100% found this document useful (1 vote)
304 views

5 Ee12-Electrical System Design-Lec (Residential) - Lec-2021

The document discusses the topics of service entrance, electric meters, plans and specifications, design analysis, branch circuit load calculation, and feeder and service load calculation. It provides information on the components and requirements for service entrance, describes what an electric meter is and how it is measured, and lists the elements that should be included in electrical plans and specifications such as the location plan, legend, general notes, and design analysis. It also covers how to calculate loads for branch circuits, feeders, and services.

Uploaded by

Silwy One
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
304 views

5 Ee12-Electrical System Design-Lec (Residential) - Lec-2021

The document discusses the topics of service entrance, electric meters, plans and specifications, design analysis, branch circuit load calculation, and feeder and service load calculation. It provides information on the components and requirements for service entrance, describes what an electric meter is and how it is measured, and lists the elements that should be included in electrical plans and specifications such as the location plan, legend, general notes, and design analysis. It also covers how to calculate loads for branch circuits, feeders, and services.

Uploaded by

Silwy One
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

TOPICS

• Service Entrance

• Electric Meter
• Plans and Specification
• Design Analysis
• Branch Circuit Load Calculation
• Feeder and Service Load Calculation
SERVICE ENTRANCE
• It is described as the supply conductors which extends from the street main duct or
transformer to the service or switchboard of the building supply.
• Most buildings service entrance are connected to the secondary line low voltage below 600 V.
• It can be 2, 3 or 4 wires including grounded neutral wire.
• Size of wires varies depending on demand load
SERVICE ENTRANCE

ELECTRIC METER
• It is a device that measures the amount of electrical energy supplied to or produced by a
residence, business or machine.
• It is usually measured in kilowatt hours

1.3.2.1 Plan Requirements


(a) Location and Site Plan (b) Legend or Symbol (c) General Notes and/or Specification (d)
Electrical Layout (a) Plan for Power (b) Plan for Lighting and Receptacle Outlets (e) Schedule of
Loads (f) Design Analysis (g) One Line Diagram
(1) Lighting and Receptacle Outlet Load
(2) Motor Loads
(3) Feeders
(4) Load Center
(h) Title Block

Plans and Specification


(c) General Notes and/or Specification.
General Notes and Specifications, written on the plans or submitted on separate standard size
sheets shall show:
(1) Nature of Electrical Service, including number of phases, number of wires, voltage and
frequency;
(2) Type of Wiring; a. Service entrance b. Feeders, sub-feeder and branch circuit for lighting
and/or power load
(3) System or method of grounding
General Notes
1. All electrical works indicated herein shall be done in accordance with the latest edition of
Philippine Electrical Code Part 1, the requirements of the local building official and the electric
utility serving the area.
2. The electrical supply/service voltage is 230V, single phase, two wires, grounded, 60 Hz.
3. Contractor shall verify and orient the actual locations of concrete terminal.
4. All installation shall be concealed from view, wiring shall be incased in PVC pipe or flexible
conduit except power service which shall be in RSC.
5. The minimum size of wire shall be 2-3.5mm2 and 15mmø conduit.
6. All materials shall be new and approved type. Appropriate for both location and intended
use.
7. Electrical installation shall be under a direct supervision of duly licensed electrical engineer
or registered master electrician.
8. No revision in the design shall be done without the prior knowledge and approval of the
designer and the owner.
9. Ground resistance shall not exceed 25 ohms.
10. Mounting heights for switches and convenience outlet shall be in 1.37m and 0.30m
respectively, unless otherwise indicated in architectural plans.

Plans and Specification Legend


Electrical Symbols Schedule of Loads - tabulated information of electrical loads,
size of wire and conduit per circuit up to service. Lighting System Layout - shows
the lighting fixture and switches location and its wiring system. Power Layout -
shows the location of convenience outlets, special outlets (acu, range, water
pump, water heater, etc.), panel board, meter, service head, and their wiring
system
Design Analysis Design
Analysis shall be included on the drawings or shall be submitted on separate sheets of standard
size, and shall show:
(1) Branch Circuit, sub-feeders, feeders, busways, and service entrance
(2) Types ratings, and trip settings of overload protective device
(3) Calculation of short circuit current for determining the interrupting capacity of overcurrent
protection device for residential, commercial, and industrial establishment
(4) Calculation of voltage drops
Branch Circuit Load Calculation
• Lighting Branch Circuit
• Small Appliance Branch Circuit
• Laundry Branch Circuit
•Individual Branch Circuit (ACU, WH, WP, etc)

Article 2.10 – Branch Circuits 2.10.1.3 Rating. Branch Circuits recognized by this article shall be
rated in accordance with the maximum permitted ampere rating or setting of the overcurrent
device

