Simatic ktp400 Basic
Simatic ktp400 Basic
1
SIMATIC HMI HMI device KTP400 Basic, KTP600 Basic, KTP1000 Basic, TP1500 Basic
______________
Overview
HMI device
4
KTP400 Basic, KTP600 Basic, ______________
Operating the user interface
KTP1000 Basic, TP1500 Basic Configuring the operating
5
Operating Instructions
______________
system
6
______________
Commissioning a project
7
______________
Maintenance and care
8
______________
Technical specifications
A
______________
Appendix
B
______________
Abbreviations
08/2008
A5E01075587-01
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only
in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage,
positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
The help integrated in WinCC flexible, the WinCC flexible Information System, contains
detailed information. The WinCC flexible Information System contains instructions, examples
and reference information in electronic form.
Photos
Photographs are sometimes used to illustrate the HMI devices in these operating
instructions. Newer versions of the products may differ from the photographs.
Conventions
The following graphical highlighting facilitates reading these operating instructions:
.7
3
Note
A note contains important information on described products and their handling or on a
section of this documentation.
Trademarks
Names labeled with a ® symbol are registered trademarks of the Siemens AG. Other names
used in this documentation may be trademarks, the use of which by third parties for their
own purposes could violate the rights of the owner.
● HMI®
● SIMATIC®
● SIMATIC HMI®
● SIMATIC ProTool®
● WinCC®
● SIMATIC WinCC flexible®
Additional information
You can find additional information and support for products described in the manual in the
following table:
Request Contact
Representatives and offices http://www.siemens.com/automation/partner
Additional technical documentation http://www.automation.siemens.com/simatic/portal/html_76/tec
hdoku.htm
Training Center Tel: +49 911 895 3200
http://www.sitrain.com
Technical Support Tel: + 49 180 5050 222
Fax: + 49 180 5050 223
http://support.automation.siemens.com
Service http://www.siemens.com/automation/service
Preface ...................................................................................................................................................... 3
1 Overview.................................................................................................................................................. 11
1.1 Product Overview.........................................................................................................................11
1.2 Design of the KTP400 Basic HMI device.....................................................................................12
1.3 Design of the KTP600 DP Basic HMI device...............................................................................13
1.4 Design of the KTP600 PN Basic HMI device...............................................................................14
1.5 Design of the KTP1000 DP Basic HMI device.............................................................................15
1.6 Design of the KTP1000 PN Basic HMI device.............................................................................16
1.7 Design of the TP1500 Basic HMI device .....................................................................................17
1.8 Product package ..........................................................................................................................18
1.9 Accessories..................................................................................................................................19
1.10 Commissioning the HMI device ...................................................................................................20
2 Safety instructions and general notes ...................................................................................................... 21
2.1 Safety instructions........................................................................................................................21
2.2 Notes about usage.......................................................................................................................22
3 Mounting and connecting......................................................................................................................... 23
3.1 Preparations.................................................................................................................................23
3.1.1 Checking the package contents...................................................................................................23
3.1.2 Checking the operating conditions...............................................................................................23
3.1.3 Selecting a mounting position ......................................................................................................24
3.1.4 Checking clearances....................................................................................................................25
3.1.5 Making the mounting cut-out........................................................................................................25
3.1.6 Labeling the function keys ...........................................................................................................27
3.2 Mounting the HMI device .............................................................................................................28
3.3 Connecting the HMI device..........................................................................................................30
3.3.1 Connection sequence ..................................................................................................................30
3.3.2 Connecting the equipotential bonding circuit ...............................................................................31
3.3.3 Connecting the power supply.......................................................................................................33
3.3.4 Connecting a programming device ..............................................................................................34
3.3.5 Connecting the configuration PC .................................................................................................35
3.3.6 Connecting the PLC.....................................................................................................................38
3.4 Switching on and testing the HMI device.....................................................................................40
4 Operating the user interface .................................................................................................................... 41
4.1 Overview ......................................................................................................................................41
4.2 General functions of the screen keyboard ...................................................................................43
4.3 Entering data on the KTP400 Basic.............................................................................................44
Product package
The following components are included in the product package of the HMI device.
Installation instructions 1
Mounting seal 1
Mains terminal 1
1.9 Accessories
The following accessories are available for the HMI devices in the Internet at
http://mall.automation.siemens.com.
PC/PPI cable
You need the PC/PPI cable to update the operating system with reset to factory settings.
You can also use the cable for data transfer. Connect the PC/PPI cable to the RS 422/485
port. The cable converts the input signals to RS-232 signals.
The cable is not included in the product package of the HMI device and is available under
order number 6ES7 901-3CB30-0XA0.
Note
Set a lower bit rate if the connection is lost during the operating system update. If you use a
higher bit rate, you must use the PC/PPI cable release 3 or higher. The version code is
printed on the cable (for example, "E-Stand 3" corresponds to version 3).
USB/PPI cable
You need the USB/PPI cable to update the operating system with reset to factory settings.
You can also use the cable for data transfer. Connect the PC/PPI cable to the RS 422/485
port. The cable converts the input signals to USB signals.
The cable is not included in the product package of the HMI device and is available under
order number 6ES7 901-3DB30-0XA0.
Clamping frame
A clamping frame is available for the KTP1000 HMI under order number
6AV6 671-8XS00-0AX0.
Protective foil
Protective foils are available for the HMI devices under the following order numbers:
● Protective foil for KTP400 Basic: 6AV6 671-2EC00-0AX0
● Protective foil for KTP600 Basic: 6AV6 671-2XC00-0AX0
● Protective foil for KTP1000 Basic: 6AV6 574-1AD00-4CX0
● Protective foil for KTP1500 Basic: 6AV6 574-1AD00-4EX0
Description Section
1. Familiarize yourself with the safety Safety instructions and general notes
instructions. (Page 21)
2. Prepare the HMI device for mounting. Preparations (Page 23)
3. Install the HMI device. Mounting the HMI device (Page 28)
4. Connect the equipotential bonding. Connecting the equipotential bonding circuit
(Page 31)
5. Connect the power supply. Connecting the power supply (Page 33)
6. Connect a configuration PC. Connecting the configuration PC (Page 35)
7. Enable sharing for data channel on the HMI Enabling a data channel (Page 57)
device.
