Expv en

This document provides information on expansion valves from Saginomiya including thermostatic and constant pressure expansion valves. It lists several models of expansion valves including their applications, connection types, maximum working pressures, and capacity ranges for various refrigerants. The document contains a product catalog and specifications for thermostatic expansion valves that can be used in various refrigeration and air conditioning systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views

Expv en

This document provides information on expansion valves from Saginomiya including thermostatic and constant pressure expansion valves. It lists several models of expansion valves including their applications, connection types, maximum working pressures, and capacity ranges for various refrigerants. The document contains a product catalog and specifications for thermostatic expansion valves that can be used in various refrigeration and air conditioning systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

EXPANSION VALVES SERIES

(THERMOSTATIC & CONSTANT PRESSURE EXPANSION VALVES)

SAGINOMIYA PRODUCT CATALOG

Thermostatic Expansion Valves

Constant Pressure Expansion Valves

Manually Operated Expansion Valves


Contents
■ EXPANSION VALVES
Max working Capacity (U.S.R.T.){kW} * ( ) : Charge type
Equalizer
Type Applications Connection Pressure
type
(MPa) R23 R134a R404A R407C

ARX ・Bottle coolers


・Display cases
・Ice making machines 2.8
0.24 to 0.34 to 0.50 to
・Industrial air ( Expect
R407C ) 1.80 1.71 2.47
conditioning systems,
etc.
Internal Solder
3.3

{ 0.85 to
6.33 } { 1.20 to
6.01 } { 1.76 to
8.70 }
(S) (S) (S)
(R407C)

QCX ・Display cases


・Commercial
refrigerators
・Cold chain boxes
・Air conditioning Internal
0.20 to
systems, Protected 2.96
horticulture equipments,
etc. 0.24 to { 0.70 to
10.4 } 0.32 to
Flare 3.64 (SA, C) 4.83

RCX Solder
3.0 ―
{ 0.85 to
12.8 } 0.13 to { 1.13 to
17.0 }
(C) 1.80 (SA, C)

{ 0.46 to
6.34 }
(SL)
External

AEX ・Refrigerators
・Freezers
・Refrigeration 0.19 to 0.36 to 0.34 to
equipments for Ships 4.75 9.58 8.39
・Chillers, etc. Internal Flare 1.4
{ 0.68 to
16.7 } { 1.27 to
33.7 } { 1.20 to
29.5 } ―

(G) (G) (G)

SCX ・Display cases 3.64 to


・Commercial 9.07
refrigerators
4.75 to { 12.8 to
31.9 } 5.94 to
・Cold chain boxes Flare 11.8 (SA, C) 14.8
・Air conditioning
systems, Protected
External
Solder
3.0 ―
{ 16.7 to
41.5 } 1.92 to { 20.9 to
52.0 }
(C) 4.75 (SA, C)
horticulture equipments,
etc. { 6.74 to
16.7 }
(SL)

ATX ・Water chillers 0.70 to


・Air conditioning systems 56.9
2.8

( ) { }
・Freezers 2.46 to
Expect
0.70 to 200 1.00 to
・Refrigerators R407C
Flare 60.0 (S) 83.3
R410A
・Brine coolers, etc. External
Solder
3.3

{ 2.46 to
211 } 0.33 to { 3.51 to
293 }
(S) 33.0 (S)
( R407C
R410A ) { 1.16 to
116 }
(SL)
Thermostatic Expansion Valve
Selection Software ⇒

Capacity (U.S.R.T.){kW} * ( ) : Charge type Evaporating Temp. (℃ ) * ( ) : Charge type


Page
Temperature R448A
R410A R448A R449A R23 R134a R404A R407C R410A
condition R449A

CT 38℃ -40 to -10 -40 to -10 -40 to -10


― ― ― ― ― ― 25
ET 5℃ (S) (S, CL) (S)

0.29 to 0.28 to
4.41 4.24
-40 to 10 -40 to 10
0.35 to { 1.03 to
15.5 } { 0.99 to
14.9 } CT 38℃
ET -5℃
(SA)
-40 to 10 -45 to 10
(SA)
5.18 (SA, C) (SA, C) (SA, C) (SA) (SA)
-30 to 10 -40 to 0 -40 to 0
{ 1.22 to
18.2 } 0.20 to 0.20 to CT 38℃

(C) (C)
-40 to 0 -40 to -10
(C)
11

(SA, C) 2.75 2.71 ET -30℃ (C) (C)


-60 to -25 -60 to -25
{ 0.70 to
9.68 } { 0.69 to
9.53 } (SL)
(SL) (SL)
(SL) (SL)

CT 38℃
ET -5℃

― ― ―
(R134a
R404A ) -100 to -70 -30 to 10 -40 to 10
― ― ― 23
(G) (G) (G)
CT -40℃
ET -80℃
(R23)

5.43 to 5.20 to
13.5 12.9
-40 to 10 -40 to 10
6.37 to { 19.1 to
47.4 } { 18.3 to
45.5 } CT 38℃
ET -5℃
(SA)
-40 to 10 -45 to 10
(SA)
15.8 (SA, C) (SA) (SA, C) (SA) (SA)
-30 to 10 -40 to 0 -40 to 0
{ 22.4 to
55.6 } 2.90 to 2.84 to CT 38℃

(C) (C)
-40 to 0 -40 to -10
(C)
15

(SA, C) 7.17 7.05 ET -30℃ (C) (C)


-60 to -25 -60 to -25
{ 10.2 to
25.2 } { 10.0 to
24.8 } (SL)
(SL) (SL)
(SL) (SL)

0.94 to 0.91 to
76.2 73.7
-40 to 10
1.09 to { 3.30 to
268 } { 3.19 to
259 } CT 38℃
ET 5℃ -40 to 10 -20 to 10
(S)
89.3 (S, C) (S, C) (S, C, CL) (S) (C)
-30 to 10 -40 to 10 -40 to 10
{ 3.85 to
314 } 0.50 to 0.49 to CT 38℃

(S)
-60 to -25
(S)
-40 to -10
(C)
19

(C, CL) 59.2 58.3 ET -30℃ (SL) (CL)


-65 to -25
{ 1.76 to
208 } { 1.73 to
205 } (SL)
(SL)
(SL) (SL)
Contents
■ CONSTANT PRESSURE EXPANSION VALVES
Max working Capacity (U.S.R.T.){kW}
Equalizer
Type Applications Connection Pressure
type
(MPa) R23 R134a

CEX ・Bulk coolers


・Water coolers
・Refrigerators
・Air dryers, etc.
0.19 to 4.75 * 0.36 to 9.58
Internal Flare 1.4
{0.68 to 16.7} {1.27 to 33.7}

CTX ・Air conditioning systems


・Bulk coolers
・Refrigerators / Freezers
・Air dryers, etc. Flare
0.70 to 60.0
External 2.8 ―
{2.46 to 211}
Solder

CGX ・Air dryers


・Spot coolers
・Refrigerators / Freezers 2.5
・Chillers, etc.
Internal Solder
( Expect
R410A ) ―
1.80 {6.33}
[0.22 {0.76}]
3.3
(R410A)

SPX ・Air dryers


・Spot coolers
・Refrigerators / Freezers 2.8
・Chillers, etc.
Internal Solder
( Expect
R410A ) ―
4.81 {16.9}
[0.33 {1.17}]
3.3
(R410A)

■ MANUALLY OPERATED EXPANSION VALVES


Max working Capacity (U.S.R.T.){kW}
Equalizer
Type Applications Connection Pressure
type
(MPa) R23 R134a

HEX ・Brine coolers


・Refrigerations
・Freezers, etc.

0.36 to 9.58
Internal Flare 1.4
( Production
possible ) {1.27 to 33.7}
Capacity (U.S.R.T.){kW}
Page
Temperature
R404A R407C R410A R448A R449A
condition

CT 38℃ / ET -5℃
0.34 to 8.39 0.51 to 13.2 0.47 to 12.0 0.45 to 11.5
― 27
{1.20 to 29.5} {1.81 to 46.4} {1.65 to 42.3} {1.59 to 40.5} * CT -40℃ / ET -80℃

0.70 to 56.9 1.00 to 83.3 0.94 to 76.2 0.91 to 73.7


― CT 38℃ / ET 5℃ 29
{2.46 to 200} {3.51 to 293} {3.30 to 268} {3.19 to 259}

CT 38℃ / ET 5℃
1.71 {6.01} 2.47 {8.69} 2.64 {9.28} 2.26 {7.93}
― 31
[0.28 {0.97}] [0.33 {1.16}] [1.24 {2.09}] [0.31 {1.09}]
[CT 40℃ / ET -10℃ ]

CT 38℃ / ET 5℃
4.55 {16.0} 6.60 {23.2} 7.05 {24.8} 6.29 {22.1}
― 31
[0.43 {1.50}] [0.51 {1.78}] [0.75 {2.64}] [0.48 {1.68}]
[CT 40℃ / ET -10℃ ]

Capacity (U.S.R.T.){kW}
Page
Temperature
R404A R407C R410A R448A R449A
condition

0.34 to 8.39 0.51 to 13.2


― ― ― CT 38℃ / ET -5℃ 33
{1.20 to 29.5} {1.81 to 46.4}
REFERENCE INFORMATION
TERMINOLOGIES RELATED TO REFRIGERATION

◦ Pressure 
Absolute Pressure Gauge Pressure Standard Atmosphere
= +
MPa (abs) MPa 0.101325 MPa

◦ Degree of Vacuum 
h
P = 0.1013・
76
  P : Absolute Pressure MPa (abs)
  h : Degree of Vacuum (Column of Mercury) cmHg

◦ Power and Heat


1 kW = 102 kgf・m/sec = 860 kcal/h

◦ Cooling Capacity
This Catalog uses "U.S.R.T." and "kW" to indicate nominal capacity.

◦ Coefficient of Performance (COP)


Absolute Pressure
Q2 Q2 273.15 + T2 MPa
ε= = = Q1
AW Q1 − Q2 T1 − T2
P2
ε : COP of a Refrigeration equipment
AW : Heat Quantity Equivalent to Compression Work (kW)
Q1 : Heat Quantity Discharged at the Condenser (kW)
Q2 : Cooling Capacity (Load) (kW)
T1 : Condensing Temperature (°C) P1
Q2 AW Enthalpy
T2 : Evaporating Temperature (°C) kJ/kg

i3
◦ Cooling Effect (Cooling Power)
i1 i2
q = i2 − i1
q : Cooling Effect (kJ/kg)
i1 : Enthalpy of liquid immediately before expansion valve (kJ/kg)
i2 : Enthalpy of vapor discharged from the evaporator (kJ/kg)

◦ Circulating Refrigerant Amount


G = 3,600 × Q/q
G : Circulating Refrigerant Amount (kg/h)
Q : Cooling Capacity (kW)
q : Cooling Effect (kJ/kg)

◦ Water Amount and Water Temperature Difference


Q = 1/60・ρ・α・GW (t1 − t2)
Q : Cooling Capacity (kW)
ρ : Specific Gravity of Water (kg/m3)
α : Specific Heat Capacity of Water (J/K・kg)
GW : Circulating Water Amount (m3/min)
t1 : Inlet Water Temperature (°C)
t2 : Outlet Water Temperature (°C)

1
CONVERSION TABLES

1) Temperature conversion table (°C ←→ °F)

The figures in the center column show the temperature to be converted. The figures on the left show
conversion from Fahrenheit to Celsius and the figures on the right from Celsius to Fahrenheit.

