Security information 1

Preface 2
2D Matrix code (QR code /
EAN code) 3
SIMATIC
Product overview 4
ET 200SP HA
DI 8x230VAC HA
Terminal 5

Parameters 6
Equipment Manual

Displays and interrupts 7

Technical specifications 8
Parameters, diagnostics
messages and address A
space

6DL1131-6GF00-0PK0
6DL1131-6GF00-0EK0

07/2022
A5E39401560-AD
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG A5E39401560-AD Copyright © Siemens AG 2020.


Digital Industries Ⓟ 07/2022 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Security information.............................................................................................................................. 5
2 Preface ................................................................................................................................................... 7
3 2D Matrix code (QR code / EAN code) .................................................................................................... 9
4 Product overview ................................................................................................................................. 11
4.1 I/O module......................................................................................................................... 11
4.2 Accessories ........................................................................................................................ 12
4.3 Terminal blocks.................................................................................................................. 12
5 Terminal ............................................................................................................................................... 13
5.1 Terminal assignment.......................................................................................................... 13
5.2 Sample connection scheme for a digital 2-wire sensor ........................................................ 14
5.3 Schematic circuit diagram .................................................................................................. 15
6 Parameters........................................................................................................................................... 17
6.1 Parameter types................................................................................................................. 17
6.2 Module/channel parameters............................................................................................... 17
6.3 Explanation of the module/channel parameters .................................................................. 18
6.3.1 Channel activated .............................................................................................................. 18
6.3.2 Potential group .................................................................................................................. 18
7 Displays and interrupts ........................................................................................................................ 19
7.1 Status and fault displays..................................................................................................... 19
7.2 LEDs .................................................................................................................................. 20
7.2.1 DIAG LED ........................................................................................................................... 20
7.2.2 MT LED .............................................................................................................................. 20
7.2.3 Channel status / fault LEDs ................................................................................................. 21
7.3 Interrupts .......................................................................................................................... 21
8 Technical specifications ....................................................................................................................... 23
8.1 Technical specifications ...................................................................................................... 23
A Parameters, diagnostics messages and address space ....................................................................... 29
A.1 Parameter assignment ....................................................................................................... 29
A.2 Parameter assignment and structure of the module/channel parameters............................. 30
A.3 Diagnostics alarms ............................................................................................................. 32
A.4 Maintenance events........................................................................................................... 33
A.5 Address space .................................................................................................................... 33

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 3
Table of contents

Tables

Table A-1 Address space of the DI 8x230VAC HA ..................................................................................... 33


Table 5-1 Pin assignment of the DI 8x230VAC HA ................................................................................... 14

Figures

Figure A-3 Configuration byte x to x+1 for the channels 0 to 7.................................................................. 32


Figure A-2 Header information and module parameters of data record 128 .............................................. 31
Figure A-1 Structure of data record 128 ................................................................................................... 30

DI 8x230VAC HA
4 Equipment Manual, 07/2022, A5E39401560-AD
Security information 1
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security
concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected to
an enterprise network or the internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
under
https://www.siemens.com/industrialsecurity.

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 5
Security information

DI 8x230VAC HA
6 Equipment Manual, 07/2022, A5E39401560-AD
Preface 2
Validity of the documentation
This equipment manual describes the following I/O modules:

System family I/O module Article No.


SIMATIC Distributed I/O System ET 200SP DI 8x230VAC HA 6DL1131-6GF00-0PK0
HA
SIMATIC Distributed I/O System ET 200SP DI 8x230VAC HA 6DL1131-6GF00-0EK0
HA

It complements the system manual of the ET 200SP HA Distributed I/O System.


Functions that generally relate to the system are described in this manual.
The information in this device manual and the system/function manuals enables you to put the
ET 200SP HA into operation.

Conventions
Please also observe notes marked as follows:

Note
A note contains important information on the product described in the documentation, on the
handling of the product and on the section of the documentation to which particular attention
should be paid.

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 7
Preface

DI 8x230VAC HA
8 Equipment Manual, 07/2022, A5E39401560-AD
2D Matrix code (QR code / EAN code) 3
The 2D matrix code on the product is a coded representation of the product-specific article
number.

