Module 3 LCAPR
Module 3 LCAPR
Day by day, the energy market and complex power generation is growing; the capacity to control
the power flow is very important. For that, a phase-shifting transformer (PST) is used. As they
defend transmission lines, they make power grids more reliable as well as decrease losses in
transmission. The classification of this transformer can be done based on the symmetrical
otherwise asymmetrical & direct otherwise indirect character of this transformer. This article
discusses an overview of the phase-shifting transformer, construction, and its types.
A phase shifting transformer (PST) is a specialised type of transformer, typically used to control
the flow of active power on three-phase electric transmission networks. It does so by regulating
the voltage phase angle difference between two nodes of the system. The principle relies on a
phase shifted voltage source injection into the line by a series connected transformer, which is
fed by a shunt transformer. The configuration of the shunt and series transformer unit induces the
phase shift.
It is a simple, robust and reliable technology. Preventive and curative control strategies are
implemented for power flow controllability. In the preventive mode, the permanent phase shift
allows redistributing the power flows and relieves network stresses in the event of line outage. In
the curative mode, the phase shift is small (sometimes down to zero) in normal operation, but it
is automatically controlled to reduce the power flow on the overloaded lines and to avoid a
tripping out. The active redirection of power flows allows exploiting lines closer to their thermal
limits.
These transformers mainly allow for controlling the flow of power within the transmission grid
separately for the generation. By avoiding overloads of the system as well as instabilities, these
transformers defend and HV equipment as well as transmission lines from thermal overload, so
that it improves the capacity of the transmission system & controls the flow of power among
various networks for parallel cables or overhead lines.
These transformers are extremely specialized devices that need leading-edge construction &
manufacturing skills united through stringent quality control. As compared to a traditional
transformer, PSTs are extremely complex power transformers including more tap changers,
windings as well as a number of connections among the 3-phases.
Construction
The theory of phase-shifting transformer is, the flow of power throughout a transmission line can
be proportional toward the sine of the disparity within the phase angle of the voltage among the
end of transmitter & the receiver of the transmission line.
So the phase angle can be shifted within the ends of the transmitter and receiver of a line. The
flow of load flow in the line will be modified & also other transmission lines’ load flow can also
be changed because they are arranged in parallel.
The construction of a phase-shifting transformer mainly includes two sets of the transformer.
The first one is the shunt unit that is connected in parallel through the transmission line whereas
the second one is the series unit that is connected within series through the transmission line.
The shunt unit is used to shift the power angle by 90° to apply this power toward the series unit.
Lastly, the series unit includes the phase-shifted power toward the transmission line. The
modification of phase angle can be done by the blend of connection as well as the position of tap
change. These kinds of transformers are also called phase angle regulator (PAR), phase angle
regulating transformer, phase shifter, phase-shifting transformer otherwise quadrature booster.
These transformers are used to control the flow of power among two power systems that are
big in size.
To modify the efficient phase displacement among the i/p voltage as well as the o/p voltage for
a transmission line, therefore controlling the quantity of active power that can supply within the
line.
The loading can be balanced when the power systems are allied jointly in the above one point so
that loops will exist & the impedances within parallel lanes result in the undesired flow of power
distribution within the lanes.
To guard from thermal overload as well as to progress the stability of the transmission system.
The phase-shifting transformers applications mainly include high voltage systems like 420 KV &
the throughput power rating can be quite high like 1630 MVA.
The classification of the phase-shifting transformer can be done based on the characteristics like
the following.
Direct PSTs
The direct PSTs or direct phase-shifting transformers mainly depend on the three-phase core and
its phase shift can be obtained by connecting the windings within a suitable way.
Indirect PSTs
The indirect PSTs or indirect phase-shifting transformers mainly depend on a design using two
separate transformers like variable tap exciter and another one is the series transformer. So,
variable tap exciter is used to change the quadrature voltage’s amplitude whereas the series
transformer is used to insert quadrature voltage within the correct phase.
Asymmetrical PSTs
Asymmetrical phase-shifting transformers are used to generate an o/p voltage through changed
amplitude as well as phase angle as compared to the i/p voltage.
Symmetrical PSTs
The rectifiers are used to convert alternating current (AC) to direct current (DC). The advantages
of increased number of phases of the AC supply are given as follows −
Therefore, because of these advantages 6-phase is preferred instead of 3-phase for rectification.
In order to obtain three to six phase supply, the double star connection is used.
Here, the terminals r1y1b1 and r4y4b4 are connected to the 6-phase load terminals 1, 3, 5, 4, 6, 2
respectively. The two neutral terminals 𝑛 and 𝑛′ may be connected together. This neutral point
serve as the neutral point of the DC supply from the rectifier. In such a way, a true 6-phase star
connected system with a neutral terminal is obtained.
The phasor diagram of the primary side and the secondary side is shown in the figure. Now, in
order to determine the connections of the transformer terminals to the load terminals, the
transformer terminal is marked 1 as shown in the figure below.
The other terminals are marked 2, 3, 4, 5, 6 in the clockwise direction. Hence, from the figure it
is clear that the terminal b4 should be connected to the load terminal 2, the terminal y1 to the load
terminal 3 and terminal r4 to the load terminal 4 and so on.
In the double star connection, six voltages are obtained which are displaced by 60° from each
other.
2.As no star point is required for the return path, a transformer can be
3.The number of pulses is increased to six and the amplitude of the ac ripple is decreased.
Bridge connections are called two way circuits, since the transformer windings carry current in
both directions. This is the reason for eliminating the dc magnetisation of core. On the other
hand, midpoint connections have no such facility and thus are one way connections. The bridge
connection has thyristors conducting for 120° which increases the utilisation of both the
thyristors and the transformer, as compared to a Six pulse bridge converter.
The current and voltage waveforms of three-pulse converters connected to form the bridge
converter are shown in Fig. 3.35 for different values of the firing angle a. The output voltage of
the bridge converter is the algebraic sum of the voltages of the component converters. The
positive group has common cathode connection, and will have a thyristor with maximum
positive anode voltage conducting. The negative group has a common anode connection and will
have a thyristor with maximum negative cathode voltage, conducting. Thus the output voltage at
the dc terminals has segments of three phase voltages. Due to the phase –difference between the
positive and negative group voltages, the output voltage has a pulse frequency of 6f. The
commutations occur alternately in the positive and negative groups. At all times, two thyristors,
one in the positive group and the other in the negative group are in conduction. From Fig. 3.35 it
is clear that the firing angle can be increased from 0 to 180°. Firing angle α = 0 is the natural
firing instant, as has already been defined in the case of a three pulse converter. As the firing
angle increases to 90°, the average dc voltage falls to zero. Power flow takes place from ac to dc
and the converter is in the rectifying mode. When the angle increases further to 180°, the mean
voltage increases from 0 to its maximum value with reversed polarity. If there is a dc source on
the load side, power flow takes place from dc to ac and the converter is in the inversion mode.
As has already been explained, there is an inverter limit, which is the maximum firing angle (<
180°), beyond which commutation failure occurs in the converter.
where VL is the line to line voltage. The control characteristic is shown in Fig. 3.36.
The peak forward or reverse voltage of a thyristor in a Six pulse bridge converter is the peak
value of the line voltage, √2VL. The average current carried by the thyristor is
Considering the effects of overlap, resistance and device drop, the terminal voltage of the
converter can be determined in the same way as for a Six pulse bridge converter. It is given by
The ripple factor of the ac voltage, the smoothing inductance, harmonics in the line current, the
power factor and the effects of overlap on these quantities can be determined in the same way as
for a Six pulse bridge converter. The performance of the converter is shown graphically in Fig.
3.37.
Six channels of firing pulses are required, each separated by 60°. During continuous conduction a single
pulse is sufficient, whereas in discontinuous conduction each thyristor must be gated for 60°, because an
initial starting current is required.
1. The primary of one transformer is connected in star and that of the other in delta.
2. The converter transformer has two secondaries, one of which is connected in star and the
other in delta.
Sometimes the advantages of increasing the pulse number are offset by the complexity of the
transformer connection and by the difficulties of maintaining balance in the system. This
happens when two Twelve pulse converter are interconnected to form a 24 pulse one. Such
difficulties do not encourage increasing the pulse number beyond 12 or at most 24.