Example : 5°C 41.0°F Temperature conversion formula :


°C = 5/9 (°F − 32)
°C °F
°F = 9/5 × °C + 32
-15.0 5 41.0

-15.0°C 5°F

°C °F °C °F °C °F °C °F °C °F
-101.1 -150 -238.0 -37.2 -35 -31.0 -23.3 -10 14.0 -9.4 15 59.0 4.4 40 104.0
-95.6 -140 -220.0 -36.7 -34 -29.2 -22.8 -9 15.8 -8.9 16 60.8 5.0 41 105.8
-90.0 -130 -202.0 -36.1 -33 -27.4 -22.2 -8 17.6 -8.3 17 62.6 5.6 42 107.6
-84.4 -120 -184.0 -35.6 -32 -25.6 -21.7 -7 19.4 -7.8 18 64.4 6.1 43 109.4
-78.9 -110 -166.0 -35.0 -31 -23.8 -21.1 -6 21.2 -7.2 19 66.2 6.7 44 111.2
-73.3 -100 -148.0 -34.4 -30 -22.0 -20.6 -5 23.0 -6.7 20 68.0 7.2 45 113.0
-67.8 -90 -130.0 -33.9 -29 -20.2 -20.0 -4 24.8 -6.1 21 69.8 7.8 46 114.8
-62.2 -80 -112.0 -33.3 -28 -18.4 -19.4 -3 26.6 -5.6 22 71.6 8.3 47 116.6
-56.7 -70 -94.0 -32.8 -27 -16.6 -18.9 -2 28.4 -5.0 23 73.4 8.9 48 118.4
-51.1 -60 -76.0 -32.2 -26 -14.8 -18.3 -1 30.2 -4.4 24 75.2 9.4 49 120.2
-45.6 -50 -58.0 -31.7 -25 -13.0 -17.8 0 32.0 -3.9 25 77.0 10.0 50 122.0
-45.0 -49 -56.2 -31.1 -24 -11.2 -17.2 1 33.8 -3.3 26 78.8 15.6 60 140.0
-44.4 -48 -54.4 -30.6 -23 -9.4 -16.7 2 35.6 -2.8 27 80.6 21.1 70 158.0
-43.8 -47 -52.6 -30.0 -22 -7.6 -16.1 3 37.4 -2.2 28 82.4 26.7 80 176.0
-43.3 -46 -50.8 -29.4 -21 -5.8 -15.6 4 39.2 -1.7 29 84.2 32.2 90 194.0
-42.8 -45 -49.0 -28.9 -20 -4.0 -15.0 5 41.0 -1.1 30 86.0 37.8 100 212.0
-42.2 -44 -47.2 -28.3 -19 -2.2 -14.4 6 42.8 -0.6 31 87.8 43.3 110 230.0
-41.7 -43 -45.4 -27.8 -18 -0.4 -13.9 7 44.6 0.0 32 89.6 48.9 120 248.0
-41.1 -42 -43.6 -27.2 -17 1.4 -13.3 8 46.4 0.6 33 91.4 54.4 130 266.0
-40.6 -41 -41.8 -26.7 -16 3.2 -12.8 9 48.2 1.1 34 93.2 60.0 140 284.0
-40.0 -40 -40.0 -26.1 -15 5.0 -12.2 10 50.0 1.7 35 95.0 65.6 150 302.0
-39.4 -39 -38.2 -25.6 -14 6.8 -11.7 11 51.8 2.2 36 96.8 71.1 160 320.0
-38.9 -38 -36.4 -25.0 -13 8.6 -11.1 12 53.6 2.8 37 98.6 76.7 170 338.0
-38.3 -37 -34.6 -24.4 -12 10.4 -10.6 13 55.4 3.3 38 100.4 82.2 180 356.0
-37.8 -36 -32.8 -23.9 -11 12.2 -10.0 14 57.2 3.9 39 102.2 87.8 190 374.0

2
2) Temperature difference conversion table (°C ←→ °F)

This table is a comparison table of temperature difference. For example, a 9°F difference (77°F − 68°F)
corresponds to a 5°C difference (25°C − 20°C).

°C °F
0.056 0.1 0.18
0.111 0.2 0.36
0.278 0.5 0.90
0.56 1 1.8
1.11 2 3.6
1.67 3 5.4
2.22 4 7.2
2.78 5 9.0
3.33 6 10.8
3.89 7 12.6
4.44 8 14.4
5.00 9 16.2
5.56 10 18.0
6.11 11 19.8
6.67 12 21.6
8.33 15 27.0

3) Pressure conversion table (kgf/cm2 ←→ MPa)

The figures in the center column show the pressure to be converted. The figures on the right show
conversion from MPa to kgf/cm2 and the figures on the left from kgf/cm2 to MPa.

Example : 1 MPa = 10.1972 kgf/cm2, 1 kgf/cm2 = 0.09807 MPa

MPa kgf/cm2 MPa kgf/cm2 MPa kgf/cm2

0.0000000 0.0 0.00000 0.0980665 1 10.1972 1.961330 20 203.944


0.0098067 0.1 1.01972 0.1961330 2 20.3944 2.941995 30 305.916
0.0196113 0.2 2.03944 0.2941995 3 30.5916 3.922660 40 407.888
0.0294200 0.3 3.05916 0.3922660 4 40.7888 4.903325 50 509.860
0.0392266 0.4 4.07888 0.4903325 5 50.9860 5.883990 60 611.832
0.0490333 0.5 5.09860 0.5883990 6 61.1832 6.864655 70 713.804
0.0588399 0.6 6.11832 0.6864655 7 71.3804 7.845320 80 815.776
0.0686466 0.7 7.13804 0.7845320 8 81.5776 8.825985 90 917.748
0.0784532 0.8 8.15776 0.8825985 9 91.7748 9.806650 100 1019.72
0.0882599 0.9 9.17748 0.9806550 10 101.972

4) Pressure conversion table (MPa ←→ psi)

Example : 1 MPa = 145.052 psi, 1 psi = 0.006895 MPa

MPa psi MPa psi MPa psi

0.000000 0 0.00000 0.006895 1 145.052 0.137900 20 2901.04


0.000690 0.1 14.5052 0.013790 2 290.104 0.206850 30 4351.56
0.001379 0.2 29.0104 0.020685 3 435.156 0.275800 40 5802.08
0.002069 0.3 43.5156 0.027580 4 580.208 0.344750 50 7252.60
0.002758 0.4 58.0208 0.034475 5 725.260 0.413700 60 8703.12
0.003448 0.5 72.5260 0.041370 6 870.312 0.482650 70 10153.6
0.004137 0.6 87.0312 0.048265 7 1015.36 0.551600 80 11604.2
0.004827 0.7 101.536 0.055160 8 1160.42 0.620550 90 13054.7
0.005516 0.8 116.042 0.062055 9 1305.47 0.689500 100 14505.2
0.006206 0.9 130.547 0.068950 10 1450.52

3
5) Capacity conversion table (kW ←→ kcal/h)

Example : 1 kW ←→ 860 kcal/h

1000 1000 1000 1000


kW kW kW kW
kcal/h kcal/h kcal/h kcal/h

0.166 0.1 0.086 1.162 1 0.86 11.62 10 8.6 116.2 100 86


0.232 0.2 0.172 2.325 2 1.72 23.25 20 17.2 232.5 200 172
0.348 0.3 0.258 3.488 3 2.58 34.88 30 25.8 348.8 300 258
0.465 0.4 0.344 4.651 4 3.44 46.51 40 34.4 465.1 400 344
0.581 0.5 0.430 5.813 5 4.33 58.13 50 43.3 581.3 500 433
0.697 0.6 0.516 6.976 6 5.16 69.76 60 51.6 697.6 600 516
0.813 0.7 0.602 8.139 7 6.02 81.39 70 60.2 813.9 700 602
0.930 0.8 0.688 9.302 8 6.88 93.02 80 68.8 930.2 800 688
1.046 0.9 0.774 10.46 9 7.74 104.6 90 77.4 104.6 900 774

6) Length conversion table (in ←→ mm)

in mm in mm in mm in mm
1/8 3.18 1/32 0.79 1/64 0.40 33/64 13.10
1/4 6.35 3/32 2.38 3/64 1.19 35/64 13.89
3/8 9.53 5/32 3.97 5/64 1.98 37/64 14.68
1/2 12.70 7/32 5.56 7/64 2.78 39/64 15.48
5/8 15.88 9/32 7.14 9/64 3.57 41/64 16.72
3/4 19.05 11/32 8.73 11/64 4.39 43/64 17.07
7/8 22.23 13/32 10.32 13/64 5.16 45/64 17.86
1 25.40 15/32 11.91 15/64 5.95 47/64 18.65
1/16 1.59 17/32 13.49 17/64 6.75 49/64 19.45
3/16 4.76 19/32 15.08 19/64 7.54 51/64 20.24
5/16 7.94 21/32 16.67 21/64 8.33 53/64 21.04
7/16 11.11 23/32 18.26 23/64 9.13 55/64 21.83
9/16 14.29 25/32 19.84 25/64 9.92 57/64 22.62
11/16 17.46 27/32 21.43 27/64 10.72 59/64 23.42
13/16 20.64 29/32 23.02 29/64 11.51 61/64 24.21
15/16 23.81 31/32 24.61 31/64 12.30 63/64 25.00

7) Vacuum conversion table (MPa ←→ MPa (abs) ←→ cmHgv ←→ kgf/cm2 (abs))

Example : -0.0667 MPa ←→ 0.0347 MPa(abs) ←→ 50 cmHgV ←→ 0.3535 kgf/cm2 (abs)

MPa cmHg kgf/cm2 MPa cmHg kgf/cm2 MPa cmHg kgf/cm2


MPa MPa MPa
(abs) V (abs) (abs) V (abs) (abs) V (abs)

-0.1013 0.0000 76 0.0000 -0.0613 0.0400 46 0.4078 -0.0213 0.0800 16 0.8157


-0.0987 0.0027 74 0.0272 -0.0587 0.0427 44 0.4350 -0.0187 0.0827 14 0.8429
-0.0960 0.0053 72 0.0544 -0.0560 0.0453 42 0.4622 -0.0160 0.0853 12 0.8700
-0.0933 0.0080 70 0.0816 -0.0533 0.0480 40 0.4894 -0.0133 0.0880 10 0.8972
-0.0907 0.0107 68 0.1088 -0.0507 0.0507 38 0.5166 -0.0107 0.0907 8 0.9245
-0.0880 0.0133 66 0.1360 -0.0480 0.0533 36 0.5438 -0.0080 0.0933 6 0.9517
-0.0853 0.0160 64 0.1631 -0.0453 0.0560 34 0.5710 -0.0053 0.0960 4 0.9788
-0.0827 0.0187 62 0.1903 -0.0427 0.0587 32 0.5981 -0.0027 0.0987 2 1.0060
-0.0800 0.0213 60 0.2175 -0.0400 0.0613 30 0.6254 0 0.1013 0 1.0332
-0.0773 0.0240 58 0.2447 -0.0373 0.0640 28 0.6526
-0.0747 0.0267 56 0.2719 -0.0347 0.0667 26 0.6798
-0.0720 0.0293 54 0.2991 -0.0320 0.0693 24 0.7069
-0.0693 0.0320 52 0.3263 -0.0293 0.0720 22 0.7341
-0.0667 0.0347 50 0.3535 -0.0267 0.0747 20 0.7613
-0.0640 0.0373 48 0.3806 -0.0240 0.0773 18 0.7885

4
OVERVIEW OF EXPANSION VALVE
Thermostatic expansion valves reduce the pressure of liquid refrigerant at high-temperature and high-pressure
discharged from the condenser to a state where it can easily evaporate, ensuring the optimum flow rate in
the evaporator.
Thermostatic expansion valves keep the superheat of refrigerant gas within a certain range in accordance
with the capacity of compressor which changes as the cooling load increases or decreases and prevent
abnormal heating and liquid return.

