Elco Burner Manual May 2018
Elco Burner Manual May 2018
LOW NOx
KEROSENE BURNERS
EN
EN
Dear Client,
We would like to thank you for having chosen a FIREBIRD product.
The model chosen by you is a high-performance product with an advanced technological
conception, high reliability and excellent construction quality.
We advise you to entrust the running and maintenance of this appliance to know qualified
professionals, and also to use only original spare parts when needed.
This manual contains important guidelines and suggestions which should be complied with in
order to obtain a simple installation and the best possible use of the appliance.
RANGE
BURNER DESIGNATION
FB 2 K 26 LN
FB 2 Burner Series
K Kerosene
BOILER TYPE
26 Boiler nominal power (max)
EMISSION
2/64
EN
CONTENTS
1 SAFETY 5
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Key to symbols used in the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 Other symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Requirements for personnel or operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Primary hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 GENERAL 8
2.1 Burner description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Structure of the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Structure of the combustion head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5 Control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6 Operating logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6.1 Operating function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6.2 Controlled shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.6.3 Safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3 TECHNICAL DATA 15
3.1 Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 INSTALLATION 18
4.1 Safety during assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Installation area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2.1 Flue gas system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Assembly tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Preliminary checks before mounting the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.5 Burner assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.6 Removing and fitting the burner cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.7 Oil systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.7.1 Hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.7.2 Oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.7.3 Oil feed and suction line with one-pipe system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.7.4 Oil feed and suction line with two-pipe system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.8 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.8.1 Electrical connection to the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.9 Removing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3/64
EN
5 COMMISSIONING 35
5.1 Safety during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2 Checks before commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3 Factory pre-setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4 Combustion adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4.1 Air flap position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5 Adjusting burner output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5.1 Burner start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5.2 Burner adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6 Oil pressure setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.1 Oil pressure setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.2 Checking negative pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.3 Cleaning the pump filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.4 Check pump rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.7 Commissioning record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.7.1 Setting and values recorded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6 MAINTENANCE 42
6.1 Safety during maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.2 Important components for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.1 List of parts typically subject to wear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.3 Removing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4 Burner maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.1 Cleaning and replacing combustion head components . . . . . . . . . . . . . . . . . . . . . . 48
6.4.2 Diffuser position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4.3 Combustion head position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4.4 Electrode position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.4.5 Replacing the coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.6 Replacing the capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.7 Cleaning the internal rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7 TROUBLESHOOTING 55
7.1 Combustion performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.2 Fault diagnosis and repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.3 Troubleshooting diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9 MANUFACTURER CERTIFICATE 60
9.1 Manufacturer Certificate / EU Design Conformity Declaration . . . . . . . . . . . . . . . . . . . . . . 60
10 APPENDIX 61
10.1 Use of bio fuel blends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2 Important advice for the use of bio fuel blends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2.2 General instructions and information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
11 NOTES 63
4/64
Safety EN
1 SAFETY
1.1 Overview
These instructions for the installation, commissioning and maintenance of the burner are for use
by technicians from professional heating companies that are qualified to carry out these activities.
The instructions contain indications and information on how to move, handle, activate, adjust,
maintain and remove the appliance and how to dispose of the components at the end of the their
useful life.
The instructions must be followed and all applicable legislation complied with in order to ensure
safe working conditions.
This manual should be stored near the product and made available to all operators involved in
its use.
The burner is designed to act as a heat source for heating and DHW generation systems in which
water is the heating fluid.
the burner cannot be installed outdoors, unless installed in a boiler specifically designed for that
use. If installed outdoors, climatic conditions could cause direct damage to the burner due to the
presence of water or frost or cause the components to overheat.
5/64
EN Safety
DANGER
Maximum danger. Indicates operations that cause serious injury, death or long-term health
DANGER risks if performed incorrectly.
DANGER
Indicates a dangerous situation that could cause serious injury, death or long-term health risks,
caused by electricity, if handled without due care or incorrectly.
WARNING
Indicates operations that could cause serious injury, death or long-term health risks if performed
WARNING incorrectly.
PRECAUTION
Indicates potentially dangerous situations and operations that could cause damage to the device
PRECAUTION or things and minor injury to persons, if handled without due care or performed incorrectly.
CAUTION
Indicates operations that could cause damage to the device or nearby things.
