UPS APC GALAXY7000 Installation Manual
UPS APC GALAXY7000 Installation Manual
05/2016
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
250–500 kVA UPS
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Electrical Safety....................................................................................9
Periodical Check.................................................................................10
Battery Safety.....................................................................................10
Specifications ............................................................................................12
Input Specifications ..................................................................................12
Bypass Specifications ...............................................................................12
Output Specifications ................................................................................12
Battery Specifications ...............................................................................13
Earthing Systems .....................................................................................13
TNS upstream, TNS downstream without Residual-Current
Protection...........................................................................................13
TNS upstream, TNS downstream with Residual-Current
Protection...........................................................................................13
TNC upstream, TNC, TNS or TT downstream installation.......................14
IT upstream, IT downstream ................................................................15
Recommended Cable Sizes ......................................................................15
Power Cables for Single UPS ..............................................................15
Power Cables for Parallel UPSs ...........................................................16
Connection Terminals ...............................................................................18
UPS Cabinets.....................................................................................18
SSC, SSC Maintenance, External Bypass Cabinets ..............................18
Recommended Upstream and Downstream Protection................................19
Permissible UPS overloads as a Function of Time .................................20
Recommended Residual Current Protection ...............................................21
Battery Protection .....................................................................................21
Setting the Circuit Breakers .................................................................21
Environmental ..........................................................................................22
Heat Dissipation .......................................................................................22
Weights and Dimensions...........................................................................23
Clearance ................................................................................................24
Introduction ................................................................................................25
Overview of Configurations .......................................................................25
Single or Integrated Parallel UPS alone ................................................25
Parallel UPS Systems .........................................................................25
UPS Set Up as a Frequency Converter.................................................29
Floor Mounting .........................................................................................30
UPS Cabinets.....................................................................................30
Static Switch Cabinets.........................................................................31
External Bypass or Static Switch Maintenance Cabinets ........................32
Auxiliary Cabinets (empty) ...................................................................33
Backfeed Cabinet ...............................................................................33
Prepare For Installation............................................................................34
Layouts....................................................................................................34
990–9898–001 3
250–500 kVA UPS
4 990–9898–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 250–500 kVA UPS
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
990–9898–001 5
Important Safety Instructions — SAVE
250–500 kVA UPS THESE INSTRUCTIONS
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category 3 according to IEC 62040-2 for commercial, industrial
and similar applications in the second environment - installation restrictions or
additional measures may be needed to prevent disturbances. The second
environment includes all commercial, light industry and industrial locations other
than residential, commercial and light industrial premises directly connected
without intermediate transformer to a public low-voltage mains supply. The
installation and cabling must follow the Electromagnetic compatibility rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on this
UPS system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
6 990–9898–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 250–500 kVA UPS
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free of
conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
990–9898–001 7
Important Safety Instructions — SAVE
250–500 kVA UPS THESE INSTRUCTIONS
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the Installation Manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.
8 990–9898–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 250–500 kVA UPS
Electrical Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• The UPS system must be installed in a room with restricted access (qualified
personnel only).
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the utility/mains supply. Before
installing or servicing the UPS system, ensure that the units are OFF and that
utility/mains and batteries are disconnected. Wait five minutes before
opening the UPS to allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. This disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 4th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.
When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective earth.
Failure to follow these instructions will result in death or serious injury.
990–9898–001 9
Important Safety Instructions — SAVE
250–500 kVA UPS THESE INSTRUCTIONS
Periodical Check
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Limited lifetime components, such as capacitors, fans, electronic boards,
batteries, etc., must be checked periodically by qualified personnel.
• Battery trip control must be done periodically by qualified personnel.
This periodical check is recommended every 6 months and required every
12 months.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
• Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Do not dispose of batteries in a fire as they can explode.
• Do not open, alter, or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
10 990–9898–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 250–500 kVA UPS
CAUTION
RISK OF EQUIPMENT DAMAGE
Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period, we
recommend that you energize the UPS system for a period of 24 hours at least
once every month. This charges the batteries, thus avoiding irreversible
damage.
Failure to follow these instructions can result in injury or equipment
damage.