Sizing of Conductors and Protective Devices


2.10.2. Branch Circuit Ratings
2.10.2.1 (a)(1) Conductors – Minimum Ampacity and Size. General. Branch Circuit conductors
shall have an ampacity not less than the maximum load to be served. Where a branch circuit
supplies continuous loads or any combination of continuous and non continuous loads, the
minimum branch circuit conductor size, before the application of any adjustment or correction
factors, shall have an ampacity not less than the non continuous load plus 125 percent of the
non continuous load.
Note: same statement as in the Article 2.15 Section 1.2 p.91 For Feeders Minimum Rating and
Size Continuous Load (Art 1.1 p.9) – A load where the maximum current is expected to continue
for 3 hours or more
Sizing of Conductors and Protective Devices
2.10.2.2 Overcurrent Protection. Branch-circuit conductors and equipment shall be protected by
overcurrent protective device that have a rating or setting not greater than the ampacity of the
branch circuit conductors
2.10.2.2 (a) Continuous and Noncontinuous Loads. Where a branch circuit supplies continuous
loads or any combination of continuous and non continuous loads, the rating of the overcurrent
device shall not be less than the non continuous load plus 125 percent of the non continuous
load.
Note: same statement as in the Article 2.15 Section 1.3 p.93 For Feeders Overcurrent Protection

2.20.2 Branch Circuit Load Calculations Lighting Branch Circuit 2.10.2.5 (a)(p.81) A 15 or 20 –
ampere branch circuits shall be permitted to supply lighting units or other utilization equipment,
or a combination of both. 2.20.2.3 Lighting Load for Specified Occupancies . For dwelling units
(Based on PEC 2009 Table 2.20.23 ) Total Lighting Load = Floor area (in sq.m) x 24 VA/sq.m or
sometimes you can use the actual wattage rating of the lighting equipment The floor area for
each floor shall be calculated from the outside dimensions of the building dwelling unit, or other
area involved. For dwelling units, the calculated floor area shall not include open porches,
garages or unused or unfinished spaces not adaptable for future use
2.10.1.11 (c)(1) Small-Appliance Branch Circuit
Also known as Convenience Outlet Branch Circuit. In addition to the number of branch circuits
required, two or more additional 20 - ampere small appliance branch circuits shall be provided
for all receptacle outlets 2.20.2.5 (i) Receptacle Outlets (p.101) receptacle outlets shall be
calculated at not less than 180 volt-amperes for each single or for each multiple receptacle in one
yoke. For four or more receptacle shall be calculated not less than 90 volt-ampere per receptacle.
Branch Circuit Rating: 1500 VA

2.10.1.11 (c)(2) Laundry Branch Circuit


In addition to the number of branch circuits required by other parts of this section, at least one
or 20- ampere branch circuit shall be provided to supply the laundry receptacle outlet(s). This
circuit shall have no other outlets. Branch Circuit Rating: 1500 VA
Motor Circuit Conductors

4.30.4 Motor Branch-Circuit Short-Circuit and Ground Fault Protection


4.30.4.2 Rating or Setting for Individual Motor Circuit. (b) The motor branch-circuit short-circuit
and ground fault protective device shall be capable of carrying the starting current of the
motor. (c) In Accordance with Table 4.30.4.2 A protective device that has a rating or setting not
exceeding the value calculated according to the values given. In Table 4.30.4.2 shall be used
2.20.3 Feeder and Service Load Calculations
2.30.3.1 General. The calculated load of a feeder or service shall not be less than that the sum
of the loads on the branch circuit supplied, after any applicable demand factors have been
applied
2.20.3 Feeder and Service Load Calculations
2.20.3.3 General Lighting The demand factors specified in the Table 2.20.3.3 shall apply to that portion
of the total branch circuit load calculated for general illumination. They shall not be applied in
determining the number of branch circuit for general illumination

2.20.3.13 Small-Appliance and Laundry Loads – Dwelling Unit

(a) Small Appliance Circuit Load. In each dwelling unit, the load shall be calculated at 1500 volt-amperes
for each 2- wire small appliance branch circuit required by 2.10.1.11 (c)(1)

(b) Laundry Circuit Load. A load not less than 1500 volt amperes shall be included for each 2-wire
laundry branch circuit installed as required by 2.10.1.11 (c)(2)

These loads shall be permitted to be included with the general lighting load and subjected to the
demand factors provided in Table 2.20.3.3

2.20.3 Feeder and Service Load Calculations

2.30.3.11 Motors

Motor loads shall be calculated in accordance with 4.30.24

4.30.2.4 Several Motor or a Motor(s) and Other Load(s).


Conductors supplying several motors, or a motor(s) and other load(s). Shall have an ampacity
not less than 125 percent of the full-load current rating of the highest motor plus the sum of
the full load current ratings of all the other motors in the group, plus the ampacity required for
other loads. Feeder Conductor Size = [125% FLA of Highest Motor load]+ [Sum of other
connected loads]