CAUTION
IMPORTANT INFORMATION
This symbol indicates important information that you must bear in mind.
CAUTION
Indicates potentially dangerous situations, caused by the presence of surfaces at high
temperatures that could cause minor injuries, or burns, if handled incorrectly.
PERSONAL PROTECTION
Several symbols are used to remind operators of the need to use all the personal protective
equipment required by applicable legislation during all installation, commissioning and
maintenance operations.
ENVIRONMENTAL PROTECTION
Reminds operators of the need to apply a suitable recycling procedure to replaced components.
ENVIRONMENTAL PROTECTION
Reminds operators of the need to deliver the product or its components to a suitable separated
waste collection centre at the end of its working life.
6/64
Safety EN
CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.
CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.
CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.
The following indications refer to “residual risks”, which must be highlighted for the full understanding
and responsibility of the proprietor, users and operators.
These risks derive from risk analyses carried out by Research and Development staff as required
by European Standard EN 267 and applicable directives (Machine directive, LVD, EMC).
DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.
Check there is no power and ensure restart is impossible.
-- In the event of damage to the electrical insulation on the product, act immediately to restore
the correct level of insulation.
CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.
FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.
7/64
EN General
2 GENERAL
2.2 Supply
8/64
General EN
2.3 Identification
414716|BRN035ELN|3146025|SN0000
000004|SL005600012348|DH26/03/201
8 15.37.39
(J)
0000000004 Made in Italy
Fig. 1
CAUTION
It is strictly forbidden to remove the identification label.
CAUTION Tampering, removal or absence of the data plate burner or anything that prevents the secure
identification of the burner will create difficulties for any installation and maintenance work.
9/64
EN General
2.4 Structure
1 2
11
10
8 7 6
Fig. 2
10/64
General EN
17
12 13 14 15 16
18
26
16
25
19
24 23 22 21 20
Fig. 3
11/64
EN General
4 5 6
2 7 6
Fig. 4
12/64
General EN
The EBR-M1 control box, controls and monitors the forced draught burner. The microprocessor-
controlled program sequence ensures maximum stability of time periods, regardless of fluctuations
in the power supply or ambient temperature.
The design of the control box protects it from the effects of flame outs. Whenever the supply
voltage drops below its rated minimum level (170 ± 8 V), the control box shuts down - even in the
absence of a fault signal.
The control box switches itself back on again once the voltage has exceeded the 190 ± 8 V.
101
103
T1
M1 M
118
102
105 106
104 Y1
Fig. 5
13/64
EN General
A safety shutdown is indicated by the malfunction lamp lighting up and it is then only possible to
reset the burner by pressing the reset button after the cause of the malfunction has been rectified.
For further information, see the automatic combustion control unit description.
General
power LINE
supply C
Boiler
temperature
control
Motor
Ignition
Transformer
Valve
Flame check
Flame
1 2 3 4 5 6 7 8
- - 20s 5s 7s - - 30s
Fig. 6
14/64
Technical data EN
3 TECHNICAL DATA
Ø 83
163
Ø 180
Ø 151,5
Ø 131,5 15 Max
45°
11
145
=
45°
10
Øi 100
Fig. 7
Weight (kg)
Model
net with packaging
FB 2 K 18 LN 8 9,8
FB 2 K 20 LN 8 9,8
270
FB 2 K 26 LN 8 9,8
FB 2 K 35 LN 8 9,8
0
300 39
15/64
EN Technical data
FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN
Oil throughput factory setting (1) 1,3 kg/h 1,5 kg/h 2,0 kg/h 2,6 kg/h
Fuel oil (2) Kerosene , visc 1÷2,5 mm2/s at 20°C (Hi=11,97 kWh/kg)
(1)
Reference conditions: Ambient temperature 20 °C – Barometric pressure 1013 mbar – Altitude 0 m. a.s.l.
WARNING
(2)
The burner is suitable for kerosene with bio content up to 10%. It is a minimum requirement
WARNING that the fuel blend (up to 10% Bio) is obtained with kerosene in accordance with the relevant
standards and regional regulations.
In case of Bio oil content higher that 10% please contact the manufacturer.
16/64
Technical data EN
TV
CONTROL BOX EBR-M1 20-30
B4 S3 T2 T1 N L1
CONNECTION KIT
B4 S3 T2 T1 N L1
MV
M
YVg B
L3 N L2 L1
L3 N L2 L1
SWITCH LIVE
BURNER LOCK OUT
EARTH
NEUTRAL
PERMANENT LIVE (230V-50Hz)
Fig. 9
17/64
EN Installation
4 INSTALLATION
DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.