990–9898–001 11
250–500 kVA UPS Specifications
Specifications
Input Specifications
250 kVA 300 kVA 400 kVA 500 kVA
Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal input 369 351 337 319 441 420 403 382 586 558 536 507 735 700 672 636
current (A)1
Input frequency 45 to 66
(Hz)
Bypass Specifications
250 kVA 300 kVA 400 kVA 500 kVA
380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal input 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)
Input frequency 45 to 66
(Hz)
Output Specifications
250 kVA 300 kVA 400 kVA 500 kVA
Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal output 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)
1. For 400 V interphase voltages and a load with a power factor of 0.9.
12 990–9898–001
Specifications 250–500 kVA UPS
Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Output voltage ± 1%
regulation
Crest factor 2.7 2.9 3.0 3.3 2.3 2.4 2.5 2.8 2.3 2.4 2.5 2.8 2.6 2.7 2.8 3.0
Battery Specifications
Type Sealed lead-acid Vented lead-acid Ni-Cad
Min./Max. floating voltage (V) 600 / 654 581 / 634 600 / 655
Earthing Systems
This section lists the main earthing systems and their wiring requirements.
For earthing systems not listed here, please contact Schneider Electric.
990–9898–001 13
250–500 kVA UPS Specifications
NOTE: Adding a transformer into the Normal AC network reduces the installation's
overall efficiency.
14 990–9898–001
Specifications 250–500 kVA UPS
IT upstream, IT downstream
For separate normal and bypass AC lines from a single source.
990–9898–001 15
250–500 kVA UPS Specifications
16 990–9898–001
Specifications 250–500 kVA UPS
UPS rating Number of UPSs Total power rating Current on AC Minimum size for AC
(kVA) bypass or load (A) bypass or load
(mm²)
Frequency Converters
UPS rating Number of UPSs Total power rating Current on AC Minimum size for
(kVA) bypass or load (A) load (mm²)
NOTE:
The power cables between the UPS units and the upstream protective devices
must be of the same size and length.
The power cables between the UPS units and the load must be of the same size
and length.
UPS rating Number Total Current on AC bypass or Minimum size for load (mm²)
of UPSs power load (A)
rating
(kVA)3
NOTE:
The power cables between the UPS units and the upstream protective devices
must be of the same size and length.
The power cables between the UPS units and the load must be of the same size
and length.
990–9898–001 17
250–500 kVA UPS Specifications
UPS rating Num- Total Current on AC bypass or Minimum size for load (mm²)
ber of power load (A)
UPS rating5
(kVA)
NOTE:
The power cables between the UPS units and the upstream protective devices
must be of the same size and length.
The power cables between the UPS units and the load must be of the same size
and length.
Connection Terminals
UPS Cabinets
Phase terminal Earth terminal Battery terminal
800 kVA 13 13
1200 kVA 13 13
2000 kVA 13 and 17 13
18 990–9898–001
Specifications 250–500 kVA UPS
Line-current Values
8. RMS current limit when inverter is coupled and bypass AC source is out of tolerances
990–9898–001 19
250–500 kVA UPS Specifications
Normal AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 3P Micrologic NS 800N 3P Micrologic
source 3P 2.3 3P 2.3 2.0 5.0
Bypass AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 4P Micrologic NS 800N 4P Micrologic
source 4P 2.3 4P 2.3 2.0 5.0
Output NSX 100 N TM D 80 NSX 100 N TM D 80 NSX 100 N TM D 100 C125N D 125
C120N C80 C120N C80 NG 125N C 125 NSX 160N TM 160D
C120N B 125 C120N B 125 C125H C 125 NG125N D125
Icw 9(kA) 26.7 22
9. RMS shortime current value that can be carried without damage under condition defined by the standard IEC
62040-1.
20 990–9898–001
Specifications 250–500 kVA UPS
Battery Protection
WARNING
HAZARD OF FIRE OR ARC FLASH
Protect battery circuit with DC circuit breaker equipped with under voltage coil
(MN 24 VDC).
• The DC breaker must be rated 660 VDC.
• The undervoltage coil must be wired to the UPS as shown on connection
diagrams (see Connect the Battery Signal Cables, page 72.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTE:
Follow the necessary precautions during connection of circuit breakers / switches
in the installation.
Pn = rated power at a power factor of 0.9; for other values, please consult
Schneider Electric.
