0% found this document useful (0 votes)
426 views64 pages

Elco Burner Manual May 2018

This document is an instruction manual for assembly, commissioning, and maintenance of FB 2 K LN low NOx kerosene burners. It provides safety information and instructions for installation, including burner assembly, oil system setup, electrical connection, and commissioning. The manual describes the burner components, operating logic, technical specifications, and maintenance requirements.

Uploaded by

Ataca Avha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
426 views64 pages

Elco Burner Manual May 2018

This document is an instruction manual for assembly, commissioning, and maintenance of FB 2 K LN low NOx kerosene burners. It provides safety information and instructions for installation, including burner assembly, oil system setup, electrical connection, and commissioning. The manual describes the burner components, operating logic, technical specifications, and maintenance requirements.

Uploaded by

Ataca Avha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

FB 2 K LN

LOW NOx
KEROSENE BURNERS

Instructions for Assembly,


Commissioning & Maintenance
Before installing and using the burner, read this manual carefully
and keep it close to the burner.

EN
EN 

Dear Client,
We would like to thank you for having chosen a FIREBIRD product.
The model chosen by you is a high-performance product with an advanced technological
conception, high reliability and excellent construction quality.
We advise you to entrust the running and maintenance of this appliance to know qualified
professionals, and also to use only original spare parts when needed.
This manual contains important guidelines and suggestions which should be complied with in
order to obtain a simple installation and the best possible use of the appliance.

RANGE

This manual refers to the following products:


BURNER MODEL FIREBIRD CODE ELCO CODE
FB 2 K 18 LN 414713 3146022
FB 2 K 20 LN 414714 3146023
FB 2 K 26 LN 414715 3146024
FB 2 K 35 LN 414716 3146025

BURNER DESIGNATION

FB 2 K 26 LN

FB 2 Burner Series

K Kerosene

BOILER TYPE
26 Boiler nominal power (max)

EMISSION

LN Low NOx emissions (NOx < 120 mg/kWh according to European


Commission Regulation No 813/2013 and to pr EN267/2016 Class 4)

2/64
 EN

CONTENTS

1 SAFETY 5
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 Key to symbols used in the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.2 Other symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Requirements for personnel or operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Primary hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2 GENERAL 8
2.1 Burner description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Structure of the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Structure of the combustion head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5 Control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6 Operating logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6.1 Operating function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6.2 Controlled shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.6.3 Safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

3 TECHNICAL DATA 15
3.1 Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4 INSTALLATION 18
4.1 Safety during assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Installation area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2.1 Flue gas system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Assembly tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Preliminary checks before mounting the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.5 Burner assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.6 Removing and fitting the burner cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.7 Oil systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.7.1 Hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.7.2 Oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.7.3 Oil feed and suction line with one-pipe system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.7.4 Oil feed and suction line with two-pipe system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.8 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.8.1 Electrical connection to the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.9 Removing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

3/64
EN 

5 COMMISSIONING 35
5.1 Safety during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2 Checks before commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3 Factory pre-setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4 Combustion adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4.1 Air flap position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5 Adjusting burner output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5.1 Burner start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5.2 Burner adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6 Oil pressure setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.1 Oil pressure setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.2 Checking negative pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.3 Cleaning the pump filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6.4 Check pump rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.7 Commissioning record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.7.1 Setting and values recorded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

6 MAINTENANCE 42
6.1 Safety during maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.2 Important components for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.1 List of parts typically subject to wear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.3 Removing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4 Burner maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4.1 Cleaning and replacing combustion head components . . . . . . . . . . . . . . . . . . . . . . 48
6.4.2 Diffuser position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4.3 Combustion head position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4.4 Electrode position check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.4.5 Replacing the coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.6 Replacing the capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.7 Cleaning the internal rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

7 TROUBLESHOOTING 55
7.1 Combustion performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.2 Fault diagnosis and repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.3 Troubleshooting diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

8 SPARE PARTS LIST 58

9 MANUFACTURER CERTIFICATE 60
9.1 Manufacturer Certificate / EU Design Conformity Declaration . . . . . . . . . . . . . . . . . . . . . . 60

10 APPENDIX 61
10.1 Use of bio fuel blends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2 Important advice for the use of bio fuel blends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10.2.2 General instructions and information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

11 NOTES 63

4/64
Safety EN

1 SAFETY

1.1 Overview

These instructions for the installation, commissioning and maintenance of the burner are for use
by technicians from professional heating companies that are qualified to carry out these activities.
The instructions contain indications and information on how to move, handle, activate, adjust,
maintain and remove the appliance and how to dispose of the components at the end of the their
useful life.

The instructions must be followed and all applicable legislation complied with in order to ensure
safe working conditions.

This manual should be stored near the product and made available to all operators involved in
its use.

1.2 Intended use

The burner is designed to act as a heat source for heating and DHW generation systems in which
water is the heating fluid.

Any other or wider application is outside of the specified intended use.

To avoid risks, the burner should only be used:

–– for its specifically intended use


–– under the appropriate safety conditions
–– following the instructions for installation, commissioning and maintenance
–– in compliance with the max. and min. operating values
–– in compliance with the required maintenance activities
–– immediately repairing any malfunctions that could compromise safety
–– maintaining all notes and notices applied to the product so that they remain legible over time

the burner cannot be installed outdoors, unless installed in a boiler specifically designed for that
use. If installed outdoors, climatic conditions could cause direct damage to the burner due to the
presence of water or frost or cause the components to overheat.

5/64
EN Safety

1.3 Symbols used

1.3.1 Key to symbols used in the manual

DANGER
Maximum danger. Indicates operations that cause serious injury, death or long-term health
DANGER risks if performed incorrectly.

DANGER
Indicates a dangerous situation that could cause serious injury, death or long-term health risks,
caused by electricity, if handled without due care or incorrectly.

WARNING
Indicates operations that could cause serious injury, death or long-term health risks if performed
WARNING incorrectly.

PRECAUTION
Indicates potentially dangerous situations and operations that could cause damage to the device
PRECAUTION or things and minor injury to persons, if handled without due care or performed incorrectly.

CAUTION
Indicates operations that could cause damage to the device or nearby things.
CAUTION

IMPORTANT INFORMATION
This symbol indicates important information that you must bear in mind.

1.3.2 Other symbols

DANGER FLAMMABLE MATERIAL


Indicates a dangerous situation that could cause serious injury, death or long-term health risks,
caused by the presence of flammable substances near the equipment, if handled without due
care or incorrectly.

CAUTION
Indicates potentially dangerous situations, caused by the presence of surfaces at high
temperatures that could cause minor injuries, or burns, if handled incorrectly.

PERSONAL PROTECTION
Several symbols are used to remind operators of the need to use all the personal protective
equipment required by applicable legislation during all installation, commissioning and
maintenance operations.

ENVIRONMENTAL PROTECTION
Reminds operators of the need to apply a suitable recycling procedure to replaced components.

ENVIRONMENTAL PROTECTION
Reminds operators of the need to deliver the product or its components to a suitable separated
waste collection centre at the end of its working life.