Check there is no power and ensure restart is impossible.
-- In the event of damage to the electrical insulation on the product, act immediately to restore
the correct level of insulation.
WARNING
Danger of death due to contact with fuel oil!
WARNING Risk of lung damage caused by inhalation or ingestion of fuel oil; take the following precautions:
-- observe the instructions on the safety data sheets for the fuel oil and any additives (available
from the associated suppliers)
-- in the event of the formation of an oil mist, use a protective mask with filter for organic
vapours and particulate filter
-- do not eat, drink or smoke when working on the heating system.
WARNING
Danger of injury due to contact with fuel oil!
WARNING Repeated and prolonged skin exposure to fuel oil can damage and irritate the skin; take the
following precautions:
-- as far as possible, avoid contact with the skin
-- use personal protective equipment, such as a protective gloves and suitable clothing
-- do not put rags soaked with oil in your pockets
-- change clothes stained with oil as soon as possible.
CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.
CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.
CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.
18/64
Installation EN
Before installation, make sure that the installation area satisfies the following requirements:
–– operating temperature between +5°C and +45°C
–– dry, frost resistant, well-ventilated
–– no accumulation of heavy powders
–– no high levels of humidity
–– no atmospheric pollutants created by halogenated hydrocarbons (contained in solvents,
adhesives, aerosols, etc.)
–– no atmospheric pollutants created by sulphurous gases
–– no vibration.
WARNING
Danger of death caused by fire!
WARNING Highly flammable materials or liquids can catch fire
-- do not use or store explosive or highly flammable substances (such as petrol, paint, paper,
wood, etc.) in the installation area of the appliance
-- do not dry clothing within the boiler installation area
-- do not use the equipment in an explosive atmosphere.
CAUTION
Flammable materials or liquids should not be stored or used near the burner.
CAUTION
IMPORTANT INFORMATION
Failure to observe these instructions will invalidate the warranty with respect to any damages
caused by any of these causes.
CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.
19/64
EN Installation
The most common and frequent operations on the burner are carried out simply using only the
hex key supplied. This key can be used to:
–– remove the burner cover
–– remove the diffuser
–– adjust the electrodes group
–– adjust the fuel pressure
–– adjust the air setting
–– operate on the pump.
Fig. 10
20/64
Installation EN
–– Check the position of the electrodes assuring that they are centered as shown in “Fig. 11”.
=
=
A
A-A 1 : 1
Fig. 11
21/64
EN Installation
CAUTION
Install the burner on the boiler according to the installation position shown in “Fig. 12”.
CAUTION Installation 2,3 and 4 are forbidden for safety reason.
OK
1 2 3 4
Fig. 12
The burner is secured to the boiler using the connection flange supplied with the burner.
Follow the instructions below:
–– couple the gasket (2) supplied with the connection flange (1).
2 1
Fig. 13
22/64
Installation EN
–– position the flange (2), with the screw (1) facing upwards, onto the boiler and secure it with the
nuts (5) supplied
–– tighten the nuts (5) of the flange evenly and diagonally with a tightening torque of 3,5 Nm
max.
–– insert the burner combustion head (6) with care inside the flange
5 1
Fig. 14
–– rotate the burner first to the right and then to the left to insert the fastening screw (1) into the
housing (7) on the burner
–– fully tighten the nut (3) and at the same time press the burner in the lower part towards the
boiler to ensure maximum seal between the burner itself and the boiler
1 3 7
Fig. 15
23/64
EN Installation
–– insert the air intake pipe (8) and secure it using a pipe clamp (9), not supplied
–– in case of conventional flue applications remove snorkel and air conveyor (10) and replace
with the conventional flue carter (11) supplied.
11
9
10
Fig. 16
–– To remove the burner cover, loosen the two screws (1) and then slide out the burner cover (2)
taking care not to damage it.
–– To refit it, invert the procedure above.
2 1
A
B
Fig. 17
24/64
Installation EN
FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.
WARNING
Danger of injury from gas in the atmosphere!
