This document provides guidance on integrating DSC PowerSeries Neo intrusion systems with exacqVision security recorders. It supports integration with DSC PowerSeries Neo equipment using the TL280E or TL280RE communicators with firmware version 5.0 or greater. The integration allows for control and monitoring of the DSC system from within the exacqVision client, including alarm states, arming status, and more. Requirements and steps for configuring the DSC system and establishing communication between the DSC communicator and exacqVision recorder are also outlined.

Uploaded by

Hector Linares
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
137 views11 pages

DSC Neo and Pro Series

This document provides guidance on integrating DSC PowerSeries Neo intrusion systems with exacqVision security recorders. It supports integration with DSC PowerSeries Neo equipment using the TL280E or TL280RE communicators with firmware version 5.0 or greater. The integration allows for control and monitoring of the DSC system from within the exacqVision client, including alarm states, arming status, and more. Requirements and steps for configuring the DSC system and establishing communication between the DSC communicator and exacqVision recorder are also outlined.

Uploaded by

Hector Linares
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

DSC PowerSeries Neo v5.

x & Pro Integration Guide

Overview
exacqVision can be integrated with DSC PowerSeries Neo intrusion systems. Configuration
controls and real-time feedback have been added into the exacqVision client giving the user
control and monitoring capabilities of the system.

NOTE: This integration applies only the DSC PowerSeries Neo line of equipment when used
with the TL280E or TL280RE Communicator and firmware version 5.0 or greater.

For more information about PowerSeries Neo equipment, please visit these DSC websites.
http://www.dsc.com/dsc-product-families/Neo/1
http://www.dsc.com/dsc-product-families/neo/alarm-verification-solutions/5
http://www.dsc.com/index.php?n=library (for looking up manuals)

Purpose
The purpose of this document is to provide guidance for integrating DSC intrusion system equipment with exacqVision and using the
exacqVision client for connecting, controlling and monitoring the PowerSeries Neo equipment.

NOTE: This guide does not cover the installation and configuration of DSC PowerSeries Neo security equipment in general.

Requirements
Exacq software requirements
• exacqVision client/server version: 7.4.x (or greater)
• Enhanced interface controls exacqVision client/server 21.09.x

Enhancements
• Intrusion Panel
▪ Supports multiple DSC Partitions
▪ Alarm state or fault - red
▪ Loss of panel comms - amber
▪ Available but disarmed/unset – green
▪ Arming with bypass zone – flash amber and blue
▪ System in exit time flashes between - green and blue
▪ System armed/set - blue
• Zone Inputs/PIR (Passive Infrared)
▪ A disarmed panel with motion on a zone - amber
▪ An armed panel with a detector in fault or alarm - red

License Requirements
• exacqVision license: Professional or Enterprise

DSC Requirements or As Tested Specifications


• One of the following Communicators:
o TL280(R)E (see COMPONENTS section below, item 5 in the list)
o TL2803G(R)E (NOTE: SIM card activation must be configured for IP communication to be enabled with exacq)
o 3G2080(R)E (NOTE: SIM card activation must be configured for IP communication to be enabled with exacq)
• Firmware version 5.x (or greater)
• No licensing required

IMPORTANT HARDWARE NOTE: Please ensure the TL280 Network Interface Port is not connected to PoE enabled port on a switch.

+1.317.845.5710 USA (Corporate Headquarters)


Page 1 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Components
The PowerSeries Neo components that were tested and integrated with Exacq were the following:
1. Keypad: HSLCD
2. Sensors: PowerG & Wired
3. Control Panels: HS2TCHP LDC TouchPad & HS2128 Keypad
▪ Compatible- HS2016, HS2032, HS2064 & HS2018
4. PowerG Transceiver: HSM2HOST9
5. Communicator module: TL280E, TL280RE/3G
▪ One of the listed TL280 range is required for this integration
6. Any model of exacqVision recorder (required)

4
3

RS422
OR Conversion to
RS232 or USB

5
1
Serial (RS232/RS422)

Ethernet (IP/UDP)

The security system communicates with the exacqVision recorder via the TL280x interface communicator module.