6/64
Safety EN

1.4 Requirements for personnel or operators

CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.

CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.

CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.

1.5 Primary hazards

The following indications refer to “residual risks”, which must be highlighted for the full understanding
and responsibility of the proprietor, users and operators.
These risks derive from risk analyses carried out by Research and Development staff as required
by European Standard EN 267 and applicable directives (Machine directive, LVD, EMC).

DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.
Check there is no power and ensure restart is impossible.
-- In the event of damage to the electrical insulation on the product, act immediately to restore
the correct level of insulation.

CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.

FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.

7/64
EN General

2 GENERAL

2.1 Burner description

FB 2 K LN is a latest generation single-stage burner fuelled by kerosene. The innovative


combustion head ensures low NOx and CO emissions within the emission limits set out by
European Regulations for energy related products (ErP).
The burner uses functional components that, in addition to ensuring a long working life, also allow
for easy installation, adjustment and maintenance. The high-performance electrical components
ensure low fuel consumption.
The ventilation system ensures a high level of efficiency, and thanks to a powerful transformer,
cold starts don’t cause problems. The operation of FB 2 K LN burners is reliable even in the event
of persistent or intermittent wind, ignition takes place effectively and with smoke-developed index
control.
The contained dimensions, low noise and ease of installation make it possible to apply the burner
to boilers installed in domestic spaces.

2.2 Supply

The burner FB 2 K LN includes the following equipments:


–– n°1 flange with fixing bolt
–– n°1 gasket
–– n°2 flexible oil pipes L=1000 mm
–– n°2 nipple G 3/8 - 1/4 (for flexible oil pipe)
–– n°4 nuts for flange to be fixed to boiler
–– n°1 conventional flue carter
–– cable kit with 7 and 5 pin connectors (already mounted)
–– n°1 hex key 4 mm
–– gauge for checking the settings
–– instruction manual

8/64
General EN

2.3 Identification

Check the identification label of the burner (“Fig. 1”).

414716|BRN035ELN|3146025|SN0000
000004|SL005600012348|DH26/03/201
8 15.37.39

(A) 3146025 414716


BRN035ELN 13-18 (B)
(C) FB 2 K 35 LN (D)
kW 26,5 31,7 36,0 (E)
kg/h 2,2 2,6 3,0
(F) 1N-230 V ~ 50 Hz
(G) IP40 175 W (H)
FUEL KEROSENE (I)
Visc. @ 20 °C 1-2,5 mm²/s
WEIGHT 8 kg

(J)
0000000004 Made in Italy

A Burner code F Electrical supply


B Week and year of manufacture G Protection level
C Burner model H Electrical consumption
D Factory power setting I Types of fuel used
E Burner power output J Serial number

Fig. 1

CAUTION
It is strictly forbidden to remove the identification label.
CAUTION Tampering, removal or absence of the data plate burner or anything that prevents the secure
identification of the burner will create difficulties for any installation and maintenance work.

9/64
EN General

2.4 Structure

2.4.1 Structure of the burner

1 2

11

10

8 7 6

1 Power indication LED 7 Fastening screws for equipment plate


2 Connection PLUG-IN between equip- 8 Housing for internal rotor
ment and ignition transformer 9 PEC
3 Snorkel 10 Reset button
4 Air setting 11 Control box
5 Air intake
6 Air valve indicator

Fig. 2

10/64
General EN

17
12 13 14 15 16

18

26

16

25
19

24 23 22 21 20

12 Combustion head 21 Electric motor for pump and fan


13 Front panel 22 Burner base
14 Burner fixing bolt 23 Oil pressure regulator
15 Burner flange (supplied) 24 Fuel-oil pump
16 Burner cover fixing screw 25 Solenoid valve
17 Conventional flue carter (supplied) 26 Ignition transformer
18 Cable kit with 7 and 5 pin connectors
19 Capacitor
20 Extended pressure port

Fig. 3

11/64
EN General

2.4.2 Structure of the combustion head

4 5 6

2 7 6

1 Combustion head 5 Electrode group fixing screw


2 Diffuser 6 Combustion head fixing screw
3 Electrode group 7 Nozzle
4 Diffuser fixing screw

Fig. 4

12/64
General EN

2.5 Control box

The EBR-M1 control box, controls and monitors the forced draught burner. The microprocessor-
controlled program sequence ensures maximum stability of time periods, regardless of fluctuations
in the power supply or ambient temperature.
The design of the control box protects it from the effects of flame outs. Whenever the supply
voltage drops below its rated minimum level (170 ± 8 V), the control box shuts down - even in the
absence of a fault signal.
The control box switches itself back on again once the voltage has exceeded the 190 ± 8 V.

2.6 Operating logic

101
103

T1

M1 M
118

102
105 106

104 Y1

M1 Burner motor 103 Air flap


T1 Ignition transformer 104 Oil pressure regulator
Y1 Solenoid valve 105 Flexible oil pipe
101 Fan 106 Filter
102 Oil pump 118 Nozzle

Fig. 5

2.6.1 Operating function


–– If heat is requested by the heating controls, the control box starts the program sequence.
–– The motor starts, the ignition transformer is switched on and the preventilation period of 20 s
commences.
–– During the preventilation period, the furnace is monitored for flame signals.
–– At the end of the preventilation period, the fuel-oil solenoid valve opens and the burner starts.
–– The ignition transformer remains switched off while the burner is in operation.

13/64
EN General

2.6.2 Controlled shutdown


–– Boiler temperature control interrupts heat request.
–– The fuel-oil solenoid valve closes and the flame is extinguished.
–– The post-ventilation starts: time factory-set at 30 s. After the burner motor switches off.
–– Burner enters standby.

2.6.3 Safety function


A safety shutdown occurs:
–– if a flame signal is present during preventilation (flame monitoring)
–– if no flame is produced within 5 seconds (safety time) of start-up (fuel authorisation)
–– if no flame is produced after an unsuccessful restart attempt in the event of 5 flame failures
during operation.

A safety shutdown is indicated by the malfunction lamp lighting up and it is then only possible to
reset the burner by pressing the reset button after the cause of the malfunction has been rectified.
For further information, see the automatic combustion control unit description.