WARNING To prevent the formation of gas caused by worst combustion/deflagration:
-- when filling the tank, switch off the burner and leave it switched off for approximately 3 hours
to ensure degassing of the fuel and the deposit of suspended particles
-- have any damage to the oil pipes repaired immediately by a specialised technician
-- never operate the burner with the oil tank empty.
IMPORTANT INFORMATION
Corresponding legislation pertaining to water resources and the installation of fuel pipes must
be observed.
IMPORTANT INFORMATION
Leaks in the fuel supply system can cause combustion problems and malfunctions in the burner.
The fuel tank, including the installation of the pipes, must be carried out in such as way as to
ensure that the temperature of the oil going into the burner is at least + 5°C.
25/64
EN Installation
NC
V P
E
H
C
S
D
Pressure
T Suction
P1 Return
A O
Fig. 18
1
8
3 7
5 6
Fig. 19
26/64
Installation EN
10
11
2
1-
13
12
Fig. 20
CAUTION
Only approved fuel lines are to be used.
CAUTION
16
10
17
11
14
2
1-
15
Fig. 21
IMPORTANT INFORMATION
There is an intake filter and an oil pressure regulator integrated in the pump. Pressure gauges
for negative pressure (vacuum) measurement must be connected before the equipment is
commissioned.
CAUTION
Before starting the burner, check that the return pipe is open. An eventual obstruction could
CAUTION damage the pump sealing device.
27/64
EN Installation
Y
X
H = x-y
Fig. 22
CAUTION
-- X < 20 m
CAUTION -- Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.
Fig. 23
28/64
Installation EN
Y
X
H = x-y
Fig. 24
CAUTION
-- X < 20 m
CAUTION -- Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.
Fig. 25
29/64
EN Installation
DANGER
Danger of death caused by live components!
Contact with live parts can lead to serious injury, take the following precautions:
-- ensure that the power is switched off for all electrical parts
-- electrical wiring installation must be carried out by qualified personnel and in compliance with
the regulations currently in force in the country of destination. Refer to the wiring diagrams.
CAUTION
-- The electrical installation should include a minimum of a type A MCB.
CAUTION -- Check to ensure that the power supply voltage is as specified in the electric diagram and in
data plate.
-- Burner fuse: 3 Amps.
WARNING
-- Use flexible cables in compliance with the EN 60 335-1 standard. Assure a correct earth
WARNING connection.
-- The wiring section must be minimum 1 mm2 (in any case verify with the standard and local
rules).
-- This control flame is equipped with the post ventilation function. Other versions of the burner
are not to be fitted.
-- Check operation of boiler thermostatic control.
-- Check operation of Photocell by withdrawing from burner and then covering to simulate flame
out condition.
30/64
Installation EN
4 3
Fig. 26
31/64
EN Installation
DANGER
Danger of death caused by live components!
Before carrying out any operations on the burner, operate the main power switch for the system
to cut off the power supply.
2 1
A
B
Fig. 27
Fig. 28
32/64
Installation EN
–– remove the fuel delivery pipe (5) and the return pipe (6), if present
5 6
Fig. 29
–– drain any fuel still inside the burner and in the fuel delivery pipe and collect it in a basin
–– loosen the pipe clamp (7) and remove the air intake pipe (8), if present
Fig. 30
33/64
EN Installation
–– loosen the nut (9) securing the burner to the boiler and, rotating the burner (10) slightly to the
right, slide it off the boiler.
10
Fig. 31
CAUTION
Dispose of any fuel that comes out of the burner in accordance with applicable legislation in the
CAUTION destination country. Separated waste management avoids potential damage to the environment
and peoples’ health. It also allows many recyclable materials to be recovered, with significant
economic and energy savings.
34/64
Commissioning EN
5 COMMISSIONING
CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.
CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.
CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.
FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation in some individuals.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
suitable personal protective equipment.
–– That the burner is assembled in accordance with the instructions given here
–– That the burner is pre-set in accordance with the values in the adjustment table
–– Setting the combustion components
–– The boiler must be ready for operation, and the operating regulations for the heater must be
observed
–– All electrical connections must be correct
–– The boiler and heating system must be filled with water and the circulating pumps must be in
operation
–– The thermostats and any other safety or limiting devices that might be fitted must be connected
and operational
–– The flue system must be unobstructed and the secondary air system, if available, must be
operational
–– An adequate supply of fresh air must be guaranteed
–– The heat request must be available
–– Fuel tanks must be full
–– The fuel supply lines must be assembled correctly, checked for leaks and bled
–– In the event the burner does not start on initial start-up following a long period of storage,
the pump should be checked to ensure it is not blocked. See chapter on “5.6.4 Check pump
rotation” on page 39
–– A standard-compliant measuring point and analyser test point must be available, the flue
system to the measuring point must be free of leaks to prevent anomalies in the measurement
results.