Communications between the exacqVision recorder and the interface module can be established via Ethernet using TCP with UDP or
via Serial (RS232/RS244). Systems requiring a wired serial integration, please ensure a serial port is available.

The security intrusion system must be configured by the keypad or Touch Screen Display to enable communications link to
exacqVision.

Please speak to a DSC representative for further options.

+1.317.845.5710 USA (Corporate Headquarters)


Page 2 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide

Configuration - DSC PowerSeries Neo & Pro

With the exacqVision system connected to the communicator module (TL280) via Ethernet (IP/UDP) or Serial (RS232/RS422), use the
keypad (HSLCD) to configure the security system to communicate with the exacqVision recorder.

Here are some general guidelines to follow when navigating the display panel’s menus.
• Use the arrows “<>” to scroll through options.
• Use the “*” key to change options.
• Use the “#” to go back one menu level.
• In the following steps a comma “,” will be used to separate segments of user input where the user should wait for the
keypad to respond.
• The default operator Code is 1234
• An installer’s code of 5555 (default value) is used throughout these instructions. Substitute your own Installer’s code if
programmed.

Wherever you see a bolded statement such as “Note these characters…”, please do so because you will need these pieces
of information in the exacqVision configuration.

• Reference NEO Communicator V5.0 Installation Manual which can be obtained here
http://www.dsc.com/index.php?n=library You may need an account to access manuals.
• Please refer to the “NEO Communicator V5.0 Manual” (sections in parenthesis).

IMPORTANT NOTE: The Newer DSC NEO software v5.x communicators use alternate codes to previous version 4.x DSC
Communicators. Please refer to the website for historic documentation

4x TCP/UDP Connections – Referred to as Sessions


The DSC Neo TL280 v5.x & DSC Pro support four simulations integrations via Ethernet.
DSC refers to each of these connections as Sessions.

Session 1 and Session 2 are defined in the document providing two Ethernet connectivity options.

E.G. - Use Integration Option - DSC Session 2 for exacqVision and Integration Option - DSC Session 1 for Kantech Entrapass
(Please refer to the application notes provided by Kantech) .
Note:- The two options listed on the next page are supported by exacqVision.

+1.317.845.5710 USA (Corporate Headquarters)


Page 3 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Global DSC Settings

Enroll Keypads
*8, 5555, 902, press * to auto enroll all keypads. Once finished press # three times to exit the menu.

DSC Neo Zone Panel Factory Reset


To reset the zone input panel, fit a wire link between connections PGM-1 & Z1 (zone 1).
Ensure the Battery connections are removed and the power to the communicator prior to adding the link.
Once the wire is linked, power up the transformer.
Wait 1 minute. After 1 minute, power down the transformer and remove the jumper link. The add the battery and transformer
connections again.

DSC Neo TL280x Communicator Reset


*8, 5555, 999, follow the on-screen display instructions.

Time & Date


*6, 1234, press the right arrow >, press *, enter HHMM (hour then minutes) followed by MMDDYY (month, day year) and pressing # twice
to exit the menu.

Communication Module Settings


*8, 5555, 382, scroll to option 5 - Alt Comm. Set value to “Y” by pressing *
*8, 5555, 401, scroll to option 7 - Alt Comm DLS. Set the value to “Y” by pressing *
*8, 5555, 851, 992 - To verify the DSC Neo IP address. This in a non-editable view.

Obtaining the DSC Neo Panel Integration Key and Panel Application Keys required for integration

Defining zone inputs for use with Partitions


*8, 5555, 201, this enters the Partition 1 mask to define zones 1-8. Press * to enter the menu and use the < & > keys to set the zone for
use with Partition 1 by pressing * to set Y (yes=on) or N (no=off). Once assigning the zone press #. Using the > arrow you can navigate to
zones 9-16 to set the zone for use in Partition 1.