8. Transfer a project. Starting manual transfer (Page 63)
9. After transferring the project, disconnect the Connecting the PLC (Page 38)
HMI device from the configuration PC and
connect the HMI device to the PLC.
WARNING
Open equipment
The HMI device is open equipment. That is, the HMI device may only be installed in
cubicles or cabinets which provide front panel access for operating the device.
The cubicle or cabinet in which the HMI device is installed may only be accessed with a key
or tool and only by trained, authorized personnel.
Dangerous voltage
Opening the cabinet will expose high voltage parts. Contact with these parts could be fatal.
Always disconnect the cabinet from the mains before opening it.
NOTICE
Unwanted operating states
High-frequency radiation, for example, from cellular phones, can trigger unwanted
operating states.
Installation as intended
WARNING
Installation only in machinery that conforms to the machinery directive
It is not allowed to commission the HMI device unless it has been verified that the machine
in which the HMI device is to be installed complies with Directive 98/37/EC. The following
applies as of December 29, 2009: The machine in which the HMI device is to be installed
must conform to Directive 2006/42/EC.
Industrial applications
The HMI device is designed for industrial applications. It conforms to the following standards:
● Requirements of the emission standard for industrial environments, EN 61000-6-4: 2007
● ESD immunity requirements to DIN EN 61000-6-2:2005
Note
The HMI device is not intended for use in residential areas. Operation of an HMI device in
residential areas can have a negative influence on radio/TV reception.
If the HMI device is used in a residential area, you must take measures to achieve Limit
Class B conforming to EN 55011 for RF interference.
A suitable measure for achieving the RF interference level to Limit Class B includes, for
example, the use of filters in power supply lines
Individual acceptance is required.
Notes on communication
NOTICE
Communication errors caused by IP address conflicts
Communication errors can occur if several devices in a network share the same IP
address.
Make sure that your HMI device is assigned a unique IP address in the network.
Note
Updating tag values following a communication error
If communication between an HMI device and PLC is interrupted, all tag values displayed on
the HMI device will be replaced by a hash mark ("#").
When the communication between the HMI device and PLC is restored, all tag values will be
updated immediately. The cycle time for updating the tag values begins again at "0."
NOTICE
Damaged parts
Do not install parts damaged during shipment. In the case of damaged parts, contact your
Siemens representative.
CAUTION
Exceeding the ambient temperature
Forced ventilation is required if the maximum permitted ambient temperature for operating
the HMI device is exceeded. The HMI device can otherwise be damaged and its approvals
and warranty will be void.
See also
Conditions of use (Page 83)
NOTICE
Stability of the mounting cut-out
The material in the area of the mounting cut-out must provide sufficient strength to
guarantee the enduring and safe mounting of the HMI device.
The force of the clamps or operation of the device may not lead to deformation of the
material in order to achieve the degrees of protection described below.
Degrees of protection
The degrees of protection of the HMI device can only be guaranteed if the following
requirements are met:
● Material thickness at the mounting cut-out for IP65 degree of protection, or for
enclosure type 4X/type 12 (indoor use only): 2 mm to 6 mm
● Permitted deviation from plane at the mounting cut-out: ≤ 0.5 mm
This condition must be fulfilled for the mounted HMI device.
● Permissible surface roughness in the area of the seal: ≤ 120 µm (Rz 120)
A clamping frame is additionally available for mounting the KTP1000 Basic to panels with a
material thickness < 2 mm at the mounting cut-out. The frame enables you to achieve IP65
degree of protection or the protection class for enclosures type 4X/type 12.
Mounting compatibility
The mounting cut-outs of the Basic panels are compatible with the mounting cut-outs of the
following SIMATIC HMI devices:
Mounting cut-out for the Basic Compatible to the mounting cut-outs of the HMI device
Panel
KTP400 TP 177B 4"
KTP600 TP 177 A, TP 177B 6", TP 177micro
KTP1000 MP 277 10" Touch, MP 377 12" Touch
TP1500 MP 377 15" Touch, Thin Client 15" Touch
.73
.73
.73
w
73
h
Dimensions of the mounting cut-out for the
Basic HMI devices in vertical mounting
position:
+1 +1
w 0 h 0
.73
.73
All dimensions in mm
See also
Accessories (Page 19)
Note
Do not write on the keyboard to label the function keys.
Any printable and writable foil can be used as labeling strips. The permitted thickness of the
labeling strip is 0.15 mm. Paper labeling strips are inappropriate.
.7
3
Mounting clamps
• KTP400 Basic: 5
• KTP600 Basic: 8
• KTP1000 Basic: 12
• TP1500 Basic: 14
.7
3
ದ
ದ
.73 .73
ದ
ದ 73
ದ .73
ದ
ದ
Screwdriver:
• Slotted screwdriver, size 2
• Philips screwdriver, size 3
• Torx screwdriver size 3
Crimp pliers
Mains terminal
Procedure
Keep to the following sequence of tasks when connecting the HMI device:
1. Connecting the equipotential bonding circuit (Page 31)
2. Connecting the power supply (Page 33)
3. Connecting the configuration PC (Page 35)
4. Connecting the PLC (Page 38)
NOTICE
Strain relief
Contacts can be broken or wires can be torn off if cables are not provided adequate
strain relief.
Provide adequate strain relief for all cables.
NOTICE
Equipotential bonding cable
Cable shielding is not suitable for equipotential bonding. Always use the prescribed
equipotential bonding conductors. The cross-section of the equipotential bonding
conductor must not be less than 16 mm². Always use cables with an adequate cross-
section when installing MPI and PROFIBUS DP networks. The interface modules may
otherwise be damaged or destroyed.
Procedure
PPt
2
PPt
PPt
352),%86
352),1(7
Procedure
CAUTION
24 VDC only
An incorrectly dimensioned power supply can lead to destruction of the HMI device.
Use a 24 VDC power supply with adequate amperage; see Specifications (Page 93).
.7
3 3. Switch off the power supply.
1
3
M 4
L+
Note
A programming device cannot be used to reset the HMI device to factory settings.
21
RS 422/ 485
PROFIBUS
3. Connect an RS 485 PROFIBUS
connector to the programming
device.
RS 485
PG
RS 232
PC
Note
Set a lower bit rate if the connection is lost during the operating system update. If you use a
higher bit rate, you must use the PC/PPI cable release 3 or higher. The version code is
printed on the cable (for example, "E-Stand 3" corresponds to version 3).