UPS Maximum Total number of QF1–1 Circuit Breaker QF1–2 Circuit Breaker
battery backup battery strings
time Number of Magnetic Number of Magnetic
battery strings setting (A) battery strings setting (A)
990–9898–001 21
250–500 kVA UPS Specifications
UPS Maximum Total number of QF1–1 Circuit Breaker QF1–2 Circuit Breaker
battery backup battery strings
time Number of Magnetic Number of Magnetic
battery strings setting (A) battery strings setting (A)
Environmental
Operating temperature 0 - 40 °C
Heat Dissipation
250 kVA 300 kVA 400 kVA 500 kVA
Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries
fully charging fully charging fully charging fully charging
charged charged charged charged
Active power 112 225 135 270 180 360 225 450
(kW)
Heat losses (kW) 8.2 14.9 9.4 18.6 11.3 22.6 13.6 27.2
Heat losses 1962 3554 2243 4449 2697 5395 3250 6501
(calories/s)
22 990–9898–001
Specifications 250–500 kVA UPS
990–9898–001 23
250–500 kVA UPS Specifications
Clearance
NOTE: Clearance dimensions are published for airflow and service access only.
Consult with the local safety codes and standards for additional requirements in
your local area.
NOTE: The UPS system can be placed up against the wall. It is preferable to leave
some space for easier maintenance.
NOTICE
HAZARD OF OVERHEATING
• Leave nothing on top of the UPS.
• Maintain 500 mm of free space above the UPS.
• Ensure that the UPS cabinet rests on its four cylindrical feet, (six feet for 500
kVA UPS).
• Ensure that the distance between the UPS rear panel and the floor is less
than 10 mm.
Failure to follow these instructions can result in equipment damage.
NOTE: Leave one meter of free space in front of the UPS for door opening.
24 990–9898–001
Introduction 250–500 kVA UPS
Introduction
Overview of Configurations
Single or Integrated Parallel UPS alone
990–9898–001 25
250–500 kVA UPS Introduction
26 990–9898–001
Introduction 250–500 kVA UPS
990–9898–001 27
250–500 kVA UPS Introduction
Parallel UPS units with Static Switch Cabinet and Static Switch Maintenance
Cabinet
28 990–9898–001
Introduction 250–500 kVA UPS
Parallel UPS units with Static Switch Cabinet and Static Switch
Maintenance Cabinet
Single UPS
990–9898–001 29
250–500 kVA UPS Introduction
Floor Mounting
The UPS can be installed on a normal or raised floor, non-flammable, level and
solid surface.
The dimensions are indicated in millimeters.
NOTICE
RISK OF OVERHEATING
The cabinet feet must not be removed.
Failure to follow these instructions can result in equipment damage.
UPS Cabinets
NOTE: The four feet (six feet for 500 kVA UPS) of the cabinet are cylindrical, 45
mm in diameter. The measurements include the cabinet cover panels and the door.
250 11
300 11
400 13
500 11
30 990–9898–001
Introduction 250–500 kVA UPS
Top view
800 5
1200 9
2000 9
2000 light 7
990–9898–001 31
250–500 kVA UPS Introduction
32 990–9898–001
Introduction 250–500 kVA UPS
400 0,9
700 1,2
1000 1,3
1400 1,8
Top View
Backfeed Cabinet
Top View
990–9898–001 33
250–500 kVA UPS Prepare For Installation
Mechanical Preparation
Install the 400 Millimeter Auxiliary Cabinet
1. Remove the two inter-cabinet uprights located behind the 400 mm cabinet.
2. Refit the rear panel on the 400 mm cabinet with the supplied screws.
3. Remove the side panel on the 400 mm cabinet.
4. Unscrew the side panel of the cabinet to be coupled without removing it.
34 990–9898–001
Prepare For Installation 250–500 kVA UPS
5. Place the three inter-cabinet uprights above the side panel of the cabinet to be
coupled.
6. Place the screws on the 400 mm cabinet.
7. Couple the 400 mm cabinet with the cabinet to be coupled and tighten the
screws from inside the 400 mm cabinet.
990–9898–001 35
250–500 kVA UPS Prepare For Installation
3. Remove the two inter-cabinet uprights located behind the right hand side
cabinet.
36 990–9898–001
Prepare For Installation 250–500 kVA UPS
CAUTION
RISK OF BURNS FROM HOT SURFACE
All the cables for the same network (normal AC line, battery, bypass AC line,
earth, load) must run through the same hole to avoid overheating of the anti-
rodent grid.
Failure to follow these instructions can result in injury or equipment
damage.
990–9898–001 37
250–500 kVA UPS Prepare For Installation
38 990–9898–001
Prepare For Installation 250–500 kVA UPS
2. For TNC (PEN) upstream, TNC, TNS or TT downstream systems only: Install
the jumper between the earth bar and the inverter neutral bar.
990–9898–001 39
250–500 kVA UPS Prepare For Installation
3. Check that switches Q1, Q4S, Q3BP, and Q5N are in the OFF position.
40 990–9898–001
Prepare For Installation 250–500 kVA UPS
If an anti-rodent grid is required, see Install the Anti-rodent Grid, page 37.
NOTE: Top cable entry is possible using an auxiliary cabinet 400 mm wide.
990–9898–001 41
250–500 kVA UPS Prepare For Installation
If an anti-rodent grid is required, see Install the Anti-rodent Grid, page 37.
NOTE: For UPSs used as frequency converters, Q4S and Q3BP switches are not
present.
NOTE: Top cable entry is possible using an auxiliary cabinet 400 mm wide.
42 990–9898–001
Prepare For Installation 250–500 kVA UPS
990–9898–001 43
250–500 kVA UPS Prepare For Installation
3. Check that the switches Q1 and Q5N are in the OFF position.
4. Connect the protective cable (PE or PEN) to the earth bar.
5. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
6. Connect the normal AC cables respecting the following order: L1, L2, L3.
7. Connect the load cables respecting the following order: N, L1, L2, L3.
8. Connect the battery.
9. Tie the cables down.
10.Connect the control cables, see Connect the Control Cables, page 60.