Press # once finished defining Partition1, the display will show Part.1 Zone Mask, press the > arow to navigate to Partition 2 labelled
Part.2 Zone Mask to select which zones apply to Partition 2. The same process applied to all Partitions available. Once finished press #
until all menus are exited.

+1.317.845.5710 USA (Corporate Headquarters)


Page 4 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
DSC Neo Communicator Integration Option – Session 1 - Type 1 Encryption
DSC Panel Integration Key
*8,5555, 851, 422, DSC panel Integration ID Number. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Panel Init Key: field.

*8,5555, 851, 423, to view Type 1 Integration Access Code. Enter Value _____________________________________
Please note Use this data in the Exacq DSC Integrations setup Application Init Key: field.
To edited the Access Code to an alternate number e.g. 1111 1111, pressing 1 eight times followed by pressing # twice to exit.

Defining Ethernet for use with UDP


*8, 5555, 851, 425, ensure bits 3 and 5 are set
*8, 5555, 851, 426, ensure bits 1, 3 and 4 are set
*8, 5555, 851, 427, set to 0005 (This increases response times from 10 to 5 seconds)
*8, 5555, 851, 428, (Enter IP of the exacqVision recorder)
*8, 5555, 851, 430, to view or set Session 1 Integration Polling port (default = 0C01). Note for Local Port in exacq
0C01 = Port 3073 for use in the Exacq DSC Integrations setup Local Port Number 3073
*8, 5555, 851, 432, to view / set Session 1 Integration Outgoing port (default = 0C04).
0C04 = Port 3076 for use in the Exacq DSC Integrations setup Panel Port Number 3076

*8, 5555, 851, 001, DSC IP Address Enter Value _____________________________________

*8, 5555, 851, 002, DSC Subnet mask, default 255.255.255.0. Enter Value _____________________________________

*8, 5555, 851, 003, d default gateway. Enter Value _____________________________________


*8, 5555,851, 999, 55 - To restart the communicator, please wait for approx. 60 seconds.

DSC Neo Communicator Integration Option – Session 1 - Type 2 Encryption


DSC Panel Integration Key
*8,5555, 851, 422, DSC panel Integration ID Number. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Panel Init Key: field.

*8,5555, 851, 700, To view the Type2, 32 Character Integration Access Code.

Enter Value ____________________________________________________________________________________________


Please note Use this data in the Exacq DSC Integrations setup Application Init Key: field.
To edited the Access Code to an alternate number e.g. 11111111111111111111111111111111, pressing ‘1’ 32 times followed by pressing
# twice to exit.

Defining Ethernet for use with UDP


*8, 5555, 851, 425, ensure bits 3, 4 and 5 are set - (Note:- bit 4 is the Type2 Encryption)
*8, 5555, 851, 426, ensure bits 1, 3 and 4 are set
*8, 5555, 851, 427, set to 0005 (This increases response times from 10 to 5 seconds)
*8, 5555, 851, 428, (Enter IP of the exacqVision recorder)
*8, 5555, 851, 430, to view or set Session 1 Integration Polling port (default = 0C01). Note for Local Port in exacq
0C01 = Port 3073 for use in the Exacq DSC Integrations setup Local Port Number 3073
*8, 5555, 851, 432, to view / set Session 1 Integration Outgoing port (default = 0C04).
0C04 = Port 3076 for use in the Exacq DSC Integrations setup Panel Port Number 3076

*8, 5555, 851, 001, DSC IP Address Enter Value _____________________________________

*8, 5555, 851, 002, DSC Subnet mask, default 255.255.255.0. Enter Value _____________________________________

*8, 5555, 851, 003, d default gateway. Enter Value _____________________________________


*8, 5555,851, 999, 55 - To restart the communicator, please wait for approx. 60 seconds.