CAUTION
Data network security for communication via Ethernet
End users are themselves responsible for ensuring security of their data network in
Ethernet-based communication, such as PROFINET IO, HTTP, Sm@rtAccess,
Sm@rtService and OPC, since operation of the device cannot be guaranteed if the device
is subject to targeted attacks resulting in overload, for example.
LAN
LAN
PC
See also
Data transmission options (Page 63)
Note
Note the diagrams of DIP switch settings on the rear panel of the HMI device.
The following table shows the DIP switch settings. The send and receive direction is toggled
internally using the RTS signal.
Communication Switch setting Meaning
DP/MPI/PPI No RTS signal on connector, for data exchange between
the SIMATIC PLC and the HMI device
21 (factory state)
CAUTION
Data network security for communication via Ethernet
End users are themselves responsible for ensuring security of their data network in
Ethernet-based communication, such as PROFINET IO, HTTP, Sm@rtAccess,
Sm@rtService and OPC, since operation of the device cannot be guaranteed if the device
is subject to targeted attacks resulting in overload, for example.
PROFINET
PROFINET
LAN
SIMATIC S7-200
SIMATIC S7-300/400
.7
3
M
L+
DANGER
Incorrect operation
A project can contain certain operations that require in-depth knowledge about the specific
plant on the part of the operator.
Ensure that only trained professional personnel operate the plant.
CAUTION
Damage to the touch screen
Pointed or sharp objects can damage the plastic surface of the touch screen.
Always operate the touch screen with your fingers or with a touch pen only.
Triggering unintended actions
Touching several operator controls at the same time can trigger unintended actions.
Touch only one operator control on the screen at a time.
Operator controls are touch-sensitive symbols on the screen of the HMI device.
They are basically operated in the same way as mechanical keys. You activate operator
controls by touching them with your finger.
Note
The HMI device returns a visual feedback as soon as it detects that an operator control has
been touched.
The visual feedback is independent of any communication with the PLC. The visual feedback
signal therefore does not indicate whether or not the relevant action is actually executed.
"Untouched" "Touched"
● Invisible buttons
The focus of invisible buttons is by default not indicated following selection. No optical
operation feedback is provided in this case.
The configuration engineer may, however, configure invisible buttons so that their outline
appears as lines when touched. This outline remains visible until you select another
operator control.
● I/O fields
A screen keyboard appears as visual feedback after you touched an I/O field, for
example, to enter a password.
Depending on the HMI device and the configured operator control, the system displays
different screen keyboards for entering numerical or alphanumerical values.
The screen keyboard is automatically hidden again when input is complete.
Note
Description of all operator controls
A comprehensive description of all operator controls for your HMI device is provided in
the WinCC flexible Online Help.
Cursor left
Cursor right
Delete character
Cancel input
Confirm input
Display infotext. This key only appears when an infotext has been configured for the
operator control.
7H[W 7H[W
681
6\PEROV 1XPEHUV
681 681
The screen keyboard appears on the HMI device touch screen when you touch an operator
control that requires input.
The screen keyboard of the KTP400 features four views. You can change the view while
making entries using the buttons in the fourth row of the screen keyboard:
Button Changes to the view
Entering text, characters "A" to "M"
Entering numbers, "0" to "9," signed or unsigned and with or without decimal places
Note
Job mailbox has no effect
PLC job 51 "Select screen" has no effect while the screen keyboard is open.
Key assignment
The alphanumerical keyboard layout is monolingual.
A language change within the project does not have any effect on the layout of the
alphanumerical screen keyboard.
7H[W 1XPEHUV
681 ))))
Note
Job mailbox has no effect
PLC job 51 "Select screen" has no effect while the screen keyboard is open.
Key assignment
The alphanumerical keyboard layout is monolingual.
A language change within the project does not have any effect on the layout of the
alphanumerical screen keyboard.
%DVLF3DQHOV31
NOTICE
If the password is no longer available for the Control Panel, you must update the operating
system before you can edit the settings in the Control Panel.
All data on the HMI device is overwritten when you update the operating system!
5.2 Overview
The following table shows the functions available in the Control Panel for configuring your
HMI device.
Symbol Function
Changing MPI/DP settings (Page 51)
Note
The settings for MPI or PROFIBUS DP communication are defined in the HMI device project.
Edit the transfer settings only in the following situations:
• Initial transfer of a project.
• Changes made to the project are activated at a later time.
NOTICE
Communication errors caused by IP address conflicts
Communication errors can occur if several devices in a network share the same IP
address.
Assign each HMI device an IP address that is unique within the network.
NOTICE
Orientation of the screen for KTP400 Basic and KTP600 Basic
The screen orientation is defined by the configuration engineer in the course of project
creation. The appropriate screen orientation is set automatically when you transfer the
project to the HMI device.
Do not make any changes to the screen orientation if a project exists on the HMI device.
The screen content may otherwise be truncated.
Note
Immediate start of the project with a delay time of 0 seconds
The project starts immediately if a delay time of 0 seconds is set. However, this setting
prevents you from calling the loader after having powered on the HMI device. To handle this
situation, you need to configure an operator control with the "Close project" function.
6 7
9
Time limit: 30 sec
Note
After having completed the project transfer, you can protect the HMI device against
unintentional overwriting of project data and of the HMI device image by locking all data
channels.
Note
Automatic transfer is activated be setting the "Remote Control" check box. If automatic
transfer is activated, the HMI device can be set remotely to transfer mode by a configuration
PC or programming device.
Note
Automatic transfer is activated be setting the "Remote Control" check box. If automatic
transfer is activated, the HMI device can be set to transfer mode by a remote configuration
PC or a programming device.
NOTICE
The password cannot contain spaces or special characters * ? . % / \ ' ".
If the password is no longer available for the Control Panel, you first have to update the
operating system before you can make any changes in the Control Panel. All data on the
HMI device will be overwritten when you update the operating system.
NOTICE
Burn-in effect
The screen contents may leave a faint version (ghost) of the image in the background if
they appear for too long.
The "ghost" will disappear automatically after some time. The longer the same content is
displayed on the screen, the longer it will take for the burn-in effect to disappear.
The screen saver helps to prevent burn-in.
Always use the screen saver.
Configuration phase
A project – the process image of the working process – is produced during configuration to
visualize automated working processes. The process displays for the project contain
displays for values and messages which provide information about process statuses. The
process control phase follows the configuration phase.