11. Reinstall the protective covers.
44 990–9898–001
Prepare For Installation 250–500 kVA UPS
3. Check that the switches Q1 and Q5N are in the OFF position.
4. Connect the protective cable (PE or PEN) to the earth bar.
5. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
6. Connect the normal AC cables respecting the following order: L1, L2, L3.
7. Connect the load cables respecting the following order: N, L1, L2, L3.
8. Connect the battery.
990–9898–001 45
250–500 kVA UPS Prepare For Installation
2. Check that the switches Q4S, Q3BP, and Q5N are in the OFF position.
3. Connect the protective cable (PE or PEN) to the earth bar.
4. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
5. Connect the UPS10 cables in the following order: N, L1, L2, L3.
6. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
10. Or static switch maintenance cabinet, see Connect Power Cables in a Static Switch Maintenance Cabinet,
page 55
46 990–9898–001
Prepare For Installation 250–500 kVA UPS
7. Connect the load cables respecting the following order: N, L1, L2, L3.
8. Connect the control cables, see Connect the Control Cables, page 60.
9. Reinstall the protective covers.
2. Check that the switches Q4S, Q3BP, and Q5N are in the OFF position.
3. Connect the protective cable (PE or PEN) to the earth bar.
4. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
5. Connect the UPS11 cables in the following order: N, L1, L2, L3.
11. Or static switch maintenance cabinet, see Connect Power Cables in a Static Switch Maintenance Cabinet,
page 55
990–9898–001 47
250–500 kVA UPS Prepare For Installation
6. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
7. Connect the load cables respecting the following order: N, L1, L2, L3.
8. Connect the control cables, see Connect the Control Cables, page 60.
9. Reinstall the protective covers.
48 990–9898–001
Prepare For Installation 250–500 kVA UPS
2. Check that the switches Q4S, Q3BP, and Q5N are in the OFF position.
3. Connect the protective cable (PE or PEN) to the earth bar.
4. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
5. Connect the UPS12 cables in the following order: N, L1, L2, L3.
6. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
7. Connect the load cables respecting the following order: N, L1, L2, L3.
8. Connect the control cables, see Connect the Control Cables, page 60.
9. Reinstall the protective covers.
12. Or static switch maintenance cabinet, see Connect Power Cables in a Static Switch Maintenance Cabinet,
page 55
990–9898–001 49
250–500 kVA UPS Prepare For Installation
2. Check that the switches Q4S, Q3BP, and Q5N are in the OFF position.
3. Connect the protective cable (PE or PEN) to the earth bar.
4. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
5. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
6. Connect the load cables respecting the following order: N, L1, L2, L3.
7. Connect the control cables, see Connect the Control Cables, page 60.
8. Reinstall the protective covers.
50 990–9898–001
Prepare For Installation 250–500 kVA UPS
2. Check that the Q3BP switches are in the OFF position on all UPS units.
3. Remove the Q3BP switch handles on all UPS units.
4. Check that the switches Q3BP ext, and Q5N ext are in the OFF position.
5. Connect the protective cable (PE or PEN) to the earth bar.
6. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
7. Connect the UPS cables in the following order: N, L1, L2, L3.
8. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
9. Connect the load cables respecting the following order: N, L1, L2, L3.
990–9898–001 51
250–500 kVA UPS Prepare For Installation
52 990–9898–001
Prepare For Installation 250–500 kVA UPS
2. Check that the Q3BP switches are in the OFF position on all UPS units.
3. Remove the Q3BP switch handles on all UPS units.
4. Check that the switches Q3BP ext and Q5N ext are in the OFF position.
5. Connect the protective cable (PE or PEN) to the earth bar.
6. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
7. Connect the UPS cables in the following order: N, L1, L2, L3.
8. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
9. Connect the load cables respecting the following order: N, L1, L2, L3.
990–9898–001 53
250–500 kVA UPS Prepare For Installation
2. Check that the Q3BP switches are in the OFF position on all UPS units.
54 990–9898–001
Prepare For Installation 250–500 kVA UPS
4. Check that the switches Q3BP ext and Q5N ext are in the OFF position.
5. Check if the cabinet needs neutral adaptation, see Adapt Cabinet for Neutral
Point Connection, page 38.
6. Connect the protective cable (PE or PEN) to the earth bar.
7. Connect the UPS cables in the following order: N, L1, L2, L3.
8. Connect the bypass AC cables respecting the following order: N, L1, L2, L3.
9. Connect the load cables respecting the following order: N, L1, L2, L3.
10.Reinstall the protective covers.
990–9898–001 55
250–500 kVA UPS Prepare For Installation
56 990–9898–001
Prepare For Installation 250–500 kVA UPS
990–9898–001 57
250–500 kVA UPS Prepare For Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective earth.
Failure to follow these instructions will result in death or serious injury.
(a) In IT earthing systems with neutral, a four pole backfeed protection device is
required.
(b) Labels as specified above must be added close to the terminals as described
on the drawing.
58 990–9898–001
Prepare For Installation 250–500 kVA UPS
(a) In IT earthing systems with neutral, a four pole backfeed protection device is
required.
(b) The backfeed protection device must open within less than fifteen seconds after
the upstream supply voltage disappears. Such device must be rated according to
the UPS specification and protected as required. A switching device equipped with
the appropriate coil is an example of backfeed protection device.
(c) Labels as specified above must be added close to the terminals as described
on the drawing.
990–9898–001 59
250–500 kVA UPS Prepare For Installation
60 990–9898–001
Prepare For Installation 250–500 kVA UPS
1. Connect the XM2 and XM3 connectors in the two UPS units.
2. Plug a blue terminator on connector XM6 in UPS 1.
3. Connect XM7 in UPS 1 to XM6 in UPS 2.
4. Plug a red terminator on connector XM7 in the UPS 2.
5. Path the cables behind protective covers, as shown in the UPS cabinet.
6. Run the cables with the earth cables outside the cabinet.
Connect Control Cables in Integrated Parallel UPS Cabinet with the External Bypass
Cabinet
The supplied cables are 10 m or 20 m long. Please contact Schneider Electric for
more information.
The characteristics of the non-supplied control cables (connected to XM4 and
XM5) are 0.5 to 1.5 mm² / AWG20 to AWG16.
The total cable length must not exceed 180 m.
990–9898–001 61
250–500 kVA UPS Prepare For Installation
1. Check that all Q3BP handles are removed from all UPS units.
2. Connect the common Q3BP ext and Q5N ext terminals on the terminal block in
the external bypass cabinet to connector XM4 in UPS 4 and XM5 in UPS 1
(cables not supplied).
3. Create a loop between XM2 and XM3 connectors in the four UPS units.
NOTE: All the connectors must be used.
4. Plug a blue terminator on connector XM6 in UPS 1.
5. Interconnect the XM6 and XM7 connectors in the four UPS units.
6. Plug a red terminator on connector XM7 in the UPS 4.
7. Path the cables behind protective covers, as shown in the UPS cabinet. Control
cables and power cables must run apart.
