To configure IQL controllers through 3xtend, bring all controllers online in the system view using the engineering tool. Right click and select IQLTool2. Press discover to display controllers in the IQLTool table. Edit controller LAN number, address, Alan, and other parameters. Press write to save changes to IQL flash memory. Refer to documentation like the IQL manual and installation sheet for more details on configuration and commissioning.

Uploaded by

Mushahid
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
354 views

IQL Commissioning Using 3xtend

To configure IQL controllers through 3xtend, bring all controllers online in the system view using the engineering tool. Right click and select IQLTool2. Press discover to display controllers in the IQLTool table. Edit controller LAN number, address, Alan, and other parameters. Press write to save changes to IQL flash memory. Refer to documentation like the IQL manual and installation sheet for more details on configuration and commissioning.

Uploaded by

Mushahid
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 9

Configuring IQL Controllers through 3xtend (version 1.

3 or Higher) Note: Use this option only single segment where controller nos less than 50 or break the segment (Bus) near IQL Router.

Goto System Engineering Tool and bring the all controllers online on system view. Right click select IQLTool2.

Press discover button on IQLTool.

All controllers will be displayed at IQLTool table.

You can edit the controller LAN no, Controller address, Alan etc..(IQL Manual) i.e: One segment create only two trend virtual Lan. Lan no 11 Controllers ID: 11.60 Lan no 12 Controllers ID:1160 Identifier: Server Room Attribute F: First Floor Attribute G: Main Building Alan: 50 (Where needs to send controller Alarm - 3xtend Lan number) A address (Where needs to send controller Alarm - 3xtend CNC no like 101,102108) Alan: 50 (Where needs to send Network Alarm - 3xtend Lan number) A address (Where needs to send Network Alarm - 3xtend CNC no like 101,102108)

You can change I/O parameters from IQLTool

After editing parameter press write button

Store information on IQL flash memory

You can edit the I/O Parameter from IC Comms (text command similar to win dos commands)

Refer IQL Manual and Installation sheet

You can use site topology option for troubleshooting.

For IQL Commissioning you have to refer following documents 1. IQL Controller Installation sheet 2. IQL Controller Data sheet 3. IQL Controller Strategy 4. IQLTool2 Manual