ITEMS TO BE DESIGNATED WHEN PLACING ORDERS

1. For standard models, please specify the catalog number.


2. For special specifications except standard models, please
f specify the following points.

◦ Normal Pressure, Minimum and Maximum Operating


b
Pressure (Condensing Pressure, Evaporating Pressure)
h
◦ Application, Charge Types���������������������������������� b

◦ Normal Temperature, Minimum and Maximum


Operating Temperature (Condensing Temperature,
Evaporating Temperature)

◦ Mounting location (Temperature of the mounting


location at the body, sensing bulb, etc.)

◦ Cooling Capacity (With condensing temperature and


evaporating temperature)

◦ Length of the Capillary Tube������������������������������� f

◦ Refrigerant

◦ Connection type (Flare, Solder) ��������������������������� h

TERMS AND DEFINITIONS

◦ Catalog No. On standard products, specify the Catalog No. only.

◦ Adjustable Range It is possible to set at any position within Adjustable Range. (Mainly
based on a valve opening start position.)

◦ Capacity Nominal capacity under standard operating conditions

◦ Connection Type Flare connections mainly adopt flare pipe connections for refrigeration.
All dimensions are shown based on the piping side to be connected.

◦ Max. Working Pressure The maximum usable pressure at which the valve will function without
any problems under normal operating conditions.

5
Condenser

Subcooling Degree Vapor

Amount of Heat Removed from the Refrigerant


(kJ/kg)
High-Temperature and
High-Pressure liquid
Increasing Pressure
Circulating Refrigerant

Expansion
Valve

Reducing Pressure

Cool Air
Low-Temperature and Superheated
Low-Pressure liquid vapor
(Slightly containing vapor) Compressor

Circulating Refrigerant Amount (G)


Evaporator (kg/h)
Heat

Cooling Capacity (Q)


(kW)

Relation between Expansion Valve and Refrigeration Cycle

1. Condensing Temperature (CT) 5. Condensing Pressure


The highest temperature of the liquid condition of The pressure equivalent to CT.
refrigerant in the refrigerant cycle. (Temperature of
saturated refrigerant liquid at the expansion valve 6. Evaporating Pressure
inlet) The pressure equivalent to ET.

2. Evaporating Temperature (ET) 7. Cooling Capacity


The temperature at mixture condition of refrigerant The amount of cooling heat in kW.
gas and liquid to cool water or air load etc. 1 U.S. Refrigeration ton (U.S.R.T.) = 3.52 kW
(Temperature of saturated refrigerant vapor at the
expansion valve outlet) 8. Pressure Drop
The major cause of pressure drop is
3. Subcooling (SC) frictional resistance in piping. Pressure drop
The degree of temperature reduction, without in the high-pressure side causes a reduction
changes of pressure, against the pressure equivalent in the degree of subcooling or the
to the refrigerant liquid temperature. (Difference generation of flush gas, while pressure drop
between the temperature at the expansion valve in the low-pressure side causes temperature
inlet and temperature equivalent to the refrigerant variance in the evaporator and a reduction
pressure) in capacity. Pressure drop in the internal
pressure equalized expansion valve leads to
4. Superheat (SH) an increase of operating superheat.
The degree of temperature increase, without
changes of pressure, against the pressure equivalent 9. Maximum Operating Pressure
to the refrigerant gas temperature. (Difference The maximum pressure (designed pressure)
between the temperature at the sensing element of at which the expansion valve functions
the expansion valve and the temperature equivalent without problems under normal conditions of
to the pressure at the equalizing section) use.

6
SENSING BULB CHARGING TYPE

It is necessary to select the most appropriate charging type in accordance with the type of refrigerant,
evaporating temperature, thermal effect by defrost, ambient temperature of the mounting part, etc.

Vapor Saturated with Refrigerant R404A Special Charging Types (S) (SA) (SL)
1.4
Vale Closing Pressure Composed a mixture of different gases, minimize the
Absolute Pressure (MPa (abs))

operating superheat compared with charging type (G) and


1.2 Internal Pressure of Sensing Bulb
control the maximum operating pressure (M.O.P.).
◦ Symbols are changed in accordance with the difference in
1
the applied range of evaporating temperature and M.O.P.
M.O.P.
◦ Mainly for cooling units (protected horticulture), heat pump
0.8
equipment, and low temperature equipment

0.6 Gas Charging Type (G)


P1
P2
Superheat 3
The same refrigerant used for the equipment is charged, and
0.4 there is a point at which charged liquid becomes superheated
-10 0 10 20 30
Temperature ( C) gas at the certain temperature rise. This point is called the

Charging Characteristics of S and G


maximum operating pressure (M.O.P.).
◦ Mainly for cooling units
Controlling M.O.P. enables to prevent liquid return at start-
up and to prevent overload of the compressor motor.

1
Vapor Saturated with Refrigerant R404A
Special Charging Types (C) and (CL)
Adsorbent and special gas are charged. Using changes
Vale Closing Pressure
in pressure by high-temperature desorption and low-
Absolute Pressure (MPa (abs))

0.8
temperature adsorption, these types can minimize the
Internal Pressure of Sensing Bulb
operating superheat at low temperature condition. These
types can be controlled correctly regardless of temperature
0.6
difference between sensing bulb temperature and ambient
P3 temperature around the body. There is no control of M.O.P.;
0.4
P3
P1 however, overload prevention effect can be expected.
P2 ◦ Symbols are changed in accordance with the difference in
Superheat 3
P2 the applied range of evaporating temperature.
Superheat 0
0.2 ◦ Mainly for low and extremely low temperature equipment
-30 -20 -10 0 10
Temperature ( C)

Characteristics of C charge

Charging types shown in ( ) are special charging types.


Charging Type
G S (SA) (SL) C (CL)
TB Application/Equipment

TS Relation between TS and TB TS > TB TS ≧ TB TS ≧ TB TS ≧ TB TS  TB TS  TB

MOP Control
TS : temperature at element. ○ ○ ○ ○ △ △
(Overloading Prevention)
TB : temperature at sensing bulb
(controlled temperature) Cooling Equipment ○ *2 ○

Low-Temperature Equipment *1 *2 ○ ○ ○

Application to Extremely-Low-
*1 *2 ○ ○
Temperature Equipment

Application to Heat Pump Equipment *2 ○ △

〇 means“applicable,”and △ means“may not be applicable.”


*1 : Applicable AEX only.
*2 : Depending on the M.O.P. setup.

7
PRESSURE EQUALIZATION TYPES

Please select external pressure equalization types for equipment with large pressure drop and fluctuation
of evaporator, and internal pressure equalization types for equipment with smaller pressure drop in the
evaporator.
For example, when there is pressure drop of 0.102 MPa on the low-pressure side, the internal pressure
equalization type will increase operating superheat approximately 5°C.

Setting :
Refrigerant R404A
Point A 0.702 MPa abs (5°C)
Point B 0.6 MPa abs (0°C)
Spring Pressure P3 0.102 MPa

External Pressure Equalization Type Internal Pressure Equalization Type

P1 0.702 MPa abs P1 0.804 MPa abs


P2 0.702 MPa abs
P2 0.702 MPa abs

A 0.702 MPa abs 5C A 0.702 MPa abs 5C

P3 P3
0.102 MPa 0.102 MPa

0.702 MPa abs 0.804 MPa abs


5C B 0.6 MPa abs 10 C B 0.6 MPa abs

Pressure in Sensing Bulb (P1) Pressure in Sensing Bulb (P1)


 = 0.6 + 0.102  = 0.702 + 0.102
 = 0.702 MPa Saturation Temperature  = 0.804 MPa Saturation Temperature
Operating superheat is 5°C - 0°C = 5°C. Operating superheat is 10°C - 0°C = 10°C.

PRESSURE DROP IN LOW-PRESSURE PIPING

Equivalent to pressure drop appears as an increase in operating superheat, which leads to pressure drop in
suction piping and reduction of cooling capacity. Therefore, it is necessary to pay attention to excessive
increases in operating superheat.
A pressure difference equivalent to 1°C temperature difference is a guideline for the selecting pressure
equalization type.
When there is a pressure difference higher than the values shown in the table bellow, is the external
pressure equalization types are effective.

Pressure Difference Equivalent to 1°C Temperature (MPa)


Evaporating Temperature (°C)
Refrigerant
10 5 0 -5 -10 -20 -30 -40 -50 -60
R134a 0.014 0.012 0.011 0.009 0.008 0.006 0.004 0.003 ― ―

R404A 0.025 0.022 0.019 0.017 0.015 0.012 0.008 0.006 0.004 0.003
R407C 0.021 0.018 0.016 0.014 0.012 0.009 0.006 0.004 0.003 0.002
R410A 0.033 0.029 0.026 0.023 0.020 0.015 0.011 0.008 0.006 0.004
R448A 0.022 0.020 0.017 0.015 0.013 0.010 0.007 0.005 0.003 0.002
R449A 0.022 0.019 0.017 0.015 0.013 0.010 0.007 0.005 0.003 0.002

8
SUPERHEAT

The degree of temperature increase, without a change of pressure, against the saturated vapor temperature
of the refrigerant. Expansion valve superheat has static superheat (SSH) and superheat change (SHC), and
the sum of SSH and SHC is the operating superheat (OSH), which is equivalent to the degree of superheat
generated at the evaporator outlet.

Operating Principle of Superheat

Thermostatic Expansion Valve

P2 Saturated Liquid

Evaporator

Sensing Bulb
B C' P1 C

Saturated Vapor Superheated Vapor P2

Static Superheat Superheat Change

Operating Superheat

Static Superheat (SSH) : Superheat from valve closing position to valve opening
Superheat Change (SHC) : Superheat from valve opening to required flow rate
Operating Superheat (OSH) : Static Superheat + Superheat Change

Static Superheat Adjustment


Adjustment of superheat means the adjustment of static superheat.
Please set the static superheat for the safety of equipment unless there is a specific reason.