Operating modes
The HMI device may be in the following operating modes:
● Offline
● Online
● Transfer
"Offline mode" and "Online mode" can be set on both the configuring PC and the HMI
device. To set these modes on the HMI device, use a corresponding operating element of
the project.
"Transfer" mode
In this mode, you can transfer a project from the configuring PC to the HMI device or backup
and restore HMI device data, for example.
The following options are available for setting "Transfer" mode on the HMI device:
● When the HMI device starts up
Start "Transfer" mode manually in the HMI device Loader.
● During ongoing operation
Start the "Transfer" mode manually within the project using an operating element. The
HMI device toggles to "Transfer" mode when automatic mode is set and a transfer is
initiated on the configuring PC.
Overview
The following table shows the options for data transfer between the HMI device and
configuration PC.
1) Applies for operations with PC/PPI cable 6ES7 901-3CB30-0XA0 or USB/PPI cable
6ES7 901-3DB30-0XA0.
6.4 Transfer
6.4.1 Overview
Transfer the executable project from the configuration PC to the HMI device.
You can start the "Transfer" mode manually or automatically on the HMI device.
Transferred data is written directly to internal flash memory of the HMI device. Parameterize
a corresponding data channel before you start the transfer.
Introduction
You can manually switch the HMI device to "Transfer" mode as follows:
● At runtime, using a configured operator control.
● In the Loader of the HMI device.
Requirements
● The "*.hmi" project is open in WinCC flexible.
● The HMI device is connected to a configuration PC.
● The data channel is parameterized on the HMI device.
● The HMI device is in "Transfer" mode.
Procedure
Proceed as follows:
1. On the configuration PC, select the "Transfer settings" command from the "Project >
Transfer" menu in WinCC flexible.
The "Select devices for transfer" dialog opens.
2. Select the HMI device in the left area of the dialog.
3. Select the type of interconnection for the HMI device and the configuration PC.
Set the connection parameters.
4. Set the transfer parameters in the right area of the dialog.
5. Start the transfer in WinCC flexible by selecting "Transfer".
The configuration PC checks the connection to the HMI device. The project is transferred
to the HMI device. An error message is displayed on the configuration PC if the
connection is either not available, or disrupted.
Result
The project is available on the HMI device after successful completion of the transfer. The
transferred project is started automatically.
Introduction
If automatic transfer is activated, the HMI device automatically changes to "Transfer" mode
at runtime as soon as a transfer is started on the connected configuration PC.
Note
With automatic transfer, the HMI device only changes into "Transfer" mode when the project
is running on the HMI device.
Automatic transfer is particularly suited for the test phase of a new project since transfer is
completed without interfering with the HMI device.
NOTICE
If automatic transfer is activated on the HMI device and a transfer is initiated on the
configuration PC, the project currently running is automatically stopped. The HMI device
then automatically switches to "Transfer" mode.
After the commissioning phase, deactivate the automatic transfer so that the HMI device
cannot be inadvertently switched to transfer mode. Transfer mode can trigger unintentional
actions in the plant.
You can issue a password in the Control Panel to restrict access to the transfer settings
and thus avoid unauthorized modifications.
Requirements
● The *.hmi project is opened in WinCC flexible.
● The HMI device is connected to a configuration PC.
● The data channel is configured on the HMI device
● The automatic transfer is activated in the data channel for the transfer
● The project is started on the HMI device.
Procedure
Proceed as follows:
1. On the configuration PC, select the "Transfer settings" command from the "Project >
Transfer" menu in WinCC flexible.
The "Select devices for transfer" dialog opens.
2. Select the HMI device in the left area of the dialog.
3. Select the type of interconnection for the HMI device and the configuration PC.
Set the connection parameters.
4. Set the transfer parameters in the right area of the dialog.
5. Start the transfer in WinCC flexible by selecting "Transfer".
The configuration PC checks the connection to the HMI device. The HMI device shuts
down the current project and automatically changes to "Transfer" mode. The project is
transferred to the HMI device. An error message is displayed on the configuration PC if
the connection is not available or disrupted.
Result
The project is available on the HMI device following successful transfer. The transferred
project is started automatically.
Introduction
There are two options to test a project:
● Test the project on the configuring PC
You can test a project at a configuring PC, using a simulator. For detailed information,
refer to the "WinCC flexible" user manual and to the WinCC flexible Online Help.
● Offline testing of the project on the HMI device
Offline testing means that communication between the HMI device and PLC is down
while the test is being carried out.
● Online testing of the project on the HMI device
Online testing means that the HMI device and PLC communicate with each other during
testing.
Perform the tests, starting with the "Offline test", followed by the "Online test".
Note
You should always test the project on the HMI device on which the project will be used.
Procedure
In "Offline" mode, you can test individual project functions on the HMI device without them
being affected by the PLC. PLC tags, therefore, are not updated.
Test the operating elements and visualization of the project as far as possible without
connecting to the PLC.
Procedure
In "Online" mode, you can test individual project functions on the HMI device without them
being affected by the PLC. PLC tags are updated in this case.
You have the option to test all communication-dependent functions, for example alarms, etc.
Test the operating elements and views of the project.
6.5.1 Overview
General information
NOTICE
Power failure
If a complete restore operation is interrupted due to power failure on the HMI device, the
operating system of the HMI device may be deleted. In this case, you have to reset the HMI
device to its factory settings.
Compatibility conflict
If a message is output on the HMI device warning of a compatibility conflict during the
restore operation, the operating system must be updated.
Requirement
● No project is open on the configuration PC in WinCC flexible.
● The HMI device is connected to this configuration PC.
● The data channel is programmed on the HMI device.
Procedure – backup
Proceed as follows:
1. On the configuration PC, select the "Communication settings" command in the menu
"Project > Transfer" in WinCC flexible.
The "Communication settings" dialog box opens.
2. Select the type of HMI device.
3. Select the type of connection between the HMI device and the configuration PC.
Set the connection parameters.
4. Close the dialog with "OK".
5. Select the "Backup" command in the menu "Project > Transfer" in WinCC flexible.
The "Backup settings" dialog opens.
6. Select the data to be backed up.
7. Select a destination folder and a file name for the "*.psb" backup file.
8. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the HMI device automatically
sets "Transfer" mode when a backup is initiated.
