Overload Overload 125%, 10min.

2.11 LCD Function running in good condition

2.12 Communicate function meet the requirement

Page 2 of 3
UPS (inverter) Panel Test Report
Product NO.:

No. Check Item Standard Result

2.13 Audible noise Audible noise <65dB

3.1 The frame and the structural parts are clean, beautiful, no exposed bottom, scratch.

The name label of panel shall be consistent with the drawing, and be clear and
3.2
distinguishable

All kinds of labels are complete and correct; the brands and specifications of components
3.3 Appearance and are correct (including all components and terminal blocks should be pasted (installed) with
assembly inspection complete label numbers), and they are consistent with the technical drawings.

3.4 Check whether the cabinet door can be opened and closed freely.

The cabinet surface shall be free from deformation, scratch, paint dropping, bubble, dirt,
3.5
dust, etc.

Display and Monitoring


3.6 System failure may be displayed.
Function
3.7 Function test Input switching Priority of the inverter input: AC input, DC input.
4.1 Withstand voltage tester CS2670AX
Test Instrument
4.2 Digital multimeter FLUKE87V

Operator: QC Inspector:
Witness:

Production past test and allow to leave factory :

Date: Result:

Page 3 of 3