General
power LINE
supply C

Boiler
temperature
control

Motor

Ignition
Transformer

Valve

Flame check

Flame
1 2 3 4 5 6 7 8

- - 20s 5s 7s - - 30s

3 Prepurge time 5 Post-Ignition time


4 Safety time 8 Post-purge

Fig. 6

14/64
Technical data EN

3 TECHNICAL DATA

3.1 Dimensions and weights

288,5 106 215

151 137,5 Ø75

Ø 83
163

Ø 180

Ø 151,5

Ø 131,5 15 Max
45°

11

145
=
45°

10

Øi 100

Fig. 7

Weight (kg)
Model
net with packaging
FB 2 K 18 LN 8 9,8
FB 2 K 20 LN 8 9,8
270

FB 2 K 26 LN 8 9,8
FB 2 K 35 LN 8 9,8
0
300 39

All measurements are given in millimetres. Fig. 8

15/64
EN Technical data

3.2 Technical data

FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN

16,0 kW 18,6 kW 24,0 kW 31,7 kW


Burner output factory setting (1)
13.760 kcal/h 16.000 kcal/h 20.640 kcal/h 27.260 kcal/h

Oil throughput factory setting (1) 1,3 kg/h 1,5 kg/h 2,0 kg/h 2,6 kg/h

Fuel oil (2) Kerosene , visc 1÷2,5 mm2/s at 20°C (Hi=11,97 kWh/kg)

< 120 mg/kWh


NOx emissions (according to European Commission Regulation No 813/2013
and to pr EN267/2016 Class 4)

Control box EBR-M1 20-30

Flame sensor Photoelectric controller (PEC)

Ignition transformer Fida 2P 26 kV pp-35 mA rms

Fuel-oil pump Danfoss BFP special

Pump coil BFP T85

EBR 90 W, 2800 rpm


Electric motor
90 watt

Capacitor Inco 4 μF , TEKNO 45T (T = top series)

Electrical supply 1 / 230 / 50 Ph / V / Hz

Power consumption (operation) (+/- 5W) 188 W 190 W 185 W 175 W

Protection level IP40

Sound pressure level 65 dB(A)

Ambient temperature for storage -20°C ... +70°C

Temperature for use -10°C ... +60°C

(1)
Reference conditions: Ambient temperature 20 °C – Barometric pressure 1013 mbar – Altitude 0 m. a.s.l.

WARNING
(2)
The burner is suitable for kerosene with bio content up to 10%. It is a minimum requirement
WARNING that the fuel blend (up to 10% Bio) is obtained with kerosene in accordance with the relevant
standards and regional regulations.
In case of Bio oil content higher that 10% please contact the manufacturer.

16/64
Technical data EN

3.3 Electrical diagram

TV
CONTROL BOX EBR-M1 20-30

B4 S3 T2 T1 N L1

CONNECTION KIT
B4 S3 T2 T1 N L1

MV
M
YVg B

L3 N L2 L1

L3 N L2 L1

SWITCH LIVE
BURNER LOCK OUT
EARTH
NEUTRAL
PERMANENT LIVE (230V-50Hz)

B Photo-resistor TV Ignition transformer


MV Fan motor YVg Oil solenoid valve

Fig. 9

17/64
EN Installation

4 INSTALLATION

4.1 Safety during assembly

DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.
Check there is no power and ensure restart is impossible.
-- In the event of damage to the electrical insulation on the product, act immediately to restore
the correct level of insulation.

WARNING
Danger of death due to contact with fuel oil!
WARNING Risk of lung damage caused by inhalation or ingestion of fuel oil; take the following precautions:
-- observe the instructions on the safety data sheets for the fuel oil and any additives (available
from the associated suppliers)
-- in the event of the formation of an oil mist, use a protective mask with filter for organic
vapours and particulate filter
-- do not eat, drink or smoke when working on the heating system.

WARNING
Danger of injury due to contact with fuel oil!
WARNING Repeated and prolonged skin exposure to fuel oil can damage and irritate the skin; take the
following precautions:
-- as far as possible, avoid contact with the skin
-- use personal protective equipment, such as a protective gloves and suitable clothing
-- do not put rags soaked with oil in your pockets
-- change clothes stained with oil as soon as possible.

CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.

CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.

CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.

18/64
Installation EN

4.2 Installation area

Before installation, make sure that the installation area satisfies the following requirements:
–– operating temperature between +5°C and +45°C
–– dry, frost resistant, well-ventilated
–– no accumulation of heavy powders
–– no high levels of humidity
–– no atmospheric pollutants created by halogenated hydrocarbons (contained in solvents,
adhesives, aerosols, etc.)
–– no atmospheric pollutants created by sulphurous gases
–– no vibration.

WARNING
Danger of death caused by fire!
WARNING Highly flammable materials or liquids can catch fire
-- do not use or store explosive or highly flammable substances (such as petrol, paint, paper,
wood, etc.) in the installation area of the appliance
-- do not dry clothing within the boiler installation area
-- do not use the equipment in an explosive atmosphere.

CAUTION
Flammable materials or liquids should not be stored or used near the burner.
CAUTION

IMPORTANT INFORMATION
Failure to observe these instructions will invalidate the warranty with respect to any damages
caused by any of these causes.

4.2.1 Flue gas system


Before installation, check the design suitability of the combustion flue system with respect to the
type of boiler to be installed and with respect to the applicable standards and regulations.

CAUTION
Operators should explain to the proprietor and person responsible for the domestic heating
CAUTION system the burner is installed on, the importance of ensuring good inflow of combustion air
and combustion product evacuation. They should also highlight that no modification should be
made to the heating system (comprised of air intake, burner, boiler and flue pipe) that could
alter the correct operation of the system.

19/64
EN Installation

4.3 Assembly tools

The most common and frequent operations on the burner are carried out simply using only the
hex key supplied. This key can be used to:
–– remove the burner cover
–– remove the diffuser
–– adjust the electrodes group
–– adjust the fuel pressure
–– adjust the air setting
–– operate on the pump.

4.4 Preliminary checks before mounting the burner

Before mounting the burner onto the boiler:


–– check the distance between tips of electrodes (2 mm)

Fig. 10

20/64
Installation EN

–– Check the position of the electrodes assuring that they are centered as shown in “Fig. 11”.

=
=

A
A-A 1 : 1

Fig. 11

21/64
EN Installation

4.5 Burner assembly

CAUTION
Install the burner on the boiler according to the installation position shown in “Fig. 12”.
CAUTION Installation 2,3 and 4 are forbidden for safety reason.

OK

1 2 3 4
Fig. 12

The burner is secured to the boiler using the connection flange supplied with the burner.
Follow the instructions below:
–– couple the gasket (2) supplied with the connection flange (1).

2 1

Fig. 13

22/64
Installation EN

–– position the flange (2), with the screw (1) facing upwards, onto the boiler and secure it with the
nuts (5) supplied
–– tighten the nuts (5) of the flange evenly and diagonally with a tightening torque of 3,5 Nm
max.
–– insert the burner combustion head (6) with care inside the flange

5 1

Fig. 14

–– rotate the burner first to the right and then to the left to insert the fastening screw (1) into the
housing (7) on the burner
–– fully tighten the nut (3) and at the same time press the burner in the lower part towards the
boiler to ensure maximum seal between the burner itself and the boiler

1 3 7

Fig. 15

23/64
EN Installation

–– insert the air intake pipe (8) and secure it using a pipe clamp (9), not supplied
–– in case of conventional flue applications remove snorkel and air conveyor (10) and replace
with the conventional flue carter (11) supplied.

11
9

10

Fig. 16

4.6 Removing and fitting the burner cover

–– To remove the burner cover, loosen the two screws (1) and then slide out the burner cover (2)
taking care not to damage it.
–– To refit it, invert the procedure above.

2 1

A
B

Fig. 17

24/64
Installation EN

4.7 Oil systems

FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.

WARNING
Danger of injury from gas in the atmosphere!
WARNING To prevent the formation of gas caused by worst combustion/deflagration:
-- when filling the tank, switch off the burner and leave it switched off for approximately 3 hours
to ensure degassing of the fuel and the deposit of suspended particles
-- have any damage to the oil pipes repaired immediately by a specialised technician
-- never operate the burner with the oil tank empty.