Adjustable Range of Static Superheat Amount of Change per Spindle Rotation


(°C) (MPa)

1 ~ 5 (R410A)
QCX
RCX
1 ~ 7 (R448A, R449A)
Approx. 0.045
1 ~ 5 (R134a, R404A, R448A, R449A)
SCX
1 ~ 7 (R407C, R410A)

AEX 0 〜 20 Approx. 0.05

1 ~ 7 (R410A, S, SL charge for R404A)

ATX 0 ~ 8 (S, SL charge) Approx. 0.007

0 ~ 10 (C charge for R448A, R449A)

9
INFORMATION ON THERMOSTATIC EXPANSION VALVE
SELECTION SOFTWARE

Thermostatic Expansion Valve Selection Software on Saginomiya website can easily and
automatically select a suitable model for the usage conditions such as refrigerant type, cooling
capacity, and condensing temperature. Please use it when selecting expansion valve.
* Available products : QCX, RCX, SCX, ATX

【How to use】
1. Access Saginomiya website from the following URL or QR code.
URL : https://www.saginomiya.co.jp/en/auto/utilitysoft.html

2. The following screen is displayed, and click "Detail".

3. The following screen is displayed. 4. Search results are displayed at the bottom of the
Select each condition and click "Search". screen.

【Note for use】


The Search results of selection software can be applied in case of general operating conditions. When
using our products, please be sure to conduct trial ran to confirm that total system is fully functional.

10
THERMOSTATIC EXPANSION VALVES / Type QCX & RCX

Thermostatic Expansion Valve


Selection Software ⇒

Capacity Table ⇒

Type QCX-B Type RCX-D

FEATURES APPLICATIONS

◦ Wide temperature range. Applicable for deep freezing, refrigeration and ◦ Display cases
air conditioning systems (single flow). ◦ Commercial refrigerators
◦ Equipped with a strainer for flare type ◦ Cold chain boxes
◦ Suitable for refrigeration systems with hot gas defrosting ◦ Air conditioning systems,
◦ Compatible with low GWP refrigerants(R448A, R449A) Protected horticulture
equipments, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ Type QCX : Internal equalizer type QCX − 03 3 4 B V SA


◦ Type RCX : External equalizer type Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Max. working pressure : 3.0 MPa
◦ Max. body and sensing bulb temperature : 80°C Ⅰ Type
◦ Adjustable range of static superheat : Ⅱ Capacity
  1 to 7°C (R134a, R404A, R448A, R449A) Ⅲ Inlet pipe size
  1 to 5°C (R407C, R410A) Ⅳ Outlet pipe size

    Increase about 0.045 MPa / rotation Ⅴ Connection


Ⅵ Refrigerant
◦ Flare connection / Solder connection
Ⅶ Charge type

Charge Evaporating Temp. (°C) MOP (°C) Temp. Condition


C R134a -30 to 10 ― TS  TB
SA -40 to 10 18 TS ≧ TB
C R404A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB
SA -40 to 10 18 TS ≧ TB
R407C
C -40 to 0 ― TS  TB
SA -45 to 10 18 TS ≧ TB
R410A
C -40 to -10 ― TS  TB
SA -40 to 10 18 TS ≧ TB
C R448A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB
SA -40 to 10 18 TS ≧ TB
C R449A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB

TS : Power Element Temp. , TB : Sensing Bulb Temp.

11
TYPE NUMBER SELECTION

Capacity
(U.S.R.T.){kW}
Catalog No. Connection Factory
Equalizer Charge : Charge : superheat Wt.
Type SA, C SL setting (kg)
CT 38°C CT 38°C (°C)
Charge
Type Model Refrigerant Inlet Outlet Equalizer
Type ET -5°C ET -30°C
0.24
0234B [D] ―
{0.85}

0.36
0434B [D] ―
{1.28}

0.61
0634B [D] ―
{2.13}

0.96
1034B [D] ―
{3.38}
M
C
(R134a)
1.21
1234B [D] ―
{4.27}

1.82
1834B [D] ―
{6.40}

2.43
2434B [D] ―
{8.54}

3.64
3634B [D] ―
{12.8}

0.20 0.13
0234B [D]
{0.70} {0.46}

0.30 0.19
0334B [D]
{1.05} {0.68}

0.49 0.32 0.28


0534B [D] (QCX-B)
{1.74} {1.11}

Internal 0.78 0.51 0.24


0834B [D] (QCX) 3/8" Flare 1/2" Flare 1/4" Flare [QCX-D]
SA {2.76} {1.79}
QCX U
RCX
1034B [D]
(R404A)
C
SL External 0.99 0.64 [ 3/8" (OD)
Solder ][ 1/2" (OD)
Solder ][ 1/4" (OD)
Solder ] 5
0.29
(RCX) {3.48} {2.25} (RCX-B)

1.48 0.98 0.24


1534B [D]
{5.22} {3.44} [RCX-D]
1.98 1.32
2034B [D]
{6.95} {4.63}

2.96 1.80
3034B [D]
{10.4} {6.34}

0.32
0334B [D] ―
{1.13}

0.48
0534B [D] ―
{1.70}

0.81
0834B [D] ―
{2.84}

1.29
1234B [D] ―
{4.54}
H SA
(R407C) C
1.61
1634B [D] ―
{5.67}

2.42
2434B [D] ―
{8.51}

3.21
3134B [D] ―
{11.3}

4.83
4734B [D] ―
{17.0}

12
TYPE NUMBER SELECTION

Capacity
(U.S.R.T.){kW}
Catalog No. Connection Factory
Equalizer Charge : Charge : superheat Wt.
Type SA, C SL setting (kg)
CT 38°C CT 38°C (°C)
Charge
Type Model Refrigerant Inlet Outlet Equalizer
Type ET -5°C ET -30°C
0.35
0334B [D] ―
{1.22}

0.52
0534B [D] ―
{1.83}

0.86
0934B [D] ―
{3.04}

1.37
1434B [D] ―
{4.82}
V SA
(R410A) C
1.73
1734B [D] ―
{6.08}

2.59
2634B [D] ―
{9.12}

3.44
3534B [D] ―
{12.1}

5.18
5234B [D] ―
{18.2}

0.29 0.20
0334B [D]
{1.03} {0.70}

0.44 0.29
0434B [D]
{1.55} {1.03}

0.74 0.48 0.28


0734B [D] (QCX-B)
{2.59} {1.70}

Internal 1.18 0.78 0.24


1234B [D] (QCX) 3/8" Flare 1/2" Flare 1/4" Flare (QCX-D)
SA {4.14} {2.73}
QCX C1
RCX
1534B [D]
(R448A)
C
SL External 1.47 0.98 [ 3/8" (OD)
Solder ][ 1/2" (OD)
Solder ][ 1/4" (OD)
Solder ] 5
0.29
(RCX) {5.17} {3.44} (RCX-B)

2.21 1.49 0.24


2234B [D]
{7.76} {5.25} (RCX-D)
2.93 2.01
2934B [D]
{10.3} {7.08}

4.41 2.75
4334B [D]
{15.5} {9.68}

0.28 0.20
0334B [D]
{0.99} {0.69}

0.42 0.29
0434B [D]
{1.49} {1.01}

0.71 0.47
0734B [D]
{2.48} {1.67}

1.13 0.76
1234B [D] SA {3.97} {2.68}
C1
C
(R449A)
SL 1.41 0.96
1534B [D]
{4.96} {3.38}

2.12 1.47
2234B [D]
{7.44} {5.17}

2.82 1.98
2934B [D]
{9.93} {6.97}

4.24 2.71
4334B [D]
{14.9} {9.53}

・ For other refrigerant, please contact SAGINOMIYA.

13
DIMENSIONS

φ2.4 1500 φ2.4 1500


φ39 φ39

22.5

22.5
32

32
L

L
φD φD

67

67
8

10

41 35.5 48 48.5

Type QCX-B Type QCX-D

φ2.4 1500 φ2.4 1500


φ39 φ39
22.5

22.5
1/4" Flare [ID] φ6.5
32

32
L

L
φD φD
67

67
10

41 35.5 48 48.5

Type RCX-B Type RCX-D Unit : mm

Unit : mm
Charge
D L
SA 12.7 80
C 9.5 50
SL 12.7 80

ACCESSORY

◦ Sensing Bulb Mounting Band

8.5 φ5.5 5 φ5.5


23

(44) 4 9.5 (=38)


0.4

92

M5 0.8 bolt Unit : mm

14
THERMOSTATIC EXPANSION VALVES / Type SCX

Thermostatic Expansion Valve


Selection Software ⇒

Capacity Table ⇒

Type SCX-B Type SCX- ** 45D

FEATURES APPLICATIONS

◦ Wide temperature range. Applicable for deep freezing, refrigeration and ◦ Display cases
air conditioning systems (single flow). ◦ Commercial refrigerators
◦ Small and lightweight design ◦ Cold chain boxes
◦ Suitable for refrigeration systems with hot gas defrosting ◦ Air conditioning systems,
◦ Capable of controling degree of superheat regardless of fluctuations in Protected horticulture
condensation pressure. equipments, etc.
◦ Compatible with low GWP refrigerants (R448A, R449A)

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ External equalizer type SCX − 05 4 5 B M C


◦ Max. working pressure : 3.0 MPa Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Max. body and sensing bulb temperature : 80°C
◦ Adjustable range of static superheat : Ⅰ Type
  1 to 7°C(R134a, R404A, R448A, R449A) Ⅱ Capacity
  1 to 5°C(R407C, R410A) Ⅲ Inlet pipe size
    Increase about 0.045 MPa / rotation Ⅳ Outlet pipe size

◦ Flare connection / Solder connection Ⅴ Connection


Ⅵ Refrigerant
Ⅶ Charge type
Charge Evaporating Temp. (°C) MOP (°C) Temp. Condition
C R134a -30 to 10 ― TS  TB
SA -40 to 10 18 TS ≧ TB
C R404A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB
SA -40 to 10 18 TS ≧ TB
R407C
C -40 to 0 ― TS  TB
SA -45 to 10 18 TS ≧ TB
R410A
C -40 to -10 ― TS  TB
SA -40 to 10 18 TS ≧ TB
C R448A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB
SA -40 to 10 18 TS ≧ TB
C R449A -40 to 0 ― TS  TB
SL -60 to -25 -20 TS ≧ TB

TS : Power Element Temp. , TB : Sensing Bulb Temp.

