Miniature circuit breakers are rated for currents up to 63A and can have 1 to 4 poles. They provide overload and short circuit protection according to IEC 60898-1 and IEC 60947-2 standards. Miniature circuit breakers come in various rated voltages from 240/415V for 1 pole and 240V for 1 pole + neutral up to 415V for 2 to 4 poles. They have trip characteristics of B, C, or D and have electrical and mechanical lives of 10,000 and 20,000 operations respectively.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views2 pages

BKJ63N BKJ63Nd 리플렛 E 202104

Miniature circuit breakers are rated for currents up to 63A and can have 1 to 4 poles. They provide overload and short circuit protection according to IEC 60898-1 and IEC 60947-2 standards. Miniature circuit breakers come in various rated voltages from 240/415V for 1 pole and 240V for 1 pole + neutral up to 415V for 2 to 4 poles. They have trip characteristics of B, C, or D and have electrical and mechanical lives of 10,000 and 20,000 operations respectively.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Miniature Circuit Breakers

⃝ Rated current: Up tp 63A


⃝ Number of pole: 1~4P
⃝ Standards
- IEC 60898-1, IEC 60947-2

Type BKJ63N BKJ63Nd


Protections Overload / Short circuit
Poles 1P, 1P+N, 2P, 3P, 3P+N, 4P
Rated current In (A) 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
1P Pole : 240 / 415Vac
Rated voltage Ue (V) 1P+N Pole : 240Vac
2~4 Pole : 415Vac
Trip characteristics B, C, D
Rated insulation voltage (Ui) 500V
Rated impulse withstand voltage (Uimp) 4kV
Rated frequency (Hz) 50 / 60
Rated conditional short-circuit current (kA) 6kA
Rated residual breaking capacity (kA) 6kA
Electrical life 10,000
Mechanical life 20,000
Protection degree IP20
Ambient temperature (℃) -5°C ~ + 40°C
Mounting 35mm Din-rail
Tightning torque 2.0N.m
Terminal Lug Lug & Screw
Dimensions (H x D x W) 68×81×18 (1P)
Accessory AX, AL, SHT, OVT, UVT
Standard IEC 60898-1 / 60947-2
Characteristics curves

Operating curves
BKJ63N / BKJ63Nd
Temperature compensation table(IEC 60898-1)

I1: 113% In, I2: 145% In according to IEC 60898-1

Dimensions (unit: mm)

BKJ63N
17.8 35.6 53.4 71.2
45
81

68
62
44

19
35

1P 2P 3P 4P
6

BKJ63Nd
17.8 35.6 53.4 71.2
45
81

68
62
44

19

35

1P 2P 3P 4P
6

www.ls-electric.com

 Headquarter
127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si,
Gyeonggi-Do, 14119, Korea
Tel. 82-2-2034-4848, 4671, 4429 Fax: 82-2-2034-4555

Specifications in this catalog are subject to change without notice due to


2021. 04 continuous product development and improvement.
ⓒ2020. 12 LS ELECTRIC Co., Ltd. All rights reserved. / English (02) 2021. 04 Staffcom