35/64
EN Commissioning
Reference conditions
–– Conventional Flue system: diameter 80 mm / length 1.5 m
–– Ambient temperature: 20°C +/-5
–– CO2 = 12.5% ± 0,2.
(*) The pump pressure is referred to a stability period of 5 min.
Note.
All the burners are factory tested and adjusted. The air flap and combustion head are set to
have the CO2 % within the above limit.
The burners leave the factory set according to the paragraph “5.3 Factory pre-setting”.
The installation of the burner on the boiler, the commissioning and servicing must be carried out
following the boiler technical manual, including the check of the CO2 and CO level in the flue
gases, their temperatures and the average temperature of the water in the boiler.
CO2 13,50
(%)
13,00
12,50
12,00
11,50
11,00
00 5 10 15 20 25 30 35
Outside air temperature (°C)
Fig. 32
36/64
Commissioning EN
O2 -
CO2 +
O2 +
CO2 -
Fig. 33
1
8
3 7
5 6
Fig. 34
WARNING
Continuously check CO, CO2 and soot emissions when adjusting the output of the burner. CO
WARNING must not exceed 50 ppm.
37/64
EN Commissioning
Fig. 35
38/64
Commissioning EN
CAUTION
If the pump is blocked, proceed as follows.
CAUTION
–– Disconnect the oil pipe from the pump
–– remove the pump (1) from the motor loosening screws (3) using the key supplied (2)
3
1
Fig. 36
–– manually rotate the shaft (3-4 rotations both clockwise and anticlockwise)
Fig. 37
Replace the pump in the event it remains blocked or if there was any sticking during manual
rotation.
39/64
EN Commissioning
Confirm the work carried out in the commissioning report below by marking and X or an ✓.
Commissioning work Note Done
40/64
Commissioning EN
Customer:__________________________________________________________________
Heating system:______________________________________________________________
BOILER
Type
kW
Output
kcal/h
BURNER
Type FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN
Serial number
Output kW
mg / kWh
CO
ppm
mg / kWh
NOx
ppm
Room temperature °C
Flue gas
°C
temperature (gross)
Pressure at the base
mbar
of chimney
Firing Efficiency
%
factor
Date:______________________________________________________________________
Signature:__________________________________________________________________
41/64
EN Maintenance
6 MAINTENANCE
The periodic maintenance is important for safety, good operation and long life cycle of the burner,
reducing also consumption and polluting emissions.
The burner must be serviced at least once a year. Only qualified and authorised personnel shall
carry out maintenance and the calibration of the burner, in accordance with this manual and in
compliance with the local standards and regulations.
DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.
CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.
FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.
PRECAUTION
Danger of injury caused by improper use!
PRECAUTION Danger of personal injury such as contusions, bruises and cuts due to incorrect handling.
-- Use personal protective equipment as required by applicable legislation, such as safety
shoes and gloves.
CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.
IMPORTANT INFORMATION
-- Inspect threaded joints to identify leaks during annual maintenance checks.
-- Replace defective or worn gaskets.
42/64
Maintenance EN
In order to ensure the long working life of the burner, we recommend periodically carrying out
component checks.
43/64
EN Maintenance
DANGER
Danger of death caused by live components!
Before carrying out any operations on the burner, operate the main power switch for the system
to cut off the power supply.
2 1
A
B
Fig. 38
Fig. 39
44/64
Maintenance EN
–– remove the fuel delivery pipe (5) and the return pipe (6), if present
5 6
Fig. 40
–– drain any fuel still inside the burner and in the fuel delivery pipe and collect it in a basin
–– loosen the pipe clamp (7) and remove the air intake pipe (8), if present
Fig. 41
45/64
EN Maintenance
–– loosen the nut (9) securing the burner to the boiler and, rotating the burner (10) slightly to the
right, slide it off the boiler.
10
Fig. 42
CAUTION
Dispose of any fuel that comes out of the burner in accordance with applicable legislation in the
CAUTION destination country. Separated waste management avoids potential damage to the environment
and peoples’ health. It also allows many recyclable materials to be recovered, with significant
economic and energy savings.