15
TYPE NUMBER SELECTION

Capacity
(U.S.R.T.){kW}
Catalog No. Connection Factory
Equalizer Charge : Charge : superheat Wt.
Type SA, C SL setting (kg)
CT 38°C CT 38°C (°C)
Charge
Type Model Refrigerant Inlet Outlet Equalizer
Type ET -5°C ET -30°C
4.75
0545B [D] ― 1/2" 5/8"
{16.7}
Flare Flare 0.39

0745B [D]
6.63
{23.3}
― [ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

8.33
0857D ―
{29.3}

9.98 5/8" 7/8"


1057D ― 0.32
M {35.1} Solder Solder
C
(R134a)
11.8
1257D ―
{41.5}

8.33
0871D ―
{29.3}

9.98 7/8" 1-1/8"


1071D ― 0.35
{35.1} Solder Solder

11.8
1271D ―
{41.5}

3.64 1.92
0445B [D] 1/2" 5/8"
{12.8} {6.74}
Flare Flare 0.39

0545B [D]
5.09
{17.9}
2.67
{9.39}
[ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

6.40 3.36
0657D
{22.5} {11.8}

7.65 4.04 5/8" 7/8" 1/4"


0857D SA 0.32
U {26.9} {14.2} Solder Solder Flare
SCX C External 5
0957D
(R404A)
SL 9.07
{31.9}
4.75
{16.7}
[ 1/4"
Solder ]
6.40 3.36
0671D
{22.5} {11.8}

7.65 4.04 7/8" 1-1/8"


0871D 0.35
{26.9} {14.2} Solder Solder

9.07 4.75
0971D
{31.9} {16.7}

5.94
0645B [D] ― 1/2" 5/8"
{20.9}
Flare Flare 0.39

0845B [D]
8.28
{29.1}
― [ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

10.4
1057D ―
{36.6}

12.5 5/8" 7/8"


1257D ― 0.32
H SA {43.9} Solder Solder
(R407C) C
14.8
1457D ―
{52.0}

10.4
1071D ―
{36.6}

12.5 7/8" 1-1/8"


1271D ― 0.35
{43.9} Solder Solder

14.8
1471D ―
{52.0}

16
TYPE NUMBER SELECTION

Capacity
(U.S.R.T.){kW}
Catalog No. Connection Factory
Equalizer Charge : Charge : superheat Wt.
Type SA, C SL setting (kg)
CT 38°C CT 38°C (°C)
Charge
Type Model Refrigerant Inlet Outlet Equalizer
Type ET -5°C ET -30°C
6.37
0645B [D] ― 1/2" 5/8"
{22.4}
Flare Flare 0.39

0945B [D]
8.87
{31.2}
― [ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

11.2
1157D ―
{39.2}

13.4 5/8" 7/8"


1357D ― 0.32
V SA {47.0} Solder Solder
(R410A) C
15.8
1657D ―
{55.6}

11.2
1171D ―
{39.2}

13.4 7/8" 1-1/8"


1371D ― 0.35
{47.0} Solder Solder

15.8
1671D ―
{55.6}

5.43 2.90
0545B [D] 1/2" 5/8"
{19.1} {10.2}
Flare Flare 0.39

0745B [D]
7.56
{26.6}
4.01
{14.1}
[ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

9.50 5.06
0957D
{33.4} {17.8}

11.4 6.06 5/8" 7/8" 1/4"


1157D SA 0.32
C1 {40.0} {21.3} Solder Solder Flare
SCX C External 5
1357D
(R448A)
SL 13.5
{47.4}
7.17
{25.2}
[ 1/4"
Solder ]
9.50 5.06
0971D
{33.4} {17.8}

11.4 6.06 7/8" 1-1/8"


1171D 0.35
{40.0} {21.3} Solder Solder

13.5 7.17
1371D
{47.4} {25.2}

5.20 2.84
0545B [D] 1/2" 5/8"
{18.3} {10.0}
Flare Flare 0.39

0745B [D]
7.25
{25.5}
3.95
{13.9}
[ 1/2"
Solder ] [ 5/8"
Solder ] [0.31]

9.13 4.98
0957D
{32.1} {17.5}

10.9 5.97 5/8" 7/8"


1157D SA 0.32
C1 {38.4} {21.0} Solder Solder
C
(R449A)
SL 12.9 7.05
1357D
{45.5} {24.8}

9.13 4.98
0971D
{32.1} {17.5}

10.9 5.97 7/8" 1-1/8"


1171D 0.35
{38.4} {21.0} Solder Solder

12.9 7.05
1371D
{45.5} {24.8}

・ For other refrigerant, please contact SAGINOMIYA.

17
DIMENSIONS

φ2.4 1500 (φ39) φ2.4 1500 (φ39)

(49) (43) (53) (53)

φ6.5

φ12.9
10

(30)
(30)
(40)

(40)
φD φD

74
74
L

L
10

φ16.1
Type SCX- **** B Type SCX- ** 45D

φ2.4 1500 (φ39) φ2.4 1500 (φ39)


(53) (53)
(53) (53)

φ22.4
11

φ6.5
φ6.5

φ16.1

10

(30)
(40)
(30)

φD
(40)

L
φD

74
74
L

11 14

φ28.8
φ22.4

Type SCX- ** 57D Type SCX- ** 71D Unit : mm

Unit : mm
Charge
D L
SA 12.7 80
C 9.5 50
SL 12.7 80

ACCESSORY

◦ Sensing Bulb Mounting Band

φ5.5 11 φ5.5
20

(53.4) 10 9.5 (=95)


159

M5 0.8 bolt Unit : mm

18
THERMOSTATIC EXPANSION VALVES / Type ATX

Thermostatic Expansion Valve


Selection Software ⇒

Capacity Table ⇒

Type ATX-B Type ATX-D

FEATURES APPLICATIONS

◦ Suitable for refrigeration systems with hot gas defrosting ◦ Water chillers
◦ Compatible with low GWP refrigerants (R448A, R449A) ◦ Air conditioning systems
◦ Freezers
◦ Refrigerators
◦ Brine coolers, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ External equalizer type ATX − 3 4 006 B U S


◦ Max. working pressure : 2.8 MPa (R134a, R404A, R448A, R449A), Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
3.3 MPa (R407C, R410A)
◦ Max. body temperature : 80°C Ⅰ Type
◦ Max. sensing bulb temperature : 40°C (C, CL Charge), Ⅱ Inlet pipe size
120°C (S, SL Charge) Ⅲ Outlet pipe size
◦ Adjustable range of static superheat : Ⅳ Capacity

  0 to 10°C (C Charge for R448A and R449A), 0 to 8°C (S, SL Charge), Ⅴ Connection
Ⅵ Refrigerant
  1 to 7°C (R410A, S, SL Charge for R404A)
Ⅶ Charge type
    Increase about 0.007 MPa / rotation
◦ Flare connection / Solder connection

Charge Evaporating Temp. (°C) MOP (°C) Temp. Condition


S R134a -30 to 10 20 TS ≧ TB
S -40 to 10 20 TS ≧ TB
R404A
SL -60 to -25 -20 TS ≧ TB
S R407C -40 to 10 20 TS ≧ TB
C -20 to 10 ― TS  TB
R410A
CL -40 to -10 ― TS  TB
S -40 to 10 20 TS ≧ TB
C R448A -40 to 10 ― TS  TB
SL -60 to -25 -20 TS ≧ TB
S -40 to 10 20 TS ≧ TB
C R449A -40 to 10 ― TS  TB
SL -60 to -25 -20 TS ≧ TB

TS : Power Element Temp. , TB : Sensing Bulb Temp.

19
TYPE NUMBER SELECTION

< S, C, CL Charge >
Catalog No. Equalizer Connection Factory superheat Wt.
Type Model Refrigerant Charge Type Type Inlet Outlet Equalizer setting (°C) (kg)
34006B [D]
34013B [D]
3/8" Flare 1/2" Flare
1.2
[ ][ ]

( )
34023B [D] 3/8" (OD) 1/2" (OD)
S [1.1]
Solder Solder
34035B [D] R134a
34045B [D] R404A
R407C
57060D M (R134a)
R448A
U (R404A)
57080D R449A 5/8" (OD) 7/8" (OD)
P (R407C)
or or 1/4"
ATX 71110D V (R410A) External 5 1.3
C 7/8" (ID) 1-1/8" (ID) Flare

( )
C (Others)
71140D R410A Solder Solder
C1 (R448A)
71160D R448A
C1 (R449A)
R449A
12220D
12270D CL 1" (OD) 1" (OD)
(R410A) or or
12330D 1.5
1-1/4" (ID) 1-1/4" (ID)
12420D Solder Solder
12500D

・ For other refrigerant, please contact SAGINOMIYA.

Catalog No. Capacity (U.S.R.T.){kW}


CT 38°C / ET 5°C
Type Model Refrigerant Charge Type
R134a R404A R407C R410A R448A R449A
0.70 0.70 1.00 1.09 0.94 0.91
34006B [D]
{2.46} {2.46} {3.51} {3.85} {3.30} {3.19}

1.60 1.50 2.20 2.31 1.97 1.91


34013B [D]
{5.63} {5.27} {7.74} {8.14} {6.94} {6.72}

2.80 2.70 3.70 3.98 3.38 3.27


34023B [D]
{9.85} {9.49} {13.0} {14.0} {11.9} {11.5}

4.21 4.01 5.69 6.06 5.15 4.98


34035B [D]
{14.8} {14.1} {20.0} {21.3} {18.1} {17.5}

5.40 5.09 7.20 7.76 6.63 6.40


34045B [D]
{19.0} {17.9} {25.3} {27.3} {23.3} {22.5}

( )
S 7.22 6.80 9.98 10.7 9.10 8.82
57060D R134a {25.4} {23.9} {35.1} {37.6} {32.0} {31.0}
R404A
R407C 9.58 9.10 13.4 14.3 12.2 11.8
57080D M (R134a)
R448A {33.7} {32.0} {47.1} {50.3} {42.9} {41.5}
U (R404A)
R449A
P (R407C)
13.2 12.5 18.3 19.6 16.7 16.2
ATX 71110D V (R410A)
C {46.4} {44.0} {64.3} {69.0} {58.8} {56.9}

( )
C (Others)
R410A
C1 (R448A) 16.8 16.0 23.3 24.9 21.2 20.5
71140D R448A
C1 (R449A) {59.1} {56.3} {81.9} {87.4} {74.6} {72.1}
R449A

CL 19.2 18.2 26.8 28.7 24.5 23.7


71160D
(R410A) {67.5} {64.0} {94.2} {101} {86.0} {83.2}

26.4 25.1 37.0 39.5 33.6 32.4


12220D
{92.8} {88.3} {130} {139} {118} {114}

32.4 30.7 44.9 48.4 41.2 39.8


12270D
{114} {108} {158} {170} {145} {140}

39.8 37.5 54.9 58.6 50.1 48.4


12330D
{140} {132} {193} {206} {176} {170}

50.3 47.8 69.7 74.2 63.4 61.1


12420D
{177} {168} {245} {261} {223} {215}

60.0 56.9 83.3 89.3 76.2 73.7


12500D
{211} {200} {293} {314} {268} {259}

・ For other refrigerant, please contact SAGINOMIYA.

