Installation & Servicing: Ideal Classic 24 30 35
Installation & Servicing: Ideal Classic 24 30 35
& SERVICING
IDEAL CLASSIC
24 30 35
When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
For the very latest copy of literature for specification and maintenance practices visit our website www.idealboilers.com
where you can download the relevant information in PDF format.
July 2018
UIN 212135 A06
ERP DATA
MODEL
SYMBOL UNITS 24 30 35
Condensing Boiler n/a n/a yes yes yes
Low Temperature Boiler n/a n/a no no no
B1 Boiler n/a n/a no no no
Cogeneration Space Heater n/a n/a no no no
Equipped with a Supplementary Heater n/a n/a no no no
Combination Heater n/a n/a yes yes yes
Nominal Heat Output for Space Heating
Full Load P4 kW 24.2 24.3 24.2
Part Load P1 kW 7.8 7.8 7.8
Auxiliary Electricity Consumption
Full Load elmax kW 0.042 0.032 0.029
Part Load elmin kW 0.012 0.013 0.013
Standby PSB kW 0.005 0.005 0.005
Seasonal Space Heating Energy Efficiency
Full Load ƞ4 % 89.8 90.0 89.8
Part Load ƞ1 % 96.9 96.9 96.9
Standby Loss Pstby kW 0.050 0.050 0.050
Ignition Pign kW 0 0 0
A
Temperature control (from fiche of temperature control) %
Class I Class II Class III Class IV Class V Class VI Class VII Class VIII
1% 2% 1.5% 2% 3% 4% 3.5% 5% B
%
= (‘III ’x + ‘IV ’ x ) x 0.9 x ( / 100 x = C
%
Seasonal Space Heating Energy Efficiency of Package TOTAL: A+B+C=
G F E D C B A A+ A++ A+++
< 30% ≥ 30% ≥ 34% ≥ 36% ≥ 75% ≥ 82% ≥ 90% ≥ 98% ≥ 125% ≥ 150%
The energy efficiency of the package of products provided for in this document may not correspond to its actual energy efficiency once installed in a
building, as the efficiency is influenced by further factors such as heat loss in the products in relation to the building size and its characteristics
DOCUMENT AMENDMENTS
Relevant Installation changes implemented in this book from Mod Level........ A05 (Feb 18) To A06 (July 18)
Page 6
Change to NOX Classification
Page 7
Removal of PI No.
Section 4
Update to Water Treatment information
*Required for maximum flow rate. Boiler operates down to 2 l/min DHW delivery
** In areas of low water pressure the DHW restrictor can be removed
Table 2 - Performance Data - Central Heating Table 3 - Performance Data - Domestic Hot Water
Boiler Input : Max. Min. Maximum DHW Input : 24 30 35
24 30 35
Nett CV kW 24.3 30.4 35.4
Boiler Input ‘Q’ Nett CV kW 24.3 4.9 6.1 7.1
Gross CV kW
27.0 5.4 6.7 7.9 Gross CV kW 27.0 33.7 39.3
Gas Consumption m3/h 2.512 0.500 0.627 0.734 Gas Consumption m3/h 2.512 3.135 3.657
(ft3/h) (89) (17.8) (22) (25.9) (ft3/h) (89) (111) (129)
Boiler Output : Maximum kW 24.2 30.3 35.3
Non Condensing kW
24.2 4.8 6.1 7.1
DHW Output
70oC Mean Water temp.
DHW Flow Rate l/min 9.9 12.4 14.5
Condensing kW
25.6 5.1 6.4 7.5 at 35°C temp. rise. (gpm) (2.2) (2.8) (3.2)
40oC Mean Water temp.
DHW Specific Rate l/min 11.5 14.5 16.9
Seasonal efficiency* SEDBUK 2005 91% 91.1% 91% (gpm) (2.5) (3.2) (3.7)
Seasonal efficiency* SEDBUK 2009 89% 89% 89%
NOx Classification CLASS 6
* The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by a notified body.
Note. Gas consumption is calculated using a Key to symbols
calorific value of 38.7 MJ/m3 (1038 Btu/ft3) gross GB = United Kingdom IE = Ireland (Countries of destination)
or 34.9 MJ/m3 (935 Btu/ft3) nett
PMS = Maximum operating pressure of water
To obtain the gas consumption at a different
C13 C33 C53 = A room sealed appliance designed for connection via ducts to a
calorific value:
horizontal or vertical terminal, which admits fresh air to the burner
a. For l/s - divide the gross heat input (kW) by and discharges the products of combustion to the outside through
the gross C.V. of the gas (MJ/m3) orifices which, in this case, are concentric. The fan is up stream of
b. For ft3/h - divide the gross heat input (Btu/h) the combustion chamber.
by the gross C.V. of the gas (Btu/ft3) I2H = An appliance designed for use on 2nd Family gas, Group H only.
c. For m3/h - multiply l/s by 3.6.
For GB, to comply with Building Regulations Part L1 (Part 6 in Scotland) the boiler should be fitted in accordance with the
manufacturer’s instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be
demonstrated by completing and signing the Benchmark Commissioning Checklist.
Before installing this boiler, read the Code of Practice sheet at the rear of this book.
2. It is important that the position of the terminal allows the free * Only one reduction down to 25mm is allowable per installation
passage of air across it at all times. otherwise BS5440-1 2008 dimensions must be followed.
ELECTRICAL SUPPLY
WARNING.
This appliance must be earthed.
Wiring external to the appliance MUST be in accordance with
the current I.E.E. (BS.7671) Wiring Regulations and any local
regulations which apply. For IE reference should be made to the
current ETCI rules for electrical installations.
The mains supply to the boiler and system wiring centre shall
be through one common fused double pole isolator and for
new heating systems, and where practical replacement boiler
installations, the isolator shall be situated adjacent to the
appliance.
CONDENSATE DRAIN
Refer to Frames 20, 21 & 36
A condensate drain is provided on the boiler. This drain must be
connected to a drainage point on site. All pipework and fittings in
the condensate drainage system MUST be made of plastic - no
other materials may be used.
IMPORTANT.
Any external runs must be in accordance with BS 6798.
The drain outlet on the boiler is sized for standard 21.5mm
overflow pipe. It is a universal fitting to allow use of different
brands of pipework.
2.5 285
2.5 from case 395
155
Side flue
dim. A
700
GAS INLET
DHW INLET
CH FLOW
COND. DRAIN
CH RETURN
PRV
103 99 99 99 103
WALL
Front clearance
The minimum front clearance when built in to a
cupboard is 5mm from the cupboard door but
450mm overall clearance is still required, with
the cupboard door open, to allow for servicing.
* Bottom clearance
Bottom clearance after installation can be
reduced to 5mm.
This must be obtained with an easily
removable panel, to enable the consumer
to view the system pressure gauge, and to
provide the 100mm clearance required for
servicing.
2 ...............CONTINUED
DOMESTIC HOT WATER b. Hot and cold water supplies to the shower are of equal
pressure.
1. The domestic hot water service must be in accordance with
BS 5546 and BS 6700. 5. Hard Water Areas - Where the water hardness exceeds
200mg/litre (200ppm), it is recommended that a proprietary
2. Refer to Table 1 for minimum and maximum working scale reducing device is fitted into the boiler cold supply
pressures. In areas of low mains water pressures the within the requirements of the local water company.
domestic hot water regulator may be removed from the
DHW flow turbine cartridge. Refer to Frame 67. The boiler IMPORTANT
will require the flow rate to be set to obtain a temperature Provision MUST be made to accomodate the expansion of DHW
rise of 35oC at the tap furthest from the boiler. contained within the appliance. If the DHW inlet contains a back
flow prevention device or non-return valve, e.g. a water meter,
3. The boilers are suitable for connection to most types of
then a mini expansion vessel should be fitted between the device
washing machine and dishwasher appliances.
and the boiler in the cold inlet pipe.
4. If the shower/mixer valve does not incorporate non-return Cold water, rising main and pipework on exposed areas need to
valves the following must be followed: be suitably lagged to prevent freezing.
a. The cold inlet to the boiler is fitted with an approved
Note. DHW Expansion Vessel Kit availabe from Ideal Boilers.
anti-vacuum or syphon non-return valve.
3 SYSTEM BALANCING
The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load of at least 10% of the
minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available. See
note regarding thermostatic radiator valves on page 11.
Note. Systems incorporating zone valves which could completely cut off the flow through the system must also include a bypass.
BALANCING
1. Set the programmer to ON. These valves should now be left as set.
Close the manual or thermostatic valves on all radiators, 2. Open all manual or thermostatic radiator valves and
leaving the twin lockshield valves (on the radiators referred to adjust the lockshield valves on the remaining radiators, to
above) in the OPEN position. give around 20oC temperature drop at each radiator.
Turn up the room thermostat and adjust the lockshield valve 3. Adjust the room thermostat and programmer to
to give an uninterrupted flow through the radiator. NORMAL settings.
4 WATER TREATMENT
DOMESTIC HOT WATER
CENTRAL HEATING In hard water areas where mains water can exceed 200ppm Total Hardness
The range of boilers have an ALUMINIUM alloy heat (as defined by BS 7593:2006 Table 2) a scale reducing device together with
exchanger. Scalemaster in-line scale inhibitor should be fitted into the boiler cold supply
IMPORTANT. within the requirements of the local water company. The use of artificially
softened water, however, is not permitted.
The application of any other treatment to this product
may render the guarantee of Ideal Boilers Invalid. Ideal Boilers recommend the use of Fernox Quantomat, Sentinel
Ideal Boilers recommend Water Treatment in accordance Combiguard and Calmag CalPhos I scale reducing devices, which must be
with the Benchmark Guidance Notes on Water Treatment in used in accordance with the manufacturers’ instructions.
Central Heating Systems.
If water treatment is used Ideal Boilers recommend only the For further information contact:
use of SCALEMASTER SM-1 PRO, FERNOX-MB-1, ADEY Fernox Cookson Electronics
MC1, SENTINEL-X100 or CALMAG CM100 inhibitors and Forsyth Road, Sheerwater, Woking, Surrey GU21 5RZ
associated water treatment products, which must be used in +44 (0) 8706 015000
accordance with the manufacturers’ instructions. Sentinel Performance Solutions
Notes. The Heath Business & Technical Park, Runcorn, Cheshire WA7 4QX
1. It is most important that the correct concentration of the Tel: 0800 389 4670
water treatment products is maintained in accordance Scalemaster Water Treatment Products
with the manufacturers’ instructions. Emerald Way, Stone, Staffordshire ST15 0SR
2. If the boiler is installed in an existing system any Tel: +44 (0) 1785 811636
unsuitable additives MUST be removed by thorough Calmag Ltd.
cleansing. BS 7593:2006 details the steps necessary to Unit 3-6, Crown Works, Bradford Road,
clean a domestic heating system. Sandbeds, Keighley, West Yorkshire BD20 5LN
3. In hard water areas, treatment to prevent lime scale may Tel: +44 (0) 1535 210320
be necessary - however the use of artificially softened
Adey Professional Heating Solutions
water is NOT permitted.
Gloucester Road, Cheltenham GL51 8NR
4. Under no circumstances should the boiler be fired Tel: +44 (0) 1242 546700
before the system has been thoroughly flushed.
5 BOILER ASSEMBLY - Exploded View Note that item numbers are linked to the spares list
INSTALLATION
104 CH RETURN VALVE 131 WATER PRESSURE SWITCH 303 CUI BOARD
105 CH FLOW VALVE 135 PRESSURE GAUGE 306 ELECTRODE IGNITION
106 DHW INLET & OUTLET 203 GAS COCK 307 ELECTRODE DETECTION
108 PUMP HEAD 204 PIPE - GAS INLET 308 IGNITER UNIT
110 AIR VENT PUMP 205 GAS VALVE 309 FLOW THERMISTOR
111 DIVERTOR VALVE MOTOR 206 PIPE - GAS INJECTOR 313 IGNITION LEAD
112 DIVERTOR VALVE BODY 211 INJECTOR ASSEMBLY 314 CONTROL BOX LENS
113 PRESSURE RELIEF VALVE 214 VENTURI 324 CONTROLS BOX LID
114 PIPE - PRV OUTLET 215 FAN 325 CONTROL BOX FRONT
115 PIPE - FLOW 217 BURNER 326 MECHANICAL TIMER
116 PIPE - RETURN 218 GASKET - BURNER 401 HEAT ENGINE
117 PIPE - EXPANSION VESSEL 219 SUMP CLEAN OUT COVER 503 WALL MOUNTING BRACKET
118 EXPANSION VESSEL 223 FLUE MANIFOLD 504 FRONT PANEL
119 RETURN GROUP KIT 224 FLUE MANIFOLD TOP 506 BRACKET - GAS VALVE
120 FLOW GROUP KIT 227 CLAMP RETAINING FLUE TURRET 507 BRACKET - EXPANSION VESSEL
121 PLATE HEAT EXCHANGER 228 HOSE CONDENSATE INTERNAL 510 ACCESS FLAP
124 FLOW REGULATOR CARTRIDGE 229 SIPHON TRAP
127 FLOW SENSOR/TURBINE 231 CONDENSATE OUTLET CONNECTION
128 RETURN THERMISTOR 302 PRIMARY PCB* * Note. that production boiler PCB’s are
factory pre-set to operate for boiler range and
output, but when ordering Primary PCB as a
spare, an additional Boiler Chip Card (BCC)
MUST also be purchased for your specific
boiler range and output.
504
227
503
224
215
309
218
214
507
306
128
211 110
116 115 111
206 307 121
223
308 401
506 120 112 113
205 131
204 117
127 114
105
228 124 119
135
510 229
219 108
231
106
203 106
104
324
302
314 303
326
325
The boiler is supplied fully assembled in Pack A. A telescopic or non-telescopic flue assembly for rear or side flue outlet in
Pack B is suppled as a separate order.
A
E
Pack A Contents
A Boiler B
B Hardware Bag
C Wall Mounting Plate
D These Installation/Users Instructions
E Wall Mounting Template
(located on internal protective packaging) C
F Boiler Guarantee & Registration Pack
G Boiler Guarantee
Note. This flue system incorporates a removable flue outlet nose that utilises a push fit location system. This enables the
installation of deflector, high level or balcony outlet flue kits without the removal of the whole ‘B’ pack terminal. The appliance
must not be operated without the desired outlet nose correctly fitted in place.
Note. Location dimples must be aligned with terminal mounting frame.
FLUE OUTLET
D
2 3
1
3G9495
side) and screw home. Ensure mounting bracket is level.
3G9948
9982b
IMPORTANT. The boiler must be installed in a vertical position in recommended that a support bracket is fitted on every 1 metre of
accordance to the installation instructions. pipe work used and the bracket is located as close to the collar as
FLUE KITS possible. The bracketing must ensure a 1.5 degree fall back to the
appliance.
Telescopic Flue‘B’ Pack - contains: Flue turret, telescopic flue
incorporating a terminal and rubber wall seals. Optional Flue Finishing Kit - UIN 155988 & Concentric Flue
Screw Retaining Kit (Optional Kit of mechanical fixing of flue joints)
Horizontal Flue Terminal (600mm long) ‘B’ Pack - contains: Flue
turret, non telescopic single piece flue incorporating a terminal and Only use water as a lubricant during assembly.
rubber wall seals. The ‘B’ pack terminal is classed as part of the maximum flue
Horizontal Flue Terminal (1000mm long) ‘B’ Pack - Flue turret, length.
telescopic flue incorporating a terminal, rubber wall seals and These flue systems incorporates a removable flue outlet nose that
instructions. utilises a push fit location system. This enables the installation
Note. If ‘B’ packs are used on their own (either 1 piece or telescopic), then of deflector, high level or balcony flue kits without the removal of
they can be fitted horizontally as the flue inside is designed to slope 1.5 the whole ‘B’ pack terminal. The appliance must not be operated
degrees. without the desired outlet nose correctly fitted in place, ensuring
the side location dimples are in line with the mounting face allowing
Flue Kit 203129 - D Pack Flue Extension 100mm DIA 1000mm long the correct sealing of the components.