Access to product-related information


For reading the 2D matrix code, SIEMENS offers an app for mobile use.
Information about the app and the download can be found on the Internet: "Mobile use via app
(https://support.industry.siemens.com/cs/ww/en/sc/2067)".
The app provides direct access to the technical forum and product-related posts, such as:
• FAQs
• Application examples
• Manuals
• Certificates
• Product notices

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 9
2D Matrix code (QR code / EAN code)

DI 8x230VAC HA
10 Equipment Manual, 07/2022, A5E39401560-AD
Product overview 4
4.1 I/O module

Definition
The DI 8x230VAC HA I/O module is a digital input module with 8 power inputs for process control.
In addition to the technical specifications, this module has the following properties:
• Parameter reassignment in RUN

Description

 DI
8x2 30VAC HA

 DIA G MT


 1 A.0
3 C.2
5 A.4
DI B.1 2
D.3 4
7 C.6 B.5 6


D.7 8
9 A.0
11 C.2 N B.1 10
13 A.4 D.3 12
15 C.6 B.5 14
D.7 16


1P1 NC
2P1 NC NC 1P2
MA X. 10 ANC 2P2

 .0

.2
.1

.3
.4 .5
.6 .7 


X 2
3 4


V 1.0.0
CC4 2


6DL1131-6GF
00- 0PK 0

① Module type and designation ⑦ Module type color coding


② LED for diagnostics ⑧ Product version
③ LED for maintenance ⑨ Function status and firmware version
④ 2D matrix code ⑩ Color code for selection of the color-coded labels
⑤ Wiring diagram ⑪ Serial number
⑥ LEDs for channel status/channel fault ⑫ Article number

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 11
Product overview
4.3 Terminal blocks

4.2 Accessories

Definition
Accessories for the I/O module must be ordered separately.

Description
The following accessories are available:
• Labeling strips
• Color-coded labels
• Reference identification label
• Shield connector
• Terminal blocks

4.3 Terminal blocks

Definition
The terminal blocks provide the process terminals (push-in terminals) for components to be
connected such as devices.

Description
The following terminal blocks are available for the I/O module:

Article No. Color Description


6DL1193-6TP00-0DK0 Lit for single operation and
new load group
6DL1193-6TP00-0BK0 Dark for single operation

Note
Terminal blocks are not included in the scope of delivery of the I/O module and must be ordered
separately.
You can find additional information on the configuration in the system manual.

DI 8x230VAC HA
12 Equipment Manual, 07/2022, A5E39401560-AD
Terminal 5
5.1 Terminal assignment

Definition
The terminal assignment provides information about the arrangement and marking of the
terminals when wiring a connector.

Description

WARNING
Risk of death or serious injury from electric shock!
Prior to working on the system and module, always disconnect them from the power supply.

Note
You can find additional information on the configuration in the system manual.

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 13
Terminal
5.2 Sample connection scheme for a digital 2-wire sensor

The terminal assignment is structured as follows:

Table 5-1 Pin assignment of the DI 8x230VAC HA

Terminal assign‐ Terminal assign‐ Explanations


ment ment
1 DI A.0 2 DI B.1 DI X.n: Input signal, channel n
3 DI C.2 4 DI D.3 N X.n: Neutral conductor, channel n
5 DI A.4 6 DI B.5 NC (Not Connected) The terminals are not connected to the DI
7 DI C.6 8 DI D.7 8x230VAC HA. However, the potentials of the power bus are on these
terminals.
9 N A.0 10 N B.1
The letters A to D indicate the assignment of the electrically isolated
11 N C.2 12 N D.3 channels to one of the 4 groups, which allow for a different difference
13 N A.4 14 N B.5 in potential.
15 N C.6 16 N D.7
1 A.0 DI B.1 2
1P1 NC 1P2 NC 3 C.2 D.3 4
5 A.4 B.5 6
2P1 NC 2P2 NC 7 C.6 D.7 8
9 A.0 N B.1 10
11 C.2 D.3 12
13 A.4 B.5 14
15 C.6 D.7 16

1P1 NC NC 1P2
2P1 NC NC 2P2
MAX. 10 A

5.2 Sample connection scheme for a digital 2-wire sensor

Example

',;Q /

1;Q

DI 8x230VAC HA
14 Equipment Manual, 07/2022, A5E39401560-AD
Terminal
5.3 Schematic circuit diagram

5.3 Schematic circuit diagram

Definition
A block diagram contains the schematic representation of individual function blocks.

