Calculation by Equivalent Static Method
Calculation by Equivalent Static Method
1. DL
2. LL
3. EQ X+
4. EQ Y+
5. WIND X+
6. WIND Y-
FACTORED LOAD COMBINATIONS FOR GIVEN LOAD PATTERNS ACCORDING TO IS 1893 : 2016
1.5(DL + LL)
1.5[DL + (EQx + 0.3EQy)] 1.2[DL + LL + (EQx + 0.3EQy)] 0.9DL + 1.5 (EQx + 0.3EQy)]
1.5[DL + (EQx - 0.3EQy)] 1.2[DL + LL + (EQx - 0.3EQy)] 0.9DL + 1.5 (EQx - 0.3EQy)]
1.5[DL - (EQx + 0.3EQy)] 1.2[DL + LL - (EQx + 0.3EQy)] 0.9DL - 1.5 (EQx + 0.3EQy)]
1.5[DL - (EQx - 0.3EQy)] 1.2[DL + LL - (EQx - 0.3EQy)] 0.9DL - 1.5 (EQx - 0.3EQy)]
1.5[DL + (EQy + 0.3EQx)] 1.2[DL + LL + (EQy + 0.3EQx)] 0.9DL + 1.5 (EQy + 0.3EQx)]
1.5[DL + (EQy - 0.3EQx)] 1.2[DL + LL + (EQy - 0.3EQx)] 0.9DL + 1.5 (EQy - 0.3EQx)]
1.5[DL - (EQy + 0.3EQx)] 1.2[DL + LL - (EQy + 0.3EQx)] 0.9DL - 1.5 (EQy + 0.3EQx)]
1.5[DL - (EQy - 0.3EQx)] 1.2[DL + LL - (EQy - 0.3EQx)] 0.9DL - 1.5 (EQy - 0.3EQx)]
Other Data
m
m
Thick
ck
kN/cum
Seismic Load Calculation
Ground Floor Load Calculation
kN
kN
kN
kN
kN
kN
kN
Time Period
Ah= (Z*I*Sa/g)/2R
Zone Factor (Z) 0.36
Importance Factor (I) 1
Response Reduction Factor ( R) 5
Spectral Acceleration (Sa/g) 2.5
Ah= (Z*I*Sa/g)/2R 0.09
Weight of the Building 23568.29 KN
Remarks
Clause 7.6.1, IS 1893:2002 T1 = 0.06 H ¾ for concrete frames
0.55 sec
Using IS 1893:2002
Fi=Vb*WiHi/sum of (Wi*Hi)
606.04
505.03
404.03
303.02
202.01
101.01
2121.15
oncrete frames Clause 7.3 a; NBC 105
0.08
285 X (0.15 X 25 + 0.23 X 68 X (0.23 X 68 X 20 X 2.5/2)+(0.15 [0.23 X (0.5-0.15) X 25 X 90] + [0.23 3.88 X 25 X
Roof 1.5) = 1497 20 X 1 = 313 X 98 X 20 X 2.5/2) = 759 - X (0.4-0.15) X 25 X 76] = 291 2982 2982
2.5/2 = 122
Earthquake Force in Short direction = 21870 X 0.09 = 1969 kN (Without ductile detailing)
= 21870 X 0.054 = 1181 kN (With ductile detailing)
Earthquake Force in Long direction = 21870 X 0.1224 = 2677 kN (Without ductile detailing)
= 21870 X 0.074 = 1619 kN (With ductile detailing)
Designed lateral forces in Short direction corresponding to entire structure
Storey Wihi2/ Storey Shear Base Moment
Wi hi Wihi2
Level ∑Wihi2 SMRF OMRF SMRF OMRF
9 2982 28.5 2422129.5 0.2353 477 793 13598 22596
8 3622 25.5 2355205.5 0.2288 464 771 11830 19659
7 3622 22.5 1833637.5 0.1781 361 600 8127 13505
6 3622 19.5 1377265.5 0.1338 271 451 5290 8791
5 3622 16.5 986089.5 0.0958 194 323 3205 5326
4 3622 13.5 660109.5 0.0641 130 216 1755 2917
3 3622 10.5 399325.5 0.0388 79 131 826 1372
2 3622 7.5 203737.5 0.0198 40 67 301 500
1 2863 4.5 57975.75 0.0056 11 19 51 85
Total 31199 10295475.8 1.0000 2028 3370 44983 74751
Earthquake Force in Short direction = 31199 X 0.108 = 3370 kN (Without ductile detailing)
= 31199 X 0.065 = 2028 kN (With ductile detailing)
Earthquake Force in Long direction = 31199 X 0.1224 = 3819 kN (Without ductile detailing)
= 31199 X 0.074 = 2309 kN (With ductile detailing)
Designed lateral forces in Long direction corresponding to entire structure
Storey Wihi2/ Storey Shear Base Moment
Wi hi Wihi2
Level ∑Wihi2 SMRF OMRF SMRF OMRF
9 2113 28.5 1716284.25 0.2372 384 635 10946 18099
8 2539 25.5 1650984.75 0.2282 369 611 9421 15577
7 2539 22.5 1285368.75 0.1777 288 476 6472 10701
6 2539 19.5 965454.75 0.1334 216 357 4213 6966
5 2539 16.5 691242.75 0.0955 155 256 2552 4220
4 2539 13.5 462732.75 0.0640 104 171 1398 2311
3 2539 10.5 279924.75 0.0387 63 104 658 1088
2 2539 7.5 142818.75 0.0197 32 53 240 396
1 1984 4.5 40176 0.0056 9 15 40 67
Total 21870 7234987.5 1.0000 1619 2677 35939 59425
1969
1181
2677
1619
3370
2028
3819
2309
Time Period in Sa/g Ah
sec
X Y X Y X
Model 0.59 0.81 1.70 1.24 0.074
No.1
Model 0.59 0.67 1.70 1.5 0.074
No.2
Ah Vb in kN
Y X Y
0.054 1619 1181