IMPORTANT INFORMATION
Corresponding legislation pertaining to water resources and the installation of fuel pipes must
be observed.

IMPORTANT INFORMATION
Leaks in the fuel supply system can cause combustion problems and malfunctions in the burner.

The fuel tank, including the installation of the pipes, must be carried out in such as way as to
ensure that the temperature of the oil going into the burner is at least + 5°C.

When the burner is replaced, also replace the fuel filter.

25/64
EN Installation

4.7.1 Hydraulic diagram

NC

V P
E

H
C
S

D
Pressure
T Suction
P1 Return
A O

A Bypass screw P Pressure gauge port


D Diaphragm P1 Pressure adjustment
E Nozzle outlet R Return outlet
H Filter S Suction inlet
NC Valve T Pressure regulator
O Constriction V Vacuum gauge port

Fig. 18

4.7.2 Oil pump

1
8

3 7

5 6

1 Fuel-oil solenoid valve 5 Suction connection


2 Solenoid valve electrical connection 6 Return connection
3 Fuel delivery pipe 7 Oil pressure regulator
4 Vacuum port pressure gauge connection 8 Oil pressure gauge connection

Fig. 19

26/64
Installation EN

• One-pipe system (standard)


The pump is supplied for operation with one pipe. The return connection is capped. Inside the
pump, there is a screw with a by-pass washer (10) which allows the fuel to recirculate inside the
pump.

To apply the fuel delivery pipe, proceed as follows:


–– remove the plastic cap (12) and screw in the delivery pipe (13) supplied with the burner.

10

11

2
1-

13

12

Fig. 20

CAUTION
Only approved fuel lines are to be used.
CAUTION

• Two-pipe system (optional)


For two-pipe operation it is necessary to remove the by-pass washer.

To apply the fuel return pipe, proceed as follows:


–– remove the cap (14) from the connection and screw in the additional return pipe (15), supplied
with the burner
–– unscrew the four screws (17) and remove the cover (16) from the pump
–– unscrew screw (11) and remove the by-pass washer (10)
–– screw in screw (11) and the cover (16).

16
10
17
11
14
2
1-

15

Fig. 21

IMPORTANT INFORMATION
There is an intake filter and an oil pressure regulator integrated in the pump. Pressure gauges
for negative pressure (vacuum) measurement must be connected before the equipment is
commissioned.

CAUTION
Before starting the burner, check that the return pipe is open. An eventual obstruction could
CAUTION damage the pump sealing device.

27/64
EN Installation

4.7.3 Oil feed and suction line with one-pipe system

Burner lower than tank

Y
X

H = x-y

Fig. 22

Pipe length (m) Pipe length (m)


H (m) H (m)
Ø6 mm Ø8 mm Ø10 mm Ø6 mm Ø8 mm Ø10 mm
0,5 19 60 100 2,5 27 85 100
1 21 66 100 3 29 91 100
1,5 23 72 100 3,5 31 98 100
2 25 79 100 - - - -

CAUTION
-- X < 20 m
CAUTION -- Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.

Burner higher than tank

Fig. 23

Pipe length (m) Pipe length (m)


H (m) H (m)
Ø6 mm Ø8 mm Ø10 mm Ø6 mm Ø8 mm Ø10 mm
0,5 15 47 100 2,5 7 22 53
1 13 41 99 3 5 15 37
1,5 11 34 84 3,5 - 9 22
2 9 28 68 - - - -

28/64
Installation EN

4.7.4 Oil feed and suction line with two-pipe system

Burner lower than tank

Y
X

H = x-y

Fig. 24

Pipe length (m) Pipe length (m)


H (m) H (m)
Ø6 mm Ø8 mm Ø10 mm Ø6 mm Ø8 mm Ø10 mm
0,5 19 60 100 2,5 27 85 100
1 21 66 100 3 29 91 100
1,5 23 72 100 3,5 31 98 100
2 25 79 100 - - - -

CAUTION
-- X < 20 m
CAUTION -- Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.

Burner higher than tank

Fig. 25

Pipe length (m) Pipe length (m)


H (m) H (m)
Ø6 mm Ø8 mm Ø10 mm Ø6 mm Ø8 mm Ø10 mm
0,5 15 47 100 2,5 7 22 53
1 13 41 99 3 5 15 37
1,5 11 34 84 3,5 - 9 22
2 9 28 68 - - - -

29/64
EN Installation

4.8 Electrical connection

DANGER
Danger of death caused by live components!
Contact with live parts can lead to serious injury, take the following precautions:
-- ensure that the power is switched off for all electrical parts
-- electrical wiring installation must be carried out by qualified personnel and in compliance with
the regulations currently in force in the country of destination. Refer to the wiring diagrams.

CAUTION
-- The electrical installation should include a minimum of a type A MCB.
CAUTION -- Check to ensure that the power supply voltage is as specified in the electric diagram and in
data plate.
-- Burner fuse: 3 Amps.

WARNING
-- Use flexible cables in compliance with the EN 60 335-1 standard. Assure a correct earth
WARNING connection.
-- The wiring section must be minimum 1 mm2 (in any case verify with the standard and local
rules).
-- This control flame is equipped with the post ventilation function. Other versions of the burner
are not to be fitted.
-- Check operation of boiler thermostatic control.
-- Check operation of Photocell by withdrawing from burner and then covering to simulate flame
out condition.

30/64
Installation EN

4.8.1 Electrical connection to the boiler


Burner FB 2 K LN leaves the factory configured for connection to a 7 pin electrical cable. ­
­­­ adaptor cable kit from 7 pins to 5 pins is also supplied and factory mounted.
An­­

Proceed as follows to connect the burner to the boiler:


–– remove the burner cover (1) as described in paragraph “4.6 Removing and fitting the burner
cover” on page 24
–– cut the band (2) and unwind the cable (3)

4 3

Fig. 26

–– refit the burner cover (1), inverting the procedure above


–– connect the 5-pin plug (4) to the boiler.

31/64
EN Installation

4.9 Removing the burner

DANGER
Danger of death caused by live components!
Before carrying out any operations on the burner, operate the main power switch for the system
to cut off the power supply.

If it becomes necessary to remove the burner, proceed as follows:


–– close the fuel taps upstream of the burner
–– loosen the two screws (1) and then slide out the burner cover (2) taking care not to damage it.

2 1

A
B

Fig. 27

–– detach the electrical connector (3) from the boiler

Fig. 28

32/64
Installation EN

–– remove the fuel delivery pipe (5) and the return pipe (6), if present

5 6

Fig. 29

–– drain any fuel still inside the burner and in the fuel delivery pipe and collect it in a basin
–– loosen the pipe clamp (7) and remove the air intake pipe (8), if present

Fig. 30

33/64
EN Installation

–– loosen the nut (9) securing the burner to the boiler and, rotating the burner (10) slightly to the
right, slide it off the boiler.