20
TYPE NUMBER SELECTION

< SL Charge >
Catalog No. Equalizer Connection Factory superheat Wt.
Type Model Refrigerant Charge Type Type Inlet Outlet Equalizer setting (°C) (kg)
34006B [D]
34013B [D]
3/8" Flare 1/2" Flare
1.2
34023B [D]
34035B [D]
[ 3/8" (OD)
Solder ][ 1/2" (OD)
Solder ] [1.1]

34045B [D]
U
57060D (R404A)
57080D SL 5/8" (OD) 7/8" (OD)

( )
C1 R404A or or 1/4"
ATX 71110D External 5 1.3
(R448A) R448A 7/8" (ID) 1-1/8" (ID) Flare
71140D R449A Solder Solder
71160D C1
(R449A)
12220D
12270D 1" (OD) 1" (OD)
or or
12330D 1.5
1-1/4" (ID) 1-1/4" (ID)
12420D Solder Solder
12500D

Catalog No. Capacity (U.S.R.T.){kW}


CT 38°C / ET -30°C
Type Model Refrigerant Charge Type
R404A R448A R449A
0.33 0.50 0.49
34006B [D]
{1.16} {1.76} {1.73}

0.82 1.26 1.24


34013B [D]
{2.90} {4.42} {4.35}

1.36 2.07 2.04


34023B [D]
{4.78} {7.29} {7.17}

2.04 3.10 3.04


34035B [D]
{7.19} {10.9} {10.7}

2.62 3.98 3.92


34045B [D]
{9.23} {14.0} {13.8}

3.67 5.57 5.49


57060D
{12.9} {19.6} {19.3}

U 4.92 7.48 7.37


57080D (R404A) {17.3} {26.3} {25.9}
SL
ATX 71110D
C1
(R448A)

C1
( R404A
R448A
R449A
) 6.94
{24.4}

8.73
9.47
{33.3}

13.3
9.33
{32.8}

13.1
71140D
(R449A) {30.7} {46.7} {46.0}

9.95 18.6 18.3


71160D
{35.0} {65.3} {64.3}

13.7 24.5 24.1


12220D
{48.2} {86.2} {84.9}

16.9 29.6 29.3


12270D
{59.3} {104} {103}

20.6 35.8 35.3


12330D
{72.4} {126} {124}

27.6 46.9 46.4


12420D
{97.1} {165} {163}

33.0 59.2 58.3


12500D
{116} {208} {205}

21
DIMENSIONS

φD φD
φ3 L φ3 L
77

H
31

A
φ16 φ16


30

h
38

Type ATX-B OD
ID

Type ATX-D Unit : mm

Catalog No. Unit : mm


Type Model H h A B ΦD L ℓ
34006B [D]
34013B [D]
34023B [D] 77 30 31 38
34035B [D]
34045B [D]
57060D
57080D
ATX 71110D 80 52 34 68 2000 100
71140D
71160D
51
12220D
12270D
12330D 82 56 36
12420D
12500D

ACCESSORY

◦ Sensing Bulb Mounting Band

For Type ATX-34006 to 71160 For Type ATX-12220 to 12500


14

14

φ6 12.6 11 φ6 φ6 12.6 12 φ6
7

7
16

16

116.6 10 12.6(=126) 174 11 12.6(=138.6)


(5.4) (5.4)
267 337
t=0.4 t=0.4

Unit : mm

22
THERMOSTATIC EXPANSION VALVES / Type AEX

Capacity Table ⇒

AEX-2333BU AEX-2333BUZ

FEATURES APPLICATIONS

◦ High performance over a wide range of evaporation temperature. ◦ Refrigerators


◦ The AEX-Z type adopts a bellow seal mechanism and performs stable ◦ Freezers
control even at extremely low temperature. ◦ Refrigeration equipments for
◦ Equipped with a strainer in inlet. Ships
◦ Chillers, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ Internal equalizer type AEX − 23 3 3 B U Z


◦ Max. working pressure : 1.4 MPa Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Max. body and sensing bulb temperature : 80°C
◦ Adjustable range of static superheat : 0 to 20°C Ⅰ Type
    Increase about 0.05 MPa / rotation Ⅱ Inlet pipe size
◦ Flare connection Ⅲ Outlet pipe size
Ⅳ Capacity

Temperature Evaporating Temp. Ⅴ Connection


Charge MOP (°C) Temp. Condition
class (°C) Ⅵ Refrigerant
R134a -30 to 10 Ⅶ Temperature class
Standard 13
R404A -40 to 10
G TS > TB
R23 Extreme Low -100 to -70 -60
R404A Temperature -70 to 10 13

TS : Power Element Temp. , TB : Sensing Bulb Temp.

23
TYPE NUMBER SELECTION

Catalog No. Capacity (U.S.R.T.){kW} * 2 Connection


Factory
*1 Equalizer CT 38°C CT -40°C superheat Wt.
Temperature Type ET -5°C ET -80°C setting (kg)
Type Model Refrigerant Inlet Outlet
class (°C)
R134a R404A R23
0.36 0.34 0.19
2333B 0.95
{1.27} {1.20} {0.68} 3/8"
Flare
2335B
0.72 0.68 0.39
{2.53} {2.39} {1.36} 1/4"
2345B (3/8")
Flare
1.10 1.05 0.60
2348B 1.15
{3.87} {3.69} {2.10}
M
1.50 1.40 0.89 1/2"
2341B (R134a) ―
{5.28} {4.92} {3.13} Flare
(Standard)
C 2.60 2.50 1.53
AEX 2342B Internal 3/8" 5
(R23, others) Z {9.14} {8.79} {5.37}

2344B U ( Extreme Low


Temperature ) (1/4")
Flare 1.30
(R404A)
4.41 4.21 2.61 1/2" 5/8"
3454B
{15.5} {14.8} {9.16} Flare Flare

4564B
5/8" 1.55
7.20 6.00 3.58 3/4"
4566B (1/2")
{25.3} {21.1} {12.6} Flare
Flare
9.58 8.39 4.75
4568B
{33.7} {29.5} {16.7}

* 1 For other refrigerant, please contact SAGINOMIYA.


* 2 If you need connection sizes in ( ), please specify first.

DIMENSIONS

φ2.4 1300 Catalog No. Unit : mm


Adjusting bolt
Type Model L H1 H2 h
2333B
70.5
2335B
47
2345B
80

(46)
2348B 132 156
H1

73.5
2341B
φ9.5
AEX 2342B 46 (47)
2344B 81 48 (49)
3454B 84.5 135 159 52
h

4564B
56.5
L 4566B 90.5 136 160
(55.5)
4568B
Type AEX
・ Values in ( ) are the dimensions in the case of connection
size ( ) in TYPE NUMBER SELECTION.
Adjusting bolt φ3 1300
80
H2

φ9.5
h

Type AEX-Z Unit : mm

24
THERMOSTATIC EXPANSION VALVES (SMALL CAPACITY TYPE) / Type ARX

High Volume OEM Item

Drawings must be exchanged for purchase.


Please contact SAGINOMIYA for more details.

Type ARX-2303D

FEATURES APPLICATIONS

◦ Compact and lightweight design ◦ Bottle coolers


◦ Static superheat fixed type ◦ Display cases
◦ Suitable for refrigeration systems with hot gas defrosting ◦ Ice making machines
◦ Industrial air conditioning
systems, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ Internal equalizer type ARX − 2 3 03 D M S


◦ Max. working pressure : 2.8 MPa (Expect R407C), 3.3 MPa (R407C) Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Max. body and sensing bulb temperature : 80°C
◦ Adjustable range of static superheat : 0 to 5°C Ⅰ Type
◦ Solder connection Ⅱ Inlet pipe size
Ⅲ Outlet pipe size
Ⅳ Capacity
Charge Evaporating Temp. (°C) MOP (°C) Temp. Condition
Ⅴ Connection
R134a
Ⅵ Refrigerant
S R404A
-40 to -10°C ― TS  TB Ⅶ Charge type
R407C
CL R404A

TS : Power Element Temp. , TB : Sensing Bulb Temp.

25
TYPE NUMBER SELECTION

Catalog No. Capacity (U.S.R.T.){kW} Connection Factory


*1 Equalizer superheat Wt.
Charge CT 38°C / ET 5°C
Type Model Refrigerant Type Inlet Outlet setting (kg)
Type R134a R404A R407C (°C)
0.24 *2
2302D ― ―
{0.85}

0.36 0.34 0.50


2303D
M {1.27} {1.20} {1.76}
S

( )
(R134a)
R134a 0.60 0.57 0.82
2305D R404A {2.11} {2.00} {2.88}
U 5/16" 3/8" 3
ARX R407C Internal 0.12
(R404A) Solder Solder (fixed) 
0.96 0.93 1.34
2308D
CL {3.37} {3.27} {4.71}
P
(R404A)
(R407C) 1.20 1.14 1.65
2310D
{4.22} {4.01} {5.80}

1.80 1.71 2.47


2315D
{6.33} {6.01} {8.70}

* 1 For other refrigerant, please contact SAGINOMIYA.


* 1 Models for flammable refrigerants are also available. Please contact SAGINOMIYA for details.
* 2 If you need to change superheat setting value, please specify first.

DIMENSIONS

Unit : mm
φ2
Charge
.4 A B
70
0 R134a
3/8"
φ34 S R404A 80
R407C 1/2"
CL R404A 3/8" 50

7
φ8.05
70

A
52
B

φ9.65
44

Unit : mm

26
CONSTANT PRESSURE EXPANSION VALVES / Type CEX

Capacity Table ⇒

CEX-2333B

FEATURES APPLICATIONS

◦ Available for bypass circuit configuration and constant load operation. ◦ Bulk coolers
(excluding hot gas circuit) ◦ Water coolers
◦ Applicable in the vacuum area. ◦ Refrigerators
◦ Equipped with a strainer in inlet. ◦ Air dryers, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ Internal equalizer type CEX − 23 3 3 B U Z


◦ Max. working pressure : 1.4 MPa Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Max. body temperature : 80°C
◦ Pressure adjustment :   increase about 0.03 MPa / rotation Ⅰ Type
◦ Flare connection Ⅱ Inlet pipe size
Ⅲ Outlet pipe size
Temperature Evaporating Temp. Ⅳ Capacity
Refrigerant
class (°C) Ⅴ Connection
R134a -30 to 10 Ⅵ Refrigerant
R404A -40 to -5 Ⅶ Temperature class
Standard R407C -40 to 0
R448A -40 to 0
R449A -40 to 0
Extreme Low R23 -100 to -70
Temperature R404A -70 to -5

27
TYPE NUMBER SELECTION

Catalog No. Adjustable Connection Factory


Equalizer range of set pressure Wt.
Temperature Type pressure setting (kg)
Type Model Refrigerant Inlet Outlet
class (MPa) (MPa)
2333B
3/8" Flare 0.70
2335B
1/4" (3/8")
2345B
Flare
2348B M (R134a) ―
-0.047 to 0.45 M : 0.142 0.85
2341B C (R23, others) (Standard) 1/2" Flare
(C, U, P, C1) C : 0.206
U (R404A)
CEX 2342B Internal 3/8" (1/4") U : 0.412
P (R407C) Z
-0.047 to 0.35 P : 0.279
( )
2344B C1 (R448A) Extreme Low Flare 1.00
(M) C1 : 0.325
3454B C1 (R449A) Temperature 1/2" Flare 5/8" Flare 1.25
4564B
5/8" (1/2")
4566B 3/4" Flare 1.40
Flare
4568B

・ If the pressure and temperature meet the specified conditions, each fluorocarbon-based refrigerants can be used with each other.
・ If you need connection sizes in ( ), please specify first.
・ The set pressure is the pressure at the beginning of valve opening.
・ For other refrigerant, please contact SAGINOMIYA.