Description

ET 200SP HA
Backplane bus
interface 9
Backplane bus

16

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 15
Terminal
5.3 Schematic circuit diagram

DI 8x230VAC HA
16 Equipment Manual, 07/2022, A5E39401560-AD
Parameters 6
6.1 Parameter types

Definition
You define and thereby influence the functions supported by the module operation of the I/O
module via the parameter types.

6.2 Module/channel parameters

Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channel.

Description
The following module/channel parameters are available:

Note
Unused channels
Disable unused channels in the configuration to improve the cycle time of the module. A
disabled channel always returns the output value 0 mA.

Parameters Value range Default Parameter reassign‐ Efficiency range


ment in RUN

Channel activated • Enabled Enabled Yes Channel


(Page 18) • Disabled
Potential group • Use potential group of the Use potential No Module
(Page 18) left module group of the left
module
• Allow new potential group

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 17
Parameters
6.3 Explanation of the module/channel parameters

6.3 Explanation of the module/channel parameters

6.3.1 Channel activated

Definition
Specifies whether a channel is activated or deactivated.

6.3.2 Potential group

Definition
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP HA
station that are supplied via a common supply voltage.

Description
A potential group is built up from left to right by using terminal blocks.
A new potential group starts on the left side with a light gray terminal block, via which the supply
voltage for the potential group is fed in.
The potential group is continued to the right with dark gray terminal blocks and ends when a
new potential group is built up next to it.
The potential group also ends if there is a black terminal block next to it. Black terminal blocks
are fed individually and cannot be included in potential groups.
You can find additional information on the configuration of the potential group in the system
manual SIMATIC; Distributed I/O System; ET 200SP HA.

DI 8x230VAC HA
18 Equipment Manual, 07/2022, A5E39401560-AD
Displays and interrupts 7
7.1 Status and fault displays

Definition
The LED displays are status and error indicators.
Diagnostics messages and maintenance events, as well as their possible causes or solutions are
described in the diagnostics messages and maintenance events.
Diagnostics alarms (Page 32)

Description
The following figure explains the LED displays of the I/O module.


DI HA
8x230VAC
DIAG MT

1 A.0 DI B.1 2
3 C.2 D.3 4
5 A.4 B.5 6
7 C.6 D.7 8
9 A.0 N B.1 10
11 C.2 D.3 12
13 A.4 B.5 14
15 C.6 D.7 16


1P1 NC NC 1P2
2P1 NC NC 2P2
MAX. 10 A

.0 .1
.2 .3
.4 .5
.6 .7

X 2
3 4
V 1.0.0
CC42

6DL1131-6GF00-0PK0

① DIAG LED (Page 20) (green/red)


② MT LED (Page 20) (yellow)
③ Channel status / fault LEDs (Page 21) (green)

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 19
Displays and interrupts
7.2 LEDs

7.2 LEDs

7.2.1 DIAG LED

Definition
The DIAG LED provides you diagnostic information.

Description
The diagnostic display of the DIAG LED is as follows:

DIAG LED Meaning


The power supply of the ET 200SP HA is disrupted or switched off.
Off
Module is not configured.
flashes
Module parameters are assigned. No diagnostic message is pending.
On
Module parameters are assigned. At least one diagnostic message is pending.
flashes

7.2.2 MT LED

Definition
The MT LED provides maintenance information.

Description
The MT LED indicates the following maintenance status:

MT LED Meaning
No maintenance is required.
Off
Maintenance is required. At least one maintenance event has occurred.
On

DI 8x230VAC HA
20 Equipment Manual, 07/2022, A5E39401560-AD
Displays and interrupts
7.3 Interrupts

7.2.3 Channel status / fault LEDs

Definition
The channel status and channel fault LEDs provide you information about the status and faults
of the channels.