10

Fig. 31

CAUTION
Dispose of any fuel that comes out of the burner in accordance with applicable legislation in the
CAUTION destination country. Separated waste management avoids potential damage to the environment
and peoples’ health. It also allows many recyclable materials to be recovered, with significant
economic and energy savings.

34/64
Commissioning EN

5 COMMISSIONING

5.1 Safety during commissioning

CAUTION
It may be hazardous to assign activities to personnel that are not sufficiently qualified. It may
CAUTION harm the operators themselves if they perform manoeuvres or operations incorrectly, with a
serious impact on personal safety, things and property.

CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.

CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.

FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation in some individuals.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
suitable personal protective equipment.

5.2 Checks before commissioning

The following must be checked before initial commissioning:

–– That the burner is assembled in accordance with the instructions given here
–– That the burner is pre-set in accordance with the values in the adjustment table
–– Setting the combustion components
–– The boiler must be ready for operation, and the operating regulations for the heater must be
observed
–– All electrical connections must be correct
–– The boiler and heating system must be filled with water and the circulating pumps must be in
operation
–– The thermostats and any other safety or limiting devices that might be fitted must be connected
and operational
–– The flue system must be unobstructed and the secondary air system, if available, must be
operational
–– An adequate supply of fresh air must be guaranteed
–– The heat request must be available
–– Fuel tanks must be full
–– The fuel supply lines must be assembled correctly, checked for leaks and bled
–– In the event the burner does not start on initial start-up following a long period of storage,
the pump should be checked to ensure it is not blocked. See chapter on “5.6.4 Check pump
rotation” on page 39
–– A standard-compliant measuring point and analyser test point must be available, the flue
system to the measuring point must be free of leaks to prevent anomalies in the measurement
results.

35/64
EN Commissioning

5.3 Factory pre-setting

Burner Nozzle Pump*


Type gph spray type bar
FB 2 K 18 LN 0,40 80° SF Fluidics 9,3
FB 2 K 20 LN 0,50 80° ES Danfoss 9,8
FB 2 K 26 LN 0,65 80° ES Danfoss 9,3
FB 2 K 35 LN 0,85 60° ES Danfoss 8,6

Reference conditions
–– Conventional Flue system: diameter 80 mm / length 1.5 m
–– Ambient temperature: 20°C +/-5
–– CO2 = 12.5% ± 0,2.
(*) The pump pressure is referred to a stability period of 5 min.

Note.
All the burners are factory tested and adjusted. The air flap and combustion head are set to
have the CO2 % within the above limit.

5.4 Combustion adjustment

The burners leave the factory set according to the paragraph “5.3 Factory pre-setting”.
The installation of the burner on the boiler, the commissioning and servicing must be carried out
following the boiler technical manual, including the check of the CO2 and CO level in the flue
gases, their temperatures and the average temperature of the water in the boiler.

In case of outside temperature conditions influencing the combustion it is recommended to adjust


the CO2 according to the diagram below.

In the cold of winter aim for 1% rise in CO2 as the


lower CO2 %. In warmer ambient temperature rises
times of the year set the by 20°C.
CO2 higher.

CO2 13,50
(%)
13,00

12,50

12,00

11,50

11,00
00 5 10 15 20 25 30 35
Outside air temperature (°C)

Fig. 32

36/64
Commissioning EN

5.4.1 Air flap position


Turn the hex key (1) supplied:
–– clockwise to increase the air flap opening (O2 rises, CO2 decreases).
–– counterclockwise to reduce the air flap opening (O2 decreases, CO2 rises).

O2 -
CO2 +

O2 +
CO2 -

Fig. 33

5.5 Adjusting burner output

1
8

3 7

5 6

1 Fuel-oil solenoid valve 5 Suction connection


2 Solenoid valve electrical connection 6 Return connection
3 Fuel delivery pipe 7 Oil pressure regulator
4 Vacuum port pressure gauge connection 8 Oil pressure gauge connection

Fig. 34

WARNING
Continuously check CO, CO2 and soot emissions when adjusting the output of the burner. CO
WARNING must not exceed 50 ppm.

37/64
EN Commissioning

5.5.1 Burner start


Before starting the burner, draw oil in until the filter is completely filled. Then start the burner by
creating a heat demand on the boiler (refer to boiler installation manual). Open the bleed screw
on the oil filter to allow the oil line to bleed fully during the preventilation phase. The negative
pressure (vacuum) must not fall below 0.4 bar. Close the bleed screw when the filter is completely
filled with oil and oil is flowing out without bubbles. Boiler has to maintain in operation at least 15
min. or reach a steady condition of operation, then check the combustion values.
5.5.2 Burner adjustment
Use the pressure regulator to adjust the oil pressure in accordance with the table (tab.1). Monitor
the combustion values continuously as you do so (CO, CO2, smoke test). Adjust the airflow
gradually if necessary. Operating on air flap setting.

5.6 Oil pressure setting

5.6.1 Oil pressure setting


The oil pressure, and therefore burner output, is adjusted using oil pressure regulator (7), see
“Fig. 34”, on the pump.
Sequence to adjust the oil pressure:
–– connect a pressure gauge at point (8).
Turn the regulator screw (7) to:
–– right: to increase pressure.
–– left: to reduce pressure.
–– verify the correct pressure with the pressure gauge.
At the end of adjustment.
–– to disconnect the pressure gauge.
–– to tight the plug (8).
5.6.2 Checking negative pressure
The vacuum gauge for checking negative pressure must be connected to point (4). Maximum
permissible negative pressure is 0.4 bar check the oil supply in case those pressures cannot be
achieved. At higher negative pressures, the fuel oil gasifies, which causes pump cavitation in the
pump and ultimately leads to pump damage.
5.6.3 Cleaning the pump filter
To be able to clean the filter (H), it is necessary to remove the pump cover.
Check the pump cover seal and replace the gasket if necessary.

Fig. 35

38/64
Commissioning EN

5.6.4 Check pump rotation

CAUTION
If the pump is blocked, proceed as follows.
CAUTION
–– Disconnect the oil pipe from the pump
–– remove the pump (1) from the motor loosening screws (3) using the key supplied (2)

3
1

Fig. 36

–– manually rotate the shaft (3-4 rotations both clockwise and anticlockwise)

Fig. 37

–– refit the pump to the motor


–– reconnect the oil pipe to the pump. Check that there is no oil leakage on the pump side after
this operation.

Replace the pump in the event it remains blocked or if there was any sticking during manual
rotation.