8. Run the cables with the earth cables outside the cabinet.
Connect Control Cables in Parallel UPS Cabinet with the Static Switch Cabinet
The supplied cables are 10 m or 20 m long. Please contact Schneider Electric for
more information.
The total cable length must not exceed 180 m.
62 990–9898–001
Prepare For Installation 250–500 kVA UPS
1. Create a loop between XM2 and XM3 connectors in the four UPS units and the
static switch cabinet.
NOTE: All the connectors must be used.
2. Plug a blue terminator on connector XM6 in UPS 1.
3. Interconnect the XM6 and XM7 connectors in the four UPS cabinets and the
static switch cabinet.
4. Plug a red terminator on connector XM7 in the static switch cabinet.
NOTE: Connectors XM4 and XM5 in the static switch cabinet are not used.
5. Path the cables behind protective covers, as shown in the UPS cabinet. Control
cables and power cables must run apart.
6. Run the cables with the earth cables outside the cabinet.
990–9898–001 63
250–500 kVA UPS Prepare For Installation
The auxiliary contact of a customer switch must be a normally open contact when
the switch is open.
1. Connect the terminal block connectors to the current sensors in the connection
panel.
64 990–9898–001
Prepare For Installation 250–500 kVA UPS
2. Connect static switch XM4 connector to switches Q5N ext, Q4S ext and Q3BP
ext.
3. Run the cables behind protective covers, as shown in the cabinet. Control
cables and power cables must run apart.
4. Run the cables along with the earth cables outside the cabinet.
990–9898–001 65
250–500 kVA UPS Prepare For Installation
2. Path the cables behind protective covers, as shown in the cabinet. Control
cables and power cables must run apart.
3. Run the cables with the earth cables outside the cabinet.
WARNING
HAZARD OF FIRE
• Protect the battery circuit with a DC circuit breaker equipped with an
undervoltage coil (MN 24 VDC).
• The DC breaker must be rated 660 VDC. The undervoltage coil must be
wired to the UPS as shown in Mount Battery Circuit Breaker Kit, page 69.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
The cables (not supplied) must have SELV insulation and the maximum size is 2.5
mm².
NOTE: To ensure sufficient isolation of EPO cables, they must be run separately
from the power cables.
66 990–9898–001
Prepare For Installation 250–500 kVA UPS
990–9898–001 67
250–500 kVA UPS Prepare For Installation
NOTE: To ensure sufficient isolation of contact signal cables, they must be run
separately from the power cables.
68 990–9898–001
Prepare For Installation 250–500 kVA UPS
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• It is mandatory to protect the battery circuit with a circuit breaker equipped
with an undervoltage coil (MN 24V DC).
• Circuit breaker type and rated must be compliant with battery specifications
and battery protection given.
Failure to follow these instructions will result in death or serious injury.
NOTE: Please contact Schneider Electric when selecting the battery circuit
breaker. In systems with several battery cabinets, only one circuit breaker is
necessary per battery cabinet group connected to a UPS cabinet. Temperature
sensors must be installed to obtain battery warranty and to optimize battery
lifetime.
990–9898–001 69
250–500 kVA UPS Prepare For Installation
1. Install the circuit breaker back plate and the circuit breaker with screws in the
battery cabinet.
70 990–9898–001
Prepare For Installation 250–500 kVA UPS
Connect Battery Cables from the UPS Cabinet to the Battery Cabinet
990–9898–001 71
250–500 kVA UPS Prepare For Installation
6. Install and fasten the protective cover with the supplied screws.
NOTE: MN 24 VDC coil must be used for battery circuit breaker monitoring (EPO
and protection).
72 990–9898–001
Prepare For Installation 250–500 kVA UPS
1. Connect the signal cables from the UPS cabinet to the battery circuit breaker in
the battery cabinet.
2. Run the cables in the cabinet as shown.
3. Use cable ties to fasten the cables.
4. Run the signal cables outside the cabinet along the earth and connection
cables between the cabinets.
990–9898–001 73
250–500 kVA UPS Prepare For Installation
1. Connect the UPS cabinet to the temperature sensor in the battery room or in
the battery cabinet (cables not supplied).
2. Run the cables in the cabinet as shown.
3. Use cables ties to fasten the cables.
4. Run the cables outside the cabinet along the earth and connection cables
between the cabinets.
74 990–9898–001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com