Description
The channel status and channel fault LEDs indicate the following:

LED channel status LED channel error Meaning


• Channel disabled or module switched off
Off Off • Process signal = 0, channel enabled and no channel diagnostics pending
• Module diagnostics pending
Process signal = 1, channel enabled and no channel diagnostics / module diag‐
On Off nostics pending
Process signal = 0, channel enabled and channel diagnostics pending
Off On
Process signal = 1, channel enabled and channel diagnostics pending
On On

7.3 Interrupts

Definition
A diagnostics interrupt is an alarm that reports activated events of a device status to the system
operator with the appropriate operating authorization (maintenance and service).

Description
The I/O module supports diagnostic interrupts.
The I/O module generates a diagnostic interrupt for the following events:
• Parameter assignment error
• Channel/component temporarily unavailable
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective

Note
A pending "Module is defective" or "Over temperature" diagnostic is not deleted from the module
without a restart.

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 21
Displays and interrupts
7.3 Interrupts

The I/O module generates a maintenance message for the following events:
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective

DI 8x230VAC HA
22 Equipment Manual, 07/2022, A5E39401560-AD
Technical specifications 8
8.1 Technical specifications

Technical specifications of the DI 8x230VAC HA

Article number 6DL1131-6GF00-0PK0


General information
Product type designation DI 8x230VAC HA
Firmware version V1.0
• FW update possible Yes
Usable terminal block TB type K0
Color code for module-specific color identifica‐ CC42
tion plate
Product function
• I&M data Yes; I&M0 to I&M3
Engineering with
• STEP 7 TIA Portal configurable/integrated V16
from version
• STEP 7 configurable/integrated from version V5.6
• PCS 7 configurable/integrated from version V9.0
• PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
• DI Yes
Redundancy
• Redundancy capability No
Supply voltage
Rated value (AC) 230 V
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Power
Power available from the backplane bus 105 mW
Power loss
Power loss, typ. 1.8 W; Active power, load voltage 230 V, all inputs
connected with 230 V, 50 Hz
Address area
Address space per module
• Address space per module, max. 1 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding
• Mechanical coding element Yes

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 23
Technical specifications
8.1 Technical specifications

Article number 6DL1131-6GF00-0PK0


Digital inputs
Input characteristic curve in accordance with IEC Yes
61131, type 3
Input voltage
• Rated value (AC) 230 V
• for signal "0" 0V AC to 40V AC
• for signal "1" 74 V AC to 264 V AC
Input delay (for rated value of input voltage)
for standard inputs
– at "0" to "1", min. 1.5 ms
– at "0" to "1", max. 4 ms
– at "1" to "0", min. 10 ms
– at "1" to "0", max. 10 ms
Cable length
• shielded, max. 1 000 m
• unshielded, max. 600 m
Encoder
Connectable encoders
• 2-wire sensor Yes
Diagnoses
• Diagnostic information readable Yes
Diagnostics indication LED
• MAINT LED Yes; Yellow LED
• Channel status display Yes; green LED
• for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels Yes
• between the channels and backplane bus Yes
Permissible potential difference
between different circuits Between channels: 230 V AC (same system phase) /
120 V AC (different system phase); between
groups: 230 V AC (different system phase)
between channels and backplane bus/supply 230 V AC
voltage
Isolation
tested with
• between channels and backplane bus/supply 4 200 V DC/1 min, type test
voltage
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -40 °C
• horizontal installation, max. 70 °C

DI 8x230VAC HA
24 Equipment Manual, 07/2022, A5E39401560-AD
Technical specifications
8.1 Technical specifications

Article number 6DL1131-6GF00-0PK0


• vertical installation, min. -40 °C
• vertical installation, max. 60 °C
Dimensions
Height 115 mm
Depth 138 mm
Weights
Weight, approx. 148 g

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 25
Technical specifications
8.1 Technical specifications