Catalog No. Capacity (U.S.R.T.){kW}


CT 38°C CT -40°C
Temperature ET -5°C ET -80°C
Type Model Refrigerant
class
R134a R404A R407C R448A R449A R23
0.36 0.34 0.51 0.47 0.45 0.19
2333B
{1.27} {1.20} {1.81} {1.65} {1.59} {0.68}
2335B 0.72 0.68 0.98 0.89 0.86 0.39
2345B {2.53} {2.39} {3.44} {3.14} {3.01} {1.36}

1.10 1.05 1.44 1.31 1.26 0.60


2348B
{3.87} {3.69} {5.07} {4.62} {4.43} {2.10}
M (R134a) ― 1.50 1.40 1.96 1.78 1.71 0.89
2341B
C (R23, others) (Standard) {5.28} {4.92} {6.88} {6.27} {6.02} {3.13}
U (R404A)
CEX 2.60 2.50 3.81 3.47 3.33 1.53
2342B P (R407C) Z
{9.14} {8.79} {13.4} {12.2} {11.7} {5.37}
2344B
C1
C1
(R448A)
(R449A) ( Extreme Low
Temperature )
4.41 4.21 6.17 5.63 5.40 2.61
3454B
{15.5} {14.8} {21.7} {19.8} {19.0} {9.16}
4564B
7.20 6.00 9.90 9.02 8.67 3.58
4566B
{25.3} {21.1} {34.8} {31.7} {30.5} {12.6}
9.58 8.39 13.2 12.0 11.5 4.75
4568B
{33.7} {29.5} {46.4} {42.3} {40.5} {16.7}

DIMENSIONS

Catalog No. Unit : mm


Type Model L H1 H2 h
2333B
70.5
2335B
47
H1

H2

2345B
(46)
2348B 92 112
73.5
2341B
CEX 2342B 46 (47)
2344B 81 48 (49)
h

3454B 84.5 93 113 52


L L 4564B
56.5
4566B 90.5 95 115
Type CEX Type CEX-Z (55.5)
4568B

・ Values in ( ) are the dimensions in the case of connection


size ( ) in TYPE NUMBER SELECTION.

28
CONSTANT PRESSURE EXPANSION VALVES / Type CTX

Capacity Table ⇒

Type CTX-B Type CTX-D

FEATURES APPLICATIONS

◦ Available for bypass circuit configuration and constant load operation ◦ Air conditioning systems
◦ Bulk coolers
◦ Refrigerators / Freezers
◦ Air dryers, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ External equalizer type CTX − 3 4 006 B U


◦ Max. working pressure : 2.8 MPa Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ
◦ Max. body temperature : 80°C
◦ Adjustable of pressure :   increase about 0.065 MPa / rotation Ⅰ Type
◦ Adjustable range of pressure setting:-0.01 to 0.45 MPa Ⅱ Inlet pipe size
◦ Flare connection / Solder connection Ⅲ Outlet pipe size
Ⅳ Capacity
Ⅴ Connection
Ⅵ Refrigerant

29
TYPE NUMBER SELECTION

Catalog No. Connection Factory pressure setting Wt.


Type Model Refrigerant Inlet Outlet Equalizer (MPa) (kg)
34006B [D]
34013B [D]
3/8" Flare 1/2" Flare
1.2
34023B [D] or or
[1.1]
[ (OD) Solder] [ (OD) Solder]
34035B [D]
34045B [D]
57060D
M (R134a)
57080D 5/8" (OD) 7/8" (OD) M : 0.142
U (R404A)
or or U : 0.412
CTX 71110D P (R407C) 1/4" Flare 1.3
7/8" (ID) 1-1/8" (ID) P : 0.279
C1 (R448A)
71140D Solder Solder C1 : 0.324
C1 (R449A)
71160D
12220D
12270D 1" (OD) 1" (OD)
or or
12330D 1.5
1-1/4" (ID) 1-1/4" (ID)
12420D Solder Solder
12500D

・ If pressure and temperature match the specified conditions, each fluorocarbon-based refrigerants can be used.
・ Factory pressure setting is the pressure when a valve starts to open.
・ For other refrigerant, please contact SAGINOMIYA.

Catalog No. Capacity (U.S.R.T.){kW}


CT 38°C / ET 5°C
Type Model Refrigerant
R134a R404A R407C R448A R449A
34006B [D] 0.70 {2.46} 0.70 {2.46} 1.00 {3.51} 0.94 {3.30} 0.91 {3.19}
34013B [D] 1.60 {5.63} 1.50 {5.27} 2.20 {7.74} 1.97 {6.94} 1.91 {6.72}
34023B [D] 2.80 {9.85} 2.70 {9.49} 3.70 {13.0} 3.39 {11.9} 3.27 {11.5}
34035B [D] 4.21 {14.8} 4.01 {14.1} 5.69 {20.0} 5.15 {18.1} 4.98 {17.5}
34045B [D] 5.40 {19.0} 5.09 {17.9} 7.20 {25.3} 6.63 {23.3} 6.40 {22.5}
57060D 7.22 {25.4} 6.80 {23.9} 9.98 {35.1} 9.10 {32.0} 8.82 {31.0}
M (R134a)
57080D 9.58 {33.7} 9.10 {32.0} 13.4 {47.1} 12.2 {42.9} 11.8 {41.5}
U (R404A)
CTX 71110D P (R407C) 13.2 {46.4} 12.5 {44.0} 18.3 {64.3} 16.7 {58.8} 16.2 {56.9}
C1 (R448A)
71140D 16.8 {59.1} 16.0 {56.3} 23.3 {81.9} 21.2 {74.6} 20.5 {72.1}
C1 (R449A)
71160D 19.2 {67.5} 18.2 {64.0} 26.8 {94.2} 24.5 {86.0} 23.7 {83.2}
12220D 26.4 {92.8} 25.1 {88.3} 37.0 {130} 33.6 {118} 32.4 {114}
12270D 32.4 {114} 30.7 {108} 44.9 {158} 41.2 {145} 39.8 {140}
12330D 39.8 {140} 37.5 {132} 54.9 {193} 50.1 {176} 48.3 {170}
12420D 50.3 {177} 47.8 {168} 69.7 {245} 63.4 {223} 61.1 {215}
12500D 60.0 {211} 56.9 {200} 83.3 {293} 76.2 {268} 73.7 {259}

DIMENSIONS

φ68 φ68
Approx. 144(146)
Approx. 141

34(36)
31

52(56)
30

38
51
0D
Type CTX-B Type CTX-57060D to 71160D
ID (Type CTX-12220D to 12500D) Unit : mm

30
CONSTANT PRESSURE EXPANSION VALVES,
CAPACITY REGULATING VALVES / Type CGX & SPX

High Volume OEM Item

Drawings must be exchanged for purchase.


Please contact SAGINOMIYA for more details.

Type CGX Type SPX

FEATURES APPLICATIONS

◦ Suitable for capacity control of equipment operating at low load. ◦ Air dryers
◦ Spot coolers
◦ Refrigerators / Freezers
◦ Chillers, etc.

COMMON SPECIFICATIONS

CGX SPX

Equalizer Type Internal

2.5 MPa (Expect R410A) 2.8 MPa (Expect R410A)


Max. working pressure
3.3 MPa (R410A) 3.3 MPa (R410A)

Body Max. temperature 80°C

0.35 to 0.5 MPa 0.2 to 0.6 MPa


   increase about 0.075 MPa / rotation    increase about 0.075 MPa / rotation
(Expect R410A) (Expect R410A)
Adjustable range
of pressure
0.5 to 0.9 MPa 0.5 to 0.9 MPa
   increase about 0.08 MPa / rotation    increase about 0.075 MPa / rotation
(R410A) (R410A)

Connection Solder

DESCRIPTION OF CATALOG NUMBER

◦ CGX, SPX (Expect CGX-2623D) ◦ CGX-2623D

CGX − 2 3 15 D U CGX − 26 2 3 D U
Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ

Ⅰ Type Ⅰ Type
Ⅱ Inlet pipe size Ⅱ Capacity
Ⅲ Outlet pipe size Ⅲ Inlet pipe size
Ⅳ Capacity Ⅳ Outlet pipe size
Ⅴ Connection Ⅴ Connection
Ⅵ Refrigeration Ⅵ Refrigeration

31
TYPE NUMBER SELECTION

Catalog No. Connection


Adjustable range Factory
Equalizer Wt.
of set pressure pressure setting
Type Model Refrigerant Type Inlet Outlet (kg)
(MPa) (MPa)

M (R134a)
M : 0.206 ± 0.02
U (R404A)
U : 0.51 ± 0.02
2315D P (R407C) 0.35 to 0.5 5/16" 3/8" 0.15
CGX P : 0.373 ± 0.02
C1 (R448A) Solder Solder C1 : 0.412 ± 0.02
C1 (R449A)

2623D V (R410A) 0.5 to 0.9 V : 0.72 ± 0.02 0.22


Internal
M (R134a)
0.5 to 0.9 M : 0.206 ± 0.02
U (R404A)
(R410A) U : 0.51 ± 0.02
P (R407C) 1/2" 5/8" 0.26
SPX 4540D P : 0.373 ± 0.02
V (R410A) Solder Solder (0.33) *
0.2 to 0.6 V : 0.72 ± 0.02
C1 (R448A)
(Others) C1 : 0.412 ± 0.02
C1 (R449A)

* SPX-4540DV
・ For other refrigerant, please contact SAGINOMIYA.

Catalog No. Capacity (U.S.R.T.){kW}


CT 38°C / ET 5°C [CT 40°C / ET -10°C]
Type Model Refrigerant
R134a R404A R407C R410A R448A

M (R134a)
U (R404A)
1.80 {6.33} 1.71 {6.01} 2.47 {8.69} 2.26 {7.93}
2315D P (R407C) ―
[0.22 {0.76}] [0.28 {0.97}] [0.33 {1.16}] [0.31 {1.09}]
CGX C1 (R448A)
C1 (R449A)

2.64 {9.28}
2623D V (R410A) ― ― ― ―
[1.24 {2.09}]

M (R134a)
U (R404A)
P (R407C) 4.81 {16.9} 4.55 {16.0} 6.60 {23.2} 7.05 {24.8} 6.29 {22.1}
SPX 4540D
V (R410A) [0.33 {1.17}] [0.43 {1.50}] [0.51 {1.78}] [0.75 {2.64}] [0.48 {1.68}]
C1 (R448A)
C1 (R449A)

・ Capacity : CT 38°C / ET 5°C : Application for constant pressure expansion valves


CT 40°C / ET -10°C : Application for capacity regulating valves (Hot gas 80°C)
・ For other refrigerant, please contact SAGINOMIYA.

DIMENSIONS

φ34 φ44.5 φ44.5 φ44.5


58

65

10
85
86

10
7
64

7
78
8

52

12
8

78

45
12

45 59

59

Type CGX-2315D Type CGX-2623D Type SPX-4540D Type SPX-4540D (for R410A)

Unit : mm

32
MANUALLY OPERATED EXPANSION VALVES / Type HEX

Capacity Table ⇒

Type HEX-B

FEATURES APPLICATIONS

◦ Widely availabe for bypass circuit configuration. ◦ Brine coolers


◦ Opening and closing the valve with a manual handle. ◦ Refrigerations
◦ Equipped with a strainer in inlet. ◦ Freezers, etc.