+1.317.845.5710 USA (Corporate Headquarters)


Page 5 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
DSC Neo Communicator Integration Option – Session 2- Type 1 Encryption
DSC Panel Integration Key
*8,5555, 851, 422, DSC panel Integration ID Number. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Panel Init Key: field.

*8,5555, 851, 450, to view Type 1 Integration Access Code. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Application Init Key: field.
To edited the Access Code to an alternate number e.g. 1111 1111, pressing 1 eight times followed by pressing # twice to exit.

Defining Ethernet for use with UDP


*8, 5555, 851, 452, ensure bits 3 and 5 are set
*8, 5555, 851, 453, ensure bits 1, 3 and 4 are set
*8, 5555, 851, 454, set to 0005 (This increases response times from 10 to 5 seconds)
*8, 5555, 851, 455, (Enter IP of the exacqVision recorder)
*8, 5555, 851, 457, to view or set Session 2 Integration Polling port (default = 0C1A). Note for Local Port in exacq
0C1A = Port 3098 for use in the Exacq DSC Integrations setup Local Port Number 3098
*8, 5555, 851, 459, to view / set Session 2 Integration Outgoing port (default = 0C17).
0C17 = Port 3095 for use in the Exacq DSC Integrations setup Panel Port Number 3095

*8, 5555, 851, 001, DSC IP Address Enter Value _____________________________________

*8, 5555, 851, 002, DSC Subnet mask, default 255.255.255.0. Enter Value _____________________________________

*8, 5555, 851, 003, d default gateway. Enter Value _____________________________________


*8, 5555,851, 999, 55 - To restart the communicator, please wait for approx. 60 seconds.

DSC Neo Communicator Integration Option – Session 2- Type 2 Encryption


DSC Panel Integration Key
*8,5555, 851, 422, DSC panel Integration ID Number. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Panel Init Key: field.

*8,5555, 851, 701, to view the Type2, 32 Character Integration Access Code.

Enter Value ____________________________________________________________________________________________


Please note for use in the Exacq DSC Integrations setup Application Init Key: field.
To edited the Access Code to an alternate number e.g. 11111111111111111111111111111111, pressing ‘1’ 32 times followed by pressing
# twice to exit.

Defining Ethernet for use with UDP


*8, 5555, 851, 452, ensure bits 3, 4 and 5 are set - (Note:- bit 4 is the Type2 Encryption)
*8, 5555, 851, 453, ensure bits 1, 3 and 4 are set
*8, 5555, 851, 454, set to 0005 (This increases response times from 10 to 5 seconds)
*8, 5555, 851, 455, (Enter IP of the exacqVision recorder)
*8, 5555, 851, 457, to view or set Session 2 Integration Polling port (default = 0C1A). Note for Local Port in exacq
0C1A = Port 3098 for use in the Exacq DSC Integrations setup Local Port Number 3098
*8, 5555, 851, 459, to view / set Session 2 Integration Outgoing port (default = 0C17).
0C17 = Port 3095 for use in the Exacq DSC Integrations setup Panel Port Number 3095

*8, 5555, 851, 001, DSC IP Address Enter Value _____________________________________

*8, 5555, 851, 002, DSC Subnet mask, default 255.255.255.0. Enter Value _____________________________________

*8, 5555, 851, 003, d default gateway. Enter Value _____________________________________


*8, 5555,851, 999, 55 - To restart the communicator, please wait for approx. 60 seconds.

+1.317.845.5710 USA (Corporate Headquarters)


Page 6 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
DSC Power Series Pro Integration Option – Session 1
Only Type 2 Encryption Supported
Initial Setup Notes
Ensure zones are not enable that do not exist as the Power Series Pro will continually try to poll for the zone PCBs and
prevent connectivity to exacqVision.

DSC Panel Integration Key


*8,5555, 851, 422, DSC panel Integration ID Number. Enter Value _____________________________________
Please note for use in the Exacq DSC Integrations setup Panel Init Key: field.