Article number 6DL1131-6GF00-0EK0


General information
Firmware version V1.0
• FW update possible Yes
Usable terminal block TB type K0
Color code for module-specific color identifica‐ CC42
tion plate
Engineering with
• SPPA-T3000 can be configured/integrated V8.0
from version
Operating mode
• DI Yes
Redundancy
• Redundancy capability No
Supply voltage
Rated value (AC) 230 V
Power
Power available from the backplane bus 105 mW
Power loss
Power loss, typ. 1.8 W; Active power, load voltage 230 V, all inputs
connected with 230 V, 50 Hz
Address area
Address space per module
• Address space per module, max. 4 byte; PII: 1 byte, +1 byte for QI information, +1
byte of PROFINET status data; PIO: 1 byte PROFINET
status data
Hardware configuration
Automatic encoding
• Mechanical coding element Yes
Digital inputs
Input characteristic curve in accordance with IEC Yes
61131, type 3
Input voltage
• Rated value (AC) 230 V
• for signal "0" 0V AC to 40V AC
• for signal "1" 74 V AC to 264 V AC
Input delay (for rated value of input voltage)
for standard inputs
– at "0" to "1", min. 1.5 ms
– at "0" to "1", max. 4 ms
– at "1" to "0", min. 10 ms
– at "1" to "0", max. 10 ms
Encoder

DI 8x230VAC HA
26 Equipment Manual, 07/2022, A5E39401560-AD
Technical specifications
8.1 Technical specifications

Article number 6DL1131-6GF00-0EK0


Connectable encoders
• 2-wire sensor Yes
Interrupts/diagnostics/status information
Diagnoses
• Diagnostic information readable Yes
Diagnostics indication LED
• MAINT LED Yes; Yellow LED
• Channel status display Yes; green LED
• for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels Yes
• between the channels and backplane bus Yes
Permissible potential difference
between different circuits Between channels: 230 V AC (same system phase) /
120 V AC (different system phase); between
groups: 230 V AC (different system phase)
between channels and backplane bus/supply 230 V AC
voltage
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -40 °C
• horizontal installation, max. 70 °C
• vertical installation, min. -40 °C
• vertical installation, max. 60 °C
Dimensions
Height 115 mm
Depth 138 mm

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 27
Technical specifications
8.1 Technical specifications

DI 8x230VAC HA
28 Equipment Manual, 07/2022, A5E39401560-AD
Parameters, diagnostics messages and address
space A
A.1 Parameter assignment

Parameter assignment in the user program


You can reconfigure individual channels of the module in RUN without this having an effect on
the other channels.

Changing parameters in RUN


The parameters are transferred to the module with the "WRREC" instruction via data record 128.

Output parameter STATUS


If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.

Error_ Error_ Cause Solution


Code_1 Code_2
0xB0 0x00 Number of the data record unknown Enter valid number for data record.
0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length.
0xB2 Variable Module cannot be reached • Check station - is the module plugged in cor‐
rectly?
• Check the parameters of the WRREC instruction.
0xE0 0x01 Wrong version in the header Correct the version number of the parameter block.
0xE0 0x02 Header error (number or length of parameter Correct the length and number of the parameter
block) blocks.
0xE1 0x01 Reserved bit set Check and correct the parameters

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 29
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

A.2 Parameter assignment and structure of the module/channel


parameters

Structure of data record 128


Data record 128 has a length of 28 bytes.
It contains the channel parameters of the 8 channels.

%\WH +HDGHULQIRUPDWLRQ PRGXOH

%\WH 0RGXOHSDUDPHWHUV

%\WH +HDGHULQIRUPDWLRQ FKDQQHO

%\WH 'LJLWDOLQSXW &KDQQHO

%\WH 'LJLWDOLQSXW &KDQQHO

 
 

%\WH 'LJLWDOLQSXW &KDQQHO

Figure A-1 Structure of data record 128

DI 8x230VAC HA
30 Equipment Manual, 07/2022, A5E39401560-AD
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

Header information and module parameters


The following figure shows the structure of the header information and module parameters.