IMPORTANT INFORMATION
Once the burner has been removed from the boiler, it can be rested on a rigid, level surface.
The burner should be placed on the ground only if resting on the burner base and should never
be turned upside down.
46/64
Maintenance EN
To facilitate maintenance operations, secure the burner to the boiler by inserting the fastening
screw (11) into the hole (12) on the burner base. Use one of the three square grooves on the
burner base to secure the burner, which should be rotated to the best position for the maintenance
operation to the carried out.
12
11
A C
A B C
Fig. 43
Position A:
–– inspection and cleaning of the internal rotor.
Position B:
–– inspection of the combustion head
–– inspection and maintenance of the nozzle
–– inspection and maintenance of the electrode group.
Position C:
–– inspection and maintenance of the pump
–– inspection and maintenance of the coil
–– inspection and maintenance of the capacitor.
47/64
EN Maintenance
–– Check the fuel supply components (pipe, pump, fuel delivery pipe) and their connections for
leaks and signs of wear, replace parts as necessary.
–– Check that the electrical connection and connection cables are not damaged, replace them if
necessary.
–– Check the pump filter and clean it if necessary.
–– Clean the fan and its housing and check for damage.
–– Check and clean the combustion head.
–– Check the ignition electrodes, adjust or replace them if necessary.
–– Replace the nozzle.
–– Fit the combustion head. Observe the adjustment dimensions.
–– Mount the burner.
–– Start the burner, check the exhaust gas data, adjust the burner settings if necessary.
–– Fuel pipes should be checked annually and replaced after 2 years.
–– Check and clean the components on the main burner.
2 4 3 5 6
Fig. 44
–– ensure that all components are in good condition, undamaged by high temperatures, clean
and soot-free. Replace if damaged
–– clean all components thoroughly
–– refit the components, reversing the procedure above.
48/64
Maintenance EN
CAUTION
If the air distributor (1) is removed from its housing, it must be repositioned, making sure that
CAUTION the hole (2) is aligned with the pin (3).
2
3
Fig. 45
8 1X
Fig. 46
49/64
EN Maintenance
–– check the distance between the diffuser (1) and the nozzle (2) as shown in the figure.
2 1
Fig. 47
–– after having adjusted the position of the diffuser tighten the screw (8).
–– refit the combustion head.
8 1X
Fig. 48
50/64
Maintenance EN
2 1
Fig. 49
51/64
EN Maintenance
Fig. 50
–– Check the position of the electrodes assuring that they are centered as shown in “Fig. 51”.
=
=
A
A-A 1 : 1
Fig. 51
52/64
Maintenance EN
2 3
Fig. 52
1 2
Fig. 53
53/64
EN Maintenance
Fig. 54
Observe the positioning diagram below when replacing the motor and blower wheel (3). The
inside flange (A) of the blower wheel must be fitted at 0,3 mm lower than the equipment plate (B),
tighten the set screw on the blower wheel.
3 B
Burner Position C
OK A FB 2 K 18 LN 0,5 mm
C
FB 2 K 20 LN 0,5 mm
FB 2 K 26 LN 0,5 mm
FB 2 K 35 LN 0,5 mm
NO
NO
Fig. 55
54/64
Troubleshooting EN
7 TROUBLESHOOTING
In the event of a malfunction, first check that the prerequisites for correct operation are fulfilled:
–– is the system connected to the power supply?
–– is there oil in the tank?
–– are all shut-off valves open?
–– are all control and safety devices, such as the boiler thermostat, low pressure device (if fitted),
limit switch, etc. adjusted correctly?
Warranty will be invalidated if genuine parts are not used on replacement. These components
must be replaced by parts with the same order number.
WARNING
To reset the equipment control, after viewing the visual diagnosis, press the release button.
WARNING
WARNING
In case of burner lock out, to avoid damage to the installation, do not reset the burner more
WARNING than twice in succession.
DANGER
If the burner goes into lock out for the third time, contact manufacturer’s service organisation.
DANGER In the case in which they occur further locks or malfunction burner, interventions must be
carried out by qualified and authorized personnel, following the information in this manual and
in accordance with the rules and legal regulations.
IMPORTANT INFORMATION
Only use original spare parts.
