50% found this document useful (2 votes)
1K views3 pages

LoopCheckProcedure E1

The document outlines a loop check procedure involving four steps: 1. Verify the parameters and alarm settings of 4-20mA analog input and output signals by forcing the signals to different percentages and checking the control station readings and device actions. 2. Verify the alarm set points of digital input and output signals by activating field devices and forcing output signals to check the control station indications and device actions. 3. Verify the parameters and alarm settings of fieldbus devices by forcing input signals and checking control station readings and control valve actions. 4. Verify the parameters and alarm settings of IPS signals by forcing analog and digital inputs, simulating shutdown signals, and checking the control station readings and shutdown verifications.

Uploaded by

mc_prayer
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
50% found this document useful (2 votes)
1K views3 pages

LoopCheckProcedure E1

The document outlines a loop check procedure involving four steps: 1. Verify the parameters and alarm settings of 4-20mA analog input and output signals by forcing the signals to different percentages and checking the control station readings and device actions. 2. Verify the alarm set points of digital input and output signals by activating field devices and forcing output signals to check the control station indications and device actions. 3. Verify the parameters and alarm settings of fieldbus devices by forcing input signals and checking control station readings and control valve actions. 4. Verify the parameters and alarm settings of IPS signals by forcing analog and digital inputs, simulating shutdown signals, and checking the control station readings and shutdown verifications.

Uploaded by

mc_prayer
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

LOOP CHECK PROCEDURE

1. 4-20mA signals (Conventional, HART) - Verify that the applicable parameters (span, alarm set point) are correct (Loop folder INTools data as the official reference) Analog Input Field: - force input to 0%, 50%, 100% of span Control Station: - verify correct reading in DeltaV operate (Control graphics / Faceplate) - verify alarm (HH, Hi, Lo, LL) Settings (Detailed Faceplate) - Check burnout for Thermocouple loop Analog Output Control Station: - Open Control Faceplate. - Force output to 0%, 50%, 100% of span Field: - verify that 4, 12, 20 mA is received. - verify device action if applicable

2. Digital Input/Output signals - Verify that the alarm set-point is correct (0 or 1 to alarm) Digital input Filed: - activate field device if applicable. (switches level, pressure, temperature, flow, Remote/Local, Start/Stop, etc.) Control Station: - verify correct indication in DeltaV operate (Control graphics / Faceplate) if applicable. Digital output Control Station: - Open Control Faceplate. - Force output to energized\deenergized, open, close Field: - verify that Control voltage is received - verify device action if applicable

LoopCheckProcedure E1.doc

1/3

3. Fieldbus Devices - Verify that the applicable parameters (span, alarm set point) are correct (Loop folder INTools data as the official reference) Transmitters (Pressure, Temperature, Level, Flow, etc) Field: - force input to 0%, 50%, 100% of span (Inject signal pressure, temperature, etc. whichever is applicable. Or simulate PV using AMS) Control Station: - verify correct reading in DeltaV operate (Control graphics / Faceplate) - verify alarm (HH, Hi, Lo, LL) Settings (Detailed Faceplate) Control Valve (PCV, TCV, LCV, FCV, etc) Control Station: - Open Control Faceplate - Set PID mode to Auto (set mode to cascade for cascade PID control) - Set PID set point to 50% Field: - force input to 0%, 50%, 100% of span (Inject signal pressure, temperature, etc. whichever is applicable. Or simulate PV using AMS) - verify correct Valve action (control action, fail action) 4. IPS signal - Verify that the applicable parameters (span, alarm set point) are correct (Loop folder INTools data as the official reference) Analog Input (AI - Conventional, HART) - Open IPS C&E display - Click Reset button to clear inactive alarm Field: - force input to 0%, 50%, 100% of span (Inject signal pressure, temperature, etc. whichever is applicable. Or simulate PV using AMS) Control Station: - verify correct reading in DeltaV operate (Control graphics / Faceplate) - verify alarm (HH, Hi, Lo, LL) Settings (Detailed Faceplate) Digital input - Open IPS C&E display - Click Reset button to clear inactive alarm Field: - activate field device if applicable. (switches level, pressure, temperature, flow, Emergency Stop, etc.)

LoopCheckProcedure E1.doc

2/3

Control Station: - verify correct indication in DeltaV operate (Control graphics / Faceplate) if applicable. Digital output - Open IPS C&E display - Make the related input in the UZ logic healthy. - Click Reset button to clear inactive alarm Field: - simulate any shutdown signal from the field. (HH, LL, 2oo3 LL, etc.) - Verify shutdown signal becomes active (SDV deactivated, Breakers off) Control Station: - Verify UZ display shows shutdown

LoopCheckProcedure E1.doc

3/3