39/64
EN Commissioning

5.7 Commissioning record

Confirm the work carried out in the commissioning report below by marking and X or an ✓.
Commissioning work Note Done

Check the heating system has been filled


correctly and the air has been removed

Check the flue system

Check there are no leaks in the fuel supply


system

Start the burner and check that it is operating


normally

Measure the parameters of the combustion


system and record all the main data pertaining
to the first ignition

Explain to the proprietor and person


responsible for the domestic heating system
the burner is installed on, the importance of
ensuring good inflow of combustion air and
combustion product evacuation. They should
also highlight that no modification should be
made to the heating system (comprised of air
intake, burner, boiler and flue pipe) that could
alter the correct operation of the system

Confirmation of correct commissioning:

Stamp / date / company signature:_______________________________________________

40/64
Commissioning EN

5.7.1 Setting and values recorded

Customer:__________________________________________________________________

Heating system:______________________________________________________________

BOILER

Type

kW
Output
kcal/h

BURNER

Type FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN

Serial number

Output kW

Nozzle size gph


Spray angle/cone
type
Fan pressure mbar
Combustion
mbar
chamber pressure
Air flap scale

Oil throughput kg/h


Oil pressure (oil
bar
pump)
CO2 Vol.%

mg / kWh
CO
ppm

mg / kWh
NOx
ppm

Room temperature °C
Flue gas
°C
temperature (gross)
Pressure at the base
mbar
of chimney
Firing Efficiency
%
factor

Date:______________________________________________________________________

Signature:__________________________________________________________________

41/64
EN Maintenance

6 MAINTENANCE

6.1 Safety during maintenance

The periodic maintenance is important for safety, good operation and long life cycle of the burner,
reducing also consumption and polluting emissions.

The burner must be serviced at least once a year. Only qualified and authorised personnel shall
carry out maintenance and the calibration of the burner, in accordance with this manual and in
compliance with the local standards and regulations.

DANGER
Danger of death!
-- Contact with live electrical components may cause serious incidents.
-- Only professionally-trained and qualified personal can operate on the electrical system.
-- Before any operation, switch off the power supply to the system by operating the main switch.

CAUTION
Hot surfaces - Risk of burns!
-- Contact with components at high temperatures may cause more or less serious superficial
burns.
-- Operators should wear suitable clothing and personal protective equipment.
-- They should ensure that all components are at ambient temperature before carrying out any
maintenance operations.

FUEL LEAKS
-- Fuel leaks may cause fire to break out.
CAUTION -- They may be toxic via inhalation and cause skin irritation.
-- Act swiftly to remove the cause of the leak. If it is connected to a maintenance operation, use
the dedicated personal protective equipment.

PRECAUTION
Danger of injury caused by improper use!
PRECAUTION Danger of personal injury such as contusions, bruises and cuts due to incorrect handling.
-- Use personal protective equipment as required by applicable legislation, such as safety
shoes and gloves.

CAUTION
Installation, commissioning and maintenance activities must only be carried out by the personnel
CAUTION of dedicated heating companies specifically qualified to perform these tasks.

IMPORTANT INFORMATION
-- Inspect threaded joints to identify leaks during annual maintenance checks.
-- Replace defective or worn gaskets.

42/64
Maintenance EN

6.2 Important components for safety

In order to ensure the long working life of the burner, we recommend periodically carrying out
component checks.

6.2.1 List of parts typically subject to wear


Parts subject to wear should be regularly checked by the technician during maintenance operations
and if necessary replaced.

Replacement intervals / years (non-binding


Worn components
factory recommendation)
Nozzles 1
Gaskets 2
Fuel delivery pipes 2
Flame monitoring devices 3
Ignition electrodes 2
Ignition cable 5

43/64
EN Maintenance

6.3 Removing the burner

DANGER
Danger of death caused by live components!
Before carrying out any operations on the burner, operate the main power switch for the system
to cut off the power supply.

To remove the burner from the boiler, proceed as follows:


–– close the fuel taps upstream of the burner
–– loosen the two screws (1) and then slide out the burner cover (2) taking care not to damage it.

2 1

A
B

Fig. 38

–– detach the electrical connector (3) from the boiler

Fig. 39

44/64
Maintenance EN

–– remove the fuel delivery pipe (5) and the return pipe (6), if present

5 6

Fig. 40

–– drain any fuel still inside the burner and in the fuel delivery pipe and collect it in a basin
–– loosen the pipe clamp (7) and remove the air intake pipe (8), if present

Fig. 41

45/64
EN Maintenance

–– loosen the nut (9) securing the burner to the boiler and, rotating the burner (10) slightly to the
right, slide it off the boiler.

10

Fig. 42

CAUTION
Dispose of any fuel that comes out of the burner in accordance with applicable legislation in the
CAUTION destination country. Separated waste management avoids potential damage to the environment
and peoples’ health. It also allows many recyclable materials to be recovered, with significant
economic and energy savings.

IMPORTANT INFORMATION
Once the burner has been removed from the boiler, it can be rested on a rigid, level surface.
The burner should be placed on the ground only if resting on the burner base and should never
be turned upside down.

46/64
Maintenance EN

To facilitate maintenance operations, secure the burner to the boiler by inserting the fastening
screw (11) into the hole (12) on the burner base. Use one of the three square grooves on the
burner base to secure the burner, which should be rotated to the best position for the maintenance
operation to the carried out.

12
11

A C

A B C
Fig. 43

Position A:
–– inspection and cleaning of the internal rotor.

Position B:
–– inspection of the combustion head
–– inspection and maintenance of the nozzle
–– inspection and maintenance of the electrode group.

Position C:
–– inspection and maintenance of the pump
–– inspection and maintenance of the coil
–– inspection and maintenance of the capacitor.

47/64
EN Maintenance

6.4 Burner maintenance

–– Check the fuel supply components (pipe, pump, fuel delivery pipe) and their connections for
leaks and signs of wear, replace parts as necessary.
–– Check that the electrical connection and connection cables are not damaged, replace them if
necessary.
–– Check the pump filter and clean it if necessary.
–– Clean the fan and its housing and check for damage.
–– Check and clean the combustion head.
–– Check the ignition electrodes, adjust or replace them if necessary.
–– Replace the nozzle.
–– Fit the combustion head. Observe the adjustment dimensions.
–– Mount the burner.
–– Start the burner, check the exhaust gas data, adjust the burner settings if necessary.
–– Fuel pipes should be checked annually and replaced after 2 years.
–– Check and clean the components on the main burner.

6.4.1 Cleaning and replacing combustion head components


–– Remove screws (1) using a screwdriver and slide out the combustion head (2)
–– loosen screw (3) using the hex key supplied and remove the diffuser (4) together with the
electrode group (5)
–– a suitable spanner of the correct size should be used on the fuel line for removing the nozzle
(6)

2 4 3 5 6

Fig. 44

–– ensure that all components are in good condition, undamaged by high temperatures, clean
and soot-free. Replace if damaged
–– clean all components thoroughly
–– refit the components, reversing the procedure above.

48/64
Maintenance EN

CAUTION
If the air distributor (1) is removed from its housing, it must be repositioned, making sure that
CAUTION the hole (2) is aligned with the pin (3).

2
3

Fig. 45

6.4.2 Diffuser position check


To check the position of the diffuser:
–– remove the combustion head as described in paragraph “6.4.1 Cleaning and replacing
combustion head components” on page 48
–– use the key provided to loosen screw (8) and allow the diffuser position check. One turn of the
key is sufficient.

8 1X

Fig. 46

49/64
EN Maintenance

–– check the distance between the diffuser (1) and the nozzle (2) as shown in the figure.

2 1

Fig. 47

–– after having adjusted the position of the diffuser tighten the screw (8).
–– refit the combustion head.