9. Start the backup operation in WinCC flexible with "OK" on the configuration PC.
10.Follow the instructions in WinCC flexible.
A status view opens to indicate the progress of the operation.
Result
The system outputs a message when the backup is completed.
The relevant data is now backed up on the configuration PC.
Procedure – restoring
Proceed as follows:
1. On the configuration PC, select the "Communication settings" command in the menu
"Project > Transfer" in WinCC flexible.
The "Communication settings" dialog box opens.
2. Select the type of HMI device.
3. Select the type of connection between the HMI device and the configuration PC.
4. Set the connection parameters.
5. Close the dialog with "OK".
6. Select the "Restore" command in the menu "Project > Transfer" in WinCC flexible.
The "Restore Settings" dialog opens.
7. Select the "*.psb" backup file to be restored from the "Open" field.
You can see the HMI device for which the backup file was created and the type of backup
data the file contains.
8. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
9. Start the restore operation in WinCC flexible with "OK" on the configuration PC.
Follow the instructions in WinCC flexible.
A status view opens to indicate the progress of the operation.
Result
When the restore is successfully completed, the data backed up on the configuration PC is
now on the HMI device.
Requirements
● The HMI device is connected to a PC on which ProSave is installed.
● The data channel is parameterized on the HMI device.
Procedure – backup
Proceed as follows:
1. Go to the Windows Start menu and start ProSave on the PC.
2. Select the HMI device type in the "General" tab.
3. Select the type of interconnection for the HMI device and the PC.
Set the connection parameters.
4. Select the data to be backed up in the "Backup" tab.
– "Complete backup" generates a backup copy of configuration data, recipe data and
the HMI device image to a file in PSB format.
– "Recipes" generates a backup copy of the HMI device's recipe data records in PSB
format.
– "Recipes (CSV format)" saves a backup copy of the HMI device's recipe data records
to a text file in CSV format. The semicolon is used as column separator.
– "User management" generates a backup copy of the HMI device's user data in PSB
format.
5. Select the folder and file name for the *.psb" backup file .
When generating a backup copy of recipes in CSV format, only select a folder. A CSV file
is generated for each recipe in this folder.
6. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the HMI device automatically
sets "Transfer" mode when a backup is initiated.
7. Start the backup operation in ProSave with "Start Backup".
Follow the instructions in ProSave.
A progress bar opens to indicate the progress of the operation.
Result
The system outputs a message when the backup is completed.
A backup copy of the data is now available on the PC.
Procedure – restore
Proceed as follows:
1. Go to the Windows Start menu and start ProSave on the PC.
2. Select the HMI device type in the "General" tab.
3. Select the type of interconnection for the HMI device and the PC.
4. Set the connection parameters.
5. Select the "*.psb" backup file to be restored from the "Restore" tab.
You can see the HMI device for which the backup file was created and the type of backup
data the file contains.
Select one or several CSV files from the source folder to restore the recipes from CSV
files.
6. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
7. Start the restore operation in ProSave on the PC with "Start Restore".
8. Follow the instructions in ProSave.
A progress bar indicates the progress of the operation.
Result
When the restore is successfully completed, the data backed up on the PC is now on the
HMI device.
6.6.1 Overview
NOTICE
Data loss
All data on the HMI device, such as the project and licenses, will be deleted when you
update the operating system.
Note
Calibrating the touch screen
After the update, you may have to recalibrate the touch screen.
NOTICE
Data channels
When resetting to factory settings, all data channel parameters are reset. The transfer
can only be started following reconfiguration of the data channels.
Note
You have to perform an operating system update with reset to factory setting if the HMI
device does not yet have an operating system or if the HMI device's operating system is
corrupt.
First, start the operating system update in ProSave or WinCC flexible and switch the
power on the HMI device off and on again when prompted.
See also
Data transmission options (Page 63)
Procedure
Proceed as follows:
1. When updating the operating system with reset to factory setting only:
Switch off power to the HMI device.
2. On the configuration PC, select the "Communication settings" command in the menu
"Project > Transfer" in WinCC flexible.
The "Communication Settings" dialog opens.
3. Select the type of HMI device.
4. Select the type of connection between the HMI device and the configuration PC, then set
the connection parameters.
5. Close the dialog box with "OK".
6. Select the "OS Update" command from the "Project > Transfer" menu in WinCC flexible.
7. Select whether to update the operating system with or without restoring the factory
settings by setting the "Reset to factory settings" check box accordingly.
8. Select the HMI device image file "*.img" under "Image path".
The HMI device image files are available under "WinCC flexible Images" in the
WinCC flexible installation folder or on the WinCC flexible installation CD.
The output area provides information on the version of the successfully opened HMI
device image file.
9. When updating without reset to the factory settings only:
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when an update is initiated.
10.In WinCC flexible, select "Update OS" on the configuration PC to run the operating
system update.
11.When updating with reset to the factory settings only:
Switch on the power supply to the HMI device.
12.Follow the instructions in WinCC flexible.
A progress bar indicates the progress of the operating system update.
Result
A message is displayed when the operating system update is successfully completed.
The HMI device no longer contains any project data.
Requirements
● The HMI device is connected to a PC on which ProSave is installed.
● When updating the operating system without reset to factory settings only:
The data channel is configured on the HMI device.
Procedure
Proceed as follows:
1. When updating the operating system with reset to factory settings only:
Switch off power to the HMI device.
2. Go to the Windows Start menu and start ProSave on the PC.
3. Select the HMI device type in the "General" tab.
4. Select the type of connection between the HMI device and the PC, then set the
connection parameters.
5. Select the "OS Update" tab.
6. Select whether to update the operating system with or without restoring the factory
settings by setting the "Reset to factory settings" check box accordingly.
7. Select the HMI device image file "*.img" under "Image path".
The HMI device image files are available under "WinCC flexible Images" in the
WinCC flexible installation folder or on the WinCC flexible installation CD.
The output area provides information on the version of the successfully opened HMI
device image file.
8. When updating without reset to the factory settings only:
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when an update is initiated.
9. Select "Update OS" on the PC to run the operating system update.
10.When updating with reset to the factory settings only:
Switch on the power supply to the HMI device.
11.Follow the instructions in ProSave.
A progress bar indicates the progress of the operating system update.
Result
A message is displayed when the operating system update is successfully completed.
The HMI device no longer contains any project data.
