0% found this document useful (0 votes)
394 views

ELECTRICAL1

This document contains general electrical notes and a schedule of loads and computation for an electrical installation project. It specifies that all electrical work must comply with the Philippine Electrical Code (PEC) and local authority rules. The service voltage will be 1-phase 230V 60Hz. Wiring will use PVC conduit with a minimum size of 15mm diameter. Copper wiring will be THHN or THW type with a minimum size of 2.0 sq.mm for power and lighting circuits. A schedule then lists the outlet number, load served, voltage, amps, circuit breaker size and wire size for various circuits.

Uploaded by

shuckss talo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
394 views

ELECTRICAL1

This document contains general electrical notes and a schedule of loads and computation for an electrical installation project. It specifies that all electrical work must comply with the Philippine Electrical Code (PEC) and local authority rules. The service voltage will be 1-phase 230V 60Hz. Wiring will use PVC conduit with a minimum size of 15mm diameter. Copper wiring will be THHN or THW type with a minimum size of 2.0 sq.mm for power and lighting circuits. A schedule then lists the outlet number, load served, voltage, amps, circuit breaker size and wire size for various circuits.

Uploaded by

shuckss talo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL ELECTRICAL NOTES: SCHEDULE OF LOADS & COMPUTATION:

1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THESE PLANS
AND SPECIFICATIONS, THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE P.E.C. THE RULES AND OUTLET BRANCH CIRCUIT
THE REGULATIONS OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL POWER CKT NO. LOAD SERVED VA VOLTS AMP SIZE OF WIRES SIZE OF CONDUIT
COMPANIES, THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED
PROTECTION
L.O. C.O.
REGISTERED CIVIL ENGINEER. 11M

3.26M LIGHTING OUTLET, 5


1 150 230 0.6500 5 20 AT, 1P CB USE: 2-2.0 sq.mm. THHN STR. WIRE 20 mm Ø PVC Conduit
2. THE ELECTRICAL SERVICE VOLTAGE SHALL BE 1-PHASE, 2-WIRE, 230 VOLTS, 60 HZ. @ 30 W MAX
LIGHTING OUTLET,1
3. THE ELECTRICAL WIRING INSTALLATION SHALL BE DONE IN PVC CONDUIT. FLEXIBLE CONDUIT SHALL BE 2 500 230 1 10 20 AT, 1P CB USE: 2-3.5 sq.mm. THHN STR. WIRE 20 mm Ø PVC Conduit
W
3
W
2 @500 W
USED WITH REQUIRED MINIMUM SIZE FOR ALL CONDUITS SHALL BE 15 mm DIA. ELECTRICAL TRADE SIZE,

BALCONY
CONDUITS SHALL BE RIGID STEEL CONDUITS (RSC) AND SHALL BE USED IN MAIN SERVICE ENTRANCE.
W
1 COVENIENCE
3 740 230 4.7000 4 20 AT, 1P CB USE: 2-3.5 sq.mm. THHN STR. WIRE 20 mm Ø PVC Conduit

3.025M
3.02M
OUTLET
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN" OR "THW" UNLESS LIVING AREA S2 S1 COVENIENCE USE: 2-3.5 sq.mm. THHN STR. WIRE
BEDROOM2 5 900 230 4.7000 5 20 AT, 1P CB 20 mm Ø PVC Conduit
OTHERWISE INDICATED, THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 2.0 SQ.MM THE CONTROL D
1
OUTLET
WIRES SHALL BE AS INDICATED OR SPECIFIED ELSEWHERE ON PLANS. S6
4 REFRIGERATOR 1500 230 1 20 AT, 1P CB USE: 2-3.5 sq.mm. THHN STR. WIRE 20 mm Ø PVC Conduit

6.05M
D 1
1
2
S5 5 SPARE STUB-IN

DINING AREA
5. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OR SERVICE OF ENTRANCE FOR
CONNECTION TO THE POWER SUPPLY. D D
2
2

3.025M
3.02M
6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTING FIXTURES AND ALL S4 S3 W
3

NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE
D
S7 3
BEDROOM1
KITCHEN
PHILIPPINE ELECTRICAL CODE.
CR
7. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED
W W
WITH THE OWNER OR ANY OF HIS REPRESENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY. 5 4
TOTAL
8. ALL MATERIALS TO BE USED AND THE EQUIPMENT TO BE INSTALLED SHALL BE BRAND NEW AND MUST CONNECTED 3790 5.35 OUTLET
BE OF THE APPROVED TYPE FOR THE PARTICULAR LOCATION AND PROPOSED INTENDED. LOAD
9.
A.
B.
THE MOUNTING HEIGHTS OF WIRING DEVICES SHALL BE AS FOLLOWS:
LIGHT SWITCHES - 1.40m ABOVE FLOOR FINISH.
CONVENIENCE OUTLETS - 1..80m ABOVE FLOOR FINISH.
A ELECTRICAL LIGHTING LAYOUT FOR FEEDER LINE:
ITOTAL = (3790 VA / 230 V) (80% D.F.) + (25% ´
SERVICE FEEDER:
USE 2 - 30.0 sq.mm. THHN
ENCLOSURE: NEMA I
MOUNTING: SURFACE
C. PANELBOARDS AND CABINETS - 1.80m ABOVE FLOOR FINISH OR REQUIRED. C-2 SCALE 1:100
6.9)
ITOTAL = 22.32 AMPERES / 50 AT MAIN
1 - 8.0 sq.mm. THW
in 32 mm Ø PVC MAIN: 50 AT, 1P, 230 V CIRCUIT BREAKER, 60 HZ (BOLT-ON)
10. ALL MOUNTING HEIGHTS SHALL BE SUBJECTS TO ARCHITECTS APPROVAL PRIOR TO INSTALLATION.
11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT & IMMEDIATE SUPERVISION OF A DULY
QUALIFIED LICENSED ELECTRICAL ENGINEER.

3.57M 3.37M 3.26M

LEGENDS: W
3
W
2

BALCONY
W

RISER DIAGRAM (POWER):


1

SCHEMATIC DIAGRAM:

3.025M
LIVING AREA
BRANCH CIRCUIT HOMERUN BEDROOM2 D
1

6.05M
D
2 PP
CONNECT TO LOCAL SERVICE PROVIDED
WEATHER HEAD CAP
CIRCUIT BREAKER 230 V, 2W, 60 Hz,
(VIA NEAREST POWERPOST)
D D
2
2

3.025M
2 - 8.0 sq. mm. THHN
CONVENIENCE OUTLET CANORECO POWER SOURCE 1 - 8.0 sq. mm. THW GROUND
W
3

230 Vac, 60 Hz, 1P, 2Wire IN 32 mm. Ø RSC D


3
BEDROOM1
CR
M
DINING AREA
GROUND
W W
5 4
PP - N
1.80M
LIGHT BULB 50 AT, 1P

LIGHTING CIRCUIT LINE LIGHTING


OUTLET 1 2
LIGHTING
OUTLET
20 AT, 1P 20 AT, 1P

M MAIN KILOWATT-HOUR METER


CONVENIENCE
OUTLET

REFRIGERATOR
3

5
20 AT, 1P

20 AT, 1P
20 AT, 1P

20 AT, 1P
4

6
CONVENIEMCE
OUTLET

SPARE
A ELECTRICAL POWER LAYOUT
C-2 SCALE 1:100
UNDERGROUND POWER LINE CONNECT TO
1 - 8.0 sq. mm.
GROUNDING BUS
PROVIDED BY
BUILDING BASE
THW (G) 6.52

S SWITCH KW-HR METER BRANCH CIRCUIT


CONDUIT (PVC) PANEL BOX

EQUIPMENT
POWER CIRCUIT LINE GROUND WIRE

MAIN CKT. BRKR. PP-N PVC CONDUIT

PP
POWER PANEL BOARD 50 AMPS. 100 A
ADAPTER
BOUNDED TO PANEL
ENCLOSURE

1.80
LOCKNUT EQUIPMENT
SERVICE ENTRANCE GROUNDING TERMINAL

GROUNDING FLOOR LINE ADAPTER


GROUND
WIRE
CONNECTOR LOCKNUT
REFRIGERATOR
GROUND
LOCKNUT
PIGTAIL
GROUND WIRE
TERMINAL TAPPED ADAPTER
TO BONDING SCREW

BONDING
SCREW

FEEDER CONDUIT (PVC)

IN FRONT AND
BACK OF THE KITCHEN,
HOUSE, LIVING BALCONY , AND
OWNERS LIVING
AREA DINING AREA DETAILS OF SWITCH BOX
AND DINING BEDROOMS
AREA DETAILS OF PANEL BOARD

12 - SETS 5 - SETS 1 - SET 1-SETS

PROJECT TITLE / LOCATION: REVISIONS: DATE: REPUBLIC ACT 545 APPROVED BY: SHEET CONTENTS: SHEET NUMBER:
SIGNED AND SEALED: DESIGNED:

FLOREBEL M. CAMUS THIS DRAWING, AS AN INSTRUMENT CAD: GJP

BACHELOR OF SCIENCE IN CIVIL ENGINEERING 3A CONSTRUCTION OF SINGLE STOREY


RESIDENTIAL BUILDING
OF SERVICE IS A PROPERTY OF GJP
MUST NOT BE REPRODUCED OR
COPIED IN PART OR IN WHOLE
WITHOUT HIS CONSENT. ALL
CHECKED:
QUETERIO AND ALICIA CAMUS AS SHOWN
E
PRC NO.: PTR NO.:

1
P-2 BRGY. AWITAN, PARACALE CAMARINES NORTE DRAWINGS ARE TO BE RETURNED OWNER
APPROVED:
WHEN NO LONGER IN USE.
VALIDITY: ISSUED AT:

ISSUED AT: TIN: DATE: