EREC-43 Load Schedule

This document provides details for a planned office building project including connected loads, maximum demand, and metering. It summarizes that the total connected load per phase is 703.41 kW, 696.39 kW, and 704.65 kW, for a total of 2104.45 kW. The maximum demand is estimated at 1894.01 kW. The building will have a total built-up area and will be metered by two 2400/5A CT meters.

Uploaded by

Partha Sundar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views61 pages

EREC-43 Load Schedule

This document provides details for a planned office building project including connected loads, maximum demand, and metering. It summarizes that the total connected load per phase is 703.41 kW, 696.39 kW, and 704.65 kW, for a total of 2104.45 kW. The maximum demand is estimated at 1894.01 kW. The building will have a total built-up area and will be metered by two 2400/5A CT meters.

Uploaded by

Partha Sundar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 61

PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR

DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

MDB-01 & MBD-02 FEED FROM DEWA (TX-01 &TX-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION OF MDB: BASEMENT-1 FLOOR LV.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

703.41 696.39 704.65 2104.45 1894.01

OUTGOING:

2500
MDB-01 4P 65 BY DEWA 2x1Cx150 294.31 293.76 293.55 881.61 793.45 1 2400/5A CT METER
Set @0.85

2500
MDB-02 4P 65 BY DEWA 2x1Cx150 409.11 402.63 411.11 1222.84 1100.56 1 2400/5A CT METER
Set @0.85

SUMMARY OF THIS PROJECT TOTAL CONNECTED LOAD PER


703.41 696.39 704.65 2104.45 1894.01 2 TOTAL
PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 2104.45 kW
STAND BY LOAD : 18.50 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 1894.01 kW * OVERALL /INSTALLED LOAD (TCL): 2085.95 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

MDB-01 FEED FROM DEWA (TX-01) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-1 FLOOR LV.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
ECC LENGTH (KW) CONNECTED/ kWh METERS
CIRCUIT/ FEEDER MCCB/ FAULT NO. OF CORES OPERATIONA
SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
SMDB/ TP DUTY LOAD
TYPE 1C, CABLE (TCL) * LV/
DB NO. RATING kA NO. OF
XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

2500
INCOMER 4P 65 BY DEWA 2x1Cx150 294.31 293.76 293.55 793.45 1 2400/5A CT METER
Set @0.85
881.61
MOBILE GENERATOR 2500 MOBILE GENERATOR
4P 65
INCOMER Set @0.85 PROVISION

OUTGOING:

REDUCED VOLTAGE SOFT


MCC-CH TP 1600 50 1600A BUSBAR TPN+E 246.48 246.48 246.48 739.43 665.49 STARTER / (ELR + SHUNT
TRIP)

SMDB-RF TP 300 50 1x4C CU/XLPE/SWA/LSZH 185 1x1Cx95 47.33 46.58 46.57 140.48 126.43

DB-SS TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 0.25 0.40 0.25 0.90 0.81

DB-RMU TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 0.25 0.30 0.25 0.80 0.72

10 STEP 400 KVAR


CAPACITOR BANK TP 1000 50 3x4C CU/XLPE/SWA/LSZH 240 3x1Cx120 CAPACITOR BANK
PROTECTED BY HRC FUSES

MDB-01 CONNECTED TO DEWA (1500 KVA TX-01) TOTAL CONNECTED LOAD PER
294.31 293.76 293.55 881.61 793.45 1 TOTAL
PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 881.61 kW
STAND BY LOAD : 18.50 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 793.45 kW * OVERALL /INSTALLED LOAD (TCL): 863.11 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

MDB-02 FEED FROM DEWA (TX-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-1 FLOOR LV.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
ECC LENGTH (KW) CONNECTED/ kWh METERS
CIRCUIT/ FEEDER MCCB/ FAULT NO. OF CORES OPERATIONA
SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
SMDB/ TP DUTY LOAD
TYPE 1C, CABLE (TCL) * LV/
DB NO. RATING kA NO. OF
XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

2500
INCOMER 4P 65 BY DEWA 2x1Cx150 409.11 402.63 411.11 1100.56 1 2400/5A CT METER
Set @0.85
1222.84
MOBILE GENERATOR 2500 MOBILE GENERATOR
4P 65
INCOMER Set @0.85 PROVISION

OUTGOING:

FIRE PUMP TP 300 50 1x4C CU/XLPE/SWA/LSZH 185 1x1Cx95 50.00 50.00 50.00 150.00 135.00 100mA ELS+ALARM+STARTER

SMDB-1ST TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 36.57 35.25 36.71 108.52 97.67

SMDB-2ND TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 33.88 32.15 32.73 98.76 88.89

SMDB-3RD TP 200 50 1x4C CU/XLPE/SWA/LSZH 95 1x1Cx50 28.12 28.36 28.26 84.73 76.26

SMDB-4TH TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 33.40 33.45 32.52 99.36 89.43

MICA GLASS-
EMDB 4P 1250 50 3x4C 300 3x1Cx150 166.76 163.37 166.70 496.83 447.15
XLPE/LSZH/SWA

SMDB-GF TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 38.64 38.12 39.37 116.13 104.51

AC COLLECTION
TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 PV SOLAR SYSTEM
BOARD (PROVISION)

SMDB-B1 TP 160 50 1x4C CU/XLPE/SWA/LSZH 70 1x1Cx35 21.74 21.94 24.82 68.50 61.65

10 STEP 400 KVAR CAPACITOR


CAPACITOR BANK TP 1000 50 3x4C CU/XLPE/SWA/LSZH 240 3x1Cx120 BANK PROTECTED BY HRC
FUSES
MDB-02 CONNECTED TO DEWA (1500 KVA TX-02) TOTAL CONNECTED LOAD PER
409.11 402.63 411.11 1222.84 1100.56 1 TOTAL
PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 1222.84 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 1100.56 kW * OVERALL /INSTALLED LOAD (TCL): 1222.84 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

EMDB FEED FROM MDB-02 / GEN-P-G LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-1 FLOOR (ELE.ROOM B01-17)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MDB-02 MICA GLASS-


4P 1250 50 3x4C 300 3x1Cx150 166.76 163.37 166.70 496.83 447.15
INCOMER XLPE/LSZH/SWA

GENERATOR MICA GLASS-


4P 1250 50 3x4C 300 3x1Cx150
INCOMER XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
ESMDB-B3 TP 200 50 1x4C 150 1x1Cx70 25.62 25.47 25.42 76.50 68.85
XLPE/LSZH/SWA
MICA GLASS-
ESMDB-B2 TP 125 50 1x4C 70 1x1Cx35 18.10 17.35 17.35 52.80 47.52
XLPE/LSZH/SWA
MICA GLASS-
ESMDB-B1 TP 160 50 1x4C 95 1x1Cx50 24.15 24.05 24.45 72.65 65.38
XLPE/LSZH/SWA
ESMDB-DATA MICA GLASS-
TP 350 50 1x4C 240 1x1Cx120 44.73 42.73 44.73 132.20 118.98
CENTER XLPE/LSZH/SWA
MICA GLASS-
ESMDB-RF TP 40 50 1x4C 10 1x1Cx10 5.88 5.73 5.73 17.35 15.62
XLPE/LSZH/SWA
MICA GLASS-
ESMDB-GF TP 125 50 1x4C 50 1x1Cx25 18.62 18.18 19.26 56.06 50.45
XLPE/LSZH/SWA
ESMDB-UPS- MICA GLASS-
TP 80 50 1x4C 25 1x1Cx16 10.96 11.16 11.06 33.17 29.85
CCTV XLPE/LSZH/SWA
MICA GLASS-
ESMDB-LIFT TP 125 50 1x4C 70 1x1Cx35 18.70 18.70 18.70 56.11 50.50
XLPE/LSZH/SWA

MDB-02 CONNECTED TO DEWA TOTAL CONNECTED LOAD PER


166.76 163.37 166.70 496.83 447.15 TOTAL
EMDB CONNECTED TO MDB-02 / GEN-P-G PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 496.83 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 447.15 kW * OVERALL /INSTALLED LOAD (TCL): 496.83 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-B3
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 03 ELE.ROOM
FED FROM: SMDB-B1
CONNECTED LOAD / POINTS
INCOMER

CCT ECC Load per circuit in


Circuit MCB
Rating of Sl Wire Wire Watts
Ref. Rating Room / Area Ex 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps Fan S/O S/O A/C Each
mm2 mm2 R Y B
1 R 1 10 2.5 2.5 PARKING 7 50 350
2 Y 1 10 2.5 2.5 DRIVEWAY 4 50 200
40A-4P 3 B 1 10 2.5 2.5 PARKING 5 50 250
ELCB-1
100mA 4 R 2 10 2.5 2.5 MAIN ELEVATOR LOBBY 3 50 150
5 Y 2 10 2.5 2.5 DRIVEWAY 8 50 400
6 B 2 10 2.5 2.5 PARKING 7 50 350
7 R 3 10 2.5 2.5 BELOW RAMP 2 50 100
8 Y 3 10 2.5 2.5 PARKING 10 50 500
40A TPN ISOLATOR (4 - POLE)

40A-4P 9 B 3 10 2.5 2.5 PARKING 9 50 450


ELCB-2
100mA 10 R 4 10 SPARE 50
11 Y 4 10 2.5 2.5 EQUIP.STORE (NEAR PUMP RM) 2 50 100
12 B 4 10 2.5 2.5 EQUIP.STORE (NEAR RAMP) 3 50 150
13 R 5 20 4.0 4.0 FCU-ELE. ROOM 1 548 548 FCU-B03-05
14 Y 5 20 SPARE 50
40A-4P 15 B 5 20 4.0 4.0 FCU-DOMESTIC PUMP ROOM 1 162 162 FCU-B03-02
ELCB-3
100mA 16 R 6 20 4.0 4.0 FCU-FIRE FIGHTING PUMP ROOM 1 162 162 FCU-B03-01
17 Y 6 20 SPARE 100
18 B 6 20 4.0 4.0 FCU-EQUIP.STORE (NEAR RAMP) 1 105 105 FCU-B03-04
19 R 7 20 4.0 4.0 FCU-MAIN ELEVATOR 1 109 109 FCU-B03-03
20 Y 7 10 SPARE 50
40A-4P 21 B 7 SPACE
ELCB-4
100mA 22 R 8 SPACE
23 Y 8 SPACE
24 B 8 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 1469 1400 1467
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 4.34 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-B3
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 03 ELE.ROOM
FED FROM: SMDB-B1
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Size Size Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 20 4.0 4.0 PARKING 3 200 600
2 Y 1 20 4.0 4.0 PARKING 2 200 400
40A-4P 3 B 1 20 4.0 4.0 EQUIP.STORE (NEAR RAMP) 2 400 800
ELCB-1
30mA 4 R 2 20 4.0 4.0 PARKING 3 200 600
5 Y 2 20 4.0 4.0 EQUIP.STORE (NEAR FF PUMP RM) 2 400 800
40A TPN ISOLATOR (4 - POLE)

6 B 2 20 4.0 4.0 PARKING 3 200 600


7 R 3 20 4.0 4.0 LIFT LOBBY 2 200 400
8 Y 3 20 4.0 4.0 PARKING 3 200 600
40A-4P 9 B 3 20 4.0 4.0 IONIZATION UNIT (PUMP ROOM) 1 200 200
ELCB-2
30mA 10 R 4 20 4.0 4.0 DIESEL PUMP (FIRE PUMP ROOM) 1 200 200
11 Y 4 20 SPARE 100
12 B 4 20 4.0 4.0 BMS-DDC-B3-01 (PUMP ROOM) 1 200 200
13 R 5 20 SPARE 100
14 Y 5 20 SPARE 100
40A-4P 15 B 5 20 SPARE 100
ELCB-3
30mA 16 R 6 SPACE
17 Y 6 SPACE
18 B 6 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 1900 2000 1900
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 5.80 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-B3
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 03 ELE.ROOM
FED FROM: ESMDB-B3
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 MAIN ELEVATOR LOBBY 4 50 200
2 Y 1 10 2.5 2.5 DRIVEWAY & PARKING 9 50 450
40A-4P 3 B 1 10 2.5 2.5 DRIVEWAY 2 50 100
ELCB-1
100mA 4 R 2 10 2.5 2.5 ELE. ROOM 4 50 200
5 Y 2 10 2.5 2.5 RAMP 12 50 600
6 B 2 10 2.5 2.5 DOMESTIC PUMP ROOM 4 50 200
7 R 3 10 2.5 2.5 FIRE FIGHTING PUMP ROOM 6 50 300
8 Y 3 10 2.5 2.5 STAIR-02 19 50 950
40A TPN ISOLATOR (4 - POLE)

40A-4P 9 B 3 10 2.5 2.5 STAIR-01 19 50 950


ELCB-2
100mA 10 R 4 10 SPARE 50
11 Y 4 10 SPARE 50
12 B 4 SPACE
13 R 5 20 4.0 4.0 LCP-EDB-B3 (ELE.ROOM) 1 200 200
14 Y 5 20 4.0 4.0 EX.FAN - FIRE FIGHTING PUMP ROOM 1 50 50
40A-4P 15 B 5 20 4.0 4.0 MOTORIZED DAMPER (MNRD-01 TO MNRD-06) 6 50 300
ELCB-3
30mA 16 R 6 20 4.0 4.0 ELE. ROOM 2 400 800
17 Y 6 20 4.0 4.0 CLEAN AGENT SYSTEM (ELE. ROOM) 1 200 200
18 B 6 20 4.0 4.0 DOMESTIC PUMP ROOM 2 200 400
19 R 7 20 4.0 4.0 FIRE FIGHTING PUMP ROOM 3 200 600
20 Y 7 SPACE
40A-4P 21 B 7 20 4.0 4.0 MOTORIZED DAMPER (SMFD-07 TO MSD-12) 6 50 300
ELCB-4
30mA 22 R 8 20 4.0 4.0 LCP-DB-L-B3 (ELE.ROOM) 1 200 200
23 Y 8 20 SPARE 100
24 B 8 20 SPARE 100
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 2550 2400 2350
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 7.30 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-B2
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 02 ELE.ROOM
FED FROM: SMDB-B1
CONNECTED LOAD / POINTS
INCOMER

CCT ECC Load per circuit in


Circuit MCB
Rating of Sl Wire Wire Watts
Ref. Rating Room / Area Ex 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps Fan S/O S/O A/C Each
mm2 mm2 R Y B
1 R 1 10 2.5 2.5 PARKING 7 50 350
2 Y 1 SPACE
40A-4P 3 B 1 10 2.5 2.5 PARKING 5 50 250
ELCB-1
100mA 4 R 2 10 2.5 2.5 MAIN ELEVATOR LOBBY 3 50 150
5 Y 2 SPACE
6 B 2 10 2.5 2.5 PARKING 7 50 350
7 R 3 10 2.5 2.5 DRIVEWAY 4 50 200
8 Y 3 10 2.5 2.5 PARKING 8 50 400
40A TPN ISOLATOR (4 - POLE)

40A-4P 9 B 3 10 2.5 2.5 PARKING 9 50 450


ELCB-2
100mA 10 R 4 10 SPARE 100
11 Y 4 10 2.5 2.5 EQUIP.STORE (NEAR STAIR-01) 6 50 300
12 B 4 10 2.5 2.5 EQUIP.STORE (NEAR RAMP) 3 50 150
13 R 5 SPACE
14 Y 5 20 4.0 4.0 FCU-EQUIP.STORE (NEAR STAIR-01) 1 50 50 FCU-B02-01
40A-4P 15 B 5 SPACE
ELCB-3
100mA 16 R 6 20 4.0 4.0 FCU-BMS ROOM 1 561 561 FCU-B02-03
17 Y 6 20 4.0 4.0 FCU-ELE. ROOM 1 726 726 FCU-B02-06
18 B 6 20 4.0 4.0 FCU-EQUIP.STORE (NEAR RAMP) 1 105 105 FCU-B02-05
19 R 7 20 4.0 4.0 FCU-MAIN ELEVATOR 1 109 109 FCU-B02-04
20 Y 7 20 4.0 4.0 FCU-EQUIP.STORE (NEAR STAIR-01) 1 88 88 FCU-B02-02
40A-4P 21 B 7 10 2.5 2.5 DRIVEWAY 8 50 400
ELCB-4
100mA 22 R 8 10 SPARE 50
23 Y 8 10 SPARE 50
24 B 8 10 SPARE 50
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 1520 1614 1755
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 4.89 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-B2
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 02 ELE.ROOM
FED FROM: SMDB-B1
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Size Size Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 20 4.0 4.0 PARKING 3 200 600
2 Y 1 20 4.0 4.0 PARKING 2 200 400
40A TPN ISOLATOR (4 - POLE)

40A-4P 3 B 1 20 4.0 4.0 EQUIP.STORE (NEAR RAMP) 2 400 800


ELCB-1
30mA 4 R 2 20 4.0 4.0 CBS PANEL (BMS ROOM) 1 200 200
5 Y 2 20 4.0 4.0 EQUIP.STORE (NEAR STAIR-01)) 2 400 800
6 B 2 20 4.0 4.0 PARKING 2 200 400
7 R 3 20 4.0 4.0 MAIN ELEVATOR 2 200 400
8 Y 3 20 4.0 4.0 PARKING 3 200 600
40A-4P 9 B 3 20 4.0 4.0 PARKING 3 200 600
ELCB-2
30mA 10 R 4 20 4.0 4.0 BMS-DDC-B2-01 (BMS ROOM) 1 200 200
11 Y 4 20 SPARE 100
12 B 4 20 SPARE 100
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 1400 1900 1900
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 5.20 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-B2
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 02 ELE.ROOM
FED FROM: ESMDB-B2
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 DRIVEWAY 2 50 100
2 Y 1 10 2.5 2.5 DRIVEWAY & PARKING 9 50 450
40A-4P 3 B 1 10 2.5 2.5 ELE. ROOM 4 50 200
ELCB-1
100mA 4 R 2 10 2.5 2.5 MAIN ELEVATOR 4 50 200
5 Y 2 10 2.5 2.5 RAMP 12 50 600
6 B 2 10 2.5 2.5 IDF ROOM , BMS ROOM 5 50 250
7 R 3 SPACE
8 Y 3 20 4.0 4.0 MOTORIZED DAMPER (MNRD-07 TO MNRD-14) 8 50 400
40A TPN ISOLATOR (4 - POLE)

40A-4P 9 B 3 20 SPARE 200


ELCB-2
30mA 10 R 4 SPACE
11 Y 4 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO MNRD-06) 6 50 300
12 B 4 20 4.0 4.0 LCP-DB-L-B2 (ELE.ROOM) 1 200 200
13 R 5 20 4.0 4.0 BMS ROOM 2 400 800
14 Y 5 20 SPARE 100
40A-4P 15 B 5 20 4.0 4.0 ELE. ROOM 2 400 800
ELCB-3
30mA 16 R 6 32 4.0 4.0 BMS ROOM 5 400 2000 RING
17 Y 6 20 4.0 4.0 LCP-EDB-B2 (ELE.ROOM) 1 200 200
18 B 6 20 4.0 4.0 IDF ROOM 1 400 400
19 R 7 SPACE
20 Y 7 20 4.0 4.0 CLEAN AGENT SYSTEM (ELE. ROOM) 1 200 200
40A-4P 21 B 7 20 SPARE 200
ELCB-4
30mA 22 R 8 SPACE
23 Y 8 20 4.0 4.0 CLEAN AGENT SYSTEM (BMS ROOM) 1 200 100
24 B 8 20 SPARE 100
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 3100 2350 2350
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 7.80 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-B1 BASEMENT - 01 ELE.ROOM
CLIENT: Emirates Real Estate Corp. LOCATION OF DB:
FED FROM: SMDB-B1 (NEAR STAIR-02)
CONNECTED LOAD / POINTS
INCOMER

CCT ECC Load per circuit in


Circuit MCB
Rating of Sl Wire Wire Watts
Ref. Rating Room / Area Ex 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps Fan S/O S/O A/C Each
mm2 mm2 R Y B
1 R 1 10 2.5 2.5 PARKING 10 50 500
2 Y 1 10 2.5 2.5 DRIVEWAY 6 50 300
40A-4P 3 B 1 SPACE
ELCB-1
100mA 4 R 2 10 2.5 2.5 MAIN ELEVATOR LOBBY 3 50 150
5 Y 2 10 2.5 2.5 DRIVEWAY 4 50 200
6 B 2 10 2.5 2.5 DRIVEWAY&PARKING 7 50 350
7 R 3 10 2.5 2.5 DRIVEWAY 4 50 200
8 Y 3 10 2.5 2.5 DRIVEWAY&PARKING 7 50 350
40A TPN ISOLATOR (4 - POLE)

40A-4P 9 B 3 10 2.5 2.5 SERVICE CORRIDOR 2 50 100


ELCB-2
100mA 10 R 4 10 2.5 2.5 DRIVEWAY&PARKING 4 50 200
11 Y 4 10 SPARE 50
12 B 4 20 4.0 4.0 FCU - LV ROOM (NEAR DRIVEWAY) 1 740 740 FCU-B01-03
13 R 5 20 4.0 4.0 FCU - LV ROOM (NEAR DRIVEWAY) 1 740 740 FCU-B01-03
14 Y 5 10 2.5 2.5 LV ROOM 5 50 250
40A-4P 15 B 5 20 4.0 4.0 FCU - CCTV EUIP.ROOM 1 211 211 FCU-B01-01
ELCB-3
100mA 16 R 6 20 4.0 4.0 FCU - MAIN ELEVATOR 1 109 109 FCU-B01-05
17 Y 6 20 4.0 4.0 FCU - ELE. ROOM NEAR STAIR-02 1 726 726 FCU-B01-02
18 B 6 20 4.0 4.0 FCU - ELE. ROOM NEAR RAMP 1 548 548 FCU-B01-06
19 R 7 10 SPARE 50
20 Y 7 10 SPARE 50
40A-4P 21 B 7 10 SPARE 50
ELCB-4
100mA 22 R 8 SPACE
23 Y 8 SPACE
24 B 8 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 1949 1926 1999
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 5.87 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-B1 BASEMENT - 01 ELE.ROOM
CLIENT: Emirates Real Estate Corp. LOCATION OF DB:
FED FROM: SMDB-B1 (NEAR STAIR-02)
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 20 4.0 4.0 PARKING 3 200 600
2 Y 1 20 4.0 4.0 PARKING 3 200 600
40A-4P 3 B 1 20 4.0 4.0 BMS-DDC-B1-03 (ELE ROOM NEAR STAIR 02) 1 200 200
ELCB-1
30mA 4 R 2 20 4.0 4.0 PARKING 2 200 400
5 Y 2 20 4.0 4.0 PARKING 2 200 400
6 B 2 SPACE
100A TPN ISOLATOR (4 - POLE)

7 R 3 20 4.0 4.0 MAIN ELEVATOR 2 200 400


8 Y 3 SPACE
40A-4P 9 B 3 20 4.0 4.0 SERVICE CORRIDOR 2 400 800
ELCB-2
30mA 10 R 4 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
11 Y 4 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
12 B 4 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
13 R 5 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
14 Y 5 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
40A-4P 15 B 5 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
ELCB-3
30mA 16 R 6 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
17 Y 6 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
18 B 6 40 10.0 6.0 ELEC. VEHICLE CHARGING POINT 1 4000 4000
40A-4P 19 R 7 40 SPARE 100
ELCB-3 20 Y 7 40 SPARE 100
30mA 21 B 7 20 SPARE 100
Cable size : 4C 35mm2 XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 13500 13100 13100
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 39.70 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-SS
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 TRANS.ROOM
FED FROM: MDB-01
CONNECTED LOAD / POINTS
INCOMER

CCT ECC Load per circuit in


Circuit MCB Wire Wire
Rating of Sl Watts
Ref. Rating Room / Area Ex 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps Fan S/O S/O A/C Each
mm2 mm2 R Y B

40A-4P 1 R 1 10 SPARE 50
ISOLATOR (4 -

ELCB-1 2 Y 1 10 2.5 2.5 TRANS. ROOM 6 50 300


40A TPN

100mA 3 B 1 10 SPARE 50
40A-4P 4 R 2 20 4.0 4.0 TRANS. ROOM 1 200 200
ELCB-2 5 Y 2 20 SPARE 100
30mA 6 B 2 20 4.0 4.0 TRANS. ROOM 1 200 200
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 250 400 250
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 0.90 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-MTEL
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 MAIN TEL.ROOM
FED FROM: ESMDB-B1
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Size Size Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 MAIN TEL. ROOM 4 50 200
2 Y 1 SPACE
40A-4P 3 B 1 SPACE
ELCB-1
100mA 4 R 2 10 SPARE 50
5 Y 2 10 SPARE 50
40A TPN ISOLATOR (4 - POLE)

6 B 2 20 4.0 4.0 FCU - MAIN TEL. ROOM 1 548 548 FCU-B01-04


40A-4P 7 R 3 1000
ELCB-2 8 Y 3 40 6.0 6.0 MAIN TEL. ROOM 1 3000 1000
30mA 9 B 3 1000
40A-4P 7 R 4 1000
ELCB-3 8 Y 4 40 6.0 6.0 MAIN TEL. ROOM 1 3000 1000
30mA 9 B 4 1000
10 R 5 20 4.0 4.0 CLEAN AGENT SYSTEM (M.TEL.ROOM) 1 200 200
11 Y 5 20 SPARE 100
40A-4P 12 B 5 20 4.0 4.0 MAIN TEL. ROOM 2 400 800
ELCB-4
30mA 16 R 6 20 4.0 4.0 MAIN TEL. ROOM 2 400 800
17 Y 6 20 4.0 4.0 MAIN TEL. ROOM 1 1000 1000
18 B 6 20 SPARE 100
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 3250 3150 3448
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 9.85 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-B1
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 ELE.ROOM (NEAR STAIR 02)
FED FROM: ESMDB-B1
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 10 2.5 2.5 MAIN ELEVATOR 4 50 200
2 Y 1 10 SPARE 50
40A-4P 3 B 1 10 2.5 2.5 DRIVEWAY 3 50 150
ELCB-1
100mA 4 R 2 10 2.5 2.5 DRIVEWAY & PARKING 7 50 350
5 Y 2 10 SPARE 50
6 B 2 10 2.5 2.5 RAMP 6 50 300
7 R 3 10 2.5 2.5 SERVER ROOM 8 50 400
8 Y 3 10 2.5 2.5 CCTV CONT. ROOM 3 50 150
40A-4P 9 B 3 10 2.5 2.5 CCTV EQUIP. ROOM 2 50 100
ELCB-2
100mA 10 R 4 10 2.5 2.5 ELE. ROOM NEAR RAMP 3 50 150
11 Y 4 10 2.5 2.5 LV ROOM 5 50 250
40A TPN ISOLATOR (4 - POLE)

12 B 4 10 2.5 2.5 ELE. ROOM NEAR STAIR-02 3 50 150


13 R 5 20 4.0 4.0 LCP-EDB-B1 (ELE.ROOM NEAR RAMP) 1 200 200
14 Y 5 20 4.0 4.0 CLEAN AGENT SYSTEM (SERVER ROOM) 1 200 200
40A-4P 15 B 5 32 4.0 4.0 ELE. ROOM NEAR STAIR-02 4 400 1600 RING
ELCB-3
30mA 16 R 6 20 4.0 4.0 ELE. ROOM NEAR RAMP 2 400 800
17 Y 6 32 4.0 4.0 LV ROOM 3 400 1200 RING
18 B 6 20 4.0 4.0 LCP-DB-L-B1 (ELE.ROOM NEAR STAIR 02) 1 200 200
19 R 7 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO MNRD-06) 6 50 300
20 Y 7 20 4.0 4.0 MOTORIZED DAMPER (SMFD-11 TO SMFD-16) 6 50 300
40A-4P 21 B 7 20 4.0 4.0 CLEAN AGENT SYSTEM (NEAR STAIR-02) 1 200 200
ELCB-4
30mA 22 R 8 20 4.0 4.0 CLEAN AGENT SYSTEM (ELE.ROOM NEAR RAMP) 1 200 200
23 Y 8 20 4.0 4.0 CLEAN AGENT SYSTEM (L.V ROOM) 1 200 200
24 B 8 20 4.0 4.0 MOTORIZED DAMPER (MSD-07 TO MSD-10) 4 50 200
25 R 9 20 4.0 4.0 CLEAN AGENT SYSTEM (CCTV EQUIP. ROOM) 1 200 200
26 Y 9 20 4.0 4.0 CLEAN AGENT SYSTEM (CCTV CONT. ROOM) 1 200 200
40A-4P 27 B 9 20 SPARE 100
ELCB-5
30mA 28 R 10 20 SPARE 100
29 Y 10 20 4.0 4.0 MOTORIZED DAMPER (SMFD-17 TO SMFD-22) 6 50 300
30 B 10 SPACE
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 2900 2900 3000
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 8.80 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-CCTV
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 CCTV CONT.ROOM
FED FROM: ESMDB-UPS-CCTV
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A 32A
Ref. Rating Size Size Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Ltg. WH SPU INDS.SO Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O CKET R Y B
1 R 1 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
2 Y 1 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
40A-4P 3 B 1 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
ELCB-1
30mA 4 R 2 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
5 Y 2 20 SPARE 100
6 B 2 20 4.0 4.0 ACP SECURITY CON. ROOM (GF) 1 200 200
7 R 3 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
8 Y 3 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
40A-4P 9 B 3 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
ELCB-2
30mA 10 R 4 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
11 Y 4 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
12 B 4 20 4.0 4.0 CCTV EQUIPMENT ROOM 2 400 800
80A TPN ISOLATOR (4 - POLE)

13 R 5 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400


14 Y 5 20 4.0 4.0 CCTV CONTROL ROOM 2 400 800
40A-4P 15 B 5 20 4.0 4.0 ACS ELE.RM NEAR STAIR 02 (B1) 1 200 200
ELCB-3
30mA 16 R 6 20 4.0 4.0 ACS ELE.ROOM (B3) 1 200 200
17 Y 6 20 4.0 4.0 ACS ELE.ROOM (B2) 1 200 200
18 B 6 20 4.0 4.0 ACS TEL. ROOM (G FLOOR ) 3 200 600
19 R 7 20 4.0 4.0 BMS ROOM (B2 FLOOR) 1 400 400
20 Y 7 20 4.0 4.0 ACS TEL. ROOM (1ST FLOOR ) 4 200 800
40A-4P 21 B 7 20 4.0 4.0 TEL. ROOM (G FLOOR) 1 400 400
ELCB-4
30mA 22 R 8 20 4.0 4.0 ACS TEL. ROOM (2ND FLOOR ) 4 200 800
23 Y 8 20 4.0 4.0 TEL. ROOM (2ND FLOOR) 1 400 400
24 B 8 20 4.0 4.0 TEL. ROOM (4TH FLOOR) 1 400 400
25 R 9 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
26 Y 9 20 4.0 4.0 ACS TEL. ROOM (3RD FLOOR ) 4 200 800
40A-4P 27 B 9 20 4.0 4.0 ACS TEL. ROOM (4TH FLOOR ) 4 200 800
ELCB-5
30mA 28 R 10 20 4.0 4.0 CCTV CONTROL ROOM 1 400 400
29 Y 10 20 SPARE 100
30 B 10 20 SPARE 100
40A-4P 31 R 11 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
ELCB-6 32 Y 11 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
30mA 33 B 11 32 4.0 4.0 CCTV EQUIPMENT ROOM 1 3000 3000
Cable size : 4C 25mm2 MICA GLASS-XLPE/LSZH/SWA
1C 16mm2 PVC Y/G AS ECC 9800 10000 9900
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 29.70 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB1-UPS-DC
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 SERVER ROOM
FED FROM: ESMDB-UPS-DC
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 32A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH INDS.SO
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 CKET R Y B

40A-4P 1 R 1 40 10.0 6.0 SERVER ROOM 1 3000 3000


ELCB-1 2 Y 1 40 10.0 6.0 SERVER ROOM 1 3000 3000
30mA 3 B 1 40 10.0 6.0 SERVER ROOM 1 3000 3000
80A TPN ISOLATOR (4 - POLE)

40A-4P 4 R 2 40 10.0 6.0 SERVER ROOM 1 3000 3000


ELCB-2 5 Y 2 40 10.0 6.0 SERVER ROOM 1 3000 3000
30mA 6 B 2 40 10.0 6.0 SERVER ROOM 1 3000 3000
40A-4P 7 R 3 40 10.0 6.0 MAIN TEL.ROOM - IT RACK - 1 1 3000 3000
ELCB-3 8 Y 3 40 10.0 6.0 TEL. ROOM (1ST FLOOR) 1 3000 3000
30mA 9 B 3 40 10.0 6.0 MAIN TEL.ROOM - IT RACK - 2 1 3000 3000
40A-4P 10 R 4 20 SPARE 200
ELCB-4 11 Y 4 40 10.0 6.0 TEL. ROOM (2ND FLOOR) 1 3000 3000
30mA 12 B 4 40 10.0 6.0 TEL. ROOM (GROUND FLOOR) 1 3000 3000
40A-4P 13 R 5 40 10.0 6.0 IDF RACK (B2 - IDF ROOM) 1 3000 3000
ELCB-5 14 Y 5 40 SPARE 200
30mA 15 B 5 40 SPARE 200
Cable size : 4C 25mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 12200 12200 12200
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 36.60 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB2-UPS-DC
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: BASEMENT - 01 SERVER ROOM
FED FROM: ESMDB-UPS-DC
CONNECTED LOAD / POINTS
INCOMER

Rating of CCT ECC


Circuit MCB Load per circuit in Watts
RCBO Sl Wire Wire 32A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
WITH No Size Size Ltg. WH INDS.SO
No. Amps Fan S/O TS/O S/O A/C Each
30mA.Sen mm2 mm2 CKET R Y B

40A-4P 1 R 1 40 10.0 6.0 SERVER ROOM 1 3000 3000


ELCB-1 2 Y 1 40 10.0 6.0 SERVER ROOM 1 3000 3000
30mA 3 B 1 40 10.0 6.0 SERVER ROOM 1 3000 3000
80A TPN ISOLATOR (4 - POLE)

40A-4P 4 R 2 40 10.0 6.0 SERVER ROOM 1 3000 3000


ELCB-2 5 Y 2 40 10.0 6.0 SERVER ROOM 1 3000 3000
30mA 6 B 2 40 10.0 6.0 SERVER ROOM 1 3000 3000
40A-4P 7 R 3 40 SPARE 200
ELCB-3 8 Y 3 40 SPARE 1000
30mA 9 B 3 40 10.0 6.0 TEL. ROOM (4TH FLOOR) 1 3000 3000
40A-4P 10 R 4 40 10.0 6.0 TEL. ROOM (3RD FLOOR) 1 3000 3000
ELCB-4 11 Y 4 40 SPARE 200
30mA 12 B 4 40 SPARE 200
40A-4P 13 R 5 SPACE
ELCB-5 14 Y 5 SPACE
30mA 15 B 5 SPACE
Cable size : 4C 25mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 9200 7200 9200
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 25.60 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-B1 (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-1 FLOOR (ELE.ROOM B01-09)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 160 35 1x4C CU/XLPE/SWA/LSZH 70 1x1Cx35 21.74 21.94 24.82 68.50 54.80

OUTGOING:

DB-L-B1 TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 1.95 1.93 2.00 5.87 4.70

DB-P-B1 TP 100 35 1x4C CU/XLPE/SWA/LSZH 35 1x1Cx16 13.50 13.10 13.10 39.70 31.76

DB-L-B2 TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 1.52 1.61 1.76 4.89 3.91

DB-P-B2 TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 1.40 1.90 1.90 5.20 4.16

DB-L-B3 TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 1.47 1.40 1.47 4.34 3.47

DB-P-B3 TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 1.90 2.00 1.90 5.80 4.64

CIRCULATION
SP 20 35 1x2C CU/XLPE/SWA/LSZH 6 1x1Cx6 0.50 0.50 0.40
PUMP

JOCKEY PUMP SP 20 35 1x2C CU/XLPE/SWA/LSZH 6 1x1Cx6 2.20 2.20 1.76

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


21.74 21.94 24.82 68.50 54.80 TOTAL
SMDB-B1 CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 68.50 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 54.80 kW * OVERALL /INSTALLED LOAD (TCL): 68.50 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-B3 (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-3 FLOOR (ELE.ROOM)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA CLASS-
INCOMER TP 200 50 1x4C 150 1x1Cx70 25.62 25.47 25.42 76.50 68.85
XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
EAF-B3-01 TP 40 35 1x4C 10 1x1Cx10 5.00 5.00 5.00 15.00 13.50 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
EAF-B3-02 TP 40 35 1x4C 10 1x1Cx10 5.00 5.00 5.00 15.00 13.50 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B3-01 TP 40 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B3-02 TP 40 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
SP-B3-01
MICA GLASS-
(FOR PETROL TP 25 35 1x4C 6 1x1Cx6 1.47 1.47 1.47 4.40 3.96 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
INTERCEPTOR)
SP-B3-02
(FOR DOMESTIC MICA GLASS-
TP 25 35 1x4C 6 1x1Cx6 1.47 1.47 1.47 4.40 3.96 100mA ELS+TIMER+ALARM
WATER PUMP XLPE/LSZH/SWA
ROOM)
SP-B3-03
MICA GLASS-
(FOR FIRE PUMP TP 25 35 1x4C 6 1x1Cx6 1.47 1.47 1.47 4.40 3.96 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
ROOM)
SP-B3-04
MICA GLASS-
(FOR SEWAGE TP 25 35 1x4C 6 1x1Cx6 1.47 1.47 1.47 4.40 3.96 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
SUMP PIT)

MICA GLASS-
TP-B3-01 TP 40 35 1x4C 10 1x1Cx10 1.83 1.83 1.83 5.50 4.95 100mA ELS+TIMER+ALARM(1D + 1S)
XLPE/LSZH/SWA

MICA GLASS-
BP-B3-01 TP 25 35 1x4C 4 1x1Cx4 0.18 0.18 0.18 0.55 0.50 100mA ELS+TIMER+ALARM(1D + 1S)
XLPE/LSZH/SWA
MAF-B3-01
(DIESEL PUMP MICA GLASS-
TP 25 35 1x4C 4 1x1Cx4 0.18 0.18 0.18 0.55 0.50 100mA ELS+TIMER+ALARM
COMBUSTION XLPE/LSZH/SWA
SUPPLY AIR
MICA GLASS-
EDB-B3 TP 40 35 1x4C 10 1x1Cx10 2.55 2.40 2.35 7.30 6.57
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


25.62 25.47 25.42 76.50 68.85 TOTAL
ESMDB-B3 CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 76.50 kW
STAND BY LOAD : kW

DEMAND FACTOR : 0.9 Max. DEMAND: 68.85 kW * OVERALL /INSTALLED LOAD (TCL): 76.50 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-B2 (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-2 FLOOR (ELE.ROOM)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 160 50 1x4C 70 1x1Cx35 18.10 17.35 17.35 52.80 47.52
XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
EAF-B2-01 TP 40 35 1x4C 10 1x1Cx10 5.00 5.00 5.00 15.00 13.50 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
EAF-B2-02 TP 40 35 1x4C 10 1x1Cx10 5.00 5.00 5.00 15.00 13.50 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B2-01 TP 32 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B2-02 TP 32 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
EDB-B2 TP 32 35 1x4C 10 1x1Cx10 3.10 2.35 2.35 7.80 7.02
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


18.10 17.35 17.35 52.80 47.52 TOTAL
ESMDB-B2 CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 52.80 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 47.52 kW * OVERALL /INSTALLED LOAD (TCL): 52.80 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-B1 (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: BASEMENT-1 FLOOR (ELE.ROOM B01-17)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
ECC LENGTH (KW) CONNECTED/ kWh METERS
CIRCUIT/ FEEDER MCCB/ FAULT NO. OF CORES OPERATIONA
SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
SMDB/ TP DUTY LOAD
TYPE 1C, CABLE (TCL) * LV/
DB NO. RATING kA NO. OF
XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 160 50 1x4C 95 1x1Cx50 24.15 24.05 24.45 72.65 65.38
XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
EAF-B1-01 TP 63 35 1x4C 16 1x1Cx16 6.17 6.17 6.17 18.50 16.65 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
EAF-B1-02 TP 63 35 1x4C 16 1x1Cx16 6.17 6.17 6.17 18.50 16.65 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B1-01 TP 32 35 1x4C 10 1x1Cx10 1.83 1.83 1.83 5.50 4.95 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
FAF-B1-02 TP 32 35 1x4C 10 1x1Cx10 1.83 1.83 1.83 5.50 4.95 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA

EAF-B1-03 MICA GLASS-


TP 32 35 1x4C 10 1x1Cx10 1.00 1.00 1.00 3.00 2.70 100mA ELS+TIMER+ALARM
(1DUTY+1STANDBY) XLPE/LSZH/SWA

FAF-B1-03 MICA GLASS-


TP 32 35 1x4C 10 1x1Cx10 1.00 1.00 1.00 3.00 2.70 100mA ELS+TIMER+ALARM
(1DUTY+1STANDBY) XLPE/LSZH/SWA
MICA GLASS-
EDB-B1 TP 32 35 1x4C 10 1x1Cx10 2.90 2.90 3.00 8.80 7.92
XLPE/LSZH/SWA
MICA GLASS-
EDB-MTEL TP 32 35 1x4C 10 1x1Cx10 3.25 3.15 3.45 9.85 8.86
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


24.15 24.05 24.45 72.65 65.38 TOTAL
ESMDB-B1 CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 72.65 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 65.38 kW * OVERALL /INSTALLED LOAD (TCL): 72.65 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-DATA CENTER (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : BASEMENT-1 FLOOR (SERVER ROOM)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 350 50 1x4C 240 1x1Cx120 44.73 42.73 44.73 132.20 118.98
XLPE/LSZH/SWA
.
MICA GLASS-
ESMDB-UPS-DC TP 160 35 1x4C 70 1x1Cx35 21.40 19.40 21.40 62.20 55.98
XLPE/LSZH/SWA
MICA GLASS-
CRAC-B01-01 TP 80 35 1x4C 25 1x1Cx16 11.67 11.67 11.67 35.00 31.50
XLPE/LSZH/SWA
MICA GLASS-
CRAC-B01-01 TP 80 35 1x4C 25 1x1Cx16 11.67 11.67 11.67 35.00 31.50
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


44.73 42.73 44.73 132.20 118.98 TOTAL
ESMDB-DATA CENTER CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 132.20 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 118.98 kW * OVERALL /INSTALLED LOAD (TCL): 132.20 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-UPS-CCTV (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : BASEMENT-1 FLOOR (ELE.ROOM B01-09)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 80 35 1x4C 25 1x1Cx16 10.96 11.16 11.06 33.17 29.85
XLPE/LSZH/SWA
OUTGOING:
MIGA GLASS-
DB-CCTV TP 80 35 1x4C 25 1x1Cx16 9.80 10.00 9.90 29.70 26.73
XLPE/LSZH/SWA
MIGA GLASS- 100mA
CRAC-B01-02 TP 32 35 1x4C 10 1x1Cx10 1.16 1.16 1.16 3.47 3.12
XLPE/LSZH/SWA ELCB+STARTER(UVR+TIMER)

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


10.96 11.16 11.06 33.17 29.85 TOTAL
ESMDB-UPS-CCTV CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 33.17 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 29.85 kW * OVERALL /INSTALLED LOAD (TCL): 33.17 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-LIFT (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : BASEMENT-1 FLOOR (ELE.ROOM B01-09)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 125 50 1x4C 70 1x1Cx35 18.70 18.70 18.70 56.11 50.50
XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
LIFT-01 TP 40 35 1x4C 16 1x1Cx16 4.84 4.84 4.84 14.53 13.08 300mA, 4P,RCCB TYPE B
XLPE/LSZH/SWA
MICA GLASS-
LIFT-02 TP 40 35 1x4C 16 1x1Cx16 4.84 4.84 4.84 14.53 13.08 300mA, 4P,RCCB TYPE B
XLPE/LSZH/SWA
MICA GLASS-
LIFT-03 TP 40 35 1x4C 16 1x1Cx16 4.84 4.84 4.84 14.53 13.08 300mA, 4P,RCCB TYPE B
XLPE/LSZH/SWA
MICA GLASS-
LIFT-04 TP 40 35 1x4C 16 1x1Cx16 4.17 4.17 4.17 12.52 11.27 300mA, 4P,RCCB TYPE B
XLPE/LSZH/SWA
MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER
18.70 18.70 18.70 56.11 50.50 TOTAL
ESMDB LIFT CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 56.11 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 50.50 kW * OVERALL /INSTALLED LOAD (TCL): 56.11 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-UPS-DC (FEED FROM ESMDB-DATA CENTER) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : BASEMENT-1 FLOOR (SERVER ROOM)

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 160 35 1x4C 70 1x1Cx35 21.40 19.40 21.40 62.20 55.98
XLPE/LSZH/SWA
OUTGOING:
MIGA CLASS-
EDB1-UPS-DC TP 80 35 1x4C 25 1x1Cx16 12.20 12.20 12.20 36.60 32.94
XLPE/LSZH/SWA
MIGA CLASS-
EDB2-UPS-DC TP 80 35 1x4C 25 1x1Cx16 9.20 7.20 9.20 25.60 23.04
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


21.40 19.40 21.40 62.20 55.98 0 TOTAL
ESMDB-UPS-DC CONNECTED TO ESMDB-DATA CENTER PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 62.20 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 55.98 kW * OVERALL /INSTALLED LOAD (TCL): 62.20 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-GF
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR ELE.ROOM
FED FROM: SMDB-GF
CCT ECC CONNECTED LOAD / POINTS

INCOMER
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 NURSERY 10 50 500
2 Y 1 10 2.5 2.5 TRAINING ROOM 18 20 / M 360
40A-4P
3 B 1 10 2.5 2.5 HAPINESS & CUSTOMER 3 50 150
ELCB-1
100mA 4 R 2 10 2.5 2.5 NURSERY 1 100 100
5 Y 2 10 2.5 2.5 TRAINING ROOM 22 28 / M 616
6 B 2 10 2.5 2.5 HAPINESS & CUSTOMER 3 50 150
7 R 3 10 2.5 2.5 NURSERY 1 50 50
8 Y 3 10 2.5 2.5 TRAINING ROOM 6 50 300
40A-4P
9 B 3 10 2.5 2.5 CORRIDOR 5 50 250
ELCB-2
100mA 10 R 4 10 2.5 2.5 NURSERY 11 28 / M 308
11 Y 4 10 2.5 2.5 TRAINING ROOM 18 20 / M 360
12 B 4 10 2.5 2.5 RAMP 8 50 400
13 R 5 10 2.5 2.5 NURSERY 10 20 / M 200
14 Y 5 10 2.5 2.5 TRAINING ROOM 6/1 50 / 20 / M 320
40A-4P
15 B 5 10 2.5 2.5 CHAIRMAN ENT 1 300 300
ELCB-3
100mA 16 R 6 10 2.5 2.5 PANTRY & TOILET 10 / 3 50 / 20 / M 560
17 Y 6 10 2.5 2.5 TRAINING ROOM 8/1 50 / 20 / M 420
40A TPN ISOLATOR (4 - POLE)

18 B 6 10 2.5 2.5 HAPINESS & CUSTOMER 7 50 350


19 R 7 10 2.5 2.5 NURSERY 12 20 / M 240
20 Y 7 10 2.5 2.5 RAMP 8 50 400
40A-4P
21 B 7 10 2.5 2.5 HAPINESS & CUSTOMER 14 50 700
ELCB-4
100mA 22 R 8 10 2.5 2.5 NURSERY 15 20 / M 300
23 Y 8 10 2.5 2.5 MALE PRAYER ROOM 1 300 300
24 B 8 10 2.5 2.5 SLEEPING KIDS AREA 3 50 150
25 R 9 10 2.5 2.5 NURSERY 1 300 300
26 Y 9 10 2.5 2.5 MALE PRAYER ROOM 25 / 7 20 / 28 / M 696
40A-4P
27 B 9 10 2.5 2.5 HAPINESS & CUSTOMER 27 20 / M 540
ELCB-5
100mA 28 R 10 10 2.5 2.5 NURSERY 1 300 300
29 Y 10 20 4.0 4.0 CURTAIN (TRAINING ROOM) 6 160 960 CURTAIN
30 B 10 10 2.5 2.5 CORRIDOR 3 50 150
31 R 11 20 4.0 4.0 CURTAIN (NURSERY,MALE PRAYER) 5 160 800 CURTAIN
32 Y 11 10 SPARE 50
40A-4P
33 B 11 10 2.5 2.5 HAPINESS & CUSTOMER 20 20 / M 400
ELCB-6
100mA 34 R 12 10 2.5 2.5 NURSERY 1 50 50
35 Y 12 10 SPARE 50
36 B 12 10 2.5 2.5 HAPINESS & CUSTOMER 26 20 / M 520
37 R 13 10 SPARE 100
38 Y 13 10 SPARE 50
40A-4P
39 B 13 10 2.5 2.5 RAMP 8 50 400
ELCB-7
100mA 40 R 14 20 4.0 4.0 HAPINESS & CUSTOMER 8 160 1280 CURTAIN
41 Y 14 SPACE
42 B 14 10 2.5 2.5 RAMP 6 50 300
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 5088 4882 4760
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 14.73 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-GFA
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR ELE.ROOM
FED FROM: SMDB-GF
CCT ECC CONNECTED LOAD / POINTS
INCOMER Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu REMARKS
ELCB No Size Size Ltg. WH SPU Others Load in Watts Each
No. Amps Fan S/O TS/O S/O A/C
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 STAFF DINNING 3 50 150
2 Y 1 10 2.5 2.5 MALE TOILET 17 50 850
40A-4P 3 B 1 10 2.5 2.5 FEMALE TOILET 15 50 750
ELCB-1
100mA 4 R 2 10 2.5 2.5 STAFF DINNING 2 50 100
5 Y 2 10 2.5 2.5 MALE TOILET 8 28 / M 224
6 B 2 10 2.5 2.5 FEMALE TOILET 8 28 / M 224
7 R 3 10 2.5 2.5 FEMALE PRAYER ROOM 25 20 500
8 Y 3 10 2.5 2.5 RECEPTION 33 20 / M 660
40A-4P 9 B 3 10 2.5 2.5 RECEPTION 44 20 / M 880
ELCB-2
100mA 10 R 4 10 2.5 2.5 STAFF DINNING 3 50 150
11 Y 4 10 2.5 2.5 MALE TOILET 5 20 / M 100
12 B 4 10 2.5 2.5 FEMALE TOILET 5 20 / M 100
13 R 5 10 2.5 2.5 STAFF DINNING 18 50 900
14 Y 5 10 2.5 2.5 RECEPTION COUNTER 4 20 / M 80
40A-4P 15 B 5 10 2.5 2.5 CORRIDOR 11 50 550
ELCB-3
100mA 16 R 6 10 2.5 2.5 STAFF DINNING 18 50 900
17 Y 6 10 2.5 2.5 RECEPTION 35 20 / M 700
40A TPN ISOLATOR (4 - POLE)

18 B 6 10 2.5 2.5 RECEPTION 44 20 / M 880


19 R 7 10 2.5 2.5 STAFF DINNING, STORE 5 50 250
20 Y 7 16 2.5 2.5 RECEPTION 56 20 / M 1120
40A-4P 21 B 7 10 2.5 2.5 GARBAGE 7 50 350
ELCB-4
100mA 22 R 8 10 2.5 2.5 GRAND STAIR - LED LIGHT 34 20 / M 680
23 Y 8 10 2.5 2.5 RECEPTION 35 20 / M 700
24 B 8 10 2.5 2.5 ATRIUM 14 50 700
25 R 9 20 4.0 4.0 STAFF DINNING 4 160 640 CURTAIN
26 Y 9 10 2.5 2.5 RECEPTION 3 50 150
40A-4P 27 B 9 10 2.5 2.5 ATRIUM 6 50 300
ELCB-5
100mA 28 R 10 10 2.5 2.5 FEMALE PRAYER ROOM 1 300 300
29 Y 10 10 2.5 2.5 PRE FUNCTIOIN 14 20 / M 280
30 B 10 16 2.5 2.5 DUBAI SERVICE CENTER 6 / 14 / 8 50 / 28 / 20 / M 852
31 R 11 20 4.0 4.0 FEMALE PRAYER ROOM 1 160 160 CURTAIN
32 Y 11 10 2.5 2.5 PRE FUNCTIOIN 7 28 / M 196
40A-4P 33 B 11 10 2.5 2.5 ENTRANCE LOBBY 4 50 200
ELCB-6
100mA 34 R 12 10 2.5 2.5 ABLUTION FEMALE PRAYER 3/9 50 / 20 / M 330
35 Y 12 10 2.5 2.5 ABLUTION MALE PRAYER 4/7 50 / 20 / M 340
36 B 12 10 SPARE 50
37 R 13 10 2.5 2.5 STAFF DINING - HOOD RANGE,CUPBOARD 3 1 20 / M / 100 160
38 Y 13 10 2.5 2.5 RECEPTION 33 20 / M 660
40A-4P 39 B 13 10 SPARE 50
ELCB-7
100mA 40 R 14 10 2.5 2.5 CORRIDOR 14 50 700
41 Y 14 10 SPARE 50
42 B 14 10 SPARE 50
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 5920 6110 5936
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 17.97 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-GF
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR ELE.ROOM
FED FROM: SMDB-GF
CONNECTED LOAD / POINTS

INCOMER
CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm 2 mm 2 R/O R Y B
1 R 1 32 4.0 4.0 STAFF DINNING, STORE 1 2 200 / 400 1000
2 Y 1 32 4.0 4.0 TRAINING,PRE FUNCTION 4 400 1600 RING
40A-4P 3 B 1 20 AUTRIUM 2 800
4.0 4.0 400
ELCB-1
30mA 4 R 2 32 4.0 4.0 FEMALE PRAYER ROOM 3 400 1200 RING
5 Y 2 20 4.0 4.0 RECEPTION 2 400 800
6 B 2 32 4.0 4.0 DUBAI SERVICE CENTER 4 400 1600 RING
7 R 3 32 4.0 4.0 NURSERY 5 400 2000 RING
8 Y 3 20 4.0 4.0 CORRIDOR & CHAIRMAN ENT. 4 200 800
40A-4P 9 B 3 20 DUBAI SERVICE CENTER 2 800
4.0 4.0 400
ELCB-2
30mA 10 R 4 20 4.0 4.0 GARBAGE ROOM 2 200 400
11 Y 4 32 4.0 4.0 MALE PRAYER ROOM 3 400 1200 RING
12 B 4 32 4.0 4.0 SLEEPING KIDS AREA 1 3 200 / 400 1400 RING
13 R 5 20 4.0 4.0 STAFF DINING - FRIDGE 1 300 300
14 Y 5 32 4.0 4.0 CORRIDOR 3 1 200 / 400 1000 RING
40A-4P 15 B 5 20 MALE & FEMALE TOILET (WC) 8 400
4.0 4.0 50
ELCB-3
30mA 16 R 6 32 4.0 4.0 STAFF DINING, CORRIDOR 1 3 200 / 400 1400 RING
17 Y 6 32 4.0 4.0 TRAINING ROOM 5 400 2000 RING
18 B 6 20 4.0 4.0 AUTRIUM 1 400 400
19 R 7 20 SPARE 100
20 Y 7 20 4.0 4.0 TRAINING ROOM 2 400 800
40A-4P 21 B 7 20 FEMALE TOILET - HAND DRYER 1 1000
4.0 4.0 1000
ELCB-4
30mA 22 R 8 32 6.0 4.0 STAFF DINING - COOKER CONTROL UNIT 1 7200 7200
23 Y 8 32 4.0 4.0 TRAINING ROOM 3 400 1200 RING
24 B 8 20 4.0 4.0 MANAGEMENT & CUS. SER. CENTER 1 400 400
25 R 9 20 4.0 4.0 TOILET NURSERY - HAND DRYER 1 1000 1000
26 Y 9 20 4.0 4.0 NURSERY PANTRY - FRIDGE 1 300 300
125A TPN ISOLATOR (4 - POLE)

40A-4P 27 B 9 20 MALE TOILET - HAND DRYER 1 1000


4.0 4.0 1000
ELCB-5
30mA 28 R 10 20 4.0 4.0 GENERATOR,CHAIRMAN ENTRANCE 2 1 200 / 400 800
29 Y 10 20 4.0 4.0 NURSERY PANTRY 2 400 800
30 B 10 20 4.0 4.0 HAPPINESS & CUSTOMER 4 200 800
31 R 11 20 4.0 4.0 STAFF DINING - OVEN 1 1000 1000
32 Y 11 20 SPARE 100
40A-4P 33 B 11 20 FEMALE TOILET - HAND DRYER 1
4.0 4.0 1000 1000
ELCB-6
30mA 34 R 12 20 4.0 4.0 STAFF DINING - OVEN 1 1000 1000
35 Y 12 20 4.0 4.0 GUARD ROOM 2 400 800
36 B 12 20 4.0 4.0 ABLUTION FEMALE PRAYER - HAND DRYER 1 1000 1000
37 R 13 20 4.0 4.0 BMS-DDC-GF-04 (BMS ROOM) 1 200 200
38 Y 13 20 4.0 4.0 ABLUTION MALE PRAYER - HAND DRYER 1 1000 1000
40A-4P 39 B 13 32 HAPPINESS & CUSTOMER 5 2000 RING
4.0 4.0 400
ELCB-7
30mA 40 R 14 20 SPARE 100
41 Y 14 20 SPARE 100
42 B 14 32 4.0 4.0 HAPPINESS & CUSTOMER 4 400 1600 RING
43 R 15 20 4.0 4.0 STAFF DINING 1 1 200 / 400 600
44 Y 15 32 4.0 4.0 RECEPTION 5 400 2000 RING
40A-4P 45 B 15 32 HAPPINESS & CUSTOMER 5 2000 RING
4.0 4.0 400
ELCB-8
30mA 46 R 16 20 4.0 4.0 NURSERY 2 400 800
47 Y 16 20 4.0 4.0 RECEPTION 2 200 400
48 B 16 20 4.0 4.0 ENTRANCE LOBBY 1 1 200 / 400 600
49 R 17 20 4.0 4.0 STAFF DINING - FRIDGE 1 300 300
50 Y 17 32 4.0 4.0 GROUND FLOOR BOUNDARY WALL 6 200 1200 RING
40A-4P 51 B 17 20 SPARE 100
ELCB-9
30mA 52 R 18 20 4.0 4.0 NURSERY TOILET (WC) 3 50 150
53 Y 18 20 4.0 4.0 TRAINING ROOM - AV RACK 1 1000 1000
54 B 18 20 SPARE 100
55 R 19 SPACE
56 Y 19 20 4.0 4.0 TRAINING,PRE FUNCTION 2 400 800
40A-4P 57 B 19 20 SPARE 100
ELCB-10
30mA 58 R 20 SPACE
59 Y 20 20 4.0 4.0 TRAINING ROOM - AV RACK 1 1000 1000
60 B 20 20 4.0 4.0 MALE TOILET - HAND DRYER 1 1000 1000
2
Cable size : 4C 50mm CU/XLPE/SWA/LSZH
2
1C 25mm PVC Y/G AS ECC 19550 18900 18100
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 56.55 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-GF
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR ELE.ROOM
FED FROM: ESMDB-GF
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 10 2.5 2.5 ELE. ROOM 2 50 100
2 Y 1 10 2.5 2.5 CORRIDOR 5 50 250
40A-4P 3 B 1 10 2.5 2.5 TEL.ROOM 1 50 50
ELCB-1
100mA 4 R 2 10 2.5 2.5 SECURITY CONTROL 4 50 200
5 Y 2 SPACE
6 B 2 10 2.5 2.5 LIFT ELEVATION 23 20 / M 460
7 R 3 10 2.5 2.5 GUARD ROOM 2 50 100
8 Y 3 SPACE
40A-4P 9 B 3 10 2.5 2.5 CHAIRMAN ENT. CORRIDOR 4 50 200
ELCB-2
100mA 10 R 4 10 2.5 2.5 GENERATOR 4 50 200
11 Y 4 10 2.5 2.5 LIFT ELEVATION 23 20 / M 460
12 B 4 10 2.5 2.5 MANAGEMENT OF CUST. SER. CENTER 3 50 150
13 R 5 SPACE
14 Y 5 20 4.0 4.0 FACP (SEC.CONTROL ROOM) 1 200 200
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 20 4.0 4.0 TEL. ROOM 1 400 400


ELCB-3
30mA 16 R 6 32 4.0 4.0 SECURITY CONTROL ROOM 4 400 1600 RING
17 Y 6 20 4.0 4.0 PAVA CON. PANEL 1 200 200
18 B 6 20 4.0 4.0 ELE.ROOM 2 400 800
19 R 7 20 4.0 4.0 LCP-DB-GF (ELE.ROOM) 1 200 200
20 Y 7 20 4.0 4.0 ACP (SEC.CONTROL ROOM) 1 200 200
40A-4P 21 B 7 20 4.0 4.0 GATE BARRIER-2 1 500 500
ELCB-4
30mA 22 R 8 20 4.0 4.0 LCP-DB-GFA (ELE.ROOM) 1 200 200
23 Y 8 20 4.0 4.0 LCP-DB-FACADE (SEC.CON. ROOM) 1 200 200
24 B 8 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO SMFD-06) 6 50 300
25 R 9 20 SPARE 500
26 Y 9 32 4.0 4.0 BATTERY CHARGER - GEN. ROOM 1 2000 2000
40A-4P 27 B 9 20 SPARE 500
ELCB-5
30mA 28 R 10 20 4.0 4.0 GATE BARRIER-1 . 1 500 500
29 Y 10 20 4.0 4.0 TOUCH PANEL - RECEPTION 1 200 200
30 B 10 20 4.0 4.0 LCP-EDB-GF (ELE.ROOM) 1 200 200
31 R 11 10 2.5 2.5 STAFF DINING 2 50 100
32 Y 11 10 SPARE 50
40A-4P 33 B 11 10 2.5 2.5 CORRIDOR 13 50 650
ELCB-6
100mA 34 R 12 10 2.5 2.5 GRAND STAIR 10 50 500
35 Y 12 20 4.0 4.0 EX.FAN - GENERATOR ROOM (EAF-GF-01) 1 151 151
36 B 12 10 SPARE 50
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 4200 3911 4260
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 12.37 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-RMU
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR RMU ROOM
FED FROM: MDB-01
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R Y B

40A-4P 1 R 1 10 SPARE 50
ISOLATOR (4 -

ELCB-1 2 Y 1 10 2.5 2.5 RMU ROOM 4 50 200


40A TPN

100mA
POLE)

3 B 1 10 SPARE 50
40A-4P 4 R 2 20 4.0 4.0 RMU ROOM 1 200 200
ELCB-2 5 Y 2 20 SPARE 100
30mA 6 B 2 20 4.0 4.0 RMU ROOM 1 200 200
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 250 300 250
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 0.80 KW
Plot No. 2641059
PROJECT: Emirates Authority For Standardization And Metrology LOAD DISTRIBUTION SCHEDULE
Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-FACADE
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR SECURITY CONTROL
FED FROM: SMDB-GF
ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl 2 Wire
Ref. Rating CCT Wire Size mm Room / Area Ex 13A 13A Fcu Load in Watts REMARKS
ELCB No Size Ltg. Others
No. Amps 2 Fan S/O TS/O A/C Each
mm R Y B
1 R 1 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 14 10 140 CONT. BY PHOTOCELL & TIMER
2 Y 1 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 17 10 170 CONT. BY PHOTOCELL & TIMER
40A-4P
3 B 1 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 15 10 150 CONT. BY PHOTOCELL & TIMER
ELCB-1
100mA 4 R 2 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 16 10 160 CONT. BY PHOTOCELL & TIMER
5 Y 2 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 13 10 130 CONT. BY PHOTOCELL & TIMER
6 B 2 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 14 10 140 CONT. BY PHOTOCELL & TIMER
7 R 3 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 15 10 150 CONT. BY PHOTOCELL & TIMER
8 Y 3 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 14 10 140 CONT. BY PHOTOCELL & TIMER
40A-4P
9 B 3 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 16 10 160 CONT. BY PHOTOCELL & TIMER
ELCB-2
100mA 10 R 4 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 12 24 288 CONT. BY PHOTOCELL & TIMER
11 Y 4 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 6 24 144 CONT. BY PHOTOCELL & TIMER
12 B 4 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 10 10 100 CONT. BY PHOTOCELL & TIMER
13 R 5 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 7 15 105 CONT. BY PHOTOCELL & TIMER
14 Y 5 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 22 10 220 CONT. BY PHOTOCELL & TIMER
40A TPN ISOLATOR (4 - POLE)

40A-4P
15 B 5 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 8 24 192 CONT. BY PHOTOCELL & TIMER
ELCB-3
100mA 16 R 6 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 5/2 10 / 42 134 CONT. BY PHOTOCELL & TIMER
17 Y 6 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 8 24 192 CONT. BY PHOTOCELL & TIMER
18 B 6 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 9 / 13 24 / 24 528 CONT. BY PHOTOCELL & TIMER
19 R 7 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 1 / 13 15 / 10 145 CONT. BY PHOTOCELL & TIMER
20 Y 7 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 9 10 90 CONT. BY PHOTOCELL & TIMER
40A-4P
21 B 7 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 11 / 1 15 / 10 175 CONT. BY PHOTOCELL & TIMER
ELCB-4
100mA 22 R 8 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 5 24 120 CONT. BY PHOTOCELL & TIMER
23 Y 8 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 11 24 264 CONT. BY PHOTOCELL & TIMER
24 B 8 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 1 / 11 15 / 10 125 CONT. BY PHOTOCELL & TIMER
25 R 9 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 13 24 312 CONT. BY PHOTOCELL & TIMER
26 Y 9 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 14 20 280 CONT. BY PHOTOCELL & TIMER
40A-4P
27 B 9 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 5/5 10 / 24 170 CONT. BY PHOTOCELL & TIMER
ELCB-5
100mA 28 R 10 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 2 50 100 CONT. BY PHOTOCELL & TIMER
29 Y 10 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 5 50 250 CONT. BY PHOTOCELL & TIMER
30 B 10 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 5 50 250 CONT. BY PHOTOCELL & TIMER
31 R 11 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 18 10 180 CONT. BY PHOTOCELL & TIMER
32 Y 11 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 13 10 130 CONT. BY PHOTOCELL & TIMER
40A-4P
33 B 11 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 9 10 90 CONT. BY PHOTOCELL & TIMER
ELCB-6
100mA 34 R 12 16 2X6 CU / XLPE / SWA / LSZH 6.0 FACADE LIGHTING 6 50 300 CONT. BY PHOTOCELL & TIMER
35 Y 12 16 SPARE 100
36 B 12 16 SPARE 100
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 2134 2110 2180
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 6.42 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-HVAC-GF
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: GROUND FLOOR ELE.ROOM
FED FROM: SMDB-GF
CONNECTED LOAD / POINTS
INCOMER
CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire
Ref. Rating Room / Area Ex 13A 13A 15A VAV / Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O FCU Each
mm mm R Y B
1 R 1 20 4.0 2.5 SECURITY CONTROL 1 300 300
2 Y 1 20 4.0 2.5 CORRIDOR 1 300 300
40A-4P 3 B 1 20 4.0 2.5 CORRIDOR 1 300 300
ELCB-1
100mA 4 R 2 20 4.0 2.5 ABLUTION - FEMALE PRAYER 1 300 300
5 Y 2 20 4.0 2.5 RECEPTION 1 300 300
6 B 2 20 4.0 2.5 CORRIDOR 1 300 300
7 R 3 20 4.0 2.5 FCU - STAFF DINNING 1 548 548 FCU-GF-02
8 Y 3 20 4.0 2.5 AIR CURTAIN - TRAINING ROOM 1 660 660 DAC-01
40A-4P 9 B 3 20 4.0 2.5 AIR CURTAIN - STAFF DINNING 1 660 660 DAC-01
ELCB-2
100mA 10 R 4 20 4.0 2.5 FCU - STAFF DINNING 1 548 548 FCU-GF-02
11 Y 4 20 4.0 2.5 TRAINING ROOM 1 300 300
12 B 4 20 4.0 2.5 DUBAI SERVICE CENTER 1 300 300
13 R 5 20 4.0 2.5 AIR CURTAIN - NURSERY 1 350 350 DAC-02
14 Y 5 20 4.0 2.5 TRAINING ROOM 1 300 300
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 20 4.0 2.5 MANAG. OF CUST.SER.CENTER 1 300 300


ELCB-3
100mA 16 R 6 20 4.0 2.5 NURSERY 1 300 300
17 Y 6 20 4.0 2.5 TRAINING ROOM 1 300 300
18 B 6 20 4.0 2.5 FCU - MAIN GARBAGE 1 238 238 FCU-GF-01
19 R 7 20 4.0 2.5 NURSERY 1 300 300
20 Y 7 20 4.0 2.5 TRAINING ROOM 1 300 300
40A-4P 21 B 7 20 4.0 2.5 HAPINESS & CUSTOMER 1 300 300
ELCB-4
100mA 22 R 8 20 4.0 2.5 NURSERY TOILET 1 300 300
23 Y 8 20 4.0 2.5 AIR CURTAIN - RECEPTION 1 660 660 DAC-01
24 B 8 20 4.0 2.5 HAPINESS & CUSTOMER 1 300 300
25 R 9 20 4.0 2.5 NURSERY 1 300 300
26 Y 9 20 4.0 2.5 AIR CURTAIN - RECEPTION 1 660 660 DAC-01
40A-4P 27 B 9 20 4.0 2.5 CHAIRMAN ENTRANCE 1 300 300
ELCB-5
100mA 28 R 10 20 4.0 2.5 CORRIDOR 1 300 300
29 Y 10 20 4.0 2.5 MALE PRAYER ROOM 1 300 300
30 B 10 20 4.0 2.5 AIR CURTAIN - CHAIRMAN ENT. 1 660 660 DAC-01
31 R 11 20 4.0 2.5 GUARD ROOM 1 300 300
32 Y 11 20 SPARE 100
40A-4P 33 B 11 20 4.0 2.5 FEMALE PRAYER ROOM LOBBY 1 300 300
ELCB-6
100mA 34 R 12 20 4.0 2.5 FCU - SECURITY CONTROL 1 272 272 FCU-GF-03
35 Y 12 20 SPARE 100
36 B 12 20 SPARE 100
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 4118 4280 4058
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 12.46 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-GF (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : GROUND FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

INCOMER TP 250 35 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 38.64 38.12 39.37 116.13 92.90

DB-L-GF TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 5.09 4.88 4.76 14.73 11.78

DB-L-GFA TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 5.92 6.11 5.94 17.97 14.37

DB-P-GF TP 125 35 1x4C CU/XLPE/SWA/LSZH 50 1x1Cx25 19.55 18.90 18.10 56.55 45.24

DB-HVAC-GF TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 4.12 4.28 4.06 12.46 9.96

COMPACTOR
TP 25 35 1x4C CU/XLPE/SWA/LSZH 6 1x1Cx6 1.83 1.83 1.83 5.50 4.40 100mA ELS + ALARM
GARBAGEROOM

DB-FACADE TP 32 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 2.13 2.11 2.18 6.42 5.14

MASTER CONT.
SP 20 35 1x2C CU/XLPE/SWA/LSZH 6 1x1Cx6 2.50 2.50 2.00
PANEL GAR. RM

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


38.64 38.12 39.37 116.13 92.90 TOTAL
ESMDB-DATA CENTER CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 116.13 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 92.90 kW * OVERALL /INSTALLED LOAD (TCL): 116.13 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-GF (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION : GROUND FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY 1C, LOAD
SMDB/ TYPE CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
1C/ 2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 125 35 1x4C 50 1x1Cx25 18.62 18.18 19.26 56.06 50.45
XLPE/LSZH/SWA
.
MICA GLASS-
EDB-GF TP 40 35 1x4C 10 1x1Cx10 4.20 3.91 4.26 12.37 11.13
XLPE/LSZH/SWA
MICA GLASS-
EDB-1ST TP 40 35 1x4C 10 1x1Cx10 3.02 2.85 2.79 8.66 7.79
XLPE/LSZH/SWA
MICA GLASS-
EDB-2ND TP 40 35 1x4C 10 1x1Cx10 4.21 4.00 4.34 12.55 11.29
XLPE/LSZH/SWA
MICA GLASS-
EDB-3RD TP 40 35 1x4C 10 1x1Cx10 2.52 2.43 2.73 7.68 6.91
XLPE/LSZH/SWA
MICA GLASS-
EDB-4TH TP 40 35 1x4C 10 1x1Cx10 4.67 5.00 5.13 14.80 13.32
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


18.62 18.18 19.26 56.06 50.45 TOTAL
ESMDB-DATA CENTER CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 56.06 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 50.45 kW * OVERALL /INSTALLED LOAD (TCL): 56.06 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)
App. No. E/F ………………………
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-1ST
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FIRST FLOOR ELE.ROOM
FED FROM: SMDB-1ST
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu REMARKS
ELCB No Size Size Ltg. WH SPU Others Load in Watts Each
No. Amps 2 2 Fan S/O TS/O S/O A/C
mm mm R/O R Y B
1 R 1 10 2.5 2.5 METEROLOGICAL 3 / 25 50 / 28 / M 850
2 Y 1 10 2.5 2.5 CONFIRMITY AFFAIRS,MANAGER 5 / 14 50 / 20 / M 530
40A-4P 3 B 1 10 2.5 2.5 CONFIRMITY AFFAIRS 21 28 / M 588
ELCB-1
100mA 4 R 2 10 2.5 2.5 METEROLOGICAL 20 20 / M 400
5 Y 2 10 2.5 2.5 TECHANICAL AFFAIRS SEC.MGR 9/1 50 / 150 600
6 B 2 10 2.5 2.5 SMART SOLUTION DEP. 18 28 / M 504
7 R 3 10 2.5 2.5 LIBRARY 9/8 50 / 28 / M 674
8 Y 3 10 2.5 2.5 OPEN AREA 23 28 / M 644
40A-4P 9 B 3 10 2.5 2.5 PRODUCT CONTROL 3 / 10 50 / 28 / M 480
ELCB-2
100mA 10 R 4 10 2.5 2.5 MEETING ROOM 1 13 50 650
11 Y 4 10 2.5 2.5 MEETING ROOM 2 13 50 650
40A TPN ISOLATOR (4 - POLE)

