6.3MVA Transformer Data Sheet SU 6tap

This document provides specifications for a 6.3MVA transformer package including: 1) The package contains two 3.15/3.78MVA transformers that are indoor, dual frequency, oil natural air natural cooled units. 2) Key ratings include 50/55°C temperature rise, 98.66% efficiency, and voltage ranges from 3.3-33kV on the HV side and 400/480V on the LV side. 3) The package also includes a 36kV ring main unit with isolators, vacuum circuit breakers, and current transformers for protection and metering.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
805 views2 pages

6.3MVA Transformer Data Sheet SU 6tap

This document provides specifications for a 6.3MVA transformer package including: 1) The package contains two 3.15/3.78MVA transformers that are indoor, dual frequency, oil natural air natural cooled units. 2) Key ratings include 50/55°C temperature rise, 98.66% efficiency, and voltage ranges from 3.3-33kV on the HV side and 400/480V on the LV side. 3) The package also includes a 36kV ring main unit with isolators, vacuum circuit breakers, and current transformers for protection and metering.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

* ENERGIA CONTROLLED TDS No.6.

3/SU/6T
TRANSFORMER DATA SHEET - 6.3MVA Doc No. Date Page
6.3/SU/6T 23-May-18 1 of 2

PLANT BOARD DETAILS


1 Ambient Temp °C, Altitude mtrs above msl & RH %1 50,1000 & 90
2 Number of Transformer in Package & type 2 & Indoor, Dual frequency, ONAN, Multi Tap, Continuous
3 Rating of each transformer in kVA ( 50Hz / 60 Hz) 3,150 / 3,780
4 Phase / Wire & class of Insulation 3φ / 4W neutral on LV & HV side & A
5 Impluse Voltage HV kVp, Power frequency kVrms (HV / LV) 170, 70/3
6 Temperature Rise in °C (Oil / Winding ) 50 / 55 over ambient of 50 °C
7 Vector Group YNyn0 / Dyn11 ( Through selector switch)
8 Type of Cooling ONAN
9 Efficiency at 33 kV, 0.8 pf, 50Hz & 100 % Load 98.66
10 No load loss 50 / 60 Hz & Load loss at 75 °C & 33kV in kW2 3.28 & 30.911
11 Voltage Chart
Vector Low Voltage V @ LV Current A HV Current A @ 50 /
HV Voltage V @ 50 / 60Hz Remarks
Group 50/60Hz @ 50 / 60 Hz 60 Hz
9526 / 11430 191 / 159
7940 / 9527 229 / 191
Dyn11 6350 / 7620 286 / 239
400 / 480 4,547
1 (Parallel) 5500 / 6600 331 / 276
3810 / 4573 477 / 398
3300 / 3960 551 / 459
Each transformer comes
16500 / 19800 110 / 91.90
filled with mineral oil; Top
13750 / 16500 132 / 110 plate of transformer has
YNyn0 11000 / 13200 165 / 133 selector switches to select
400 / 480 4,547
2 (Parallel) 9526 / 11431 191 / 159 a) vector group, b)
6600 / 7920 276 / 290 voltage change over and
5716 / 6859 318 / 255 c) voltage selection;
Marshalling box of each
19053 / 22862 95.50 / 89.5
transformer controls its
15877 / 19053 165.32 / 137.78 own cooling fans linked
Dyn11 12702 / 15242 238.64 / 198.85 with temp of oil & high
400 / 480 4,547
1 (Series) 11000 / 13200 190.92 / 159.10 pressure have been built;
7621 / 9145 275.55 / 229.63 Local temp indication &
remote indication are
6600 / 7920 286.3 / 238.62
available
33000 / 39600 55 / 46
27500 / 33000 66.10 / 65.10
YNyn0 22000 / 26400 82.70 / 68.90
400 / 480 4,547
2 (Series) 19052 / 22862 95.50 / 79.50
13200 / 15840 138 / 115
11431 / 13717 159 / 133
12 Number of LV Isolators & rating 6 (3 on each transformer) & 2500 A
Configuration of 36kV, 20kA Ring Main unit (RMU) RMU comprises 4 sections outward on both sides housing an isolator
13 & VCB while inward sections house a switch in a CLLC configuration.

14 Current rating of switch / Isolator / CB / busbar in A 630 A


15 Rated short time withstand / Peak withstand current in kA 25 in 1sec / 52.5
Rated insulation Voltage / Power Freq withstand voltage / Lighting
16 36 / 70 / 170
impluse withstand voltage kV
17 CT [C] ; CT [L] ; PT with fuses (L) 600:1A; 600/350/100; 5A; 33000/√3 : 200/√3
18 RMU 36 kV, SLD (CLLC)

This line called C gets connected to transformer 2. It has a protection


class CT, an Isolator followed by VCB that gets connected to a bus.

This line goes to load side called L provided with a switch and then a
metering CT within RMU. PT is loacted outside RMU and is
connected through load cable

This line goes to load side called L provided with a switch and then a
metering CT within RMU. PT is loacted outside RMU and is
connected through load cable

This line called C gets connected to transformer 1. It has a protection


class CT, an Isolator followed by VCB that gets connected to a bus.
* ENERGIA CONTROLLED TDS No.6.3/SU/6T
TRANSFORMER DATA SHEET - 6.3MVA Doc No. Date Page
6.3/SU/6T 23-May-18 2 of 2

CONTROL, PROTECTION & GENERAL DATA


Control & Relay Transfomer panel is provided inside this package mounted on top of RMU to control, operate, monitor & protect package; A
19 battery unit provides 24V DC supply for breaker operation along with charger. Panel receives external supply through 63A TPN breaker for
distributing external supply to power pack.
20 The RMU are equiped with ABB PR521 LSIG self powered protection devices.
Isolator's - Type: TPR6; In (A) - 630A; Icw (kA) - 25kA
Switch - Type: TPR6; In (A) - 630A; Icw (kA) - 25kA
Circuit Breaker - Type: Vacuum C.B; In (A) - 630A; Icw (kA) - 25kA
C.T Ratio : Type - S.T.E TCN 250/1; S.T.E TCR1020 ; 250A/1 ; 600-350-100/5A
21 Transformer package has ladder to access roof of container where one can remove separate covers for transfomer & RMU; Transformer has its
own cooling fans that is integrated to its own temperature circuit while in addition. Transformer package is fully tested functionally while its
integrity, interlock, safeties, polarity & ratio tests conducted.
WEIGHT & DIMENSIONAL DATA With doors open With doors close
Length(L) Width (W) Height(H) Length(L) Width (W) Height(H)
22 Overall Dimension of Transformer Pack Mm 8496 4876 2896 6058 2438 2896
23 Total Weight of Transformer Pack Dry Kg 20,600
24 Total Weight of Transformer Pack Dry Kg 24,000
25 Container is outdoor type, ISO certified, high cube, CSC plated with tracing reference that can be furnished
Package rating has been defined under specified environmental conditions for all equipment.
Controller meets with IEC 60255-26 & EN 61000-6-1/2/3/4 standards
RMU confirms to IEC 62271-1 standard in general with switchgear classification of PM class, loss of service continunity of LSC2, intergal arc
classification of AFL including standards 62271-200, 62271-103, 62271-100,62271-102,62271-105 & IEC 60529
Rated short time withstand current is 50kArms ans isolator confirms to IEC 60947-3 standards. 2000A is a derived rating at specified
enviromental conditions. Actual rating is 2500A at 415VAC & AC228 utilisation category