IMPORTANT INFORMATION
After each operation:
-- Under normal operating conditions (doors closed, cover fitted, etc.), check combustion and
check the individual lines for leaks.
-- Record the results in the relevant documents.
55/64
EN Troubleshooting
No
Replace
Check green Motor Pump
Yes No No motor
LED lights seized blocked
capacitor
No Yes Yes
Cleaned
Unblock/Replace
pump
Lock out
Yes after 20 sec Yes
pre-purge
No
* Yes solenoid
functionality
Yes sensor
functionality **
Is there a Replace
Flame sensor
No Yes false flame No control
work well?
signal box
Replace No Yes
pump
solenoid
Replace Remove false
flame sensor flame causes
No No No No Yes
Replace ignitor
Check main
fuel filter
* Yes Recycle?
Fig. 56
56/64
Troubleshooting EN
Replace flame
sensor
Fig. 57
Check
procedure
Fig. 58
57/64
EN
58/64
FB 2 K 18 LN
FB 2 K 20 LN
FB 2 K 26 LN
FB 2 K 35 LN
Spare parts list
0400
0390
0180
0170
0410 0200
0160
0130 0150
0100
0190 0020 0010 0040 0350 0360 0370 0030 0060 0330 0070 0340 0110 0080 0090 0050
Fig. 59
0120
Spare parts list EN
FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN
N° Description
3146022 3146023 3146024 3146025
0010 OIL PUMP 65327227 65327227 65327227 65327227
0020 COIL 65327245 65327245 65327245 65327245
0030 COUPLING 65327229 65327229 65327229 65327229
0040 FLEXIBLE OIL HOSE 65327230 65327230 65327230 65327230
0050 BURNER COVER 65327231 65327231 65327231 65327231
0060 MOTOR 65327232 65327232 65327232 65327232
0070 CAPACITOR 65327233 65327233 65327233 65327233
0080 IGNITION TRANSFORMER 65327234 65327234 65327234 65327234
0090 CONTROL BOX WITH CABLES 65327235 65327235 65327235 65327235
0100 PHOTORESISTOR 65327236 65327236 65327236 65327236
0110 SUPPORT 65327240 65327240 65327240 65327240
0120 CABLE KIT WITH 7 AND 5 PIN CONNECTORS 65327237 65327237 65327237 65327237
0130 CLAMP 65327241 65327241 65327241 65327241
0140 FAN 65327280 65327280 65327239 65327239
0150 ORING 65327224 65327224 65327224 65327224
0160 AIR INLET COVER GASKET 65327223 65327223 65327223 65327223
0170 AIR INLET COVER 65327279 65327279 65327283 65327283
0180 ORING 65327247 65327247 65327247 65327247
0190 SET FILTER+SEAL 65327228 65327228 65327228 65327228
0200 IGNITION CABLES 65327284 65327284 65327284 65327284
0210 ELECTRODE GROUP 65327285 65327285 65327285 65327285
0220 BLAST TUBE 65327286 65327286 65327286 65327200
0230 BLAST TUBE ORING 65327201 65327201 65327201 65327201
0240 DIFFUSER 65327202 65327203 65327203 65327203
0250 NOZZLE HOLDER 65327287 65327287 65327287 65327288
0260 SPRING 65327206 65327206 65327206 65327206
0270 ROD ORING 65327210 65327210 65327210 65327210
0280 AIR DISTRIBUTOR 65327281 65327211 65327282 65327294
0290 AIR DISTRIBUTOR ORING 65327213 65327213 65327213 65327213
0300 FLANGE 65327289 65327289 65327289 65327289
0310 GASKET 65327290 65327290 65327290 65327290
0320 ORING 65327216 65327216 65327216 65327216
0330 MOTOR GASKET 65327222 65327222 65327222 65327222
0340 PIPE 65327217 65327217 65327217 65327217
0350 GASKET 65327205 65327205 65327205 65327205
0360 EXTENDED PRESSURE PORT 65327242 65327242 65327242 65327242
0370 THREADED STOPPER 65327243 65327243 65327243 65327243
0380 NOZZLE 65327218
0380 NOZZLE 65327219
0380 NOZZLE 65327220
0380 NOZZLE 65327221
0390 SNORKEL 65327225 65327225 65327225 65327225
0400 CONVENTIONAL FLUE CARTER 65327226 65327226 65327226 65327226
0410 FRONT PANEL 65327291 65327291 65327291 65327291
0420 COVER SCREW GROUP 65327209 65327209 65327209 65327209
59/64
EN Manufacturer Certificate
9 MANUFACTURER CERTIFICATE
We, Firebird, declare under our sole responsibility that the kerosene burners named FB 2 K ... LN
is conform to the following standards:
–– EN 267
–– EN 55014-1
–– EN 60335-1
–– EN 61000-6-2
–– EN 50156-1
–– EN 55014-2
–– EN 60335-2-102
–– EN 61000-6-3
These products bear the CE mark in accordance with the stipulations of the following directives:
–– 2014/35/UE Low Voltage Directive
–– 2014/30/UE EMC Directive
–– 2006/42/EC Machine Directive
–– 2011/65/EU RoHS2 Directive
R&D Director
60/64
Appendix EN
10 APPENDIX
The burner is suitable for kerosene with a biofuel content of up to 10%. It is a minimum requirement
that the fuel blend (up to 10% Biofuel) is obtained with kerosene in accordance with the relevant
standards, regional regulations and FAME in accordance with EN 14214.