8 1X

Fig. 48

50/64
Maintenance EN

6.4.3 Combustion head position check


To check the position of the combustion head:
–– check the distance between the combustion head (1) and the nozzle (2) as shown in the figure.

2 1

Fig. 49

51/64
EN Maintenance

6.4.4 Electrode position check


–– Check the distance between tips of electrodes (2 mm)

Fig. 50

–– Check the position of the electrodes assuring that they are centered as shown in “Fig. 51”.

=
=

A
A-A 1 : 1

Fig. 51

52/64
Maintenance EN

6.4.5 Replacing the coil


The pump coil is designed and built to withstand temperatures of up to 85°C. In the event of
malfunctions or faults, replace the coil using the following procedure:
–– remove the connector (1)
–– remove the nut (2) using the key supplied
–– slide off the coil (3) and replace it

2 3

Fig. 52

–– refit the components, reversing the procedure above.

6.4.6 Replacing the capacitor


Proceed as follows to replace the capacitor:
–– detach the electrical connection from the capacitor (1)
–– remove the capacitor (2) and replace it

1 2

Fig. 53

–– refit the components, reversing the procedure above.

53/64
EN Maintenance

6.4.7 Cleaning the internal rotor


Check there is no dust inside the fan wheel because this could reduce the combustion
performances. Carry out maintenance operations, avoiding to damage the fan. Verify the correct
position of fan wheel within the burner housing.

Follow the sequence


–– loose the screws (1) and remove the air intake duct (2)
–– clean the fan (3) and the inside of the air intake using a brush
–– if necessary, disassembly and re-assembly the fan.

Fig. 54

Observe the positioning diagram below when replacing the motor and blower wheel (3). The
inside flange (A) of the blower wheel must be fitted at 0,3 mm lower than the equipment plate (B),
tighten the set screw on the blower wheel.

3 B

Burner Position C

OK A FB 2 K 18 LN 0,5 mm
C

FB 2 K 20 LN 0,5 mm
FB 2 K 26 LN 0,5 mm
FB 2 K 35 LN 0,5 mm

NO

NO

Fig. 55

54/64
Troubleshooting EN

7 TROUBLESHOOTING

7.1 Combustion performances

After carrying out commissioning, cleaning or maintenance, combustion parameters must be


verified.
Boiler has to maintain in operation at least 15 min. or reach a steady condition of operation, then
check:
–– pump pressure
–– flue gas temperature
–– CO2 (%)
–– CO (ppm)
–– NOx (ppm)
–– Bacharach index.

7.2 Fault diagnosis and repair

In the event of a malfunction, first check that the prerequisites for correct operation are fulfilled:
–– is the system connected to the power supply?
–– is there oil in the tank?
–– are all shut-off valves open?
–– are all control and safety devices, such as the boiler thermostat, low pressure device (if fitted),
limit switch, etc. adjusted correctly?

Warranty will be invalidated if genuine parts are not used on replacement. These components
must be replaced by parts with the same order number.

WARNING
To reset the equipment control, after viewing the visual diagnosis, press the release button.
WARNING

WARNING
In case of burner lock out, to avoid damage to the installation, do not reset the burner more
WARNING than twice in succession.

DANGER
If the burner goes into lock out for the third time, contact manufacturer’s service organisation.
DANGER In the case in which they occur further locks or malfunction burner, interventions must be
carried out by qualified and authorized personnel, following the information in this manual and
in accordance with the rules and legal regulations.

IMPORTANT INFORMATION
Only use original spare parts.

IMPORTANT INFORMATION
After each operation:
-- Under normal operating conditions (doors closed, cover fitted, etc.), check combustion and
check the individual lines for leaks.
-- Record the results in the relevant documents.

55/64
EN Troubleshooting

7.3 Troubleshooting diagram

Boiler control Burner


supplied with motor Yes
heat demand runs

No
Replace
Check green Motor Pump
Yes No No motor
LED lights seized blocked
capacitor
No Yes Yes

Check boiler Replace Check


Dirty Clean filter
control motor pump filter

Cleaned

Unblock/Replace
pump

Lock out
Yes after 20 sec Yes
pre-purge

No

Check pump Check flame

* Yes solenoid
functionality
Yes sensor
functionality **
Is there a Replace
Flame sensor
No Yes false flame No control
work well?
signal box
Replace No Yes
pump
solenoid
Replace Remove false
flame sensor flame causes

Replace Clean filter


drive or replace Replace
coupling pump solenoid
Why is
No broken? No No

Check Yes Check pump Yes Check Yes Replace


the drive filter solenoid pump
coupling

Check pressure loss


or complete system
(boiler + fuel)
No
Yes
No

Ignition Check Nozzle Combustion Combustion


spark Yes pump Yes atomising Yes air set Yes head set
functionality pressure full correct correct

No No No No Yes

Check Set or Replace nozzle Adjust Adjust


ignition No replace parameters parameters
electrodes electrodes
No
Yes

Replace ignitor
Check main
fuel filter
* Yes Recycle?

Fig. 56

56/64
Troubleshooting EN

Boiler control Burner


Lock out Is there a Remove
supplied with motor Yes Yes Yes
during pre false flame false flame
heat demand runs
purge phase signal causes

Boiler control Burner No


Lock out Is there a Remove
supplied with motor Yes Yes Yes
during pre false flame false flame
heat demand runs
purge phase Check flame
signal causes
sensor
functionality
No **
Flame sensor Replace
Checkwork
flame
well?
Yes
control box
sensor
**
functionalityNo