Branch Circuit, Individual (Art 1.1)


A Branch Circuit that supplies only one utilization equipment (ACU, Range, Water Heater, Water
Pump, etc.) Most Common Rating Range: 8000 W Water Heater: 5000 W For Motors (see table
4.30.14.2 (p.732)) 1 Hp at 230 V = 8 A 1 ½ Hp at 230 V = 10 A 2 Hp at 230 V = 12 A Range @
8000 W computed @ 80% DF (see table 2.20.3.16(p.108)) ACU or motor load computed @
100% DF
2.20.3 Feeder and Service Load Calculations

4.30.5.3 Rating or Setting – Power and Lighting Loads (p.706) Where a feeder supplies a motor load and
in addition, a lighting or a lighting and appliance load, the feeder protective device shall have a rating
sufficient to carry the lighting or lighting and appliance load plus the largest rating or setting of the
branch-circuit short-circuit and ground fault protective device for any motor supplied by the feeder.
Overcurrent Protective Device Rating = [OCP rating of Highest Motor load] + [Sum of the other
connected loads

Branch Circuit, Individual (Art 1.1) (p.7) A Branch Circuit that supplies only one utilization equipment
(ACU, Range, Water Heater, Water Pump, etc.) Most Common Rating Range:

8000 W Water Heater:

5000 W For Motors (see table 4.30.14.2 (p.732))

1 Hp at 230 V = 8 A 1 ½ Hp at 230 V = 10 A

2 Hp at 230 V = 12 A Range @ 8000 W computed @ 80% DF (see table 2.20.3.16(p.108)) ACU or motor
load computed @ 100% DF
Some Conductor data's

2.50.6.13 Size of Equipment Grounding (Bonding) Conductor

2.50.6.13 (f)(1) Based on Rating of Overcurrent Protective Device. Each parallel equipment grounding
conductor shall be sized on the basis of the ampere rating of the overcurrent protecting the circuit
conductors in the raceway or cable in accordance with Table 2.50.6.13
Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment

Sizing of Service Entrance Conductors


Size of Service Entrance Conductors = sum of the computed load + 25% of the largest motor FLA
Size of Service Equipment = largest motor protective device + sum of ampere rating of
remaining branch circuit
Sample Computation

Ex. Single Family Dwelling Unit The dwelling has a floor area of 145 m2 . It has the typical household
appliances including one 8-kW electric range, two 1-Hp room air conditioning unit, 1.5-Hp room air
conditioning unit, and one 1-Hp water pump. Total Load

a) General Lighting 145 m2 x 24 VA/ m2 = 3480 VA The computed load is 3480 VA/230 V =15 A One
branch circuit of 20-ampere would be theoretically adequate, however for the flexibility and to
allow future needs provide two 20 ampere branch circuits for lighting and convenience outlet

b) Small Appliance Load One 20-ampere @ 1500 VA = 1500 VA Provide one 20-ampere small appliance
circuit

c) Laundry Circuit One 20-ampere @ 1500 VA = 1500 VA Provide one 20-ampere laundry circuit Sub-
Total = 6480 VA

Application of Demand Factors First 3000 VA @ 100% DF = 3000 VA Remainder @ 35% DF (3480 x 0.35)
= 1218 VA

Other Loads:

One 8-kW electric range @ 80% = 6400 VA

Provide one 40-ampere electric range circuit

Two 1-Hp room acu, 8A x 230V x 2 @ 100% DF = 3680 VA

Provide two 30-ampere room acu circuits

One 1.5-Hp room acu, 10A x 230V @ 100% DF = 2300 VA

Provide one 30-ampere room acu circuit

One 1-Hp water pump, 8A x 230V @ 100% DF = 1840 VA


Provide one 30-ampere water pump circuit

Total Net Computed Load = 18438 VA


Circuit Requirement:

Use two 20-ampere 2-wire branch circuits, two 20-ampere 3-wire branch circuits, four 30-ampere 3-
wire branch circuits, and one 40-ampere 3-wire branch circuit.

Service Entrance Conductors:


Total Full Load Current: [18438 + 25%(2300)] / 230V = 83 Amperes Use 2-38mm2 + 1-8.0mm2 THWN
wire

Service Equipment:

Maximum Current Rating of Protective

Device Inverse Time Circuit Breaker:

[3000 VA + 1218 VA + 6400 VA + 3600 VA + 250%(2300 VA) + 1840 VA] / 230 V = 95 Amperes

Service Equipment Rating:

Use one 125 AT/225AF, 2P 240V molded case circuit breaker

You might also like