Introduction
The HMI device is designed for maintenance-free operation. The touch screen and keyboard
membrane should nevertheless be cleaned regularly.
Requirements
Use a cleaning cloth dampened with a cleaning agent to clean the equipment. Only use
water with a little liquid soap or a screen cleaning foam.
NOTICE
Unintentional response
When cleaning the touch screen, an unintentional response in the controller can be
triggered by touching keys.
Switch the HMI device off before cleaning to prevent unintentional responses.
Damage caused by unauthorized cleaning products
The HMI device may be damaged if compressed air, steam jet-air ejectors, aggressive
solvents or scouring powders are used for cleaning purposes.
Do not clean the HMI device with compressed air or steam jet blowers. Do not use
aggressive solvents or scouring powder.
Procedure
Proceed as follows:
1. Switch off the HMI device.
2. Spray the cleaning solution onto a cleaning cloth.
Do not spray directly onto the HMI device.
3. Clean the HMI device.
When cleaning the display wipe from the screen edge inwards.
7.2 Recycling
Approvals
CAUTION
The following overview shows possible approvals.
The HMI device itself is certified as shown on the rear panel labels.
CE approval
The HMI device meets the general and safety-related requirements of the following EC
directives and conforms to the harmonized European standards (EN) for programmable logic
controllers published in the official gazettes of the European Union:
● 2006/95/EG "Low Voltage Directive"
● 2004/108/EC "Electromagnetic Compatibility" (EMC Directive)
● Specific absorption rate to EN 50392
EC Declaration of Conformity
The EC Declarations of Conformity are available to the relevant authorities at the following
address:
Siemens AG
Industry Sector
I IA AS RD ST PLC
PO Box 1963
D-92209 Amberg
N117
The HMI device fulfills the requirements of standard AS/NZS 2064 (Class A).
UL approval
IEC 61131
The HMI device fulfills requirements and criteria to IEC 61131-2, Programmable Logic
Controllers, Part 2: Operating resource requirements and tests.
Introduction
The HMI device fulfills, among other things, the requirements of the EMC laws pertaining to
the European domestic market.
Pulse-shaped disturbance
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. The precondition for electromagnetic compatibility is that the HMI
device meets the specifications and guidelines for electrical installation.
Pulse-shaped disturbance Tested with Degree of
severity
Electrostatic discharge Air discharge: 8 kV 3
in accordance with IEC 61000-4-2 Contact discharge: 6 kV
Burst pulses 2 kV power supply cable 3
(high-speed transient interference) 2 kV signal cable, > 30 m
in accordance with IEC 61000-4-4 1 kV signal cable, < 30 m
High-power surge pulses in accordance with IEC 61000-4-5, external protective circuit required (refer
to the manual Automation System S7-300, Installation, "Lightning and overvoltage protection"
section)
Asymmetrical coupling 2 kV power cable 3
DC voltage with protective elements
2 kV signal/data cable, > 30 m,
with protective elements as required
Symmetrical coupling 1 kV power cable 3
DC voltage with protective elements
1 KV signal cable, > 30 m, with protective
elements as required
Sinusoidal interference
The following table shows the EMC behavior of the modules with respect to sinusoidal
interference. This requires the HMI device to meet the specifications and directives for
electrical installation.
Sinusoidal interference Test values Degree of
severity
HF radiation (in • 80% amplitude modulation at 1 kHz 3
electromagnetic fields) in with 10 V/m in the range of 80 MHz to 1 GHz
with 3 V/m in the range 1.4 GHz to 2 GHz
accordance with with 1 V/m the range 2 GHz to 2.7 GHz
IEC 61000-4-3
• 10 V/m with 50% pulse modulation at 900 MHz
10 V/m with 50% pulse modulation at 1.89 GHz
NOTICE
Ensure that no condensation (dewing) develops on or inside the HMI device after
transporting it at low temperatures or after it has been exposed to extreme temperature
fluctuations.
The HMI device must have acquired room temperature before it is put into operation. Do
not expose the HMI device to direct radiation from a heater in order to warm it up. If dewing
has developed, wait approximately 4 hours until the HMI device has dried completely
before switching it on.
Proper transport and storage, installation and assembly as well as careful operation and
maintenance are required to ensure trouble-free and safe operation of the HMI device.
The warranty for the HMI device will be deemed void if these stipulations are not heeded.
Reducing vibrations
If the HMI device is subjected to greater shocks or vibrations, you must take appropriate
measures to reduce acceleration or amplitudes.
We recommend fitting the HMI device to vibration-absorbent material (on metal shock
absorbers, for example).
Test voltages
Insulation strength is demonstrated in the type test with the following test voltages in
accordance with IEC 61131-2:
Protection class
Protection Class I in accordance with IEC 60536, i.e. PE/ground terminal to profile rail
required!
See also
Making the mounting cut-out (Page 25)
CAUTION
Safe electrical isolation
Use only 24 VDC power supply units with safe electrical isolation in accordance with IEC
60364-4-41 or HD 384.04.41 (VDE 0100, Part 410), e.g. to PELV standard.
The supply voltage must be within the specified voltage range. Otherwise, malfunction at
the HMI device cannot be ruled out.
Applies to non-isolated plant configurations:
Connect the connection for GND 24 V from the 24 V power supply output to equipotential
bonding for uniform reference potential. You should always select a central point of
termination.
The following table shows the permitted rated voltage and the corresponding tolerance
range.
$OOGLPHQVLRQVLQPP
$OOGLPHQVLRQVLQPP
$OOGLPHQVLRQVLQPP
$OOGLPHQVLRQVLQPP
$OOGLPHQVLRQVLQPP
$OOGLPHQVLRQVLQPP
8.8 Specifications
Weight
KTP400 Basic KTP600 Basic KTP600 Basic Color KTP600 Basic Color
Mono PN Mono PN DP PN
Weight without packaging Approx. 320 g Approx. 1070 g
Display
Input device
Memory
Interfaces
Supply voltage
Miscellaneous
HMI device
Display
Input device
Memory
Interfaces
Supply voltage
Miscellaneous
Alarms
Screens
Recipes
The specified values are maximum values and should not be used additive.
Safety
Info texts
Additional functions
Definition of ESD
All electronic modules are equipped with large-scale integrated ICs or components. Due to
their design, these electronic elements are highly sensitive to overvoltage, and thus to any
electrostatic discharge. These electronic components are therefore specially identified as
ESDs.
Abbreviations
The following abbreviation is commonly used for electrostatic sensitive devices:
● EGB – Elektrostatisch Gefährdete Bauteile/Baugruppen (Germany)
● ESD – Electrostatic Sensitive Device (internationally recognized term)
Labeling
ESDs are labeled with the following symbol:
Electrostatic charging
CAUTION
Electrostatic charging
ESDs may be destroyed by voltages far below the level perceived by human beings.
Voltages of this kind develop when a component or an assembly is touched by a person
who is not grounded against static electricity. Usually, it is unlikely that damage to an ESD
as a result of overvoltage is detected immediately but may become apparent only after a
longer period of operation.
Prevent electrostatic charging of your body before you touch the ESD!
Anyone who is not connected to the electrical potential of their surroundings is subjected to
electrostatic charging.
The following figure indicates the maximum electrostatic charge anyone is subjected to when
coming into contact with the materials shown. These values correspond with specifications to
IEC 801-2.
>N9@
9ROWDJH
>@
5HODWLYHKXPLGLW\
① Synthetic materials
② Wool
③ Antistatic materials such as wood or concrete
CAUTION
Observe grounding measures
When working with electrostatic sensitive devices, make sure that the person, the
workplace and the packaging are properly grounded. This helps to avoid electrostatic
charging.
As a rule, only touch the ESD if this is unavoidable, for example for maintenance. When you
touch modules, make sure that you do not touch the pins on the modules or the PCB tracks.
In this way, the discharged energy can not affect the sensitive devices.
Discharge electrostatic electricity from your body if you are performing measurements on an
ESD. Do so by touching grounded metallic parts.
Always use grounded measuring instruments.
Note
System events are only indicated if an alarm window was configured. System events are
output in the language currently set on your HMI device.
"Transfer" mode
HMI device operating mode for transferring an executable project from the configuration PC
to an HMI device.
Acknowledge
Acknowledgment of an alarm confirms that it has been noted.
Alarm, acknowledgment
Acknowledgment of an alarm confirms that it has been noted.
Alarm, activated
Moment at which an alarm is triggered by the PLC or HMI device.
Alarm, deactivated
Moment at which the initiation of an alarm is reset by the PLC.
Alarm, user-specific
User-specific alarms report specific states of a plant that is interconnected with the HMI
device via the PLC.
Automation system
An automation system is a PLC of the SIMATIC S7 product line, e.g. SIMATIC S7-300
Boot loader
The boot loader is used to start the operating system and is started automatically after power
on of the HMI device. The Loader is displayed after the operating system has loaded.
Configuration PC
A configuration PC is a programming device or PC on which plant projects are created using
an engineering software.
Configuration software
The configuration software is used to create projects for process visualization.
WinCC flexible is such a configuration software, for example.
Display duration
Defines whether a system alarm is displayed on the HMI device and the duration of the
display.
EMC
Electromagnetic compatibility is the ability of electrical equipment to function properly in its
electromagnetic environment without influencing this environment.
Event
Incoming events trigger defined functions. Events can be configured. Events which can be
assigned to a button include "Press" and "Release", for example.
Field
Area reserved in configured screens for the input and output of values.
Flash memory
Flash memory is a non-volatile memory with EEPROM chips that is implemented either as
mobile storage medium, or as permanently installed memory module on the motherboard.
Function key
Function keys on the HMI device can be assigned user-specific functions. The functions
assigned to those keys are defined in the engineering phase. The function key assignment
can be specific to an active screen or not.
HMI device
HMI devices are used to operate and monitor machinery and plants. The machine or plant
states are visualized on the HMI device by means of graphic objects or signal lamps. The
operator controls of the HMI device enable intervention in machine or plant processes and
sequences.
I/O field
Enables the input or output of values on the HMI device and their transfer to the PLC.
Info text
A configured info text provides information about objects within a project. An alarm info text,
for example, can contain information on the cause and troubleshooting of faults.
Object
An object is a project element such as a screen or an alarm. Objects are used to view or
enter texts and values on the HMI device.
Operator control
An operator control is a project component that is used to enter values and trigger functions.
A button is such an operator control.
Plant
General term referring to machinery, processing centers, systems, plants and processes
which are operated and monitored using an HMI device.
PLC
PLC is a general term for devices and systems with which the HMI device communicates,
e.g. SIMATIC S7.
PLC job
A PLC job triggers a function at the HMI device.
Process visualization
Denotes visualization of technical processes by means of text and graphic elements.
Configured plant screens enable intervention in runtime plant processes by means of data
input and output.
Project
A project is the result of a configuration using an engineering software. The project usually
contains several screens with embedded system-specific objects, basic settings and alarms.
A project configured in WinCC flexible is saved to a project file with the extension *.hmi.
There is a difference between an offline project on a configuration PC and an online
executable project on an HMI device. A project can be available in more languages on the
configuration PC than can be managed on the HMI device. The project on the configuration
PC can also be set up for different HMI devices. However, on the HMI device you can only
transfer the executable project that has been generated specifically for this HMI device.
Project file
Source file from which the executable project file for the HMI device is generated. The
project file is usually not transferred and is retained on the configuration PC.
Project files have the extension *.hmi.
Recipe
A recipe represent a combination of tags that form a fixed data structure. The configured
data structure can be assigned data in the configuration software or on the HMI device and
is then referred to as a data record. The use of recipes ensures that all data assigned to a
data record is transferred synchronously to the PLC.
Runtime software
The Runtime software is a process visualization software which can be used to test projects
on a configuration PC.
Screen
Mode of visualization of all logically associated process data of a plant. Visualization of the
process data can be supported by means of graphic objects.
Screen object
Refers to objects such as rectangles, I/O fields, or alarm views which are configured for
visualization or operation of the plant.
STEP 7
STEP 7 is the programming software for SIMATIC S7, SIMATIC C7 and SIMATIC WinAC
PLCs.
STEP 7 Micro/WIN
STEP 7 Micro/WIN is the programming software for SIMATIC S7-200 PLCs.
System alarms
System alarms are assigned the "System" alarm class. A system alarm reports internal
states of the HMI device and of the PLC.
Tab order
The tab order defined in the course of project engineering determines the sequence for
activating objects by pressing the <TAB> key.