Flue Kit 211037 - D Pack Flue Extension 100mm DIA 500mm long
It is IMPORTANT that all attachments are fitted in accordance to
Flue Kit 211038 - D Pack Flue Extension 100mm Dia 2000mm long the installation instructions provided with them.
Flue Kit 211039 - Roof Flue Kit with Vertical Connector
The TURRET supplied in the ‘B’ Pack has an upper combustion
When extension ‘D’ Packs are used the flue duct must incline sample point with a screw cap seal and a lower air sample point
1.5 degrees away from the appliance, to allow the condensate with an air stopper seal. Ensure all caps & seals are in place.
to drain back to the boiler and out of the condensate drain. It is
Additional Termination Kits available for use with these ‘B’ packs.
Flue Deflector Kit The resistance is the equivalent of 1 metre of flue pipe and therefore must be deducted from
any maximum flue length
High Level Flue Outlet Kit The maximum permissible concentric flue length when using a standard (500mm) kit is 4.5 metres
Balcony Flue Outlet Kit The maximum permissible concentric flue length when using this kit is dependant on the length
of the balcony flue outlet run which combined with the concentric run must not exceed the
maximum flue length requirement of the appliance it is to be fitted to
Soffit Kit This kit enables fitment of an external flue below soffits.
Total Maximum Permissible Horizontal Concentric Flue Length combining both ‘B’ Packs and ‘D’ Packs
(Measured from centreline of the turret to the outside of the wall terminal)
24 kW appliances Total Maximum: 9 metres - minus any flue kit options or bends
FLUE OUTLET
30 kW Appliances Total Maximum: 8 metres - minus any flue kit options or bends
35 kW Appliances Total Maximum: 6 metres - minus any flue kit options or bends
Total Maximum Permissible Vertical Flue Length combining both Roof Terminal and ‘D’ Packs
24, 30 & 35 kW Appliances Total Maximum: 7.5 Metres - minus any bends
WALL
WALL
WALL
off Frame
FIGURE 2
Shows the flue required when measured from outside edge of turret to the outside face of the wall (to obtain cut length add 44mm)
Minimum & Maximum finished flue lengths obtainable (dimension ‘A’ +44mm)
Horizontal Flue Terminal Telescopic Flue B Pack Horizontal Flue Horizontal Flue Terminal
(600mm long) B Pack Terminal (1000mm long) (1000mm long) B Pack
B Pack (Telescopic) (Telescopic) Cut 75mm
Minimum Maximum Minimum Maximum Minimum Maximum Minimum Maximum
B Pack (Standard) 171 556 286 484 601 816 526 741
FLUE OUTLET
Max output 35 kW
Plus 1 (1m D pack) 1121 1506 1236 1434 1551 1766 1476 1691
Plus 2 (1m D pack) 2071 2456 2186 2384 2501 2716 2426 2641
Max output 30 kW
Plus 3 (1m D pack) 3021 3406 3136 3334 3451 3666 3376 3591
Plus 4 (1m D pack) 3971 4356 4086 4284 4401 4616 4326 4541
Max output 24 kW
Plus 5 (1m D pack) 4921 5306 5036 5234 5351 5566 5276 5491
Plus 6 (1m D pack) 5871 6256 5986 6184 6301 6516 6226 6441
Plus 7 (1m D pack) 6821 7206 6936 7134 7251 7466 7176 7391
Plus 8 (1m D pack) 7771 8186 7886 8084 8201 8416 8126 8341
Plus 9 (1m D pack) 8721 9000 8836 9000 9000 9000 9000 9000
Note; Telescopic flue B Pack or attached “D” pack extensions do not need to be cut between minimum and maximum values
shown above (except where specified). Horizontal Flue Terminal (600mm long) B Pack flue will require cutting on values
below maximum values shown in the table above.
If using the 2000mm D Pack , the maximum usable length per extension is 1950mm
If using the 500mm D Pack, the maximum usable length per extension is 450mm.
TELESCOPIC FLUES
TELESCOPIC FLUE B PACK SHOULD ONLY BE ADJUSTED FOR USE WITHIN ITS SPECIFIED RANGE AND MUST NOT
BE CUT
HORIZONTAL FLUE TERMINAL (1000MM LONG) B PACK (TELESCOPIC) MUST ONLY BE CUT IF REQUIRED FLUE
LENGTHS ARE BETWEEN 602 & 652MM. THIS WILL REQUIRE 75MM TO BE CUT OFF THE TERMINAL END OF THE
1000MM TELESCOPIC FLUE.
ALL OTHER LENGTHS OBTAINED USING “D” PACK EXTENSIONS IN FLUE LENGTH TABLE 1, COLUMN “HORIZONTAL
FLUE TERMINAL (1000MM LONG) B PACK CUT 75MM” (TELESCOPIC) SHOULD HAVE THE 75MM CUT OFF THE “D”
PACK EXTENSION AND NOT TELESCOPIC FLUE
CUT 75MM OFF HORIZONTAL FLUE TERMINAL 1000MM LONG B PACK (TELESCOPIC)
1. Measure cut flue length (A+44mm). (If required telescopic length is not between
658 and 708 then proceed to “Setting Telescopic Flue B Pack”).
2. Remove telescopic end piece from the flue body and set aside.
3. Mark the circumference 75mm from the open end of the outer flue.
4. Cut along the 75mm mark cutting only the outer flue ensuring the cut is square.
5. Dress the cut end to make sure all burr is removed and the cut edge is in its
original shape.
6. Measure 20mm from the newly cut edge of the outer flue, place a mark at the top of the flue approximately 20mm wide &
write stop the terminal side of the line.
7. Mark the inner tube 10mm longer than the outer tube around its circumference and cut following the mark to ensure its cut
square
8. Remove all burrs and place a chamfer on the outer edge to aid assembly.
9. Re-assemble telescopic section.
FLUE OUTLET
desired length is achieved. ENSURE THE STOP MARK IS NOT VISIBLE,
IF IT IS, THE FLUE IS TOO SHORT AND SHOULD NOT BE USED.
3. Check that both flue seams are at the top and the outlet terminal is upper
most.
4. Drill a 3.5mm hole through one of the 2 outer side holes in the outer flue
section into the inserted outer flue (as shown). Take care not to pierce the
inner plastic flue. Fit screw provided.
5. Seal the joint on the outer air duct with the tape provided.
6. Fit external wall seal (see installing flue).
Rubber
Terminal
Wall Seal
FITTING THE TURRET - Ensure the condense trap/siphon is filled with water
1. Ensure the rubber seal is fitted correctly on the appliance manifold and that all flue seals are undamaged.
2. Hold the flue firmly and push the turret on until it has travelled 30mm on to the flue pipe and is fully engaged. Make sure the
flue has not rotated or moved forward during fitting and the flue seam is upper most.
3. Push the turret into the manifold ensuring the upper plastic lip is flush with the top of the manifold.
4. Fully engage the clamp location section into the manifold location holes. Rotate down on to turret flange.
5. Secure clamp to appliance using securing screw.
6. Ensure all sample points are accessible and all sample plugs and caps are fitted.
D
A
B
Flue Outlet
A - Duct Assembly
B - Flue Turret
C - Turret Clamp
D - Seal
Flue Outlet
C
This kit is suitable for both flat and pitched roof terminations, using a concentric
flue to run vertically from the top of the boiler and terminating above roof level.
Connection to the top of the boiler is made
using a separately supplied vertical connector.
WEATHER PROOFING
Where the flue passes through the roof line
an adequate seal must be made. This is
achieved by using either:
- Flat roof weather collar
or
- Universal weather collar.
ACCESSORIES
Flue Duct Extension Kits are available for flue
lengths extending beyond 1m. These packs
contain 1m extension ducts and may be cut to
the desired length.
If the offset vertical option is used an elbow Kit
is required.
Soffit Flue Kit supplied as an optional extra.
For a full accessories list refer to page 8,
Optional Extras.
FLUE OUTLET
Flue Terminal Flue Seal Collar - Flat Roof Vertical connector 90o elbow
UIN 211039 UIN 152259 UIN 208175 UIN 203130
Vertical
Connector
Flue
duct
support
Roof Flue Extension Duct
UIN 211037 (500mm)
Soffit Flue Kit
UIN 203129 (1000mm)
UIN 211302 UIN 211038 (2000mm)
Flue
duct
support
m 690mm
0m
30 Fixed
300mm in
m
min
rf8394-1
625mm
Fixed
rf8393-1
A A
A
B
RF
98
07
A = 600mm
B = 2000mm
The flue terminal shall not penetrate the shaded area of the roof
Pitched roof - with velux window
or opening
Where two or more vertical fanned draught chimney configurations terminate in close
Note.
proximity at the same height, they shall be separated by at least 300mm. Where any
one vertical outlet is more than 300mm above the other, then they shall be separated The equivalent flue length
by at least 1500mm. resistance of the elbow kits are:
90o elbow kit = 1m
Where any vertical fanned draught chimney configuration outlet is within 2000mm
measured horizontally of an opening window, then it shall be at least 300mm above 45o elbow kit = 0.6m
the opening.
o
min 25
o
max 45
1. Position the roof flashing plate (supplied separately) over the
hole cut in the roof and insert flue terminal from the roof end.
MAX LENGTH:
7.5m
nm8739
BOILER
4. Position the clamp on the top face of the flue manifold and push
it horizontally backwards. Locate both clamp lugs into the flue
manifold and secure to the flue manifold clamp with the M5
retaining screw.
5. “Push” fit extension duct (if required (supplied separately)) into
Pitched roof tile vertical connector.
Flat roof tile weather collar
weather collar Note. Ensure turret sample points are servicable and all caps and
plugs are fitted. Fill the condensate trap siphon with water.
nm8740
Extension
FLUE OUTLET
5 Duct
Vertical
4 connector
2
3G9557b
6. If the last extension duct requires cutting, measure ‘X’, the distance (outer ducts),
between the duct and the terminal and add 100 mm to this dimension. This
gives the length of the last extension duct.
6
'X' Note. Check the position of the inner flue duct relative to the outer duct on the
assembled extension duct(s) and ensure the terminal flue duct is cut longer than
the air duct to ensure engagement in the final flue duct seal.
7. Finally ensure the roof flashing plate is correctly sealed to the roof.
Condensate Pump
Where gravity discharge to an internal termination is not physically
possible or where very long internal pipe runs would be required
to reach a suitable discharge point, a condensate pump of a
Condensate specification recommended by the boiler or pump manufacturer
47 should be used terminating into a suitable internal foul water
Drain
discharge point such as an internal soil and vent stack or internal
kitchen or bathroom waste pipe etc. (fig 3).
137 156 External Drain Connections
The use of an externally run condensate drainage pipe should
only be considered after exhausting all internal termination options
This appliance is fitted with a siphonic 75mm condensate trap as described previously. An external system must terminate at a
system that requires filling before operating the appliance for the suitable foul water discharge point or purpose designed soak away.
1st time or after maintenance. If an external system is chosen then the following measures must
be adopted:
All condensate pipework should conform to the following:
a. Where a new or replacement boiler is being installed, access to The external pipe run should be kept to a minimum using the most
an internal ‘gravity discharge’ termination should be one of the direct and “most vertical” route possible to the discharge point, with
main factors considered in determining boiler location. no horizontal sections in which condensate might collect.
b. Plastic with push fit or solvent connections. - For connections to an external soil/vent stack see Fig 4.
c. Internal plastic pipe work a minimum of 19mm ID (typically Insulation measures as described should be used.
22mm OD) - When a rainwater downpipe is used, an air break must be
d. External plastic pipe must be a minimum of 30mm ID (typically installed between the condensate drainage pipe and the
32 OD) before it passes through the sleeved wall. downpipe to avoid reverse flow of rainwater into the boiler
e. All horizontal pipe runs, must fall a minimum of 45mm per metre should the downpipe become flooded or frozen, see Fig 5.
away from the Boiler. - Where the condensate drain pipe terminates over an open
f. External & unheated pipe work should be kept to a minimum foul drain or gully, the pipe should terminate below the grating
and insulated with Class “O” waterproof pipe insulation. level, but above water level, to minimise “wind chill” at the open
g. All installations must be carried out in accordance to the end. The use of a drain cover (as used to prevent blockage by
relevant connection methods as shown in the “Condensate leaves) may offer further prevention from wind chill. See Fig 6.
installation diagrams” & BS6798:2009 - Where the condensate drain pipe terminates in a purpose
h. Pipe work must be installed so that it does not allow spillage designed soak away (see BS 6798) any above ground
into the dwelling in the event of a blockage (through freezing) condensate drain pipe sections should be run and insulated as
i. All internal burrs should be removed from the pipe work and any described above. See Fig 7
fittings. Unheated Internal Areas
In order to minimise the risk of freezing during prolonged very cold Internal condensate drain pipes run in unheated areas, e.g. lofts
spells, one of the following methods of terminating condensate basements and garages, should be treated as external pipe.
drainage pipe should be adopted. Ensure the customer is aware of the effects created by a frozen
Internal Drain Connections condensate and is shown where this information can be found in
the user manual.
Wherever possible, the condensate drainage pipe should be routed
to drain by gravity to a suitable internal foul water discharge point
such as an internal soil and vent stack or kitchen or bathroom
waste pipe etc. See Figs 1 and 2.
Boiler Boiler
with 75mm with 75mm
sealed sealed
condensate
Soil & vent stack
condensate
trap trap
Min Ø 19mm
Internal soil & vent stack
≥ 100
Sink/basin/
75
Minimum
bath or
connection shower
≥ 450
height up to 3
storeys
continued . . . . .
INSTALLATION
Figure 3 - Connection of a Condensate Pump Typical Figure 4 - Connection of condensate Drainage Pipe to
Method (see manufacturers detailed instructions) External Soil & Vent Stack
Boiler Water/weather
Visible air break with 75mm proof insulation
Boiler sealed
with 75mm condensate
sealed trap
Internal pipe
75
Min Ø 19mm
Internal pipe Minimum
≥ 450
connection
height up to 3
Condensate pump
Boilers without 75mm sealed storeys
(Install in accordance with manufacturers instructions)
condensate trap must be fitted with
a 75mm trap and visible air break
Figure 5 - Connection of a Condensate Drainage Pipe to an Figure 6 - Connection of Condensate Drainage Pipe
External Rainwater Downpipe (only combined foul/rainwater Upstream of a Sink, Basin, Bath or Shower Waste Trap to
drain) External Drain, Gulley or Ranwater Hopper
Boiler Boiler
with 75mm with 75mm
sealed sealed
≥ 100
condensate
condensate Visible air break
trap
Water/ trap at plug hole
weather proof Water/
Min Ø 19mm combined foul/
insulation weather proof
Internal pipe rain water drain Min Ø 19mm
insulation
Internal pipe
Min Ø 30mm External air
Internal pipe break Sink, basin, bath or
≥ 25 Below grate
Minimum 30mm
75
Boiler
with 75mm
sealed
condensate
trap
Min Ø 30mm Water/Weather
Internal pipe proof insulation
Min Ø 19mm
Internal pipe Max 3m external
75
pipework
≥ 25
≥ 300
NOTES.
Ensure all boss blanking plugs are removed before connecting hardware. Each valve must be fitted to the correct boss as shown
in the picture.
Ensure each union is fitted with fibre seals provided.
Do not subject any of the isolating valves to heat as the seals may be damaged.
CH Flow
Note that all isolation
DHW Outlet
handles are shown in the
Gas Supply open postion.
DHW Inlet
CH Return
Black
Handle Yellow
Pressure Relief Valve
Drain Connection
Handle
15mm elbow
or fittings Gas Pressure Safety
Pressure Relief Valve Blue
(not supplied) Drain Pipe Test Point Drain
Handle Valve
Black
Handle
23 ELECTRICAL CONNECTIONS
INSTALLATION
WARNING. This appliance MUST be earthed. Wiring should be 3 core PVC insulated cable, not less than
A mains supply of 230Vac ~ 50 Hz is required. 0.75mm2 (24 x 0.2mm), and to BS 6500 Table 16. For IE
reference should be made to the current ETCI rules for electrical
The fuse rating should be 3A. All external controls and wiring
installations.
must be suitable for mains voltage.
Connection must be made in a way that allows complete isolation
Wiring external to the boiler MUST be in accordance with the
of the electrical supply such as a double pole switch having
current I.E.E. (BS.7671) Wiring Regulations and any local
a 3mm (1/8”) contact separation in both poles. The means of
regulations.
isolation must be accessible to the user after installation.
24 INTERNAL WIRING 2
A mains cable must be connected to a permanent live supply and NOT switched by
thermostats/programmers. To do so follow the instructions below:
1. Swing the lower front panel down. Refer to Frame 33.
2. Route cable through the grommet and cable clamp and tighten to provide cord anchorage.
3. Connect the live, neutral and earth wires to the terminal strip. When making the mains
electrical connections to the boiler it is important that the wires are prepared in such a
way that the earth conductor is longer than the current carrying conductors, such that if
the cord anchorage should slip, the current carrying conductors become taut before the
earthing conductor.
4. Swing the control box back up into the operating position and retain with the screws
previously removed.
The boiler comes pre-fitted with a link wire between the room thermostat/Timer
connections on the terminal strip. This creates a permanent call for heat
and must be removed when adding a room thermostat.
ROOM THERMOSTAT - WIRING
1. Remove link wire between Room stat/timer terminals. Optional
2. Connect room stat as shown in wiring diagram opposite. Frost Stat
30
KEY
b - blue
bk - black
br - brown
r - red PCB
p - pink
y - yellow
w - white
y/g - yellow/green
g - grey
or - orange
v - violet
26 WIRING DIAGRAM
11 10 9 8 7 6 5 4 3 2 1 6 5 4 3 2 1 4 3 2 1 5 4 3 2 1 3 2 1 9 8 7 6 5 4 3 2 1 5 4 3 2 1 6 5 4 3 2 1
y/g
b
br
bk y/g
y bk
b
bk p
bk bk bk bk y/g
p bk b
r or r br
b r
b r
bk
INSTALLATION
y/g Spark
Generator Earth Room Main Frost
bk b br bk
bk y/g Stat Supply Stat
b p y bk b b br b bk
Flame b br r bk
Water Water Flow Return y/g
Sensor y/g
Flow pressure Thermistor Thermistor 1 2 3 4
Electrode
Turbine Switch Fan
bk
Pump
Spark TIMER
Service Electrode Gas Divertor
Connector Valve Valve p bk
y
INSTALLATION
A. Electrical Installation B. Gas Installation
1. Checks to ensure electrical safety should be carried out by a 1. The whole of the gas installation, including the meter,
competent person. should be inspected and tested for tightness and purged in
accordance with the recommendations of BS. 6891.
2. ALWAYS carry out the preliminary electrical system checks,
In IE refer to IS.813:2002.
i.e. earth continuity, polarity, resistance to earth and short
circuit, using a suitable test meter. 2. Purge air from the gas installation by the approved methods
only.
3. After wiring the boiler, all grommets in the bottom panel
MUST be in place to ensure that the boiler case sealing is
maintained.
WARNING. Whilst effecting the required gas tightness test and purging air from the gas installation,
open all windows and doors, extinguish naked lights and DO NOT SMOKE.
GENERAL
Please Note: The combustion for this appliance has
been checked, adjusted and preset at the factory for
operation on the gas type defined on the appliance
data plate. DO NOT adjust the air/gas ratio valve.
Having checked:
- That the boiler has been installed in accordance
with these instructions.
- The integrity of the flue system and the flue seals,
as described in the Flue Installation section.
Proceed to put the boiler into operation as follows:
CHECK THE OPERATIONAL (WORKING) GAS
INLET PRESSURE
CH Flow
Set up the boiler to operate at maximum rate by
DHW flow.
opening hot tap to maximum Outlet
With the boiler operating in
the maximum rate condition Gas Supply
check that the operational
(working) gas pressure at DHW Inlet
the inlet gas pressure test
CH Return
point complies with the
requirements - refer to “Gas
Black
Supply” on page 10.
Handle Yellow
Ensure that this inlet pressure
Handle
can be obtained with all other
gas appliances in the property
working. Gas Pressure Safety
Test Point Blue Drain
Handle Valve
Black
Handle
3G9927
As part of the commissioning process, the combustion of this appliance must be checked
and the Benchmark Checklist completed. A flow chart to assist is provided on page 65.
ATTENTION !
IT IS A CONDITION OF THE MANUFACTURERS WARRANTY THAT THE
BENCHMARK COMMISSIONING CHECKLIST IS FULLY COMPLETED
AND LEFT WITH THE APPLIANCE
E
Legend
A. Mode Control Knob off e
status burner
max
B. DHW/Preheat Control
C. CH Control
D. Boiler Status mode
reset min preheat min max preheat
H. Pressure Gauge 21 7
16
22
I 0
15
23
J. Gas Inlet Pressure Test Point
14 13 12 1
24
H
Classic
1
K. Gas Service Cock
2
3
1
10
L
4
M
7
3. Check that the drain cock is closed and that the CH and DHW isolating Permanently OFF
valves (M, L and G) are OPEN.
4. Check that the electrical supply is OFF. 20 19 18 1
21 7
16
5. Check that the boiler mode control knob (A) is off.
22
15
23
6. Check that the gas service cock (K) is OPEN.
1 4 13 1 2 1
24
7. Slacken the screw in the inlet pressure test point (J) and connect a
1
gas pressure gauge via a flexible tube.
2
8. Switch electricity supply ON & check mechanical timer is in “Permanently
1
10
4
On” position. 5 9
6 7 8
CENTRAL HEATING
9. Set the CH temp control (C) to max and turn the mode control knob (A) to
. The boiler control should now go through its ignition sequence until THE DISPLAY
the burner is established. The user control has one neon and one display to
10. If the boiler does not light code will be displayed. After 5 attempts inform the user about the status. The display will
the boiler will lock out and display fault code constantly. Reset the show the status of the boiler. The neon will show
boiler (Refer to Frame 30). The boiler will repeat its ignition sequence. If the status of the flame. If no flame is detected the
reset occurs 5 times within 15 minutes then will be shown. If power is neon is off. When the flame is detected the neon
removed this will be reset. will be lit permanently.
When the burner is established the BLUE ‘Burner On’ neon (E) will be Below is a list with display function in normal
illuminated, the LED display (D) will show status . operation.
DOMESTIC HOT WATER Standby, no demand for heat present.
11. With the boiler firing, set the DHW Temp Control knob (B) to maximum Boiler is active for central heating.
and fully open a DHW tap.
Boiler is active for domestic hot water.
The boiler should continue to run and the LED display (D) should show
status Boiler is heating up the plate heat exchanger.
12. Ensure that with the boiler operating the dynamic gas pressure is able to Boiler is active for boiler frost protection.
obtain maximum output. Refer to Table 2.
Boiler is in lockout for a specific error. Display
IMPORTANT - The gas input to the burner is regulated by the gas valve will be blinking, alternating with a number or
according to the air flow produced by the fan. It is NOT user-adjustable. letter to show which error is detected.
Any interference to sealed settings on the gas valve will adversely
Boiler has a fault for a specific error. Display
affect operation and render our warranty void.
will be blinking, alternating with a number or
For additional gas supply info refer to “Gas Supply” on page 10. letter to show which error is detected.
13. Turn off the DHW tap.
Note: Boiler frost protection - boiler fires if
14. To turn on the DHW pre heat facility, turn the DHW knob (B) fully temperature is below 5 degrees C.
clockwise and then back to the desired setting, a decimal point (F) will
appear in the boiler status window indicating pre heat ‘ON’.
15. To turn off the pre heat facility, turn the DHW knob (B) fully clockwise and Note. The boiler incorporates a fan overrun cycle
then back to the desired setting, the decimal point (F) will disappear in the which MUST NOT be prematurely interrupted by
boiler status window indicating pre heat ‘OFF’. isolation of the mains electricity supply.
29 GENERAL CHECKS
INSTALLATION
Make the following checks for correct operation in: WATER CIRCULATION SYSTEM
DOMESTIC HOT WATER (DHW) MODE 1. With the system COLD, check that the initial pressure
1. Fully open all DHW taps in turn and ensure that water flows is correct to the system design requirements.
freely from them. For pre-pressurised systems, this should be 1.0 bar.
The display should read: 2. With the system HOT, examine all water connections
for soundness. The system pressure will increase with
temperature rise but should not exceed 2.5 bar.
then:
when the burner lights. 3. With the system still hot, turn off the gas, water and
electricity supplies to the boiler and drain down to
2. Close all taps except the furthest one from the boiler and check
complete the flushing process.
that the boiler is firing at maximum rate.
Note: A flushing solution should be used during the
This is factory set to give a DHW temperature rise of flushing procedure. Flushing solutions: Fernox
approximately 35oC at the flow rate stated on page 8 under Superfloc, Sentinel X300 (new systems) or X400
“operation”. (existing systems). Refer to Frame 4.
3. Reduce the DHW draw-off rate to about 3 l/min (0.7gpm) and 4. Refill and vent the system, add inhibitor (see Frame
check that the boiler modulates to deliver DHW at approximately 4), clear all air locks and again check for water
64oC. soundness.
4. Close the DHW tap and check that the main burner extinguishes. 5. Reset the system initial pressure to the design
The pump should overrun for 60 seconds and the display requirement.
sequence should read: 6. Balance the system. Refer to Frame 3.
7. Check the condensate drain for leaks and check that it
When the pump stops the display sequence should read: is discharging correctly.
8. Finally, set the controls to the User’s requirements.
Note. On systems in excess of 2 bar inlet pressure a water Note: The pump will operate briefly as a self-check
pressure governor may be required to prevent water noise. once every 24 hours in the absence of any system
demand.
CENTRAL HEATING (CH)
& DOMESTIC HOT WATER (DHW) MODE.
5. Set the central heating external controls to OFF. The burner Due to system variations and seasonal temperature
should go off and the pump continue to run for four minutes fluctuations DHW flow rates/temperature rise will vary, requiring
The display should read: adjustment at the draw off tap : the lower the rate the higher the
temperature, and vice versa.
6. Check the correct operation of the timer and all other system
controls. Operate each control separately and check that the
main burner responds.
To reset the boiler, turn the mode control (A) to the reset position and immediately turn the knob back to the required setting.
The boiler will repeat the ignition sequence if a heat demand is present.
30
E
A B C D F
20 19 18 1
21 7
16
22
I 0
15
23
14 13 12 1
24
Classic
1
2
Legend
1
10
4
5 9
6 7 8
31 HANDING OVER
After completing the installation and commissioning of the system the installer should hand over to the householder by
the following actions:
1. Hand the User Instructions to the householder and 7. Draw attention to the timer Users Instructions and hand them
explain his/her responsibilities under the relevant national to the householder.
regulations.
8. Loss of system water pressure
2. Explain and demonstrate the lighting and shutting down
Explain that the dial underneath the boiler indicates the
procedures.
central heating system pressure and that if the normal
3. The operation of the boiler and the use and adjustment of all COLD pressure of the system is seen to decrease over a
system controls should be fully explained to the householder, period of time then a water leak is indicated. Explain the re-
to ensure the greatest possible fuel economy consistent with pressurising procedure and if unable to re-pressurise or if the
the household requirements of both heating and hot water pressure continues to drop a registered local heating installer
consumption. should be consulted.
Advise the User of the precautions necessary to prevent 9. Explain Boiler reset procedure.
damage to the system and to the building, in the event of the
10. After installation and commissioning please complete
system remaining inoperative during frosty conditions.
4. Explain the function and the use of the boiler heating and
domestic hot water controls. the Commissioning Checklist before
Explain that due to system variations and seasonal handover to the customer. For IE, its is necessary to
temperature fluctuations DHW flow rates/temperature complete a “Declaration of Conformity” to indicate compliance
rise will vary, requiring adjustment at the draw off tap. It to I.S. 813:2002.
is therefore necessary to draw the users attention to the IMPORTANT
section in the Users Instructions titled “Control of Water
Temperature” and the following statement: 11. A comprehensive service should be carried out ANNUALLY.
“Additionally, the temperature can be controlled by the Stress the importance of regular servicing by a Gas Safe
user via the draw-off tap: the lower the rate the higher Registered Engineer. In IE servicing work must be carried out
the temperature, and vice versa”. by a Registered Gas Installer (RGII).
5. Explain the function of the boiler fault mode. 12. Inform the householder of the guarantee/registration found
within the envelope pack and the requirement to register it to
Emphasise that if a fault is indicated refer to “Fault Codes” in
receive the full benefit of the warranty.
the User Guide.
6. Explain and demonstrate the function of time and
temperature controls, radiator valves etc., for the economic
use of the system.
INSPECTION GENERAL
1. Light the boiler and carry out a pre-service check, noting any Please Note: During routine servicing, and after any
operational faults. maintenance or change of part of the combustion
2. Check the flue terminal (and terminal guard if fitted) is undamaged circuit, the following must be checked:
and clear of any obstruction. - The integrity of the flue system and the flue seals,
3. Check all water and gas joints for signs of leakage. Remake any - The integrity of the boiler combustion circuit and
suspect joints ensuring a gas tightness check is carried out if the relevant seals
applicable and the water system is correctly refilled, vented and - The operational (working) gas inlet pressure at
re-pressurised. maximum rate.
CLEANING PROCEDURE - The gas rate
Note. In order to carry out either servicing or replacement of - The combustion performance.
components the boiler upper and lower front panels must be
removed. Refer to Frame 33. COMPETENCE TO CARRY OUT THE CHECK
SERVICING
1. Clean the main burner. Refer to frame 35. OF COMBUSTION PERFORMANCE
Please Note: BS 6798:2009 Specification for
2. Clean the heat exchanger & condensate trap/siphon. Refer to
installation and maintenance of gas-fired boilers of
Frames 36 & 37.
rated input not exceeding 70kW net advises that:
3. Check the main injector for blockage or damage. Refer to Frame
- The person carrying out a combustion
41.
measurement should have been assessed as
4. Check that the flue terminal is unobstructed and that the flue system competent in the use of a flue gas analyser and the
is sealed correctly. interpretation of the results.
ALSO IF THE DHW FLOW RATE IS IN QUESTION :- - The flue gas analyser used should be one meeting
the requirements of BS7927 or BS-EN50379-3
5. Check the DHW filter for blockage. Refer to Frame 61. and be calibrated in accordance with the analyser
The cleaning procedures are covered more fully in Frames 34-38 and manufacturers requirements, and
MUST be carried out in sequence. - Competence can be demonstrated by satisfactory
IMPORTANT. completion of the CPA1 ACS assessment, which
6. After completing the servicing or exchange of components always covers the use of electronic portable combustion
ensure all gas valve connections are gas tight with a gas soundness gas analysers in accordance with BS7967, Parts 1
check up to the gas control valve. to 4.
REMOVAL REPLACEMENT
1. Lift the lower front panel access panel. 4. Hook the upper panel onto the top retaining clips.
2. Unscrew the two fixing screws, close the access panel to 5. Retain the upper panel with the two fixing screws previously
retain the two screws and hinge the lower front panel down removed ensuring a good seal is made.
into the service position.
6. Swing the lower front panel up and retain with the two
3. Remove the two upper front panel fixing screws, lift the screws.
panel and remove.
7. Close the lower front panel access panel.
2&6 3&5
1&7
SERVICING
Injector
SERVICING
4
1
Note: Ensure the condensate trap/siphon
is fully drained before cleaning. Refer to Ignition Electrode Flame Detection
Frame 48.
1. Remove ignition and flame detection
electrodes. Refer to Frames 43 & 44.
2. It is advisable to replace the sump cover
prior to the water flush process.
3. Thoroughly flush the heat exchanger
by pouring water into the top of the
combustion chamber ensuring the full top
area is covered.
4. Remove the sump cover and clean loose
deposits from the sump.
Earth Wire
5. Inspect the ignition and detection 3
electrodes. Ensure that they are clean
and in good condition - replace if
necessary.
6. Re-fit the ignition and flame detection
SERVICING
38 REASSEMBLY
Reassemble the boiler in the following order:
1. Ensure that the condensate trap/siphon is full of water. 6. Refit the sump cover.
2. Refit the burner ensuring the sealing gasket is correctly 7. Refit the boiler upper and lower front panels.
positioned and free from damage (tighten the 4 fixing screws
in the sequence A,B,C,D, shown below). IMPORTANT. Ensure that the boiler upper front panel is
correctly fitted and that a good seal is made.
3. Refit the fan / venturi assembly ensuring the retaining tabs
are correctly positioned and the sealing gasket is correctly 8. Turn on the gas supply at the gas service cock.
positioned and free from damage. 9. Reconnect the electrical supply.
4. Reconnect the fan electrical leads.
5. Remove the sump cover and refit the lower flue manifold as
shown.
D
B
A
C
GENERAL IMPORTANT.
When replacing ANY component Ensure all gas valve connections are gas tight with a gas
soundness check up to the gas control valve.
1. Isolate the electricity supply.
When work is complete, the front panels must be correctly
2. Turn off the gas supply. refitted - ensuring that a good seal is made.
3. Remove the lower front panel fixing screws, swing the panel Notes.
into the servicing position and remove the upper front panel. 1. In order to assist fault finding, the control panel has an
Refer to Frame 33. LED diagnostic display.
2. In order to replace components in Frames 53-65 it is
After replacing ANY component check operation of the boiler, necessary to drain the boiler. Refer to Frame 52.
including gas soundness, gas rate and combustion test.
THE BOILER MUST NOT BE OPERATED WITHOUT THE FRONT PANEL FITTED
SERVICING
40 FAN REPLACEMENT
3
10. Check operation of the boiler. Refer to
Frames 28 & 29.
42 BURNER REPLACEMENT
1. See Frame 39.
4
2. Remove Fan. Refer to Frame 40.
3. Undo the two screws and remove the sump cover. 3 3
4. Lift the manifold to clear the bottom sealing gasket and remove
manifold.
5. Remove the 2 front fixing screws and loosen the 2 rear
extended nuts.
6. Lift off the burner from the combustion chamber. To facilitate
the removal angle the burner as shown.
7. Fit the new burner, replacing any damaged or deteriorating
sealing gasket.
8. Reassemble in reverse order.
5
9. Check the operation of the boiler. Refer to Frames 28 & 29.
ge
t ed
Spark Gap h
aig
3.5mm Str
m
3m
SERVICING
44 FLAME DETECTION ELECTRODE REPLACEMENT
1. Refer to Frame 39.
2. Remove the burner. Refer to Frame 42.
3. Unplug the flame detection lead from the
electrode. Flame Detection Electrode
4. Remove the 2 screws retaining the detection
electrode.
5. Remove the electrode.
6. Fit the new flame detection electrode, using the
new gasket supplied.
7. Reassemble in reverse order.
8. Check the operation of the boiler. Refer to
Frames 28 & 29.
ge
t ed
h
aig
Str
m m
1 2.5
SERVICING
position.
e. The divertor valve will initially drive all the
way out, this may cause the spindle to
become detached from the body. If this
occurs simply screw back into the body so
the cycle can continue driving fully in before
going to mid-position.
f. Replace the actuator into the boiler.
6
6. Fit the new motor ensuring the arm is correctly
engaged in the metal fork and re-assemble in
reverse order ensuring the condensate trap/
siphon is refilled with water.
7. Check the operation of the boiler. Refer to Frames
28 & 29.
Note. All spares will be delivered in mid-position
therefore ignore point 5 and proceed to point 6 after
re-connecting the inline connector.
upwards to clear the retaining posts. b. Displays “8” blue light on/off, “first digit input”, “second
7. Take the new Primary PCB and attach the appropriate digit input”, “1st letter appliance type”, i.e. “2”, “4”, “c”
Boiler Chip Card (BCC) to it (this should correspond to c. Move knob to required setting (standby, summer,
the output of the boiler: 24kW, 30kW or 35kW). winter)
Note. Ensure the correct orientation of BCC by placing Note. If no BCC fitted on non programmed board “C2” will
“TOP” side up. be displayed. The correct BCC for this appliance will need
to be fitted.
8. Re-connect all plug connections.
11. Check operation of the boiler. Refer to Frames 28 & 29.
9. Reassemble in reverse order.
Plastic
Clip 5 5
6
PCB
SERVICING
Potentiometer spindle
20 19 18 1
21 7
16
22
I 0
15
23
14 13 12 1
24
1
10
4
5 9
6 7 8
4
1. Refer to Frame 39.
2. Swing the boiler lower front panel into the service
position. Refer to Frame 33.
3. Remove the 4 fixing screws.
4. Disconnect the 4 push on connectors.
5. Remove programmer.
6. Re-fit 4 push on connectors to new programmer.
7. Fit programmer and retain with 4 screws previously
removed. 3
8. Replace the lower front panel.
9. Check operation of the boiler. Refer to Frames 28 &
29.
Note. To program refer to user guide at rear of this
book.
9960
CH
Gas DHW Circuit
DOMESTIC HOT WATER CIRCUIT CH DHW Inlet Drain
Flow CH
1. Refer to Frame 39. Outlet
Return
2. Close the DHW water isolating valve on the boiler inlet.
3. To drain the domestic hot water circuit: As there is no direct drain for the domestic hot water circuit, depending on the
location of the boiler, opening the lowest hot water tap may drain this circuit. However it must be noted that some residual
water will be experienced during replacement of components.
SERVICING
4. After replacing any component on the boiler, close tap, close the drain valve and open all system isolating valves (re-
pressurise as appropriate)
5. Check operation of the boiler. Refer to Frames 28 & 29.
SERVICING
boiler. Refer to Frames 28 & 29.
SERVICING
2. Drain the boiler. Refer to frame 52.
3. Turn the housing anti clockwise and pull
forward to remove the cartridge.
3
4. Using a pair of pliers, pull out the plastic
filter/flow regulator.
5. Clean or replace filter as necessary.
6. Reassemble in reverse order.
7. Refill the boiler.
4
8. Check operation of the boiler. Refer to
Frames 28 & 29.
1. Refer to Frame 39. 14. Remove the two heat exchanger fixing screws.
2. Drain the boiler. Refer to Frame 52. 15. To remove the Heat exchanger slide out of location bracket.
SERVICING
3. Remove the fan / venturi assembly and place on one side. 16. If replacement sump required: Rotate heat exchanger
Refer to Frame 40. assembly 180º. Place new sump onto heat exchanger,
4. Remove burner and place on one side. Refer to Frame 42. ensuring correct orientation and seal is in place. Then
gently apply pressure to the base of the sump at each tab
5. Remove the ignition and detection electrodes. Refer to
fixing point and engage tabs onto the heat exchanger.
Frames 43 & 44.
17. Reassemble in reverse order, ensuring the heat exchanger LH
6. Remove the spark generator. Refer to Frame 45.
retaining bracket is correctly positioned. Replace any new ‘o’
7. Remove the gas valve. Refer to Frame 46. rings supplied with new heat exchanger and replacing gaskets
8. Remove the expansion vessel. Refer to Frame 65. or seals if any sign of damage is evident. When replacing the
9. Remove the flow thermistor. Refer to Frame 62. spring clips located on the return pipe connection, ensure clip
is oriented to correctly match connecting pipe diameters.
10. Remove the 2 M5 screws retaining the gas valve mounting
bracket and transfer bracket to the new heat exchanger. 18. Ensure the trap/siphon is filled with water. Refer to Frame
48.
11. Undo the inlet pipe union nut, swing the pipe and pull down
to remove from heat exchanger. 19. Refill the boiler.
12. Pull out the flow pipe spring clip, pull the pipe down to 20. Ensure all gas valve connections are gas tight with a gas
remove from heat exchanger. soundness check up to the gas control valve.
13. Remove the condensate rubber pipe from the sump. 21. Check operation of the boiler. Refer to Frames 28 & 29.
14
10
13 11
12
16
SERVICING
14. Check operation of the boiler. Refer to Frames 28
& 29.
Is the Boiler and CH System filled with water and all NO Fill and vent the system and open all
isolation and radiator valves open? isolation valves, then reset boiler
YES
Is the Flow/Return Differential across the Boiler in YES Check that the Pump is rotating freely. Is
excess of 30°C? the Differential now below 20°C?
NO NO YES
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
If the boiler is reset does the boiler NO Is the Gas Pressure available at NO Check gas supply and
ignite for a short time and then the Boiler Inlet (>18 mbar)? rectify fault
extinguish?
YES
YES
Replace Ignition
Check siphon and condensate Check ignition electrode and NO
YES Electrode and
drain pipe work for blockage and associated harness for: continuity,
associated harness as
rectify if necessary. Boiler now visual condition and position.
necessary
working OK? (Refer to Frame 43) Are these
functioning correctly?
NO
* Note: due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to measure the
value. In general terms a reading greater than 150V indicates that the correct voltage is supplied to the gas valve.
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
Turn power off and on
NO
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
Are the Boiler and CH System filled with water and NO Fill and vent the system and open all
all isolation and radiator valves open (check pressure isolation valves
gauge is between 1 to 1.5 bar)?
YES
NO
Are connections on water pressure switch secure? Re-fit connections
YES
Does the boiler ignite for a short NO Is the Gas Pressure available at NO Check gas supply and
time and then extinguish? the Boiler Inlet (18 mbar)? rectify fault
YES YES
* Note: due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to measure the
value. In general terms a reading greater than 150V indicates that the correct voltage is supplied to the gas valve.
YES
NO
Replace PCB
Is there 230Vac at the Blue and Brown connections
to the 3 way connection on the Fan? YES
Replace Fan
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
Check the resistance using a suitable multimeter NO
connected across the thermistor’s terminal pins. Fit a new Thermistor
At 25 oC expect 9,700 - 10,300 Ohms
At 60 C expect
o
2,400 - 2,600 Ohms
At 85 oC expect 1,000 - 1,100 Ohms
YES Is there continuity between the PCB and
Is the Thermistor value correct? the Thermistor?
NO YES
NO YES
Replace PCB -
Ensure that the BCC (boiler chip card - small plastic part) is
fitted to the PCB otherwise replace PCB.
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
Is the correct BCC for the boiler securely inserted into the NO Securely insert the correct BCC for the boiler
slot at the front left of the PCB? into the PCB and after switching power on and
(identified by the label on the BCC) ‘c0’ being shown, reset boiler.
Note. Ensure the correct orientation of BCC by
YES
placing “TOP” side up.
Replace the BCC with a new BCC (that is correct for the
boiler). After switching power on and ‘c0’ being shown, YES
press reset. Is ‘c2’ still shown? Replace PCB
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
Reset Boiler
RESET PROCEDURE - To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.
NO
Is the mode knob in the Winter position? Move the mode knob to the Winter position
YES
YES
NO
Are the Radiator Valves Open? Open the Radiator Valves
YES
82 NO HW BUT CH ON
NO
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
Does the display show “d” when a tap is on? Is hot and cold pipework crossed?
YES
NO
Are the flow rates correct as per Frame 2. Adjust flow rates to achieve 35º
temp rise and check filter fitted in
YES turbine is not blocked with debris.
NO
83 NO DISPLAY
YES
Is the wiring from the terminal block to the Main PCB NO Connect the wiring from the terminal block to the
connected securely? Main PCB securely.
YES
Is the ribbon cable from the main PCB to the User NO Connect the ribbon from the main PCB to the User
Interface PCB connected securely? Interface PCB securely
YES
NO Replace the
Is ribbon cable damaged? User Interface
PCB
YES
L N
Comprehensive spares parts information and details of approved Ideal Parts Distributors are available on www.idealparts.com
Our Parts team are also available to help with your Spare Parts enquiries on 01482 498665.
When calling, and to ensure we can provide you with the most accurate parts information, please ensure you have the following to
hand;
- Boiler Model
- Appliance GC Number
- Boiler Serial Number
IMPORTANT NOTE.
Propane Boilers - After installation of a conversion kit, and when ordering future spares be sure to quote the serial letter code AAV -
which indicates a Propane boiler - and the boilers original serial letter code from the original data plate.
To instigate the boiler guarantee the boiler needs to be registered with the
manufacturer within one month of the installation.
To maintain the boiler guarantee it is essential that the boiler is serviced annually
by a Gas Safe registered engineer who has been trained on the boiler installed.
The service details should be recorded on the Benchmark Service Interval
Record and left with the householder.
www.centralheating.co.uk
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
CONTROLS
Programmable room thermostat
Optimum start control
Combination Boiler
Fitted
Fitted
Fitted
Automatic bypass to system Fitted
Boiler interlock
ALL SYSTEMS
Yes
Yes
ALL INSTALLATIONS
AND ² Ratio
AND ² Ratio
Yes
Yes
Yes
Yes
* Allinstallations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
www.centralheating.co.uk
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
SERVICE 01 SERVICE 02
AND ²% AND ²%
(Where Possible) AND ²% (Where Possible) AND ²%
Signature Signature
SERVICE 03 SERVICE 04
AND ²% AND ²%
(Where Possible) AND ²% (Where Possible) AND ²%
Signature Signature
SERVICE 05 SERVICE 06
AND ²% AND ²%
(Where Possible) AND ²% (Where Possible) AND ²%
Signature Signature
SERVICE 07 SERVICE 08
AND ²% AND ²%
(Where Possible) AND ²% (Where Possible) AND ²%
Signature Signature
SERVICE 09 SERVICE 10
AND ²% AND ²%
(Where Possible) AND ²% (Where Possible) AND ²%
Signature Signature
* Allinstallations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
KEY:
CO = carbon monoxide
CO2 = carbon dioxide
O2 = oxygen
Combustion Ratio = The CO reading measured in ppm divided by the CO2 reading first converted to ppm
ppm = parts per million
GS(I&U)R = Gas Safety (Installation and Use) Regulations
Set Boiler to Maximum Gas Rate Carry Out Flue Integrity Check Using Analyser
In accordance with boiler instructions, Insert analyser probe into air inlet test point (where available) and allow
set boiler to operate at maximum rate readings to stabilise.
(full load condition). Allow sufficient Note. Where no air inlet test point is provided then a flue integrity check with
time for combustion to stabilise. the analyser is not possible. The installer should verify that flue integrity has
Note. Do not insert analyser probe been visually checked in accordance with the “Prior to CO level and
during this period to avoid possible combustion ratio check” (see opposite page) before proceeding to the
flooding of sensor. “check CO level and combustion ratio at maximum rate” stage below.
Yes
Turn off appliance and call Ideal Technical Helpline for advice
The appliance must not be commissioned until problems are identified Is
and resolved. If commissioning cannot be fully completed, the appliance CO level less
No than 350ppm AND CO/CO2
must be disconnected from the gas supply in accordance with GSIUR.
ratio less than
0.0040?
Technical Training
The Ideal Technical Training Centre offers a series of first class training courses for domestic, commercial and
industrial heating installers, engineers and system specifiers.
For details of courses please ring:............ 01482 498432
Ideal Boilers Ltd. pursues a policy of continuing improvement in the design and performance of its products.
The right is therefore reserved to vary specification without notice.
Ideal Boilers Ltd., PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN
Tel 01482 492251 Fax 01482 448858
Registration No. London 322 137