COMMON SPECIFICATIONS DESCRIPTION OF CATALOG NUMBER

◦ Internal equalizer type HEX − 23 3 3 B U Z


◦ Max. working pressure : 1.4 MPa Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ Ⅵ Ⅶ
◦ Ambient temperature : 80°C
◦ Flare connection Ⅰ Type
Ⅱ Inlet pipe size
Temperature Evaporating Temp. Ⅲ Outlet pipe size
Refrigerant
class (°C) Ⅳ Capacity
R134a -30 to 10 Ⅴ Connection
Standard R404A -40 to 10 Ⅵ Refrigerant
R407C -40 to 10 Ⅶ Temperature class
Extreme Low R23 -100 to -70
Temperature R404A -70 to 10

33
TYPE NUMBER SELECTION

Catalog No. Capacity (U.S.R.T.){kW} Connection


Equalizer Wt.
Temperature CT 38°C / ET -5°C
Type Model Refrigerant Type Inlet Outlet (kg)
class R23 R134a R404A R407C
0.36 0.34 0.51
2333B
{1.27} {1.20} {1.81}
3/8"
0.7
Flare
2335B
0.72 0.68 0.98
{2.53} {2.39} {3.44} 1/4"
2345B (3/8")
Flare
1.10 1.05 1.44
2348B M {3.87} {3.69} {5.07}
(R134a) 0.85
1.50 1.40 1.96 1/2"
2341B C ― {5.28} {4.92} {6.88} Flare
(R23, others) (Standard)
Production 2.60 2.50 3.81
HEX 2342B Internal
U Z possible {9.14} {8.79} {13.4} 3/8"

2344B
(R404A)
( Extreme Low
Temperature ) (1/4")
Flare
1.0
P
(R407C)
4.41 4.21 6.17 1/2" 5/8"
3454B 1.25
{15.5} {14.8} {21.7} Flare Flare

4564B

5/8"
7.20 6.00 9.90 3/4"
4566B (1/2") 1.4
{25.3} {21.1} {34.8} Flare
Flare
9.58 8.39 13.2
4568B
{33.7} {29.5} {46.4}

・ If the pressure and temperature meet the specified conditions, each fluorocarbon-based refrigerant can be used with each other.
・ If you need connection sizes in ( ), please specify first.

DIMENSIONS

Catalog No. Unit : mm


Type Model L H1 H2 h
2333B
70.5
2335B
H1

H2

2345B 47 (46)
2348B 92 112
73.5
2341B
HEX 2342B 46 (47)
2344B 81 48 (49)
h

3454B 84.5 93 113 52


L L 4564B
56.5
4566B 90.5 95 115
Type HEX Type HEX-Z (55.5)
4568B

・ Values in ( ) are the dimensions in the case of connection


size ( ) in TYPE NUMBER SELECTION.

34
MEMO
CONSENT RELATED TO DISCLAIMERS
We, SAGINOMIYA SEISAKUSHO, INC., (hereinafter referred to as“Saginomiya” ), truly appreciate your choosing Saginomiya’s products (hereinafter referred to
as“Products” ).
When the Products are used, this document as provided below shall be applicable except to the extent that there is anything to the contrary in any applicable
estimate, agreement, catalogue, specification, etc.

● CONFIRMATION OF OPERATION
All customers using the Products (hereinafter referred to as“Customers” ) are requested to, after properly installing the Products, test the operation of the
Products to confirm that all the systems in connection with the Products fully function.
In order to prevent the occurrence of bodily injury, fire accidents, serious damage, etc., in connection with the Customers’machinery or equipment due to
improper installation of the Products, Saginomiya kindly requests the Customers to take the necessary safety measures by preparing safe designs such as a
fail-safe design (*1) and a fire spread prevention design, as well as to make the proper adjustments for product reliability necessary for fault-tolerance (*2).

(*1) Fail-safe design: Design to ensure safety in the event of any mechanical failure
(*2) Fault-tolerance: Utilization of redundancy technology

Periodic Inspection of the Products


Be sure to confirm the proper operation of the Products and keep records of such operation at least once a year.

Saginomiya shall be held harmless and be indemnified by the Customers from any damages incurred due to the Customers failing to conduct the above operational
procedures, provided, however, that, this shall not apply if the damages which the Customers incurred due to the defect of the Products caused by Saginomiya.

● RESTRICTIONS OF USE
The Products are designed and manufactured for the purpose of using them for cooling and heating and refrigerating appliances and air conditioning equipment
or various industrial equipment, but are not designed and manufactured for the purpose of using the Products for any instrument or system related to human life
or health purposes.
Therefore, the use of the Products in fields related to items (1) through (3) below is not intended whatsoever. Saginomiya shall be held harmless and be
indemnified from any and all damages incurred by use of the Products under item (3).

(1) In any field related to nuclear power and radiation;


(2) In any field related to space or seafloor equipment;
(3) In any equipment or device requiring a high degree of reliance on such equipment or device with respect to which it is reasonably foreseeable that failure
or malfunction of the equipment or device would either directly or indirectly cause serious damage to human life, health or property;

Also, when using the Products under the fields related to items (1) through (9) below (except for item (3), in relation to which the Products must never be used),
please be sure to notify our Saginomiya’s contact desk in charge of sales and obtain Saginomiya’s prior written approval for such use. Saginomiya shall be held
harmless and be indemnified from any and all damages incurred by use of the Products in relation to these fields if the Customers do not notify Saginomiya’ s
contact desk and obtain Saginomiya’ s prior written approval.

(4) Transportation device (railroad, aviation, ship or vessel, vehicle equipment, etc.);
(5) Disaster-prevention or crime-prevention device;
(6) Facility or application directly related to medical equipment, burning appliances, electro thermal equipment, amusement rides and devices, facilities/applications
associated directly with billing, or device using flammable fluid;
(7) Equipment requiring high reliance on supply systems such as electricity, gas, water, etc., in large-scale communication system, or in transportation or air
traffic control system;
(8) Facilities that are to comply with regulations of governmental / public agencies or specific industries or
(9) Other machineries or equipment equivalent to those set forth in the above items (4) to (8) which require for high reliability and safety.

It is recommended to replace the Products within 5 to 10 years of delivery if no other duration of use is provided in the applicable specifications or instruction
manual because the conditions and environment of use also have an impact on the Products.

● SCOPE OF WARRANTY
SAGINOMIYA WILL PROVIDE THE CUSTOMERS WITH REPLACEMENT OR REPAIRED THE PRODUCTS DELIVERED, FREE OF COST,
ONLY WITHIN ONE YEAR OF DELIVERY TO THE CUSTOMER, IF FAILURE OCCURS IN THE CUSTOMERS’EQUIPMENT USING THE PRODUCTS
DUE TO A DEFECT OF THE PRODUCTS; PROVIDED, HOWEVER, THAT IN ANY EVENT THE RATIO OF THE AMOUNT THAT SAGINOMIYA
BEARS FOR THE DAMAGES INCURRED BY THE FAILURE OF THE PRODUCTS OR CUSTOMERS’EQUIPMENT SHALL NOT EXCEED THE PRICE
OF THE PRODUCTS WE DELIVERED. IN ADDITION, SAGINOMIYA SHALL BE HELD HARMLESS AND BE INDEMNIFIED FROM ANY AND ALL
DAMAGES INCURRED WHEN THE FAILURE OF THE CUSTOMERS’EQUIPMENT OCCURRED DUE TO ANY CAUSE SET FORTH BELOW.

(1) WHEN CAUSED BY INAPPROPRIATE HANDLING OR USE OF THE PRODUCTS BY THE CUSTOMERS (SUCH AS NOT COMPLYING WITH THE
CONDITIONS, ENVIRONMENTAL SPECIFICATIONS OR CAUTIONS INDICATED IN ANY APPLICABLE CATALOGUE, SPECIFICATIONS,
INSTRUCTION MANUAL, ETC.);
(2) WHEN FAILURE OCCURRED DUE TO ANY REASON OTHER THAN THE PRODUCTS;
(3) WHEN CAUSED BY MODIFICATION OR REPAIR OF THE PRODUCTS MADE BY ANYONE OTHER THAN SAGINOMIYA OR DESIGNEE OF
SAGINOMIYA;
(4) WHEN CAUSED BY THE USE OF THE PRODUCTS IN VIOLATION OF THE ABOVE“RESTRICTIONS OF USE”OR“CONFIRMATION OF
OPERATION” ;
(5) WHEN SUCH FAILURE WAS NOT REASONABLY FORESEEABLE AT THE TIME OF SAGINOMIYA’ S SHIPMENT; OR
(6) BY ANY OTHER CAUSE NOT ATTRIBUTABLE TO SAGINOMIYA, SUCH AS AN ACT OF GOD, DISASTER, OR ACT OF ANY THIRD PARTY.

PLEASE NOTE THAT THE CUSTOMERS WILL NOT BE ENTITLED TO ANY OF THE ABOVE WARRANTY IF THE CUSTOMERS PURCHASED THE
PRODUCTS FROM INTERNET AUCTION, ETC.

Revsion1
(2014.12)
 2014.10

WARNING
Failure to read and follow all instruction carefully before
installing or operation the product could cause personal injury
and/or property damage.

Specifications are subject to change without notice.


Shinjyuku Garden Tower 22F
8-2, Okubo 3-chome, Sinjyuku-ku
Tokyo, 169-0072 Japan

Sayama Plant

Headquarters Tokorozawa Plant Yonezawa Plant

OVERSEAS NETWORK

SAGINOMIYA EUROPE Sp. z o.o. (Poland) FOSHAN HUALU AUTOMATIC SAGINOMIYA AMERICA, INC. (USA)
Aleje Jerozolimskie 212 02-486 CONTROLS LIMITED (China) 655 Metro Place South suite 220, Dublin
Warsaw, Poland No.59&61, Wenhua Nan Road, Chancheng District Ohio 43017, U.S.A.
Sales Foshan, Guangdong, China Sales
Sales & Manufacturing

Danfoss Saginomiya Sp. z o.o. (Poland) Saginomiya (Thailand) Co., Ltd. (Thailand)
ul. Chrzanowska 5, 05-825 Grodzisk 159/38 Serm-mit Tower, Room No.2401, 24th
Mazowiecki, Poland floor,Sukhumvit 21 Road, Klongtoey
Manufacturing Nua Sub-district,Wattana District,
Bangkok 10110, Thailand
Sales & Manufacturing
<Asia> 2022.4
Saginomiya (Thailand) Co., Ltd. E-mail : [email protected]
Tel : +66-2260-8364 Fax : +66-2260-8366
<Europe, Middle East, Africa>
SAGINOMIYA EUROPE Sp. z o.o. E-mail : [email protected]
<Japan, Korea, Oceania> Tel : +48-22-101-30-00 Fax : +48-22-101-30-01
E-mail : [email protected] <North America, Latin America>
Tel : +81-3-6205-9120 Fax : +81-3-6205-9122 SAGINOMIYA AMERICA, INC. E-mail : [email protected]
URL : http://www.saginomiya-global.com/en/ Tel : +1-614-766-7390 Fax : +1-614-766-7391