12 B 4 10 2.5 2.5 MAIN ARCHING & PANTRY 4 / 10 / 3 50 / 28 / 20 / M 540


13 R 5 10 2.5 2.5 TOILETS 11 20 / M 220
14 Y 5 16 2.5 2.5 CORRIDOR 21 50 1050
40A-4P 15 B 5 10 2.5 2.5 CONFIRMITY AFFAIRS - COVE LIGHT 18 20 / M 360
ELCB-3
100mA 16 R 6 10 2.5 2.5 LIBRARY 6 50 300
17 Y 6 10 2.5 2.5 MANAGER CONFIRMITY AFFAIRS 11 20 / M 220
18 B 6 20 4.0 4.0 PRODUCT CONTROL 5 160 800 CURTAIN
19 R 7 10 2.5 2.5 FEMALE TOILET 14 50 700
20 Y 7 20 4.0 4.0 MEETING ROOM 1 & 2 2 160 320 CURTAIN
40A-4P 21 B 7 10 2.5 2.5 CALL CENTER 13 28 / M 364
ELCB-4
100mA 22 R 8 10 2.5 2.5 MALE TOILET 14 50 700
23 Y 8 10 2.5 2.5 TOILET- EXCECUTIVE & TECH. AFFAIRS 3/9 50 / 20 / M 330
24 B 8 10 2.5 2.5 CORRIDOR & STORE 8 50 400
25 R 9 10 2.5 2.5 GRAND STAIR - LED LIGHT 28 20 / M 560
26 Y 9 20 4.0 4.0 CONFIRMITY AFFAIRS,MANAGER 7 160 1120 CURTAIN
40A-4P 27 B 9 20 4.0 4.0 CONFIRMITY AFFAIRS 8 160 1280 CURTAIN
ELCB-5
100mA 28 R 10 20 4.0 4.0 TECH. AFF. MAIN ARCH. LIBRARY 8 160 1280 CURTAIN
29 Y 10 10 SPARE 200
30 B 10 20 4.0 4.0 SMART SOLUTION DEP. 6 160 960 CURTAIN
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 6334 5664 6276
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 18.27 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-1ST
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FIRST FLOOR ELE.ROOM
FED FROM: ESMDB-GF
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 10 2.5 2.5 METEROLOGICAL, MANAGER 2 / 12 50 / 28 / M 436
2 Y 1 10 2.5 2.5 CONFIRMITY AFFAIR 2 / 1 / 11 50 / 60 / 28 / M 468
40A-4P 3 B 1 10 2.5 2.5 MAIN ARCHIVING 8 20 / M 160
ELCB-1
100mA 4 R 2 10 2.5 2.5 MALE & FEMALE TOILET 2 / 14 50 / 28 / M 492
5 Y 2 10 2.5 2.5 CORRIDOR 5 50 250
6 B 2 10 SPARE 50
7 R 3 10 2.5 2.5 MEETING ROOM-1 2 50 100
8 Y 3 10 2.5 2.5 MEETING ROOM-2 2 50 100
40A-4P 9 B 3 10 2.5 2.5 SMART SOLUTION DEP. 18 20 / M 360
ELCB-2
100mA 10 R 4 10 2.5 2.5 MEETING ROOM-1 5 20 / M 100
11 Y 4 10 2.5 2.5 MEETING ROOM-2 5 20 / M 100
12 B 4 10 2.5 2.5 CORRIDOR 4 50 200
13 R 5 20 4.0 4.0 METEROLOGICAL 3 160 480 CURTAIN
14 Y 5 10 2.5 2.5 EXCECUTIVE ,TECH.AFFAIRS 5 50 250
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 10 2.5 2.5 PRODUCT CONTROL 11 20 / M 220


ELCB-3
100mA 16 R 6 SPACE
17 Y 6 10 2.5 2.5 CORRIDOR 10 / 1 50 / 60 560
18 B 6 10 2.5 2.5 PRODUCT CONTROL 2 / 10 50 / 28 / M 380
19 R 7 10 2.5 2.5 GARBAGE & ELE ROOM 4 50 200
20 Y 7 10 2.5 2.5 TEL. ROOM 2 50 100
40A-4P 21 B 7 10 2.5 2.5 MAIN ARCHIVING 14 28 / M 392
ELCB-4
100mA 22 R 8 10 2.5 2.5 LIBRARY 10.5 20 / M 210
23 Y 8 10 2.5 2.5 TECH.AFFAIRS SEC.MANAGER 6 20 / M 120
24 B 8 10 2.5 2.5 CONFIRMITY AFFAIRS 14 28 / M 392
25 R 9 20 4.0 4.0 LCP-DB-L-1ST (ELE.ROOM) 1 200 200
26 Y 9 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO SMFD-04) 4 50 200
40A-4P 27 B 9 20 4.0 4.0 METEROLOGICAL,OPEN AREA 4 160 640 CURTAIN
ELCB-5
30mA 28 R 10 20 4.0 4.0 ELE.ROOM 2 400 800
29 Y 10 20 4.0 4.0 TEL. ROOM 1 400 400
30 B 10 SPACE
31 R 11 SPACE
32 Y 11 20 4.0 4.0 LCP-EDB-1ST (ELE.ROOM) 1 200 200
40A-4P 33 B 11 SPACE
ELCB-6
30mA 34 R 12 SPACE
35 Y 12 20 SPARE 100
36 B 12 SPACE
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 3018 2848 2794
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 8.66 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-1ST
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FIRST FLOOR ELE.ROOM
FED FROM: SMDB-1ST
INCOMER
CCT ECC CONNECTED LOAD / POINTS
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 32 4.0 4.0 METROLOGICAL 5 400 2000 RING
2 Y 1 32 4.0 4.0 CONFIRMITY AFFAIRS 5 400 2000 RING
40A-4P
3 B 1 32 4.0 4.0 CONFIRMITY AFFAIRS 4 400 1600 RING
ELCB-1
30mA 4 R 2 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
5 Y 2 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
6 B 2 32 4.0 4.0 CONFIRMITY AFFAIRS 4 400 1600 RING
7 R 3 32 4.0 4.0 METROLOGICAL & MANAGER 3 400 1200 RING
8 Y 3 32 4.0 4.0 CONFIRMITY AFFAIRS & MANAGER 3 400 1200 RING
40A-4P
9 B 3 32 4.0 4.0 CONFIRMITY AFFAIRS 4 400 1600 RING
ELCB-2
30mA 10 R 4 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
11 Y 4 32 4.0 4.0 MEETING ROOM-2 4 400 1600 RING
12 B 4 32 4.0 4.0 CALL CENTER 4 400 1600 RING
13 R 5 32 4.0 4.0 MEETING ROOM-1 4 400 1600 RING
14 Y 5 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
40A-4P
15 B 5 32 4.0 4.0 SMART SOUL. DEP 5 400 2000 RING
ELCB-3
100A TPN ISOLATOR (4 - POLE)

30mA 16 R 6 20 4.0 4.0 PANTRY - FRIDGE 1 300 300


17 Y 6 32 4.0 4.0 TECH.AFFAIRS SEC.MANAGER 5 400 2000 RING
18 B 6 32 4.0 4.0 PRODUCT CONTROL,MANAGER 4 400 1600 RING
19 R 7 20 4.0 4.0 PANTRY 2 400 800
20 Y 7 32 4.0 4.0 EXCECUTIVE 3 400 1200 RING
40A-4P
21 B 7 32 4.0 4.0 MAIN ARCHING 4 400 1600 RING
ELCB-4
30mA 22 R 8 32 4.0 4.0 LIBRARY 4 400 1600 RING
23 Y 8 32 4.0 4.0 MEETING ROOM-2 1 2 200 / 400 1000 RING
24 B 8 20 4.0 4.0 MALE & FEMALE TOILET (WC) 8 50 400
25 R 9 32 4.0 4.0 MEETING ROOM-1 5 400 2000 RING
26 Y 9 20 4.0 4.0 CORRIODR 4 200 800
40A-4P
27 B 9 20 4.0 4.0 CALL CENTER 2 400 800
ELCB-5
30mA 28 R 10 20 4.0 4.0 MALE TOILET - HAND DRYER 1 1000 1000
29 Y 10 20 4.0 4.0 FEMALE TOILET - HAND DRYER 1 1000 1000
30 B 10 20 4.0 4.0 PRODUCT CONTROL 2 400 800
31 R 11 20 4.0 4.0 MALE TOILET - HAND DRYER 1 1000 1000
32 Y 11 20 4.0 4.0 FEMALE TOILET - HAND DRYER 1 1000 1000
40A-4P
33 B 11 20 4.0 4.0 STORE,CORRIODR 2 1 200 / 400 800
ELCB-6
30mA 34 R 12 20 4.0 4.0 LIBRARY 2 400 800
35 Y 12 20 4.0 4.0 TECH.AFFAIRS SEC.MGR TOILET (WC) 1 50 50
36 B 12 20 SPARE 100
40A-4P 37 R 13 20 SPARE 100
ELCB-7 38 Y 13 20 SPARE 100
30mA 39 B 13 20 SPARE 100
Cable size : 4C 35mm2 XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 14400 13950 14600
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 42.95 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-HVAC-1ST
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FIRST FLOOR ELE.ROOM
FED FROM: SMDB-1ST
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl
Ref. Rating Room / Area Ex 13A 13A 15A VAV Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R Y B
1 R 1 20 4.0 2.5 METROLOGICAL 1 300 300
2 Y 1 20 4.0 2.5 CORRIDOR 1 300 300
40A-4P 3 B 1 20 4.0 2.5 CORRIDOR (OPEN SPACE OFFICE) 1 300 300
ELCB-1
100mA 4 R 2 20 4.0 2.5 METROLOGICAL 1 300 300
5 Y 2 20 4.0 2.5 EXCECUTIVE 1 300 300
6 B 2 20 4.0 2.5 PROCUCT CONTROL 1 300 300
7 R 3 20 4.0 2.5 OPEN AREA 1 300 300
8 Y 3 20 4.0 2.5 CORRIDOR 1 300 300
40A-4P 9 B 3 20 4.0 2.5 CALL CENTER 1 300 300
ELCB-2
100mA 10 R 4 20 4.0 2.5 LIBRARY 1 300 300
11 Y 4 20 SPARE 100
40A TPN ISOLATOR (4 - POLE)

12 B 4 20 4.0 2.5 CALL CENTER 1 300 300


13 R 5 20 4.0 2.5 LIBRARY 1 300 300
14 Y 5 20 4.0 2.5 MEETING ROOM-2 1 300 300
40A-4P 15 B 5 20 4.0 2.5 CONFIRMITY AFFAIRS 1 300 300
ELCB-3
100mA 16 R 6 20 4.0 2.5 MEETING ROOM-1 1 300 300
17 Y 6 20 4.0 2.5 CONFIRMITY AFFAIRS 1 300 300
18 B 6 20 4.0 2.5 SMART SOUL. DEP 1 300 300
19 R 7 20 4.0 2.5 LIBRARY 1 300 300
20 Y 7 20 4.0 2.5 CONFIRMITY AFFAIRS 1 300 300
40A-4P 21 B 7 20 4.0 2.5 PROCUCT CONTROL 1 300 300
ELCB-4
100mA 22 R 8 20 4.0 2.5 LIBRARY 1 300 300
23 Y 8 20 4.0 2.5 EXCECUTIVE 1 300 300
24 B 8 20 4.0 2.5 MAIN ARCHING 1 300 300
25 R 9 20 SPARE 100
26 Y 9 20 SPARE 100
40A-4P 27 B 9 20 SPARE 100
ELCB-5
100mA 28 R 10 SPACE
29 Y 10 SPACE
30 B 10 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 2500 2300 2500
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 7.30 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-1ST (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: FIRST FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 36.57 35.25 36.71 108.52 86.82

OUTGOING:

DB-L-1ST TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 6.33 5.66 6.28 18.27 14.62

DB-P-1ST TP 100 35 1x4C CU/XLPE/SWA/LSZH 35 1x1Cx16 14.40 13.95 14.60 42.95 34.36

DB-HVAC-1ST TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 2.50 2.30 2.50 7.30 5.84

FURURE LOAD TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 13.33 13.33 13.33 40.00 32.00

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


36.57 35.25 36.71 108.52 86.82 0 TOTAL
SMDB-1ST CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 108.52 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 86.82 kW * OVERALL /INSTALLED LOAD (TCL): 108.52 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-2ND
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: SECOND FLOOR ELE.ROOM
FED FROM: SMDB-2ND
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu REMARKS
ELCB No Size Size Ltg. WH SPU Others Load in Watts Each
No. Amps Fan S/O TS/O S/O A/C
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 HUMAN & FINANCIAL AFFAIR MANAGER 4 50 200
2 Y 1 10 2.5 2.5 PANTRY 3 / 3.5 50 / 20 / M 220
40A-4P
3 B 1 10 2.5 2.5 CORRIDOR ,LIFT LOBBY 8 50 400
ELCB-1
100mA 4 R 2 10 2.5 2.5 GRAND STAIR - LED LIGHT 28 20 / M 560
5 Y 2 10 2.5 2.5 TECHANICAL LEGISLATION,MANAGER 3 / 15 50 / 28 / M 570
6 B 2 10 2.5 2.5 POLICY& LEGIS.MANAGER,EXECUTIVE 9/1 50 / 150 600
7 R 3 10 2.5 2.5 MEETING ROOM 7 / 10 50 / 20 / M 550
8 Y 3 10 2.5 2.5 CORRIDOR 8 50 400
40A-4P
9 B 3 10 2.5 2.5 MANAGER ROOM 12 50 600
ELCB-2
100mA 10 R 4 10 2.5 2.5 MEETING ROOM 1 13 50 650
11 Y 4 10 2.5 2.5 SPECIFICATION , MANAGER 5 / 25 50 / 28 / M 950
63A TPN ISOLATOR (4 - POLE)

12 B 4 10 2.5 2.5 MEETING ROOM 2 13 50 650


13 R 5 10 2.5 2.5 HUMAN & FINANCIAL MANAGER 12 50 600
14 Y 5 10 2.5 2.5 HUMAN & FINANCIAL CORRIDOR 4/9 50 / 28 / M 452
40A-4P
15 B 5 16 2.5 2.5 HUMAN & FINANCIAL 58 28 / M 1624
ELCB-3
100mA 16 R 6 10 2.5 2.5 TOILET - FEMALE 14 50 700
17 Y 6 10 2.5 2.5 CORRIDOR 13 50 650
18 B 6 10 2.5 2.5 TOILET - POLICY& LEGIS.MANAGER 5/7 50 / 20 / M 390
19 R 7 20 4.0 4.0 HUMAN & FINANCIAL AFFAIR MANAGER 7 160 1120 CURTAIN
20 Y 7 10 2.5 2.5 METEROLOGY,MANGER 4 / 12 50 / 28 / M 536
40A-4P
21 B 7 20 4.0 4.0 HUMAN & FINANCIAL 12 160 1920 CURTAIN
ELCB-4
100mA 22 R 8 10 2.5 2.5 TOILET - MALE 14 50 700
23 Y 8 10 2.5 2.5 BUSINESS DEVELOP. & MANAGER 3/9 50 / 28 / M 402
24 B 8 10 SPARE 50
25 R 9 10 2.5 2.5 TOILET - MALE & FEMALE 9 20 / M 180
26 Y 9 20 4.0 4.0 MEETING ROOM,SPECIFICATION 8 160 1280 CURTAIN
40A-4P
27 B 9 20 4.0 4.0 METROLOGY,BUS.DEV. MANAGER 5 160 800 CURTAIN
ELCB-5
100mA 28 R 10 20 4.0 4.0 SPECIFICATION 12 160 1920 CURTAIN
29 Y 10 20 4.0 4.0 MEETING ROOM 1 & 2,MANAGER 4 160 640 CURTAIN
30 B 10 SPACE
Cable size : 4C 16mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 7180 6100 7034
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 20.31 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-2ND
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: SECOND FLOOR ELE.ROOM
FED FROM: ESMDB-GF
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 MANAGER (NEAR STAIR-02) 12 20 / M 240
2 Y 1 20 4.0 4.0 MANAGER (NEAR LIFT-04) 1 160 160 CURTAIN
40A-4P
3 B 1 10 2.5 2.5 HUMAN & FINANCIAL 28 28 / M 784
ELCB-1
100mA 4 R 2 10 2.5 2.5 MANAGER 4 50 200
5 Y 2 10 2.5 2.5 BUSINESS DEVELOPMENT 9 28 / M 252
6 B 2 20 4.0 4.0 MANGER,CORRIDOR NEAR STAIR-02 6 160 960 CURTAIN
7 R 3 10 2.5 2.5 MANAGER LOBBY 6 28 / M 165
8 Y 3 10 2.5 2.5 TECHNICAL LEG. & METROLOGY BUSS.DEV. MANAGER 34 20 / M 680
40A-4P
9 B 3 10 2.5 2.5 MEETING ROOM - 2 2 50 100
ELCB-2
100mA 10 R 4 10 2.5 2.5 MEETING ROOM 3 50 150
11 Y 4 SPACE
12 B 4 10 2.5 2.5 POLICY& LEG.MANAGER,EXCECUTIVE 5 50 250
13 R 5 10 2.5 2.5 MEETING ROOM - 1 2 50 100
14 Y 5 10 2.5 2.5 MANAGER,SPECIFICATIONS 3 / 10 / 4 50 / 28 / 20 / M 510
40A-4P
15 B 5 10 2.5 2.5 MANAGER 5 50 250
ELCB-3
100mA 16 R 6 10 2.5 2.5 MANAGER (NEAR STAIR-02) 8 50 400
17 Y 6 16 2.5 2.5 METROLOGY & BUS.DEV MANAGER 4 50 200
40A TPN ISOLATOR (4 - POLE)

18 B 6 10 2.5 2.5 CORRIDOR 10 / 1 50 / 57 557


19 R 7 10 2.5 2.5 MANAGER ROOMS,LOBBY 22 20 / M 440
20 Y 7 10 2.5 2.5 TECHNICAL LEG.,MANAGER & METROLOGY 2 / 11 50 / 28 / M 408
40A-4P
21 B 7 10 2.5 2.5 CORRIDOR 5 50 250
ELCB-4
100mA 22 R 8 10 2.5 2.5 ELE.ROOM,GARBAGE ROOM 4 50 200
23 Y 8 10 2.5 2.5 TEL. ROOM 2 50 100
24 B 8 10 2.5 2.5 MANAGER (NEAR STAIR-02) 13 20 / M 260
25 R 9 10 2.5 2.5 MEETING ROOM - 1 & 2 11 20 / M 220
26 Y 9 20 4.0 4.0 TECHNICAL LEG. , METROLOGY & POLICIES LEG. 9 160 1440 CURTAIN
40A-4P
27 B 9 10 2.5 2.5 POLICY& LEG.MANAGER 6 20 / M 120
ELCB-5
100mA 28 R 10 10 2.5 2.5 MALE & FEMALE TOILET 2 / 14 50 / 28 / M 492
29 Y 10 SPACE
30 B 10 10 2.5 2.5 HUMAN & FINANCIAL 28 20 / M 560
31 R 11 20 4.0 4.0 LCP-DB-L-2ND (ELE.ROOM) 1 200 200
32 Y 11 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO SMFD-04) 4 50 200
40A-4P
33 B 11 SPACE
ELCB-6
30mA 34 R 12 20 4.0 4.0 ELE.ROOM 2 400 800
35 Y 12 SPACE
36 B 12 20 4.0 4.0 BMS-DDC-2F-05 (ELE. ROOM) 1 200 200
37 R 13 20 4.0 4.0 LCP-EDB-2ND (ELE.ROOM) 1 200 200
38 Y 13 20 SPARE 50
40A-4P
39 B 13 20 SPARE 50
ELCB-7
30mA 40 R 14 20 4.0 4.0 TEL. ROOM 1 400 400
41 Y 14 SPACE
42 B 14 SPACE
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 4207 4000 4341
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 12.55 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-2ND
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: SECOND FLOOR ELE.ROOM
FED FROM: SMDB-2ND
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R Y B
1 R 1 32 4.0 4.0 CORRIDOR 5 200 1000 RING
2 Y 1 32 4.0 4.0 CORRIDOR HUMAN & FINANCE 5 400 2000 RING
40A-4P 3 B 1 32 4.0 4.0 HUMAN & FINANCIAL 3 400 1200 RING
ELCB-1
30mA 4 R 2 32 4.0 4.0 HUMAN & FINANCE MANAGER 4 400 1600 RING
5 Y 2 20 4.0 4.0 PANTRY - FRIDGE 1 300 300
6 B 2 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING
7 R 3 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING
8 Y 3 32 4.0 4.0 BUSINESS DEVELOPMENT 3 400 1200 RING
40A-4P 9 B 3 32 4.0 4.0 EXCECUTIVE 3 400 1200 RING
ELCB-2
30mA 10 R 4 32 4.0 4.0 MEETING ROOM 3 400 1200 RING
11 Y 4 20 4.0 4.0 PANTRY 2 400 800
80A TPN ISOLATOR (4 - POLE)

12 B 4 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING


13 R 5 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING
14 Y 5 20 4.0 4.0 BUSINESS DEV. MANAGER 2 400 800
40A-4P 15 B 5 32 4.0 4.0 POLICY & LEGISLATION 4 400 1600 RING
ELCB-3
30mA 16 R 6 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING
17 Y 6 32 4.0 4.0 METEROLOGY MANAGER 4 400 1600 RING
18 B 6 32 4.0 4.0 HUMAN & FINANCIAL 2 400 800
19 R 7 32 4.0 4.0 HUMAN & FINANCIAL 4 400 1600 RING
20 Y 7 32 4.0 4.0 METEROLOGY 4 400 1600 RING
40A-4P 21 B 7 32 4.0 4.0 HUMAN & FINANCE 4 400 1600 RING
ELCB-4
30mA 22 R 8 32 4.0 4.0 MEETING ROOM 4 400 1600 RING
23 Y 8 32 4.0 4.0 METEROLOGY 4 400 1600 RING
24 B 8 32 4.0 4.0 HUMAN & FINANCIAL 4 400 1600 RING
25 R 9 SPACE
26 Y 9 32 4.0 4.0 BUSINESS DEVELOPMENT 3 400 1200 RING
40A-4P 27 B 9 20 SPARE 100
ELCB-5
30mA 28 R 10 20 SPARE 100
29 Y 10 20 4.0 4.0 METEROLOGY 2 400 800
30 B 10 20 SPARE 200
Cable size : 4C 25mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 11900 11900 11500
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 35.30 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-2NDA
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: SECOND FLOOR ELE.ROOM
FED FROM: SMDB-2ND
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Size Size Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 32 4.0 4.0 HUMAN & FINANCIAL MANAGER 3 400 1200 RING
2 Y 1 32 4.0 4.0 SPECIFICATIONS 3 400 1200 RING
40A-4P 3 B 1 32 4.0 4.0 MEETING ROOM-2 1 2 200 / 400 1000
ELCB-1
30mA 4 R 2 32 4.0 4.0 MEETING ROOM-1 4 400 1600 RING
5 Y 2 32 4.0 4.0 SPECIFICATIONS 4 400 1600 RING
6 B 2 32 4.0 4.0 MEETING ROOM-2 4 400 1600 RING
7 R 3 32 4.0 4.0 MEETING ROOM-1 5 400 2000 RING
8 Y 3 32 4.0 4.0 SPECIFICATIONS 4 400 1600 RING
40A-4P 9 B 3 32 4.0 4.0 MANAGER NEAR STAIR-02 3 400 1200 RING
ELCB-2
30mA 10 R 4 32 4.0 4.0 HUMAN & FINANCE MANAGER 3 400 1200 RING
11 Y 4 32 4.0 4.0 SPECIFICATIONS 5 400 2000 RING
12 B 4 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
80A TPN ISOLATOR (4 - POLE)

13 R 5 20 4.0 4.0 MEETING ROOM-1 1 1000 1000


14 Y 5 32 4.0 4.0 TECHNICAL LEGISLATION 4 400 1600 RING
40A-4P 15 B 5 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
ELCB-3
30mA 16 R 6 20 4.0 4.0 MEETING ROOM 1 1000 1000
17 Y 6 32 4.0 4.0 TECHNICAL LEG. MANAGER 4 400 1600 RING
18 B 6 20 4.0 4.0 MALE TOILET HAND DRYER 1 1000 1000
19 R 7 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
20 Y 7 32 4.0 4.0 SPECIFICATIONS MANAGER 3 400 1200 RING
40A-4P 21 B 7 32 4.0 4.0 MANAGER NEAR STAIR-02 3 400 1200 RING
ELCB-4
30mA 22 R 8 20 4.0 4.0 MALE & FEMALE TOILET (WC) 8 50 400
23 Y 8 20 4.0 4.0 POLICY & LEGISLATION MGR. TOILET (WC) 1 50 50
24 B 8 20 4.0 4.0 TOILET FEMALE - HAND DRAYER 1 1000 1000
25 R 9 20 4.0 4.0 MEETING ROOM 1 1000 1000
26 Y 9 20 SPARE 100
40A-4P 27 B 9 20 4.0 4.0 TOILET MALE - HAND DRAYER 1 1000 1000
ELCB-5
30mA 28 R 10 32 4.0 4.0 HUMAN & FINANCIAL MANAGER 3 400 1200 RING
29 Y 10 20 SPARE 100
30 B 10 20 4.0 4.0 TOILET FEALE - HAND DRAYER 1 1000 1000
40A-4P 31 R 11 20 SPARE 100
ELCB-6 32 Y 11 SPACE
30mA 33 B 11 20 SPARE 100
Cable size : 4C 25mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 11700 11050 11100
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 33.85 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-HVAC-2ND
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FIRST FLOOR ELE.ROOM
FED FROM: SMDB-2ND
CONNECTED LOAD / POINTS
INCOMER
CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire
Ref. Rating Room / Area Ex 13A 13A 15A VAV Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R Y B
1 R 1 20 4.0 2.5 MEETING ROOM - 1 1 300 300
2 Y 1 20 4.0 2.5 TECHNICAL LEGISLATION 1 300 300
40A-4P 3 B 1 20 4.0 2.5 POLICIES & LEGISLATION MANAGER 1 300 300
ELCB-1
100mA 4 R 2 20 4.0 2.5 CORRIDOR 1 300 300
5 Y 2 20 4.0 2.5 TECHNICAL LEG. (TEL.ROOM) 1 300 300
6 B 2 20 4.0 2.5 HUMAN & FINANCIAL 1 300 300
7 R 3 20 4.0 2.5 LIFT LOBBY 1 300 300
8 Y 3 20 4.0 2.5 BUS. DEV. MANAGER 1 300 300
40A-4P 9 B 3 20 4.0 2.5 HUMAN & FINANCIAL 1 300 300
ELCB-2
100mA 10 R 4 20 4.0 2.5 HUMAN & FINANCIAL 1 300 300
11 Y 4 20 4.0 2.5 METROLOGY MANAGER 1 300 300
12 B 4 20 4.0 2.5 CORRIDOR 1 300 300
13 R 5 20 4.0 2.5 HUMAN & FINANCIAL 1 300 300
14 Y 5 20 4.0 2.5 SPECIFICATIONS 1 300 300
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 20 4.0 2.5 MEETING ROOM - 2 1 300 300


ELCB-3
100mA 16 R 6 20 4.0 2.5 MANAGER OFFICES LOBBY 1 300 300
17 Y 6 20 4.0 2.5 SPECIFICATIONS 1 300 300
18 B 6 20 4.0 2.5 HUMAN & FINANCIAL 1 300 300
19 R 7 20 4.0 2.5 MANAGER OFFICES LOBBY 1 300 300
20 Y 7 20 4.0 2.5 BUSINESS DEVELOPMENT 1 300 300
40A-4P 21 B 7 20 4.0 2.5 CORRIDOR 1 300 300
ELCB-4
100mA 22 R 8 20 4.0 2.5 MANAGER OFFICES LOBBY 1 300 300
23 Y 8 20 4.0 2.5 METROLOGY 1 300 300
24 B 8 20 4.0 2.5 MANAGER (NEAR MEETING ROOM-1) 1 300 300
25 R 9 20 4.0 2.5 MANAGER OFFICES LOBBY 1 300 300
26 Y 9 20 4.0 2.5 TECHNICAL LEGISLATION 1 300 300
40A-4P 27 B 9 20 4.0 2.5 EXCECUTIVE 1 300 300
ELCB-5
100mA 28 R 10 20 4.0 2.5 MEETING ROOM 1 300 300
29 Y 10 20 4.0 2.5 METROLOGY (ELE.ROOM) 1 300 300
30 B 10 20 4.0 2.5 MANAGER (NEAR MEETING ROOM-1) 1 300 300
31 R 11 20 SPARE 100
32 Y 11 20 SPARE 100
40A-4P 33 B 11 20 SPARE 100
ELCB-6
100mA 34 R 12 SPACE
35 Y 12 SPACE
36 B 12 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 3100 3100 3100
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 9.30 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-2ND (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: 2ND FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 33.88 32.15 32.73 98.76 79.01

OUTGOING:

DB-L-2ND TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 7.18 6.10 7.03 20.31 16.25

DB-P-2ND TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 11.90 11.90 11.50 35.30 28.24

DB-P-2NDA TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 11.70 11.05 11.10 33.85 27.08

DB-HVAC-2ND TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 3.10 3.10 3.10 9.30 7.44

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


33.88 32.15 32.73 98.76 79.01 TOTAL
SMDB-2ND CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 98.76 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 79.01 kW * OVERALL /INSTALLED LOAD (TCL): 98.76 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-3RD
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: THIRD FLOOR ELE.ROOM
FED FROM: SMDB-3RD
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu REMARKS
ELCB No Size Size Ltg. WH SPU Others Load in Watts Each
No. Amps Fan S/O TS/O S/O A/C
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 LOBBY 22 20 / M 440
2 Y 1 10 2.5 2.5 INSTITUTAIONAL MANAGER 7 / 25 50 / 28 / M 1050
40A-4P
3 B 1 10 2.5 2.5 GOVT. COMMUNICATION 23 28 / M 646
ELCB-1
100mA 4 R 2 10 2.5 2.5 NATIONAL ACCREDIATION 2 / 34 50 / 28 / M 1052
5 Y 2 20 4.0 4.0 NATIONAL ACCREDIATION 11 160 1760 CURTAIN
6 B 2 10 2.5 2.5 GOVT. COMMUNICATION MANAGER 7 50 350
7 R 3 10 2.5 2.5 OFFICE OF INT. AFFAIRS,MANAGER 4/6 50 / 20 /M 320
8 Y 3 10 2.5 2.5 GEN.DIRECTOR MEETING ROOM 55 20 / M 1100
40A-4P
9 B 3 SPACE
ELCB-2
100mA 10 R 4 10 2.5 2.5 FEMALE TOILET 14 50 700
11 Y 4 10 2.5 2.5 GEN.DIRECTOR MEETING ROOM 5 50 250
12 B 4 10 2.5 2.5 GEN.DIRECTOR SECRETARIES 6 / 12 50 / 20 540
13 R 5 10 2.5 2.5 GEN.DIRECTOR OFFICE MANAGER 7 50 350
14 Y 5 10 2.5 2.5 GEN.DIRECTOR MEETING ROOM 15 50 750
63A TPN ISOLATOR (4 - POLE)

40A-4P
15 B 5 10 2.5 2.5 MEETING ROOM 1 & 2 21 50 1050
ELCB-3
100mA 16 R 6 10 2.5 2.5 MALE & FEMALE TOILET 9 / 14 50 / 20 / M 880
17 Y 6 10 2.5 2.5 CORRIDOR,LIFT LOBBY 12 50 600
18 B 6 10 2.5 2.5 MEETING ROOM 1 & 2 17 20 / M 340
19 R 7 10 2.5 2.5 NATIONAL ACCREDIATION 27 20 / M 540
20 Y 7 10 2.5 2.5 CORRIDOR 10 50 500
40A-4P
21 B 7 20 4.0 4.0 GEN.DIRECTOR SECRETARIES 8/4 15 / 160 760 CURTAIN
ELCB-4
100mA 22 R 8 10 2.5 2.5 STORE,NATIONAL ACCREDIATION 8/9/1 50 / 28 / M / 57 709
23 Y 8 10 2.5 2.5 GENERAL DIRECTOR 1 / 12 200 / 28 / M 536
24 B 8 10 2.5 2.5 MAJLIS 8/1 50 / 60 460
25 R 9 10 2.5 2.5 GOVT. COMMUNICATION & MANAGER 24 20 / M 480
26 Y 9 10 2.5 2.5 INSTITUTAIONAL 17 20 / M 340
40A-4P
27 B 9 20 4.0 4.0 INSTITUTAIONAL ,GOV. COMUNICATION 12 160 1920 CURTAIN
ELCB-5
100mA 28 R 10 10 2.5 2.5 GRAND STAIR - LED LIGHT 28 20 / M 560
29 Y 10 10 2.5 2.5 PRIVATE LOBBY, LOBBY, COR, , PANTRY 15 / 4 50 / 20 / M 830
30 B 10 10 2.5 2.5 GEN. DIRECTOR TOILET 4/7 50 / 20 / M 380
31 R 11 10 2.5 2.5 NATIONAL ACCREDIATION & MANAGER 20 20 / M 400
32 Y 11 20 4.0 4.0 GEN.DIR.& MEETING ROOM,OFF. MGR. 16 15 240 CURTAIN
40A-4P
33 B 11 20 4.0 4.0 MEETING RM 1 & 2 NATIONAL ACC. MGR. 6 160 960 CURTAIN
ELCB-6
100mA 34 R 12 20 4.0 4.0 GOVT. COMMUNICATION & MANAGER 4 160 640 CURTAIN
35 Y 12 10 SPARE 200
36 B 12 20 4.0 4.0 MAJLIS 10 15 150 CURTAIN
Cable size : 4C 16mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 7071 8156 7556
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 22.78 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-3RD
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: THIRD FLOOR ELE.ROOM
FED FROM: ESMDB-GF
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 10 2.5 2.5 NATIONAL ACCREDITATION 4 / 22 50 / 28 / M 816
2 Y 1 10 2.5 2.5 INSTITUTIONAL 2 / 14 50 / 28 / M 492
40A-4P 3 B 1 10 2.5 2.5 GOVT. COMMUNICATION, MANAGER 3/8 50 / 28 / M 374
ELCB-1
100mA 4 R 2 10 2.5 2.5 OFFICE OF INT. AFFAIRS 1 / 18 50 / 28 / M 554
5 Y 2 10 2.5 2.5 GEN.DIRECTOR MEETING ROOM 2 50 100
6 B 2 10 2.5 2.5 MAJLIS 50 20 / M 1000
7 R 3 10 2.5 2.5 GEN.DIRECTOR OFFICE MANAGER 3 20 / M 60
8 Y 3 10 2.5 2.5 GENERAL DIRECTOR 8 28 / M 224
40A-4P 9 B 3 10 2.5 2.5 GEN.DIRECTOR SECRETARIES 3 50 150
ELCB-2
40A TPN ISOLATOR (4 - POLE)

100mA 10 R 4 10 2.5 2.5 CORRIDOR,OFFICE OF INT. AFFAIRS 2 50 100


11 Y 4 10 SPARE 50
12 B 4 10 2.5 2.5 CORRIDOR,LIFT LOBBY 10 / 1 50 / 57 557
13 R 5 10 2.5 2.5 MALE & FEMALE TOILET 2 / 14 50 / 28 / M 492
14 Y 5 10 2.5 2.5 GENERAL DIRECTOR 8 20 / M 160
40A-4P 15 B 5 10 2.5 2.5 MEETING ROOM- 1 & 2 4 50 200
ELCB-3
100mA 16 R 6 10 2.5 2.5 ELE.ROOM & GARBAGE ROOM 4 50 200
17 Y 6 10 2.5 2.5 TEL. ROOM 2 50 100
18 B 6 10 SPARE 50
19 R 7 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO SMFD-04) 4 50 200
20 Y 7 20 4.0 4.0 TEL. ROOM 1 400 400
40A-4P 21 B 7 20 4.0 4.0 LCP-EDB-3RD (ELE.ROOM) 1 200 200
ELCB-4
30mA 22 R 8 SPACE
23 Y 8 20 4.0 4.0 ELE.ROOM 2 400 800
24 B 8 20 4.0 4.0 LCP-DB-L-3RD (ELE.ROOM) 1 200 200
40A-4P 25 R 9 20 SPARE 100
ELCB-5 26 Y 9 20 SPARE 100
30mA 27 B 9 SPACE
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 2522 2426 2731
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 7.68 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-3RD
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: 3RD FLOOR ELE.ROOM
FED FROM: SMDB-3RD
CCT ECC CONNECTED LOAD / POINTS

INCOMER
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 32 4.0 4.0 MAJLIS 1 5 200 / 400 2200 RING
2 Y 1 32 4.0 4.0 PRIVATE LOBBY,CORRIDOR 6 2 200 / 400 2000 RING
40A-4P 3 B 1 32 4.0 4.0 GENERAL DIRECTOR SECRETARIES 4 400 1600 RING
ELCB-1
30mA 4 R 2 32 4.0 4.0 GENERAL DIRECTOR OFF.MANAGER 3 400 1200 RING
5 Y 2 32 4.0 4.0 GENERAL DIRECTOR 5 400 2000 RING
6 B 2 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
7 R 3 32 4.0 4.0 OFFICE OF INT. AFFAIRS 3 400 1200 RING
8 Y 3 32 4.0 4.0 GENERAL DIRECTOR MEETING ROOM 1 3 200 / 400 1400 RING
40A-4P 9 B 3 32 4.0 4.0 MEETING ROOM - 1 4 400 1600 RING
ELCB-2
30mA 10 R 4 32 4.0 4.0 NATIONAL ACCREDITATION,MANAGER 4 400 1600 RING
11 Y 4 32 4.0 4.0 GENERAL DIRECTOR MEETING ROOM 4 400 1600 RING
12 B 4 32 4.0 4.0 MEETING ROOM - 2 4 400 1600 RING
13 R 5 32 4.0 4.0 PANTRY 3 400 1200 RING
14 Y 5 32 4.0 4.0 GENERAL DIRECTOR MEETING ROOM 3 400 1200 RING
40A-4P 15 B 5 32 4.0 4.0 MEETING ROOM - 2 4 400 1600 RING
ELCB-3
30mA 16 R 6 20 4.0 4.0 TOILET MALE - HAND DRAYER 1 1000 1000
17 Y 6 20 4.0 4.0 GEN.DIRECTOR MEETING ROOM 1 1000 1000
18 B 6 32 4.0 4.0 MEETING ROOM - 2 1 2 200 / 400 1000 RING
19 R 7 20 4.0 4.0 TOILET GEN.DIRECTOR - HAND DRAYER 1 1000 1000
125A TPN ISOLATOR (4 - POLE)

20 Y 7 20 4.0 4.0 TOILET FEMALE - HAND DRAYER 1 1000 1000


40A-4P 21 B 7 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
ELCB-4
30mA 22 R 8 20 4.0 4.0 GEN.DIRECTOR-TOILET (WC) 1 50 50
23 Y 8 20 4.0 4.0 INSTITUTIONAL 2 400 800
24 B 8 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
25 R 9 32 4.0 4.0 NATIONAL ACCREDITATION 3 400 1200 RING
26 Y 9 32 4.0 4.0 INSTITUTIONAL 4 400 1600 RING
40A-4P 27 B 9 32 4.0 4.0 GOVT. COMM. & MANGER 3 400 1200 RING
ELCB-5
30mA 28 R 10 32 4.0 4.0 NATIONAL ACCREDITATION 4 400 1600 RING
29 Y 10 20 4.0 4.0 MALE & FEMALE TOILET (WC) 8 50 400
30 B 10 32 4.0 4.0 GOVT. COMMUNICATION 5 400 2000 RING
31 R 11 32 4.0 4.0 NATIONAL ACCREDITATION 4 400 1600 RING
32 Y 11 32 4.0 4.0 INSTITUTIONAL 5 400 2000 RING
40A-4P 33 B 11 32 4.0 4.0 GOVT. COMMUNICATION 3 400 1200 RING
ELCB-6
30mA 34 R 12 32 4.0 4.0 NATIONAL ACCREDITATION 4 400 1600 RING
35 Y 12 32 4.0 4.0 INSTITUTIONAL, MANAGER 4 400 1600 RING
36 B 12 32 4.0 4.0 NATIONAL ACCREDITATION 3 400 1200 RING
37 R 13 32 4.0 4.0 OFFICE OF INT. AFFAIRS, MANAGER 3 400 1200 RING
38 Y 13 32 SPARE 200
40A-4P 39 B 13 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
ELCB-7
30mA 40 R 14 20 4.0 4.0 NATIONAL ACCREDITATION 2 400 800
41 Y 14 32 SPARE 100
42 B 14 20 4.0 4.0 GEN.DIRECTOR MEETING ROOM 1 1000 1000
43 R 15 20 4.0 4.0 TOILET MALE - HAND DRAYER 1 1000 1000
44 Y 15 20 4.0 4.0 TOILET FEMALE - HAND DRAYER 1 1000 1000
40A-4P 45 B 15 20 SPARE 100
ELCB-8
30mA 46 R 16 20 SPARE 100
47 Y 16 SPACE
48 B 16 20 SPARE 100
Cable size : 4C 50mm2 CU/XLPE/SWA/LSZH
1C 25mm2 PVC Y/G AS ECC 18550 17900 18200
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 54.65 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-HVAC-3RD
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: 3RD FLOOR ELE.ROOM
FED FROM: SMDB-3RD
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Wire Wire Load per circuit in Watts
Rating of Sl
Ref. Rating Room / Area Ex 13A 13A 15A VAV Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R Y B
1 R 1 20 4.0 2.5 MAJLIS 1 300 300
2 Y 1 20 4.0 2.5 PRIVATE LOBBY 1 300 300
40A-4P 3 B 1 20 4.0 2.5 GENERAL DIRECTOR SECRETARIES 1 300 300
ELCB-1
100mA 4 R 2 20 4.0 2.5 GENERAL DIRECTOR OFF.MANAGER 1 300 300
5 Y 2 20 4.0 2.5 GENERAL DIRECTOR 1 300 300
6 B 2 20 4.0 2.5 GOVT. COMMUNICATION 1 300 300
7 R 3 20 4.0 2.5 OFFICE OF INT. AFFAIRS 1 300 300
8 Y 3 20 4.0 2.5 GENERAL DIRECTOR MEETING ROOM 1 300 300
40A-4P 9 B 3 20 4.0 2.5 CORRIDOR 1 300 300
ELCB-2
40A TPN ISOLATOR (4 - POLE)

100mA 10 R 4 20 4.0 2.5 OFFICE OF INT. AFFAIRS 1 300 300


11 Y 4 20 4.0 2.5 LIFT LOBBY 1 300 300
12 B 4 20 4.0 2.5 GOVT. COMMUNICATION 1 300 300
13 R 5 20 4.0 2.5 NATIONAL ACCREDITATION 1 300 300
14 Y 5 20 4.0 2.5 INSTITUTIONAL 1 300 300
40A-4P 15 B 5 20 4.0 2.5 NATIONAL ACCREDITATION 1 300 300
ELCB-3
100mA 16 R 6 20 4.0 2.5 NATIONAL ACCREDITATION 1 300 300
17 Y 6 20 4.0 2.5 INSTITUTIONAL 1 300 300
18 B 6 20 4.0 2.5 MEETING ROOM-1 1 300 300
19 R 7 20 4.0 2.5 NATIONAL ACCREDITATION 1 300 300
20 Y 7 20 4.0 2.5 INSTITUTIONAL 1 300 300
40A-4P 21 B 7 20 4.0 2.5 MEETING ROOM-2 1 300 300
ELCB-4
100mA 22 R 8 20 4.0 2.5 CORRIDOR 1 300 300
23 Y 8 20 SPARE 100
24 B 8 20 4.0 2.5 GOVT. COMMUNICATION 1 300 300
40A-4P 25 R 9 20 SPARE 100
ELCB-5 26 Y 9 20 SPARE 100
100mA 27 B 9 20 SPARE 100
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 2500 2300 2500
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 7.30 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-3RD (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: 3RD FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 200 50 1x4C CU/XLPE/SWA/LSZH 95 1x1Cx50 28.12 28.36 28.26 84.73 67.79

OUTGOING:

DB-L-3RD TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 7.07 8.16 7.56 22.78 18.23

DB-P-3RD TP 125 35 1x4C CU/XLPE/SWA/LSZH 50 1x1Cx25 18.55 17.90 18.20 54.65 43.72

DB-HVAC-3RD TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 2.50 2.30 2.50 7.30 5.84

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


28.12 28.36 28.26 84.73 67.79 TOTAL
SMDB-3RD CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 84.73 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 67.79 kW * OVERALL /INSTALLED LOAD (TCL): 84.73 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-L-4TH
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FOURTH FLOOR ELE.ROOM
FED FROM: SMDB-4TH
CCT ECC CONNECTED LOAD / POINTS
INCOMER Rating of Sl
Circuit MCB Wire Wire 13A
Load per circuit in Watts
Ref. Rating Room / Area Ex 13A 13A 15A Fcu REMARKS
ELCB No Size Size Ltg. WH SPU Others Load in Watts Each
No. Amps Fan S/O TS/O S/O A/C
mm2 mm2 R/O R Y B
1 R 1 10 2.5 2.5 MANAGER IHAF STAFF 6 / 12 50 / 20 / M 540
2 Y 1 10 2.5 2.5 IHAF STAFF 4 / 28 50 / 28 / M 984
40A-4P 3 B 1 10 2.5 2.5 MANAGER & CORPORATE GOVERNANCE 3/9 50 / 28 / M 402
ELCB-1
100mA 4 R 2 10 2.5 2.5 INTERNAL AUDIT,COUNSELOR 15 50 750
5 Y 2 10 2.5 2.5 PRIVATE LOBBY, LOBBY 11 50 550
6 B 2 10 2.5 2.5 BOARD ROOM 7 50 350
7 R 3 10 2.5 2.5 MAJLIS 8/1 50 / 77 477
8 Y 3 10 2.5 2.5 CHAIRMAN'S OFF. MANAGER,SECRETARY 4/5/6 50 / 28 / 20 / M 460
40A-4P 9 B 3 10 2.5 2.5 BOARD ROOM 14 50 700
ELCB-2
100mA 10 R 4 10 2.5 2.5 GRAND STAIR - LED LIGHT 28 20 / M 560
11 Y 4 10 2.5 2.5 IHAF STAFF 14 20 / M 280
12 B 4 10 2.5 2.5 MEETING ROOM 2 15 50 750
13 R 5 10 2.5 2.5 IHAF, IHAF GENERAL 1 / 11 50 / 28 / M 358
14 Y 5 10 2.5 2.5 CHAIRMAN OFFICE 1/3 50 / 100 350
40A-4P 15 B 5 10 2.5 2.5 MANAGER CORPORATE GOVERANCE 13 20 / M 260
ELCB-3
100mA 16 R 6 10 2.5 2.5 COUNSELOR-1 & 2 & INTERNAL AUDIT 15 20 / M 300
17 Y 6 20 4.0 4.0 CHAIRMAN OFFICE & METTING,MAJLIS 16 15 240 CURTAIN
63A TPN ISOLATOR (4 - POLE)

18 B 6 10 2.5 2.5 MEETING ROOM 1 10 50 500


19 R 7 10 2.5 2.5 CORRIDOR, LIFT LOBBY 10 50 500
20 Y 7 20 4.0 4.0 IHAF STAFF 10 160 1600 CURTAIN
40A-4P 21 B 7 10 2.5 2.5 BOARD ROOM 12 50 600
ELCB-4
100mA 22 R 8 10 2.5 2.5 CORRIDOR , PANTRY 7 / 5.5 50 / 20 / M 460
23 Y 8 20 4.0 4.0 IHAF,IHAF GENERAL 9 160 1440 CURTAIN
24 B 8 10 2.5 2.5 IHAF GENERAL MANAGER TOILET 4/2 50 / 20 / M 240
25 R 9 10 2.5 2.5 IHAF, IHAF ASSISTANT 9/1 50 / 150 600
26 Y 9 SPACE
40A-4P 27 B 9 10 2.5 2.5 MALE & FEMALE TOILET 14 / 9 50 / 20 / M 880
ELCB-5
100mA 28 R 10 10 SPARE 200
29 Y 10 10 2.5 2.5 INTERNAL AUDIT CORRIDOR 2/7 50 / 28 / M 296
30 B 10 10 2.5 2.5 MALE TOILET 14 50 700
40A-4P 31 1333
20A 4C,6
ELCB-6 32 RYB 11 6.0 ATRIUM - CHANDLIER 1 1 4000 1333
TPN mm2
100mA 33 1333
40A-4P 34 R 12 20 4.0 4.0 COU.-1 & 2 & IN. AUDIT,MGR & COR. GOV. 7 160 1120 CURTAIN
ELCB-7 35 Y 12 10 2.5 2.5 CHAIRMAN OFFICE TOILET 5/2 50 / 20 / M 290
100mA 36 B 12 20 4.0 4.0 MEETING ROOM 1 & 2 4 160 640 CURTAIN
37 R 13 20 4.0 4.0 CHA. OFF. MGR & SEC. ,BOARD ROOM 10 / 3 15 / 160 630 CURTAIN
38 Y 13 SPACE
40A-4P 39 B 13 10 2.5 2.5 CHAIRMAN'S MEETING ROOM 9 50 450
ELCB-8
100mA 40 R 14 SPACE
41 Y 14 10 2.5 2.5 CORRIDOR 13 / 1 50 / 57 707
42 B 14 SPACE
Cable size : 4C 16mm2 CU/XLPE/SWA/LSZH
1C 16mm2 PVC Y/G AS ECC 7828 8530 7805
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 24.16 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: EDB-4TH
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: FOURTH FLOOR ELE.ROOM
FED FROM: ESMDB-GF
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R/O R Y B
1 R 1 10 2.5 2.5 MANAGER ROOMS - IHAF STAFF 4 50 200
2 Y 1 10 2.5 2.5 IHAF STAFF 22 28 / M 616
40A-4P 3 B 1 10 2.5 2.5 MEETING ROOM 1 & 2 18.5 20 / M 370
ELCB-1
100mA 4 R 2 10 2.5 2.5 INTERNAL AUDIT OFFICE 10 50 500
5 Y 2 10 2.5 2.5 CHAIRMAN MEETING ROOM 16 20 / M 320
6 B 2 10 2.5 2.5 BOARD ROOM 98 20 / M 1960
7 R 3 10 2.5 2.5 PRIVATE LOBBY & LOBBY 34 20 / M 680
8 Y 3 10 2.5 2.5 CHAIRMAN MEETING ROOM 1 125 125
40A-4P 9 B 3 10 2.5 2.5 BOARD ROOM 18 20 / M 360
ELCB-2
100mA 10 R 4 10 2.5 2.5 MAJLIS 48 20 / M 960
11 Y 4 10 2.5 2.5 CHAIRMAN OFFICE 49 20 / M 980
12 B 4 10 2.5 2.5 BOARD ROOM 7 50 350
13 R 5 10 2.5 2.5 CORRIDOR 10 50 500
14 Y 5 10 2.5 2.5 CHAIRMAN OFF. MANAGER & SECRETARY 3/3 50 / 28 / M 234
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 10 2.5 2.5 TEL. ROOM 2 50 100


ELCB-3
100mA 16 R 6 10 2.5 2.5 IHAF, IHAF GENERAL,CORRIDOR 24 20 / M 480
17 Y 6 20 4.0 4.0 CORRIDOR (NEAR STAIR-02) 2 160 320
18 B 6 10 2.5 2.5 CORPORATIVE GOVERANCE MANAGER 2 50 100
19 R 7 10 2.5 2.5 ELE.ROOM & GRABAGE ROOM 4 50 200
20 Y 7 20 4.0 4.0 LIFT - 4 LIGHTING 1 500 500
40A-4P 21 B 7 10 2.5 2.5 MALE & EFMALE TOILET 2 / 14 50 / 28 / M 492
ELCB-4
100mA 22 R 8 20 4.0 4.0 LIFT - 1 LIGHTING 1 500 500
23 Y 8 20 4.0 4.0 LIFT - 2 LIGHTING 1 500 500
24 B 8 20 4.0 4.0 LIFT - 3 LIGHTING 1 500 500
25 R 9 20 4.0 4.0 LCP-DB-L-4TH (ELE.ROOM) 1 200 200
26 Y 9 20 4.0 4.0 ELE.ROOM 2 400 800
40A-4P 27 B 9 20 4.0 4.0 TEL. ROOM 1 400 400
ELCB-5
30mA 28 R 10 20 SPARE 200
29 Y 10 20 4.0 4.0 M. DAMPER (SMFD-01 TO MD-06) -U.FLOOR 6 50 300
30 B 10 20 4.0 4.0 ELE.ROOM UTILITY FLOOR (OBS. LCP) 1 200 200
31 R 11 20 4.0 4.0 LCP-EDB-4TH (ELE.ROOM) 1 200 200
32 Y 11 20 4.0 4.0 M. DAMPER- (SMFD-07 TO CAV-12) - U.FLOOR 6 50 300
40A-4P 33 B 11 20 4.0 4.0 MOTORIZED DAMPER (SMFD-01 TO SMFD-04) 4 50 200
ELCB-6
30mA 34 R 12 20 Spare 50 50
35 Y 12 SPACE
36 B 12 20 SPARE 100
Cable size : 4C 10mm2 MICA GLASS-XLPE/LSZH/SWA
1C 10mm2 PVC Y/G AS ECC 4670 4995 5132
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 14.80 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-P-4TH
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: 4TH FLOOR ELE.ROOM
FED FROM: SMDB-4TH
CONNECTED LOAD / POINTS

INCOMER
CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire 13A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O R Y B
1 R 1 32 4.0 4.0 MANAGER - IHAF STAFF 3 400 1200 RING
2 Y 1 32 4.0 4.0 IHAF ASSISTANT 4 400 1600 RING
40A-4P
3 B 1 32 4.0 4.0 BOARD ROOM 4 400 1600 RING
ELCB-1
30mA 4 R 2 32 4.0 4.0 MANAGER - IHAF STAFF 4 400 1600 RING
5 Y 2 32 4.0 4.0 IHAF STAFF 2 2 400 1200 RING
6 B 2 32 4.0 4.0 BOARD ROOM 5 400 2000 RING
7 R 3 32 4.0 4.0 IHAF GENERAL 4 400 1600 RING
8 Y 3 32 4.0 4.0 IHAF STAFF 5 400 2000 RING
40A-4P
9 B 3 20 4.0 4.0 BOARD ROOM 1 1000 1000
ELCB-2
30mA 10 R 4 32 4.0 4.0 IHAF 3 400 1200 RING
11 Y 4 32 4.0 4.0 IHAF STAFF 4 400 1600 RING
12 B 4 32 4.0 4.0 BOARD ROOM 2 4 200 / 400 2000 RING
13 R 5 32 4.0 4.0 COUNSELOR-1 & 2 5 400 2000 RING
14 Y 5 32 4.0 4.0 IHAF STAFF 4 400 1600 RING
40A-4P
15 B 5 32 4.0 4.0 COR. GOVERANCE & MANAGER 6 400 2400 RING
ELCB-3
30mA 16 R 6 32 4.0 4.0 INTERNAL AUDIT 4 400 1600 RING
17 Y 6 32 4.0 4.0 CHAIRMAN MEETING ROOM 5 400 2000 RING
18 B 6 32 4.0 4.0 MEETING ROOM-2 1 2 200 / 400 1000 RING
19 R 7 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
20 Y 7 32 4.0 4.0 IHAF STAFF 5 400 2000 RING
40A-4P
21 B 7 20 4.0 4.0 TOILET FEMALE - HAND DRAYER 1 1000 1000
125A TPN ISOLATOR (4 - POLE)