*8,5555, 382, select option 5 and set to N – Sets the ADC Enable to off (this disabled the www.alarm.com if no account is enabled).
*8,5555, 851, 700, To view the Type2, 32 Character Integration Access Code.

Enter Value ____________________________________________________________________________________________


Please note Use this data in the Exacq DSC Integrations setup Application Init Key: field.
To edited the Access Code to an alternate number e.g. 11111111111111111111111111111111, pressing ‘1’ 32 times followed by pressing
# twice to exit.

Defining Ethernet for use with UDP


*8, 5555, 851, 425, ensure bits 3, 4 and 5 are set - (Note:- bit 4 is the Type2 Encryption)
*8, 5555, 851, 426, ensure bits 1, 3 and 4 are set
*8, 5555, 851, 427, set to 0005 (This increases response times from 10 to 5 seconds)
*8, 5555, 851, 428, (Enter IP of the exacqVision recorder)
*8, 5555, 851, 430, to view or set Session 1 Integration Polling port (default = 0C01). Note for Local Port in exacq
0C01 = Port 3073 for use in the Exacq DSC Integrations setup Local Port Number 3073
*8, 5555, 851, 432, to view / set Session 1 Integration Outgoing port (default = 0C04).
0C04 = Port 3076 for use in the Exacq DSC Integrations setup Panel Port Number 3076

*8, 5555, 851, 001, DSC IP Address Enter Value _____________________________________

*8, 5555, 851, 002, DSC Subnet mask, default 255.255.255.0. Enter Value _____________________________________

*8, 5555, 851, 003, d default gateway. Enter Value _____________________________________


*8, 5555,851, 999, 55 - To restart the communicator, please wait for approx. 60 seconds.

+1.317.845.5710 USA (Corporate Headquarters)


Page 7 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Configuration – exacqVision Type 1 Encryption 1
Session 1 on the DSC Neo TL280 Communicator
Add Security Integration
Launch the exacqVision client and perform the following steps.
Please refer to the “NEO Communicator V5.0 Manual” (sections in parenthesis).

1. Click on the Config(Setup)Page


2. Click on “Add Security Integration”
3. Click New
4. Select “DSC PowerSeries NEO”
5. New Feature - A user definable description
6. Select “UDP Port Configuration”
7. Panel IP Address - Enter IP address of the security system (from above)
8. Local Port Number - Enter 3073 (0C01h hex = 3073dec, from above)
9. Panel Port Number - Enter 3076 (0C04 hex = 3073dec, from above)
2
To quickly convert hexadecimal to decimal, go here:

Example integration using the DSC Neo Session 1 Option listed previously.

4
5
6
7
8
3073

9 3076 10
11
12
13

16 14
10. Panel Init (Integration) Key - (from above) 6 15
a. Enter the first 8 characters of this code 4 times in a row. For example, if the first 8 characters of your code are
“15102105” then enter “15102105151021051510210515102105”.
11. Encryption Type to Type 1
12. Application Init Key - (from above) – The DSC Type1 Integration Access Code using *851 423
a. Enter the first 8 characters of this code 4 times in a row. For example, if the first 8 characters of your code are
“11111111” then enter “11111111111111111111111111111111”.
13. Enter the 4-digit Installer Access Code. We have been using “5555”. Exacq encrypts this data so it appears as more
characters than four after being entered and accepted.
14. Click Apply
15. Ensure that the status reports “Connected”
16. This is the Status information, currently showing a Health warning of No Battery.

+1.317.845.5710 USA (Corporate Headquarters)


Page 8 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Configuration – exacqVision Type 2 Encryption 1
Session 2 on the DSC TL280 Communicator and DSC Pro
Add Security Integration
Launch the exacqVision client and perform the following steps.
Please refer to the “NEO Communicator V5.0 Manual” (sections in parenthesis).