Tags
A tag is a defined memory area that is used to read and write values. Those tags can be
accessed from the PLC or using the HMI device. We distinguish between external tags
(process tags) and internal tags, depending on whether or not the tag is interconnected with
the PLC.
Transfer
Transfer of an executable project from the configuration PC to the HMI device.
H N
High frequency radiation, 21
Non-isolated plant configuration, 86
HMI device
Connecting, 30
EMC-compatible installation, 80
O
Mounting, 28
Shutting down, 40 Offices, 6
Specifications, 93, 95 Offline
Switching on, 40 Operating mode, 62
Testing, 40 Test, 66
Online
Operating mode, 62
I Test, 67
OP properties
Initial startup, 61
Device, 50
Input device
Display, 50
KTP1000, TP1500 Basic, 95
License, 50
KTP400, KTP600 Basic, 93
Touch, 50 Recommissioning, 61
Operating instructions Recycling, 78
Purpose of, 3 Registered trademarks, 5
Scope, 3 Regulations for the prevention of accidents, 21
Operating mode, 62 Representatives, 6
Changing, 62 Restore, 63, 72
Offline, 62 With ProSave, 72
Online, 62 Restoring, 68, 70
Transfer, 62 With WinCC flexible, 70
Operating system RF interference, 22
Update using ProSave, 76 RS 422 to RS 232 converter, 19
Update using WinCC flexible, 75 RS-422/485 interface
Updating, 73 Configuring, 38
Operators, 3
S
P Safe electrical isolation, 86
Package content Safety
Checking, 23 Standards, 79
Password properties, 50 Safety instruction
Password protection Compatibility conflict, 68
Activating, 59 Data channel, 74
Deactivating, 59 Data loss, 73
Password protection, 49, 50 Electrostatic charging, 100
PC/PPI cable, 19 Equipotential bonding cable, 31
PELV, 86 General, 22
Plant configuration High frequency radiation, 21
Non-isolated, 86 Observe grounding measures, 101
PLC Power failure, 68
Configuring the interface, 38 Preventing inadvertent operation, 77
Power failure, 68 Storage, 82
Precautions Transport, 82
Electrostatic discharge, 101 unauthorized cleaning products, 77
Process control phase, 61 Unintentional response, 77
Product illustrations, 4 Working on the control cabinet, 21
PROFIBUS bus connector, 20 Safety regulations, 21
Profinet Settings, 50 Screen keyboard
Project Alphanumerical, 45, 47
Offline testing, 66 Key assignment, 45, 47
Testing online, 67 KTP400 Basic, 44
Transferring, 61 KTP600, KTP1000, TP1500 Basic, 47
Protection class, 85 Numerical, 46, 48
Protective foil, 20 Screen saver, 50
Screen settings
Editing, 50
R Service
In the Internet, 6
Radiation
Service technicians, 3
High frequency, 21
Shutting down
Radio interference
HMI device, 40
Emission, 81
Sound Settings, 50
Rated voltage, 86
Specifications
KTP1000 Basic DP
Produktinformation
Kompatible Steuerungen
Gültigkeit
Die vorliegende Produktinformation gilt für das Bediengerät KTP1000 Basic DP, Bestellnummer 6AV6647-0AE11-3AX0.
Diese Produktinformation enthält wichtige Hinweise. Die Hinweise ergänzen die Betriebsanleitung für das Bediengerät und
sind den Aussagen in der Betriebsanleitung, in den Release Notes und in der Online-Hilfe in der Verbindlichkeit
übergeordnet.
Hinweis
Das Bediengerät ist in der ersten Lieferstufe ausschließlich mit folgenden Steuerungen kompatibel:
● SIMATIC S7-200
● SIMATIC S7-300/400
Das Bediengerät ist nicht mit Steuerungen anderer Hersteller kompatibel.
Compatible controllers
Applicability
This product information is valid for the HMI device KTP1000 Basic DP, order number 6AV6647-0AE11-3AX0.
This product information contains important information. The notes supplement the operating instructions for the HMI device
and take precedence over statements in the operating instructions, the release notes, and in the online help.
Note
The HMI device is, in delivery stage 1, compatible with the following controllers:
● SIMATIC S7-200
● SIMATIC S7-300/400
The HMI device is not compatible with the controllers of other manufacturers.
Automates compatibles
Validité
La présente information produit est valable pour le pupitre opérateur KTP1000 Basic DP, N° de référence 6AV6647-0AE11-
3AX0.
Cette information produit contient des indications importantes. Les remarques complètent les instructions de service du
pupitre opérateur et, en cas de conflit avec les indications des instructions de service, des Release Notes et de l'aide en
ligne, c'est à elle que vous devez vous reporter.
Remarque
Le pupitre opérateur est uniquement compatible avec les automates suivants dans la première version :
● SIMATIC S7-200
● SIMATIC S7-300/400
Le pupitre opérateur n'est pas compatible avec des automates d'autres constructeurs.
© Siemens Ⓟ2008
A5E02296525-01, 08/2008 1
Controllori compatibili
Validità
Le presenti informazioni sul prodotto sono valide per il pannello operatore KTP1000 Basic DP, numero di
ordinazione 6AV6647-0AE11-3AX0.
Le presenti informazioni sul prodotto contengono avvertenze importanti. Le avvertenze sono da considerarsi parte integrante
delle Istruzioni operative del pannello operatore e hanno valore di veridicità superiore a quello delle Informazioni contenute
nelle Istruzioni operative, nelle Note di rilascio e nella Guida in linea.
Nota
Nel primo livello di fornitura il pannello operatore è compatibile esclusivamente con i seguenti controllori:
● SIMATIC S7-200
● SIMATIC S7-300/400
Il pannello operatore non è compatibile con controllori di altri produttori.
Controladores compatibles
Validez
La presente Información de producto es válida para el panel de operador KTP1000 Basic DP, referencia 6AV6647-0AE11-
3AX0.
La presente Información de producto contiene indicaciones importantes. Las indicaciones complementan las instrucciones
de servicio del panel de operador y prevalecen sobre lo mencionado en las instrucciones de servicio, en las Release Notes
y en la Ayuda en pantalla.
Nota
La primera versión suministrada deL panel de operador es compatible únicamente con los siguientes controladores:
● SIMATIC S7-200
● SIMATIC S7-300/400
El panel de operador no es compatible con controladores de terceros.