Flame sensor Replace


Yes
Replace
work well? flame control box
sensor
No

Replace flame
sensor

Fig. 57

(**) Check flame sensor functionality

Check
procedure

Check Sensor see


Take sensor Lock out
procedure 1 Reset external light
on hands before 20 s

Take sensor Sensor see Lock out


1 Reset on hands external light before 20 s
Obscure Lock out
1 Reset sensor to after 20 s
light

Obscure Lock out


1 Reset sensor to after 20 s
light

Fig. 58

57/64
EN

58/64
FB 2 K 18 LN
FB 2 K 20 LN
FB 2 K 26 LN
FB 2 K 35 LN
Spare parts list

0280 0290 0310 0300 0320 0420 0140


SPARE PARTS LIST

0220 0230 0380 0240 0210 0250 0270 0260

0400
0390
0180
0170
0410 0200

0160

0130 0150

0100

0190 0020 0010 0040 0350 0360 0370 0030 0060 0330 0070 0340 0110 0080 0090 0050

Fig. 59
0120
Spare parts list EN

FB 2 K 18 LN FB 2 K 20 LN FB 2 K 26 LN FB 2 K 35 LN
N° Description
3146022 3146023 3146024 3146025
0010 OIL PUMP 65327227 65327227 65327227 65327227
0020 COIL 65327245 65327245 65327245 65327245
0030 COUPLING 65327229 65327229 65327229 65327229
0040 FLEXIBLE OIL HOSE 65327230 65327230 65327230 65327230
0050 BURNER COVER 65327231 65327231 65327231 65327231
0060 MOTOR 65327232 65327232 65327232 65327232
0070 CAPACITOR 65327233 65327233 65327233 65327233
0080 IGNITION TRANSFORMER 65327234 65327234 65327234 65327234
0090 CONTROL BOX WITH CABLES 65327235 65327235 65327235 65327235
0100 PHOTORESISTOR 65327236 65327236 65327236 65327236
0110 SUPPORT 65327240 65327240 65327240 65327240
0120 CABLE KIT WITH 7 AND 5 PIN CONNECTORS 65327237 65327237 65327237 65327237
0130 CLAMP 65327241 65327241 65327241 65327241
0140 FAN 65327280 65327280 65327239 65327239
0150 ORING 65327224 65327224 65327224 65327224
0160 AIR INLET COVER GASKET 65327223 65327223 65327223 65327223
0170 AIR INLET COVER 65327279 65327279 65327283 65327283
0180 ORING 65327247 65327247 65327247 65327247
0190 SET FILTER+SEAL 65327228 65327228 65327228 65327228
0200 IGNITION CABLES 65327284 65327284 65327284 65327284
0210 ELECTRODE GROUP 65327285 65327285 65327285 65327285
0220 BLAST TUBE 65327286 65327286 65327286 65327200
0230 BLAST TUBE ORING 65327201 65327201 65327201 65327201
0240 DIFFUSER 65327202 65327203 65327203 65327203
0250 NOZZLE HOLDER 65327287 65327287 65327287 65327288
0260 SPRING 65327206 65327206 65327206 65327206
0270 ROD ORING 65327210 65327210 65327210 65327210
0280 AIR DISTRIBUTOR 65327281 65327211 65327282 65327294
0290 AIR DISTRIBUTOR ORING 65327213 65327213 65327213 65327213
0300 FLANGE 65327289 65327289 65327289 65327289
0310 GASKET 65327290 65327290 65327290 65327290
0320 ORING 65327216 65327216 65327216 65327216
0330 MOTOR GASKET 65327222 65327222 65327222 65327222
0340 PIPE 65327217 65327217 65327217 65327217
0350 GASKET 65327205 65327205 65327205 65327205
0360 EXTENDED PRESSURE PORT 65327242 65327242 65327242 65327242
0370 THREADED STOPPER 65327243 65327243 65327243 65327243
0380 NOZZLE 65327218
0380 NOZZLE 65327219
0380 NOZZLE 65327220
0380 NOZZLE 65327221
0390 SNORKEL 65327225 65327225 65327225 65327225
0400 CONVENTIONAL FLUE CARTER 65327226 65327226 65327226 65327226
0410 FRONT PANEL 65327291 65327291 65327291 65327291
0420 COVER SCREW GROUP 65327209 65327209 65327209 65327209

59/64
EN Manufacturer Certificate

9 MANUFACTURER CERTIFICATE

9.1 Manufacturer Certificate / EU Design Conformity Declaration

We, Firebird, declare under our sole responsibility that the kerosene burners named FB 2 K ... LN
is conform to the following standards:
–– EN 267
–– EN 55014-1
–– EN 60335-1
–– EN 61000-6-2
–– EN 50156-1
–– EN 55014-2
–– EN 60335-2-102
–– EN 61000-6-3

These products bear the CE mark in accordance with the stipulations of the following directives:
–– 2014/35/UE Low Voltage Directive
–– 2014/30/UE EMC Directive
–– 2006/42/EC Machine Directive
–– 2011/65/EU RoHS2 Directive

April 2018 / Mr. Filippo Maltempi

R&D Director

60/64
Appendix EN

10 APPENDIX

10.1 Use of bio fuel blends

The burner is suitable for kerosene with a biofuel content of up to 10%. It is a minimum requirement
that the fuel blend (up to 10% Biofuel) is obtained with kerosene in accordance with the relevant
standards, regional regulations and FAME in accordance with EN 14214.

IMPORTANT INFORMATION
In the event that the burner needs to be used with fuels containing biofuel percentages higher
than 10%, contact the manufacturer.

10.2 Important advice for the use of bio fuel blends

10.2.1 Introduction
The growing attention focussed on renewable and sustainable energy sources would suggest an
ever-increasing use of biofuels.

If you plan to make use of these fuels, you need to consider several technical aspects in order to
reduce the potential for faults in the burner and heating system and the risk of fuel leaks.
The term ‘liquid Biofuel’ is a broad definition that includes oils made from numerous different
raw materials, including recycled cooking oil. These types of oil must be considered and treated
differently from common mineral and fossil fuels. This is because they are more acidic, hygroscopic
and less stable.

Particular care should be taken in the storage of this fuel, in the supply pipe, in the ancillary
equipment, in the filtration and in the choice of burner.

The classification of the biofuel is important for the smooth operation of the equipment.

IMPORTANT INFORMATION
The proprietor or the system manager is responsible for the detailed analysis of potential risks
associated with the introduction of a mixture of biofuels and the suitability of the devices and
installation.

10.2.2 General instructions and information


The supplier of the fuel must demonstrate compliance with an accredited quality management
system for their storage, mixing and delivery processes.

During installation, make sure that all the materials and sealing devices used on the storage tank
and oil delivery pipe to the burner are compatible with biofuels.

The tank must have a good quality biofuel-compatible oil filter and a 60 micron secondary filter to
protect the burner from contaminants.

61/64
EN Appendix

Wherever an existing tank is to be used to store the oil, in addition to the above mentioned checks
on the materials, it is essential that the tank is first inspected to verify its condition and check for
the presence of water or other contaminants. If contaminants are found, a deep clean should be
carried out. If this is not carried out the hygroscopic nature of the fuel could dissolve and detach
complex components and cause faults in the equipment.

Based on the capacity of the storage tank and how the system is used, fuels can be stored
inside it for a considerable amount of time. Consult your biofuel distributor for the use of biocidal
products to prevent microbial growth inside the tanks and for instructions on fuel filtering.

During the commissioning of the burner, check that all combustion parameters are compliant with
the recommendations in the technical manual for the appliance.
Check the filters on the burner oil pipe and oil pump, and if necessary replace them:
–– at least every 4 months during burner use
–– before starting the burner following a long period of disuse
–– more often in the event of contamination.

CAUTION
Pay particular attention during the check and inspection to detecting fuel leaks from sealing
CAUTION devices, gaskets and hoses.

CAUTION
IF Bio fuel is used consult your Bio fuel distributor.
CAUTION

62/64
Appendix EN

11 NOTES

63/64
UK Ireland
Firebird Products Ltd Firebird Heating Solutions Ltd
Phoenix House Baile Mhic Íre
Eastern Wood Road Co. Cork
Langage Industrial Estate P12 HK51
Plympton Ireland
This brochure was correct at the time of going to
Plymouth PL7 5ET T: +353 (0)26 45253 print. However, Firebird’s policy is one of continuous
development. The right is reserved to change
T: 01752 691177 F: +353 (0)26 45309 specifications, colour, and prices of the models and
F: 01752 691131 E: [email protected] items illustrated and described in the publication at
any time. Whilst every care has been exercised in the
E: [email protected] www.firebird.ie production of this brochure, Firebird cannot accept
any liability for errors or omissions. For current details
www.firebird.uk.com always consult Firebird Products Ltd.

You might also like