1. Click on the Config(Setup)Page


2. Click on “Add Security Integration”
3. Click New
4. Select “DSC PowerSeries NEO”
5. New Feature - A user definable description
6. Select “UDP Port Configuration”
7. Panel IP Address - Enter IP address of the security system (from above)
8. Local Port Number - Enter 3098 (0C1A hex = 3073dec, from above)
9. Panel Port Number - Enter 3095 (0C17 hex = 3073dec, from above)
2
To quickly convert hexadecimal to decimal, go here:

Example integration using the DSC Neo Session 2 Option listed previously.

4
5
6
7
8

9 10
11
12
13

16 14
10. Panel Init Key - (from above) 6 15
a. Enter the first 8 characters of this code 4 times in a row. For example, if the first 8 characters of your code are
“15102105” then enter “15102105151021051510210515102105”.
11. Encryption Type to Type 2
12. Application Init Key - (from above) – The DSC Type2 Integration Access Code using *851 450
a. Enter the first 8 characters of this code 4 times in a row. For example, if the first 8 characters of your code are
“11111111” then enter “11111111111111111111111111111111”.
13. Enter the 4-digit Installer Access Code. We have been using “5555”. Exacq encrypts this data so it appears as more
characters than four after being entered and accepted.
14. Click Apply
15. Ensure that the status reports “Connected”
16. This is the Status information, currently showing a Health warning of No Battery.

+1.317.845.5710 USA (Corporate Headquarters)


Page 9 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Supported controls now appear when you click on the PowerSeries Neo entry in the configuration tree.

1. Click on PowerSeries Neo.


2. Arming and Disarming can be performed here with the following options:
a. Arm - State when user arms the panel at the keypad using their personal access code
b. Arm Away - provides an exit and entry delay, includes all zones
c. Arm Stay - provides an exit delay, bypasses interior zones
d. Arm (No Delay) - Arms immediately, triggers immediately
3. Zones can be bypassed.

The DSC PowerSeries Neo security is now integrated with exacqVision. For more information, please see your DSC Neo Panel User
information. Visit http://www.dsc.com/index.php?n=library to look up DSC documents.

RS232/422 Connection
You can connect the DSC system via RS232/422 to an exacq system. You may need a serial to USB adapter. If so ensure the driver
for the adapter is installed in the Windows or Linux operating system and the COM port shows up properly in the Serial Ports page,
UART section, of exacqVision. Configure the serial port with a meaningful name and proper attributes for connecting to the DSC
hardware. Those attributes can be configured for the DSC equipment in Step 3 (outlined below)

Enable (RS232/422) (Ethernet/Cellular Programming Options | SMS Event Notification/Command and Control Options)
1. *8, 5555, 851, 425, ensure bits 1 and 5 are set
2. *8, 5555, 851, 420, set or check baud rate
3. *8, 5555, 851, 421, set or check parity, stop bits, flow control, etc. (See NEO Communicator V5.0 Manual)

Follow the same steps as in the Configuration - exacqVision section except make the following selections:

1. Panel Connection Type: Select Serial Port Configuration


2. Serial Port Name: Select name of serial port you configured on Serial Ports page, UART section

+1.317.845.5710 USA (Corporate Headquarters)


Page 10 of 11
www.exacq.com +5255.56080817
+44.1438.310163
+31.485.324.347
Mexico
Europe/Middle East/Asia
Central Europe
Updated 4/2022
DSC PowerSeries Neo v5.x & Pro Integration Guide
Troubleshooting
When using IP/UDP to connect and the status in the “Add Security Integration” is not showing connected, you may have to delete
and allow the integration to re-create the serial port. Follow these steps.

1. Navigate to the Serial Ports page


2. Select the itv2 serial port (this was created automatically)
3. Click Delete

You should notice that the port is re-created almost immediately. Now go back to the “Add Security Integrations” area and check
the status again.

Contact info and Support


Support (Technical Support, Customer Service, Sales, and more)
https://www.dsc.com/index.php?o=contact

Exacq Support (Technical Support, Training tools, and more)