       
%\WH        

0LQRUYHUVLRQ
0DMRUYHUVLRQ

       
%\WH         1XPEHURIWKHIROORZLQJSDUDPHWHUVWUXFWXUHV

       
%\WH         1XPEHURIWKHIROORZLQJPRGXOHSDUDPHWHUEORFNV

       
%\WH         /HQJWKRIWKHPRGXOHSDUDPHWHUEORFN

       
%\WH         5HVHUYHG

  

       
%\WH         5HVHUYHG

       
%\WH         1XPEHURIWKHIROORZLQJFKDQQHOSDUDPHWHUEORFNV 

       
%\WH         /HQJWKRIDFKDQQHOSDUDPHWHUEORFN 

Figure A-2 Header information and module parameters of data record 128

Channel parameters
The following figure shows the configuration of the channel parameters for channels 0 to 7.
x = 12 + (channel number * 2); with channel number 0…7
All unused bits and the bits or bytes marked as "reserved" must be set to zero.
You activate a channel parameter by setting the corresponding bit to "1" or the corresponding
value.

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 31
Parameters, diagnostics messages and address space
A.3 Diagnostics alarms

       
%\WH[         5HVHUYHG

       
%\WH[       
&KDQQHOHQDEOHG
 (QDEOHG
 'LVDEOHG
Figure A-3 Configuration byte x to x+1 for the channels 0 to 7

A.3 Diagnostics alarms

Diagnostics messages
A diagnostic message is generated for each diagnostic event and the DIAG LED on the DI
8x230VAC HA flashes red or the MT LED lights up yellow.
The diagnostic messages can be read in the diagnostics buffer of the CPU, for example.
Diagnostic messages are assigned channel-specific to an input or assigned as module messages
to all inputs. All channels are switched off for diagnostic messages that affect the entire module.
Only the corresponding digital input is affected by diagnostic messages, which refer to individual
channels.

Diagnostics Error code Assignment Meaning Solution


message
Parameter assign‐ 10H Module • Parameter assignment does not • Correct the parameter as‐
ment error match the terminal block used signment
• Incorrect parameter assignment • Check terminal block1
Channel/compo‐ 1FH Module Firmware update is currently in pro‐ • Restart the firmware up‐
nent temporarily gress or has been canceled. The mod‐ date
unavailable ule does not read any process values
• Wait for firmware update
in this state.
Retentive memo‐ 154H Module An error of the memory block on the Replace carrier module
ry in carrier mod‐ adapter module was detected during
ule defective startup
Retentive memo‐ 155H Module An error of the memory block on the Replace terminal block
ry in the terminal terminal block was detected during
block defective startup
1
Only the terminal blocks (TB 45 ...) are suitable for operating I/O modules with IO redundancy.

DI 8x230VAC HA
32 Equipment Manual, 07/2022, A5E39401560-AD
Parameters, diagnostics messages and address space
A.5 Address space

A.4 Maintenance events

Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED lights
up on the module.
Maintenance messages do not have a direct influence on the functions of the module or digital
inputs.

Maintenance Error code Assignment Meaning / Cause Solution


message
Retentive memo‐ 154H Module Fault detected in the data block on the Replace carrier module
ry in carrier mod‐ carrier module during operation
ule defective
Retentive memo‐ 155H Module An error of the memory block on the Replace terminal block
ry in the terminal terminal block was detected during
block defective operation

A.5 Address space

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "DI" stands for digital input
• "QDIn" stands for the value status (QI) of digital input n

Address space
The following figure shows the mapping of the address space of the DI 8x230VAC HA.

Table A-1 Address space of the DI 8x230VAC HA

IB x + 7 6 5 4 3 2 1 0
0 DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
1 QDI7 QDI6 QDI5 QDI4 QDI3 QDI2 QDI1 QDI0

Evaluating the value status


There is a bit value status for each digital input in the input address space.
Irrespective of the diagnostics enables, each value status (each QI bit) provides information on
the validity of the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"

DI 8x230VAC HA
Equipment Manual, 07/2022, A5E39401560-AD 33
Parameters, diagnostics messages and address space
A.5 Address space

Basically, the value status is set to "good" if the digital value can be output without error. The
value status is set to "bad" in the following cases:
• The digital value cannot be output due to an error.
• The digital channel is deactivated

DI 8x230VAC HA
34 Equipment Manual, 07/2022, A5E39401560-AD

You might also like