IMPORTANT INFORMATION
In the event that the burner needs to be used with fuels containing biofuel percentages higher
than 10%, contact the manufacturer.
10.2.1 Introduction
The growing attention focussed on renewable and sustainable energy sources would suggest an
ever-increasing use of biofuels.
If you plan to make use of these fuels, you need to consider several technical aspects in order to
reduce the potential for faults in the burner and heating system and the risk of fuel leaks.
The term ‘liquid Biofuel’ is a broad definition that includes oils made from numerous different
raw materials, including recycled cooking oil. These types of oil must be considered and treated
differently from common mineral and fossil fuels. This is because they are more acidic, hygroscopic
and less stable.
Particular care should be taken in the storage of this fuel, in the supply pipe, in the ancillary
equipment, in the filtration and in the choice of burner.
The classification of the biofuel is important for the smooth operation of the equipment.
IMPORTANT INFORMATION
The proprietor or the system manager is responsible for the detailed analysis of potential risks
associated with the introduction of a mixture of biofuels and the suitability of the devices and
installation.
During installation, make sure that all the materials and sealing devices used on the storage tank
and oil delivery pipe to the burner are compatible with biofuels.
The tank must have a good quality biofuel-compatible oil filter and a 60 micron secondary filter to
protect the burner from contaminants.
61/64
EN Appendix
Wherever an existing tank is to be used to store the oil, in addition to the above mentioned checks
on the materials, it is essential that the tank is first inspected to verify its condition and check for
the presence of water or other contaminants. If contaminants are found, a deep clean should be
carried out. If this is not carried out the hygroscopic nature of the fuel could dissolve and detach
complex components and cause faults in the equipment.
Based on the capacity of the storage tank and how the system is used, fuels can be stored
inside it for a considerable amount of time. Consult your biofuel distributor for the use of biocidal
products to prevent microbial growth inside the tanks and for instructions on fuel filtering.
During the commissioning of the burner, check that all combustion parameters are compliant with
the recommendations in the technical manual for the appliance.
Check the filters on the burner oil pipe and oil pump, and if necessary replace them:
–– at least every 4 months during burner use
–– before starting the burner following a long period of disuse
–– more often in the event of contamination.
CAUTION
Pay particular attention during the check and inspection to detecting fuel leaks from sealing
CAUTION devices, gaskets and hoses.
CAUTION
IF Bio fuel is used consult your Bio fuel distributor.
CAUTION
62/64
Appendix EN
11 NOTES
63/64
UK Ireland
Firebird Products Ltd Firebird Heating Solutions Ltd
Phoenix House Baile Mhic Íre
Eastern Wood Road Co. Cork
Langage Industrial Estate P12 HK51
Plympton Ireland
This brochure was correct at the time of going to
Plymouth PL7 5ET T: +353 (0)26 45253 print. However, Firebird’s policy is one of continuous
development. The right is reserved to change
T: 01752 691177 F: +353 (0)26 45309 specifications, colour, and prices of the models and
F: 01752 691131 E: [email protected] items illustrated and described in the publication at
any time. Whilst every care has been exercised in the
E: [email protected] www.firebird.ie production of this brochure, Firebird cannot accept
any liability for errors or omissions. For current details
www.firebird.uk.com always consult Firebird Products Ltd.