ELCB-4
30mA 22 R 8 20 4.0 4.0 CORRIDOR 4 200 800
23 Y 8 32 4.0 4.0 CHAIRMAN OFF. MANAGER 3 400 1200 RING
24 B 8 20 4.0 4.0 BOARD ROOM 1 1000 1000
25 R 9 20 4.0 4.0 TOILET MALE - HAND DRAYER 1 1000 1000
26 Y 9 32 4.0 4.0 CHAIRMAN OFFICE 2 4 400 2000 RING
40A-4P
27 B 9 20 4.0 4.0 IHAF GENERAL -TOILET (WC) 1 50 50
ELCB-5
30mA 28 R 10 20 4.0 4.0 CHAIRMAN MEETING ROOM 1 1000 1000
29 Y 10 32 4.0 4.0 CHAIRMAN MEETING ROOM 1 3 400 1400 RING
30 B 10 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
31 R 11 32 4.0 4.0 MAJLIS 1 5 200 / 400 2200 RING
32 Y 11 20 4.0 4.0 MALE & FEMALE TOILET (WC) 8 50 400
40A-4P
33 B 11 32 4.0 4.0 MEETING ROOM-1 4 400 1600 RING
ELCB-6
30mA 34 R 12 32 4.0 4.0 LOBBY,CORRIDOR 2 2 200 / 400 1200 RING
35 Y 12 20 4.0 4.0 CHAIRMAN OFFICE -TOILET (WC) 1 50 50
36 B 12 32 4.0 4.0 MEETING ROOM-1 4 400 1600 RING
37 R 13 20 4.0 4.0 PANTRY 2 400 800
38 Y 13 32 4.0 4.0 IHAF STAFF 4 400 1600 RING
40A-4P
39 B 13 20 4.0 4.0 MEETING ROOM-1 1 1000 1000
ELCB-7
30mA 40 R 14 20 4.0 4.0 PANTRY FRIDGE 1 300 300
41 Y 14 32 4.0 4.0 CHAIRMAN SECRETARY 3 400 1200 RING
42 B 14 32 4.0 4.0 MEETING ROOM-2 4 400 1600 RING
43 R 15 20 4.0 4.0 MEETING ROOM-2 1 1000 1000
44 Y 15 20 SPARE 100
40A-4P
45 B 15 20 4.0 4.0 TOILET FEMALE - HAND DRAYER 1 1000 1000
ELCB-8
30mA 46 R 16 20 4.0 4.0 CHAIRMAN MEETING ROOM 1 1000 1000
47 Y 16 32 SPARE 100
48 B 16 32 SPARE 100
40A-4P 49 R 17 20 4.0 4.0 TOILET MALE - HAND DRAYER 1 1000 1000
ELCB-9 50 Y 17 SPACE
30mA 51 B 17 SPACE
Cable size : 4C 50mm2 CU/XLPE/SWA/LSZH
1C 25mm2 PVC Y/G AS ECC 20500 20050 19950
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 60.50 KW
PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-HVAC-4TH
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: 4TH FLOOR ELE.ROOM
FED FROM: SMDB-4TH
CONNECTED LOAD / POINTS
INCOMER

CCT ECC
Circuit MCB Load per circuit in Watts
Rating of Sl Wire Wire
Ref. Rating Room / Area Ex 13A 13A 15A VAV Load in Watts REMARKS
ELCB No Size Size Ltg. WH Others
No. Amps 2 2 Fan S/O TS/O S/O A/C Each
mm mm R Y B
1 R 1 20 4.0 2.5 MAJLIS 1 300 300
2 Y 1 20 4.0 2.5 CHAIRMAN SECRETARY 1 300 300
40A-4P 3 B 1 20 4.0 2.5 BOARD ROOM 1 300 300
ELCB-1
100mA 4 R 2 20 4.0 2.5 INTERNAL AUDIT 1 300 300
5 Y 2 20 4.0 2.5 CHAIRMAN OFFICE MANAGER 1 300 300
6 B 2 20 4.0 2.5 BOARD ROOM 1 300 300
7 R 3 20 4.0 2.5 INTERNAL AUDIT 1 300 300
8 Y 3 20 4.0 2.5 IHAF STAFF 1 300 300
40A-4P 9 B 3 20 4.0 2.5 BOARD ROOM 1 300 300
ELCB-2
100mA 10 R 4 20 4.0 2.5 INTERNAL AUDIT 1 300 300
11 Y 4 20 4.0 2.5 IHAF STAFF 1 300 300
12 B 4 20 4.0 2.5 BOARD ROOM 1 300 300
13 R 5 20 4.0 2.5 INTERNAL AUDIT 1 300 300
14 Y 5 20 4.0 2.5 IHAF STAFF 1 300 300
40A TPN ISOLATOR (4 - POLE)

40A-4P 15 B 5 20 4.0 2.5 CORPORATIVE GOVERANCE MANAGER 1 300 300


ELCB-3
100mA 16 R 6 20 4.0 2.5 IHAF STAFF MANAGER 1 300 300
17 Y 6 20 4.0 2.5 IHAF ASSISTANT 1 300 300
18 B 6 20 4.0 2.5 CORPORATIVE GOVERANCE 1 300 300
19 R 7 20 4.0 2.5 IHAF STAFF MANAGER 1 300 300
20 Y 7 20 4.0 2.5 CORRIDOR 1 300 300
40A-4P 21 B 7 20 4.0 2.5 INTERNAL AUDIT CORRIDOR 1 300 300
ELCB-4
100mA 22 R 8 20 4.0 2.5 IHAF GENERAL 1 300 300
23 Y 8 20 4.0 2.5 CHAIRMAN MEETING ROOM 1 300 300
24 B 8 20 4.0 2.5 MEETING ROOM - 1 1 300 300
25 R 9 20 4.0 2.5 IHAF 1 300 300
26 Y 9 20 4.0 2.5 CHAIRMAN MEETING ROOM 1 300 300
40A-4P 27 B 9 20 4.0 2.5 MEETING ROOM - 2 1 300 300
ELCB-5
100mA 28 R 10 20 4.0 2.5 LOBBY NEAR STAIR - 01 1 300 300
29 Y 10 20 4.0 2.5 LIFT LOBBY 1 300 300
30 B 10 20 4.0 2.5 CORRIDOR 1 300 300
31 R 11 20 4.0 2.5 CORRIDOR 1 300 300
32 Y 11 20 SPARE 100
40A-4P 33 B 11 20 SPARE 100
ELCB-6
100mA 34 R 12 20 SPARE 100
35 Y 12 20 SPARE 100
36 B 12 SPACE
Cable size : 4C 10mm2 CU/XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 3400 3200 3100
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 9.70 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-4TH (FEED FROM MDB-02) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: 4TH FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 250 50 1x4C CU/XLPE/SWA/LSZH 150 1x1Cx70 33.40 33.45 32.52 99.36 79.49

OUTGOING:

DB-L-4TH TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 7.83 8.53 7.81 24.16 19.33

DB-P-4TH TP 125 35 1x4C CU/XLPE/SWA/LSZH 50 1x1Cx25 20.50 20.05 19.95 60.50 48.40

DB-HVAC-4TH TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 3.40 3.20 3.10 9.70 7.76

ISO-GSM ROOM TP 20 35 1x4C CU/XLPE/SWA/LSZH 6 1x1Cx6 1.67 1.67 1.67 5.00 4.00 100mA ELS + ALARM

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


33.40 33.45 32.52 99.36 79.49 TOTAL
SMDB-4TH CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 99.36 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 79.49 kW * OVERALL /INSTALLED LOAD (TCL): 99.36 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: Emirates Authority For Plot No. 2641059
LOAD DISTRIBUTION SCHEDULE
Standardization And Metrology Sheet No. 1 OF 1
D.B. IDENTIFICATION: DB-RF
CLIENT: Emirates Real Estate Corp. LOCATION OF DB: UTILITY FLOOR ELE.ROOM
FED FROM: SMDB-RF
CCT ECC CONNECTED LOAD / POINTS
INCOMER

Circuit MCB Load per circuit in Watts


Rating of Sl Wire Wire 13A 16A
Ref. Rating Room / Area Ex 13A 13A 15A Fcu Load in Watts REMARKS
ELCB No Size Size Ltg. WH SPU INDS.SO Others
No. Amps Fan S/O TS/O S/O A/C Each
mm2 mm2 R/O CKET R Y B
1 R 1 10 2.5 2.5 CHILLER PUMP ROOM,MCC ROOM 13 50 650
2 Y 1 10 2.5 2.5 ROOF 7 50 350
40A-4P
3 B 1 10 2.5 2.5 ROOF 5 50 250
ELCB-1
100mA 4 R 2 10 2.5 2.5 ROOF 6 50 300
5 Y 2 10 2.5 2.5 ROOF 6 50 300
6 B 2 10 2.5 2.5 ELE.ROOM,GRABAGE VENT.ROOM,GSM ROOM 5 50 250
7 R 3 20 4.0 4.0 ELECTRICAL ROOM 1 455 455 FCU-UF-03
8 Y 3 20 4.0 4.0 CHILLER PUMP ROOM 1 162 162 FCU-UF-04
40A-4P
9 B 3 20 4.0 4.0 MCC ROOM 1 445 445 FCU-UF-01
ELCB-2
100mA 10 R 4 20 4.0 4.0 CHILLER PUMP ROOM 1 162 162 FCU-UF-04
11 Y 4 20 4.0 4.0 GSM ROOM 1 445 445 FCU-UF-02
40A TP ISOLATOR (4 - POLE)

12 B 4 20 SPARE 100
13 R 5 20 4.0 4.0 MCC ROOM 2 400 800
14 Y 5 20 4.0 4.0 ROOF PARAPET WALL 3 200 600
40A-4P
15 B 5 20 4.0 4.0 ELE CTRICAL ROOM 2 400 800
ELCB-3
30mA 16 R 6 20 4.0 4.0 CHILLER PUMP ROOM 3 200 600
17 Y 6 20 4.0 4.0 CHEMICAL DOSING UNIT 1 800 800
18 B 6 20 4.0 4.0 GSM ROOM 2 400 800
19 R 7 20 4.0 4.0 BMS-DDC-RF-08 (MCC ROOM) 1 200 200
20 Y 7 32 4.0 4.0 ROOF PARAPET WALL 5 200 1000 RING
40A-4P
21 B 7 20 4.0 4.0 BMS-DDC-RF-06 (ELE. ROOM) 1 200 200
ELCB-4
30mA 22 R 8 20 4.0 4.0 MCC ROOM (CHILLER PLANT MANAGER) 1 400 400
23 Y 8 20 4.0 4.0 EX.FAN - CHILLER ROOM (EAF-UF-01) 1 100 100
24 B 8 20 4.0 4.0 BMS-DDC-RF-07 (ELE. ROOM) 1 200 200
25 R 9 20 4.0 4.0 ROOF PARAPET WALL 2 200 400
26 Y 9 20 SPARE 100
40A-4P
27 B 9 20 4.0 4.0 UV STERLIZER 1 800 800
ELCB-5
30mA 28 R 10 SPACE
29 Y 10 20 SPARE 100
30 B 10 20 SPARE 100
Cable size : 4C 10mm2 XLPE/SWA/LSZH
1C 10mm2 PVC Y/G AS ECC 3967 3957 3945
Ltg : Lights,EX.Fan : Exhaust fan,S/o : Socket,WH : Water Heater,FCU : Fan Coil Unit TOTAL CONNECTED LOAD 11.87 KW
PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

SMDB-RF (FEED FROM MDB-01) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: UTILITY FLOOR ELE.ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 300 50 1x4C CU/XLPE/SWA/LSZH 185 1x1Cx95 47.33 46.58 46.57 140.48 112.38

OUTGOING:

AHU-01 TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 10.00 10.00 10.00 30.00 24.00 100mA ELS+TIMER+ALARM

AHU-02 TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 12.33 12.33 12.33 37.00 29.60 100mA ELS+TIMER+ALARM

AHU-03 TP 80 35 1x4C CU/XLPE/SWA/LSZH 25 1x1Cx16 10.00 10.00 10.00 30.00 24.00 100mA ELS+TIMER+ALARM

FAHU-01 TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 6.96 6.96 6.96 20.87 16.70 100mA ELS+TIMER+ALARM

HWCP - FOR
SP 20 35 1x2C CU/XLPE/SWA/LSZH 6 1x1Cx6 0.37 0.37 0.30 100mA ELS+TIMER+ALARM
SOLAR PANEL
HWCP - FOR
SP 20 35 1x2C CU/XLPE/SWA/LSZH 6 1x1Cx6 0.37 0.37 0.30 100mA ELS+TIMER+ALARM
BUILDING
SOLAR SYSTEM
TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 3.33 3.33 3.33 10.00 8.00 100mA ELS+TIMER+ALARM
BACKUP

DB-RF TP 40 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 3.97 3.96 3.95 11.87 9.50

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


47.33 46.58 46.57 140.48 112.38 TOTAL
SMDB-4TH CONNECTED TO MDB-02 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 140.48 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 112.38 kW * OVERALL /INSTALLED LOAD (TCL): 140.48 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

MCC-CH (FEED FROM MDB-01) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: UTILITY FLOOR MCC ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 1600 50 1600A BUS BAR TPN+E 246.48 246.48 246.48 739.43 591.54

OUTGOING:

CH-UF-01 TP 630 50 2x4C CU/XLPE/SWA/LSZH 185 2x1Cx95 73.77 73.77 73.77 221.31 177.05 1000mA ELS+TIMER+ALARM

CH-UF-02 TP 630 50 2x4C CU/XLPE/SWA/LSZH 185 2x1Cx95 73.77 73.77 73.77 221.31 177.05 1000mA ELS+TIMER+ALARM

CH-UF-03 TP 630 50 2x4C CU/XLPE/SWA/LSZH 185 2x1Cx95 73.77 73.77 73.77 221.31 177.05 1000mA ELS+TIMER+ALARM

MCC-RF TP 160 50 1x4C CU/XLPE/SWA/LSZH 70 1x1Cx35 25.17 25.17 25.17 75.50 60.40 1000mA ELS+TIMER+ALARM

MDB-01 CONNECTED TO TR-01 TOTAL CONNECTED LOAD PER


246.48 246.48 246.48 739.43 591.54 TOTAL
MCC-CH CONNECTED TO MDB-01 PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 739.43 kW
STAND BY LOAD : 18.50 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 591.54 kW * OVERALL /INSTALLED LOAD (TCL): 720.93 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

MCC-RF FEED FROM MCC-CH LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: UTILITY FLOOR MCC ROOM

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

INCOMER TP 160 35 1x4C CU/XLPE/SWA/LSZH 70 1x1Cx35 25.17 25.17 25.17 75.50 60.40

OUTGOING:

CHWP-UF-01 TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 6.17 6.17 6.17 18.50 14.80 100mA ELR

CHWP-UF-02 TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 6.17 6.17 6.17 18.50 14.80 100mA ELR

CHWP-UF-03 TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 6.17 6.17 6.17 18.50 14.80 100mA ELR

CHWP-UF-04
TP 63 35 1x4C CU/XLPE/SWA/LSZH 16 1x1Cx16 6.17 6.17 6.17 18.50 14.80 100mA ELR (STANDBY)
(STANDBY)

100mA ELS+TIMER+ALARM
PRESS.UNIT TP 25 35 1x4C CU/XLPE/SWA/LSZH 10 1x1Cx10 0.50 0.50 0.50 1.50 1.20
(1D + 1S)

MDB-01 CONNECTED TO TR-01 TOTAL CONNECTED LOAD PER


25.17 25.17 25.17 75.50 60.40 TOTAL
MCC-RF CONNECTED TO MCC-CH PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 75.50 kW
STAND BY LOAD : 18.50 kW

DEMAND FACTOR : 0.8 Max. DEMAND: 60.40 kW * OVERALL /INSTALLED LOAD (TCL): 57.00 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)

App. No. E/F ………………………


PROJECT: (3B+G+4+ROOF) EMIRATES AUTHORITY FOR
DETAIL OF CONNECTED LOAD, MAX. DEMAND & kWh METERING AREA: MUHAISNAH SECOND - DUBAI
STANDARDIZATION AND METROLOGY OFFICE BUILDING
PLANNED COMPLETION DATE: OWNER : EMIRATES REAL ESTATE CORP. PLOT NO.: 2641059

PROJECT MANAGEMENT: HILL INTERNATIONAL

ESMDB-RF (FEED FROM EMDB) LEAD CONSULTANT: EHAF Consulting Engineers LOCATION: UTILITY FLOOR (ELE.ROOM )

CABLE SIZE, TYPE MAX.


CONNECTED LOAD TOTAL PROPOSED TYPE & No. OF
ACB/ AND DEMAND/
CIRCUIT/ ECC LENGTH (KW) CONNECTED/ kWh METERS
MCCB/ FAULT NO. OF CORES OPERATIONA
FEEDER SIZE OF INSTALLED LOAD
SP/ ISOLATOR L
REMARKS
TP DUTY LOAD
SMDB/ TYPE 1C, CABLE (TCL) * LV/
RATING kA NO. OF
DB NO. XLPE/ mm2 (Mtrs.) R - PH Y - PH B - PH * 1 - PH 3 - PH HV
(AMPS) CORES 1C/ SIZE (MDL)
PVC/ KW KW KW KW (1) (2) CT
2C/ 4C KW
SWA (3)

MICA GLASS-
INCOMER TP 40 35 1x4C 10 1x1Cx10 5.88 5.73 5.73 17.35 15.62
XLPE/LSZH/SWA
OUTGOING:
MICA GLASS-
BP-UF-01 TP 25 35 1x4C 10 1x1Cx10 0.73 0.73 0.73 2.20 1.98 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
SEF-UF-01 TP 25 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
SEF-UF-02 TP 25 35 1x4C 10 1x1Cx10 2.50 2.50 2.50 7.50 6.75 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA
MICA GLASS-
EAF-UF-02 SP 25 35 1x2C 6 1x1Cx6 0.15 0.15 0.14 100mA ELS+TIMER+ALARM
XLPE/LSZH/SWA

MDB-02 CONNECTED TO TR-02 TOTAL CONNECTED LOAD PER


5.88 5.73 5.73 17.35 15.62 TOTAL
ESMDB-B1 CONNECTED TO EMDB PHASE:
TOTAL CONNECTED LOAD (3 PHASE) : 17.35 kW
STAND BY LOAD : 0.00 kW

DEMAND FACTOR : 0.9 Max. DEMAND: 15.62 kW * OVERALL /INSTALLED LOAD (TCL): 17.35 kW TOTAL BUILD-UP AREA

CONSULTANT/ CONTRACTOR: TEL: FAX

* TCL - Shall include all loads proposed to be installed including standby, spare and future load provisions.

Type of Meter (Rating of Incomer) : (1) Upto 60A (2) Upto 125A (3) LV CT / A / HV CT / A (* 200/5Amps CT Metering)

(1Phase) (3 Phase)